Spacelogic VBB/VBS: Notice

This document provides installation instructions for SpaceLogic VBB/VBS ball valves with two-position actuators. It describes inspecting the product for damage upon receipt, piping requirements, mounting instructions including aligning the valve stem and keyed post with the actuator holes, and instructions for installing normally open and normally closed models. Tools required and notes on media compatibility are also included.

Uploaded by

hamza alhassan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views

Spacelogic VBB/VBS: Notice

This document provides installation instructions for SpaceLogic VBB/VBS ball valves with two-position actuators. It describes inspecting the product for damage upon receipt, piping requirements, mounting instructions including aligning the valve stem and keyed post with the actuator holes, and instructions for installing normally open and normally closed models. Tools required and notes on media compatibility are also included.

Uploaded by

hamza alhassan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Installation Instructions schneider-electric.

com | 1

SpaceLogic VBB/VBS
Ball Valves with Two-Position Actuators

Inspection A
Inspect the package for damage. If package is damaged, A AB B AB
notify the appropriate carrier immediately. If undamaged, open
the package and inspect the device for obvious damage.
Two-Way Valve: Three-Way Valve: Mixing
Return damaged products.
Flow A to AB Only A and/or B to AB.

Requirements
Manual Crankshaft
NOTICE Lock
Allen Wrench
RISK OF EQUIPMENT DAMAGE
• Read and understand these instructions before installing or
servicing this product.
• Do not install this product in hazardous or classified
locations unless expressly permitted.
• Turn off all power supplying equipment before working on
the product.
• Make all connections in accordance with the electrical wiring 1
diagram. Valve release Stem hole
• Do not exceed the product’s technical ratings. lever
• Use copper conductors only. Make all connections in
accordance with the appropriate electrical wiring diagram. Keyed post hole
• Avoid installation locations exposed to vibration, excessive
moisture, and/or corrosive or explosive vapours. Keyed post Stem Slot
• Avoid electrical noise interference. Do not install near large
conductors, electrical machinery, or welding equipment.
• When making wiring connections within the actuator, do not
put leads or connectors below the motor.
• This product is a class 2 (Limited Voltage Limited Energy)
device. 1 Parts on bottom of both actuators are identical.
• The installer is responsible for conformance to all applicable
codes. 360°
• Check the Electrical terminals and any configuration switch
settings before powering up the actuator.
Failure to follow these instructions may cause equipment
damage.
90˚
If this product is used in a manner not specified by the manufacturer,
the protection provided by the product may be impaired. Horizontal Pipe
No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this product. Horizontal Plane Vertical Pipe

Tools (not provided) Training


• Wrench/adjustable spanners: 24…42mm (1”…1-5/8”) • Installer must be a qualified, experienced technician
• Pipe wrench according to pipe size Other accessories
• Volt-ohm multimeter • As appropriate.
• Phillips Head screwdriver

www.schneider-electric.com

© 2020 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. January, 2021 tc
Document Number: F-27392-5
Installation Instructions
schneider-electric.com | 2

Piping Installing Normally Open M21xxxx Models


1. Turn the valve stem so the slot on top of the stem is pointing
NOTICE towards the large keyed post.
2. Align the valve body with the actuator to ensure the stem
RISK OF EQUIPMENT DAMAGE
lines up with the large stem hole and the large keyed post
• Do not install in open systems using substantial make-up water. lines up with the post hole on the bottom of the actuator.
• Follow proper water treatment practices and system
3. Press the valve and actuator together to assemble.
procedures.
Failure to follow these instructions may cause equipment Installing Normally Closed M22xxxx Models
damage. 1. Turn the valve stem so that the slot on the top of the stem is
pointing towards the large keyed post.
These valves must be piped according to the water flow 2. Insert the allen wrench into the manual crank shaft on
diagram. Two-Way valve flow should go A to AB. Three-way the top of the actuator. Crank eight turns in the direction
valves should be applied only as mixing valves (see diagram). indicated on the label. In the last turn, align the indicator
notch to the opening in the crankshaft. Press the button
Best Practice Guidelines around manual crankshaft to lock in place. Remove and
It is recommended to fit a strainer upstream of the valve to replace allen wrench in cover slot.
increase reliability and to follow water treatment guidelines as 3. Align the valve body with the actuator to ensure the stem
detailed in VDI 2035. lines up with the large stem hole and the large keyed post
lines up with the post hole on the bottom of the actuator.
Recommendations 4. Press the valve and actuator together to assemble.
The pipework system should be flushed prior to the operation.
5. The first time the valve is operated electrically, the manual
operating lever of the actuator will move to the automatic
Mounting position. The manual operating lever can be used to allow
The valves can be mounted in horizontal or vertical piping. flushing of the system after installation.
When installed in horizontal piping, the actuator must be above
the valve body. It can be tilted left or right but it must not be Removing the Actuator
tilted below 90° from vertical. 1. Press and hold the valve release lever inward, towards the
valve.
Installation Notes 2. Lift the actuator from the valve.
• It is the responsibility of the installer or product specifier
to verify media compatibility of the valves construction Checkout
materials with the supplier of water treatment/heat transfer Make sure the valve stem rotates freely before and after
solution. installing the actuator. If the stem does not operate freely it
• Confirm there is no overhead water source that may drip may indicate that the stem was damaged and may require
onto valve actuator. that the valve be replaced. After the piping is under pressure,
• In normal service, some condensation may occur on or check the valve body and the connections for leaks. After the
around the valve. A drip pan may be necessary or the valve and actuator are installed, power the actuator and check
valve body may be insulated.
the operation by varying the control signal. On spring return
• Do not cover the actuator or obstruct the manual operator models, the valve should return to its normal position when
lever.
power is removed.
• Reference product label and Product Datasheet
F-27395 (Global) or F-27895 (EU) for additional product
specifications.
Theory of Operation
When powered, the actuator moves to the desired position,
Installing the Valve Body winding the spring return system. When power is removed
the spring returns the actuator to the normal position. This
1. Apply PTFE tape to the male pipe thread.
series of two-position spring return valve assemblies can be
2. Hand screw the pipe into the valve, turning it as far as it will purchased with an optional built-in auxiliary SPDT end switch
go. for interfacing or signaling; for example, zone pump burner
3. Use a wrench to fully tighten the valve to the pipe. Do not control. The auxiliary switch is designed for contact closure
over tighten or strip the threads. after the valve is more than 50% open. Do not exceed the
published switch electrical ratings. The manual override lever
Installing the Actuator is designed to manually position the actuator to install on the
valve or to manually position the valve. Turning the allen wrench
in the manual crankshaft while power is applied or in the
NOTICE opposite direction as shown on the label will cause permanent
RISK OF EQUIPMENT DAMAGE damage. Use only the allen wrench provided with a maximum
• Do not use the valve body to manually open the actuator. torque of 10 in-lb.
Failure to follow this instruction will result in damage to
the actuator.

© 2020 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. January, 2021 tc
Document Number: F-27392-5
Installation Instructions
schneider-electric.com | 3

Power Action (Two-Position) Wiring Terminals


Control Spring Return Open Spring Return Board Terminal AC Control DC Control
Signal Actuator Closed Actuator Marking Marking Signal Signal
Power On A to AB Closed A to AB Open 24H 2 24v +
Power Off A to AB Open A to AB Closed 24G 1 24v -
Two-Way valve operation described. For a three-way valve, A to AB
operation is the same. B to AB operation is opposite that of A to AB
operation.

24G
Wiring
Make all connections according to job wiring diagrams and in 24H 24 H
compliance with local and national electrical codes. Refer to
diagrams shown for typical wiring. 25 G

NOTE: 24G
• Multiple actuators may be connected to a single controller.
• Do not exceed the maximum current draw of the controller. 24H Circuit Board
• Use of a properly sized, inherently limited, Class 2
With Auxilliary Switch
transformer is recommended.
• Use only 18…24 AWG copper wire for all 24V Wiring (M2x0Axx)
connectors.
Terminal AC Input DC Input Lead
Maintenance Marking 50/60 Hz 50/60 Hz Colors
The ball valve assembly itself requires no maintenance. 1 24 Vac -24 Vdc Black
The stem and packing design eliminates the need for 2 24 Vac +24 Vdc Red
packing adjustment for the life of the valve. However, regular
Orange
maintenance of the total heating and cooling system is SPST Aux Switch
recommended to ensure sustained optimum performance. Yellow

Field Repair
Neither valve nor actuator are field repairable. Replace entire Universal Wiring (M2x0MAxx) Wire Color Table
unit as necessary. (100 through 277 50/60 Hz)
Lead Colors
N/HOT Blue
HOT/HOT Brown
Ground Lead GND Green with Yellow Stripe
Orange
SPST Aux Switch
Yellow

Application Drawing
Typical applications. For simplicity, balancing valves and
control devices not shown.

Mixing applications
A AB
Supply Supply
Return
A AB B

Typical Two-Way
Fan Coil Application Typical Three-Way Three-Way
Bypass
Bypass

Fan Coil Application Constant Flow


Variable Temperature

Supply B
AB A
Return Return

© 2020 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. January, 2021 tc
Document Number: F-27392-5
Installation Instructions
schneider-electric.com | 4

Dimensions

4-9/16 (116)
1-1/4 7/8
3/4
(32) (22)
(19)
2-3/4
(70)
4-1/8
(105)
2-1/8
(54)

3/4 (19)
1-7/16 1-15/16
1-3/8 1-3/8 (37) (49)
(35) (35)
3-3/8 (86)
2-9/16
(65)

4-9/16 (116)

1-1/4
(32) 7/8
3/4 (22)
2-3/4 (19)
(70)
4-1/8
(105)

2-1/8
(54)

3/4 (19)
1-3/8 1-3/8 1-7/16 1-15/16
(35) (35) (37) (49)
2-9/16
3-3/8 (86)
(65)

All dimensions shown in inches (mm) format and are rounded to the nearest 1/16”.
An additional 1 in (25 mm) is required to remove the actuator from the valve.

Agency Listings
UL873: Underwriters laboratories (File #E9429 Category Temperature
Indicating and Regulating Equipment)
CUL: Listed for use in Canada by Underwriters Laboratory. Canadian
Standards C22.2 No. 24.
European Community: EMC Directive (2004/108/EC). Low Voltage Directive
2014/35/EU.
Australia: This product meets requirements to bear RCM according to
the terms specified by the Communications Authority under the Radio
Communications Act of 1992.

© 2020 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. January, 2021 tc