SIMIT & S7-PLCSIM Advanced Training
SIMIT & S7-PLCSIM Advanced Training
siemens.com/sce
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved.
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
Note that these trainer packages are replaced with successor packages when necessary.
An overview of the currently available SCE packages is available at: siemens.com/sce/tp
Continued training
For regional Siemens SCE continued training, get in touch with your regional SCE contact
siemens.com/sce/contact
This document is only to be used for initial training on Siemens products/systems. This means it can be copied in
whole or in part and given to trainees/students for use within the scope of their training/course of study.
Disseminating or duplicating this document and sharing its content is permitted within public training and advanced
training facilities for training purposes or as part of a course of study.
Exceptions require written consent from Siemens. Send all related requests to
[email protected].
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 2
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
Offenders will be held liable. All rights including translation are reserved, particularly if a patent is granted or a
utility model or design is registered.
Use for industrial customer courses is explicitly not permitted. We do not consent to commercial use of the Learn-
/Training Document.
We wish to thank the TU Dresden and the Michael Dziallas Engineering Corporation and all other involved persons
for their support during the preparation of this Learn-/Training Document.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 3
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
Table of contents
1 Goal ................................................................................................................................................................. 4
2 Requirement .................................................................................................................................................... 4
4 Theory .............................................................................................................................................................. 6
6 Task ............................................................................................................................................................... 12
7 Planning ......................................................................................................................................................... 12
8.2 Download the TIA Portal project to SIMATIC S7-PLCSIM Advanced ...................................................18
8.4 Start an existing SIMIT project with "OPC UA Client" coupling with SIMATIC S7-PLCSIM Advanced
as OPC UA server .................................................................................................................................34
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 3
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
The order in which existing SIMIT projects with this coupling variant can be started together with a TIA
Portal project for simulation of a program solution will also be described.
2 Requirement
This chapter builds on the chapter "SCE_EN_092-300 OPC UA with SIMATIC S7-1500 as OPC Server
…". To perform the work in this chapter, you can use the following project, for example: "sce-092-300-
opc-ua-s7-1500….".
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 4
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
2 SIMATIC STEP 7
Professional (TIA
Portal) – V15.1 or
higher
3 SIMATIC S7-PLCSIM
Advanced – V2.0 SP1
or higher
1 Engineering station
4 SIMIT – V10.0
Update 1 or higher
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 5
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
4 Theory
4.1 SIMIT V10
SIMIT is process simulation software that can be used for the following:
Chart
To build a simulation, components available in the libraries are put together in the chart editor and
suitable parameters are entered.
Visualization
Visualizations provide an overview of the signals of your plant. Signals are visualized with controls
(input and display objects) and graphical objects.
Coupling
The coupling is the interface to the automation system and is required for signal exchange. In addition
to couplings with PLCSIM, PLCSIM Advanced, PRODAVE, etc., there is also a coupling with SIMIT
as OPC UA client.
Demo mode
In demo mode you can get an impression of the use and performance capability of SIMIT without having
to have a valid license.
Existing models can be opened and simulated in demo mode. It is also possible to change these models
and create new models. The models created or modified in this way can only be run on the computer on
which they were created.
SIMIT Simulation is limited to 45 minutes in demo mode. The simulation must then be restarted.
Note:
– Further details and information can be found in the manuals, which can be downloaded from
support.automation.siemens.com.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 6
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
C:\ProgramData\Siemens\Automation\SIMIT\8.0\PKI\own\private
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 7
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ If you receive the message shown here, you can get access to this folder by clicking "Continue".
However, this only works if you have administrator rights on the computer. If not, you must reach out
to your administrator. (→ Continue)
The procedure for setting the IP address of the Siemens PLCSIM Virtual Ethernet Adapter with Windows
10 operating system is shown here.
→ Select the network icon in the taskbar at the bottom and click → "Network settings".
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 8
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ In the network settings window that opens, click → "Ethernet" and then on → "Change adapter
options".
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 9
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 10
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ You can now use the following IP address, for example → IP address: 192.168.0.99 and enter the
following → subnet mask 255.255.255.0. Then apply the settings. (→ "OK")
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 11
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
6 Task
A SIMIT simulation with a coupling with SIMATIC S7-PLCSIM Advanced via OPC UA is to be created. In
so doing, the symbols of the inputs and outputs in SIMATIC S7-PLCSIM Advanced are to be accessed.
7 Planning
First, an existing TIA Portal project with activated OPC UA server is retrieved.
– In the project properties, the "Support simulation during block compilation" option must be selected
for "Protection".
– All FBs and DBs are removed from the project because the tags created there will otherwise be
imported as signals.
– In the tag tables, the "Writable from HMI/OPC UA" attribute must be deselected for the PLC outputs.
Otherwise, they will be imported into SIMIT as PLC inputs.
– The IO addresses to be simulated using SIMIT must not exist as hardware modules. Accordingly, we
remove all affected IO modules.
Finally, the hardware configuration with the tag tables is also downloaded to SIMATIC S7-PLCSIM
Advanced.
Now, a SIMIT project is created and a new "OPC UA Client" coupling with SIMATIC S7-PLCSIM
Advanced is created there.
Next, the IO addresses are imported from SIMATIC S7-PLCSIM Advanced via OPC UA.
For simulation of a program solution, an existing TIA Portal project with activated OPC UA server is
opened and downloaded to SIMATIC S7-PLCSIM Advanced.
The SIMIT project is then opened and started for testing the program solution.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 12
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ The next step is to select the destination folder where the retrieved project will be stored. Confirm
your selection with "OK" (→ Destination folder … → OK).
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 13
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ In the project properties, the " Support simulation during block compilation" option still needs to be
selected for "Protection". (→ 092-300_OPC UA S7-1500… → Properties → Protection → Support
simulation during block compilation → OK)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 14
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ All FBs and DBs are to be removed from the project because the tags created there will otherwise be
imported as signals. Here, we delete all program blocks of the project by selecting them and right-
clicking. We now select "Delete" from the options. (→ CPU_1516F → Program blocks → Delete)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 15
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ In the tag tables, the "Writable from HMI/OPC UA" attribute must be deselected for the PLC outputs.
Otherwise, they will be imported into SIMIT as PLC inputs. Open the "Tag table_sorting station" and
deselect the "Writable from HMI/OPC UA" attribute for all output signals. (→ CPU_1516F → PLC
tags → Tag table_ sorting station → Writable from HMI/OPC UA)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 16
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ The IO addresses to be simulated using SIMIT must not exist as hardware modules. Accordingly, we
also remove all IO modules by selecting them, right-clicking on them and selecting "Delete". (→
CPU_1516F → Device configuration → Delete)
→ Then click on the "CPU_1516F" folder. In the menu, first select the " " button and then
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 17
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ Open "S7-PLCSIM Advanced" from the desktop of your computer by double-clicking on the logo for
the application. (→ S7-PLCSIM Advanced)
→ In the "Control Panel" of S7-PLCSIM Advanced, select the settings shown here for the virtual S7-
1500 and start it. (→ Control Panel → PLCSIM Virtual Ethernet Adapter → <Local> → CPU_1516F
→ 192.168.0.1 → 255.255.255.0 → Unspecified CPU 1500 → Start)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 18
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ The virtual S7-1500 is now started in S7-PLCSIM Advanced. The virtual controller of the TIA Portal
and SIMIT can be accessed via the configured address.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 19
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ To download your entire CPU, select the → "CPU_1516F [CPU1516F-3 PN/DP]" folder in the TIA
→ The manager for configuring connection properties then opens. (Extended download).
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 20
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ First, the interface must be correctly selected. This happens in three steps.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 21
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ The → "Show all compatible devices" check box must then be selected. The search for devices in
the network is started by clicking the → button.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 22
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ If the controller is shown in the list, it must be selected before the download can be started.
(→ CPU1516F-3 PN/DP → Load)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 23
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ You first obtain a preview. Confirm the suggested actions and continue with → "Load".
Note:
– The symbol should be visible in every line of the "Load preview". You can find additional
information in the "Message" column
→ The → "Start module" option is now selected before the download operation can be completed with
→ "Finish".
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 24
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ Create a new project "020-111_SIMIT PLCSIMAdv OPC UA". (→ Create new project → 020-
111_SIMIT PLCSIMAdv OPC UA → Create)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 25
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 26
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ Create a "New coupling" "OPC UA Client" for your project under "Couplings".
(→ Couplings → New coupling → OPC UA Client → OK)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 27
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ Switch to the TIA Portal and open the "Device configuration" in the previously retrieved project "092-
300_OPC UA S7-1500". Select the CPU. In the properties under OPC UA, copy the address of the
activated OPC UA server. (→ 092-300_OPC UA S7-1500 → Device configuration → CPU_1516F →
Properties → OPC UA → General → Server addresses → opc-tcp://192.168.0.1:4840 → Copy)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 28
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ Paste the previously copied OPC UA server address of the CPU 1516F into SIMIT as "OPC UA
Server URL" under "Couplings", "OPC UA client". (→ SIMIT → Couplings → OPC UA Client →
Properties → OPC UA Server URL → Paste)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 29
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ Under "Properties", select the settings shown below for "Endpoint" and "Namespace URI". (→
Properties → Endpoint → Name space URI)
Note:
– If the following error message appears, you need to check the requirements of the settings in
Windows 10 described in chapter 5.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 30
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ When you click the " " button, the inputs and outputs from the tag table previously downloaded
to the CPU 1516F are imported and are now ready for further use in the simulation. (→ Browse)
→ Finally, select " Save all". (→ ) Click " Start" to start the simulation. (→ )
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 31
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ After starting the simulation, you can test the access to the inputs and outputs of SIMATIC S7-
PLCSIM Advanced in SIMIT.
→ You can see whether this access is functioning in the tag tables in TIA Portal by clicking the " "
symbol. (→ )
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 32
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 33
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
8.4 Start an existing SIMIT project with "OPC UA Client" coupling with
SIMATIC S7-PLCSIM Advanced as OPC UA server
→ First, start the TIA Portal from the desktop of your computer by double-clicking on the logo for the
application. (→ TIA Portal)
→ Open or retrieve the desired TIA Portal project. Here, the project for the sorting station "sce-092-300-
opc-ua-s7-1500…" is opened. Switch to the Project view. (→ Open existing project → sce-092-300-
opc-ua-s7-1500… → Open → Project view)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 34
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
Before you can download the CPU_1516F from the "092-300_OPC UA S7-1500" project, SIMATIC S7-
PLCSIM Advanced must be opened and a CPU with the appropriate settings must be started.
→ Open "S7-PLCSIM Advanced" from the desktop of your computer by double-clicking on the logo for
the application. (→ S7-PLCSIM Advanced)
→ In the "Control Panel" of S7-PLCSIM Advanced, select the settings shown here for the virtual S7-
1500 and start it. (→ Control Panel → PLCSIM Virtual Eth. Adapter → <Local> → CPU_1516F →
192.168.0.1 → 255.255.255.0 → Unspecified CPU 1500 → Start)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 35
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ The virtual S7-1500 is immediately started in S7-PLCSIM Advanced and can be accessed from the
TIA Portal and SIMIT via the configured address.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 36
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ To download your entire CPU, select the → "CPU_1516F [CPU1516F-3 PN/DP]" folder and click the
Note:
– The IO addresses to be simulated using SIMIT must not exist as hardware modules.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 37
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ The manager for configuring the connection properties (Extended download) then opens.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 38
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ First, the interface must be correctly selected. This happens in three steps.
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 39
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ The → "Show all compatible devices" check box must then be selected. The search for devices in
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 40
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ If the controller is shown in the list, it must be selected before the download process can be started.
(→ CPU1516F-3 PN/DP → Load)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 41
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ You first obtain a preview. Confirm the suggested actions and continue with → "Load".
Note:
– The symbol should be visible in every line of the "Load preview". You can find additional
information in the "Message" column.
→ Following this, the → "Start module" option is selected before the download operation can be
completed with → "Finish".
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 42
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ Now start SIMIT from the desktop of your computer by double-clicking on the logo for the "SIMIT SP"
application (→ SIMIT SP)
→ Open or retrieve the desired project. Here, the project for the sorting station "sce-020-111-sce-
sorting-station-plcsim-advanced-opc-ua-r1904-en.simarc" is retrieved from the archive. (→ Retrieve
project → sce-020-111-sce-sorting-station-plcsim-advanced-opc-ua-r1904-en.simarc → Retrieve)
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 43
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 44
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ Select " Save all" and select " Start" to start the simulation. (→ → )
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 45
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
→ The application can be subsequently be tested in SIMIT. Clicking on " " again ends the simulation
in SIMIT. (→ )
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 46
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
9 Additional information
More information for further practice and consolidation is available as orientation, for example:
Getting Started, videos, tutorials, apps, manuals, programming guidelines and trial software /
firmware, under the following link:
siemens.com/sce/s7-1200
For unrestricted use in educational / R&D institutions. © Siemens 2019. All rights reserved. 47
sce-020-111-simit-plcsim advanced-opc-ua-r1904-en.docxn.docx
Learn-/Training Document | TIA Portal Module 020-111, Edition 08/2019 | Digital Industries, FA
Further Information