Catalog

HA 40.3 ·
2022

MEDIUM-VOLTAGE SWITCHGEAR

Switchgear Type 8DJH 36 for Secondary


Distribution Systems up to 36 kV, ­Gas-Insulated
siemens.com/8DJH36
Application
Typical uses

Application
in public
and industrial
energy systems

R_HA403_001 jpg
R_HA40-138 png

R_HA403_002 jpg
R_HA403_003 jpg

R_HA403_003 tif

2  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
ContentsPage

MEDIUM-VOLTAGE SWITCHGEAR Application

Switchgear
Types 4
Typical uses, ratings, standards 5

Type 8DJH 36 Requirements


Features 6

for Secondary Technology 7

­Distribution Systems
Technical data
Electrical data of the switchgear,

up to 36 kV, ­ number of operating cycles, classifications


Number of operating cycles, classifications,
8

Gas-Insulated
design and construction, internal arc classification 9

Product range
Individual panels and modules 10
Air-insulated billing metering panel type M,
1100 mm wide 11
Catalog HA 40.3 · 2022 Product range overview of panel blocks 12

Invalid: Catalog HA 40.3 · 2017 Design


Overview 14
siemens.com/medium-voltage-switchgear
Panel design (examples) 16
Outdoor enclosure 19

Components
Busbar extension, modularity 20
Current transformers, voltage transformers 21
Current sensors, voltage sensors 22
Cable connection 23
Low-voltage compartment 25

Dimensions
Room planning 26

ANSI design
Panel design 28
Electrical data of the switchgear 29
Viewing & Lighting System, position indication 30
Current transformers, voltage transformers 31

The products and systems described in this catalog are


­manufactured and sold according to a certified ­management
system (acc. to ISO 9001, ISO 14001 and BS OHSAS 18001).

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  3
Application
Types

R-HA40-138 png
R-HA40-160 jpg

Ring-main panel and circuit-breaker panel as individual panels RRT block

4  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Application
Typical uses, ratings, standards

8DJH 36 switchgear is a factory-assembled, type-tested, Electrical data (maximum values) and dimensions
3-pole metal-enclosed single-busbar switchgear for indoor
installation. Rated voltage kV 36
Rated frequency Hz 50 / 60
8DJH 36 switchgear is used in public and industrial energy Rated short-duration
systems of the secondary distribution level, e.g. in power-frequency withstand voltage kV 70
Rated lightning impulse withstand voltage kV 170
• Local ring-main units, customer transfer substations and Rated peak withstand current kA 63 / 65
switching substations of power supply and public utilities Rated short-circuit making current kA 63 / 65
• Wind power plants and solar plants, hydroelectric power Rated short-time withstand current 3 s kA 25
plants Rated normal current of the busbar A 630
• Water and treatment plants Rated normal current of the feeders A 200 / 630
• Airports, train stations, underground stations Width 
• High-rise buildings – Ring-main feeder mm 430
• Data centers. – Transformer feeder mm 500
– Circuit-breaker feeder mm 590
– Metering panel mm 1100
Depth
– Without pressure relief duct  mm 920 1)
– With pressure relief duct mm 1035 1)
Height
– Standard mm 1600
– With low-voltage compartment mm 1800 / 2000 / 2200

Standards

IEC ­standard  /
EN standard
Switchgear 62271-1
62271-200
Devices Circuit-breakers 62271-100
Disconnectors and 62271-102
­earthing switches
Switch-disconnectors 62271-103
Switch-disconnector / 62271-105
fuse combination
Voltage detecting systems 62271-213
HV HRC fuses 60282
Surge arresters / surge limiters 60099
Degree of protection 60529
62262
Insulation 60071
Instrument General requirements 61869-1
transformers Current transformers 61869-2
Inductive voltage transformers 61869-3
Low-power current transformers 61869-6
61869-10
Low-power voltage transformer 61869-6
61869-11
SF6 60376
Installation 61936-1 / EN 50522
Environmental conditions 60721-3-3
Operation EN 50110

1) I n circuit-breaker feeders with circuit-breakers type 1, the depth in the area of the front operating mechanism of the circuit-breaker is increased by 60 mm.
In metering panels, the depth is increased by 60 mm.

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  5
Requirements
Features

Environmental independence Personal safety


Hermetically tight, welded switchgear vessels made of stainless • Safe-to-touch and hermetically sealed primary enclosure
steel as well as single-pole solid insulation make the parts of • Standard degree of protection IP65 for all high-voltage
the primary circuit under high voltage of 8DJH 36 switchgear parts of the primary circuit, at least IP2X for the switchgear
• Insensitive to certain aggressive ambient conditions, enclosure according to IEC 60529
such as: • Cable terminations, busbars and voltage transformers are
– Saline air surrounded by earthed layers in all feeders except for the
– Humidity air-insulated metering panels. All high-voltage parts
– Dust including the cable terminations, busbars and voltage
– Condensation transformers are metal-enclosed
• Tight to ingress of foreign objects, such as: • Operating mechanisms and auxiliary switches safely acces-
– Dust sible outside the primary enclosure (switchgear vessel)
– Pollution • High resistance to internal arcs by logical mechanical
– Small animals interlocks and tested switchgear enclosure
– Humidity • Panels tested for resistance to internal faults up to 25 kA
• The switchgear meets the requirements of “design class 2” • Capacitive voltage detecting system to verify safe isolation
according to IEC/TS 62271‑304. from supply
Compact design • Due to the system design, operation is only possible with
Thanks to the use of SF6 insulation, compact dimensions are closed switchgear enclosure
possible. • Logical mechanical interlocks prevent maloperation
Thus: • HV HRC fuses and cable sealing ends are only accessible
• Existing switchgear rooms and substation rooms can be when outgoing feeders are earthed
used effectively • Feeder earthing via make-proof earthing switches.
• New constructions cost little Security of operation
• Costly city-area space is saved. • Hermetically sealed primary enclosure independent of envi-
Maintenance-free design ronmental effects (pollution, humidity and small animals)
Switchgear vessels designed as sealed pressure systems, • Maintenance-free in an indoor environment (IEC 62271‑1)
maintenance-free switching devices and enclosed cable plugs • Operating mechanisms of switching devices accessible
ensure: outside the primary enclosure (switchgear vessel)
• Maximum supply reliability • Metal-enclosed and plug-in inductive voltage trans­formers
• Personnel safety mounted outside the SF6 switchgear vessel
• Sealed-for-life design according to IEC 62271‑200 • Current transformers as ring-core current transformers
(sealed pressure system) mounted outside the SF6 switchgear vessel
• Installation, operation, extension and replacement • Complete switchgear interlocking system with logical
without SF6 gas work mechanical interlocks
• Reduced operating costs • Welded switchgear vessels, sealed for life
• Cost-efficient investment • Minimum fire load
• No maintenance cycles. • Type and routine-tested
• Standardized and manufactured using numerically
Innovation
controlled machines
The use of digital secondary systems and combined
• Quality assurance in accordance with DIN EN ISO 9001
­protection and control devices ensures:
• More than 1,500,000 switchgear panels of Siemens in
• Clear integration in process control systems
operation worldwide for many years.
• Flexible and highly simplified adaptation to new system
conditions and thus to cost-efficient operation. Reliability
• Type and routine-tested
Service life
• Standardized and manufactured using numerically
Under normal service conditions, the expected service life of
controlled machines
gas-insulated switchgear 8DJH 36 is at least 35 years, prob-
• Quality assurance in accordance with DIN EN ISO 9001
ably 40 to 50 years, taking the tightness of the hermetically
• More than 1,500,000 switchgear panels of Siemens in
welded switchgear vessel into account. The service life is
operation worldwide for many years.
limited by the maximum number of operating cycles of the
switchgear devices installed:
• For circuit-breakers, according to the endurance class
defined in IEC 62271‑100
• For three-position disconnectors and earthing switches,
according to the endurance class defined in IEC 62271‑102
• For three-position switch-disconnectors and earthing
switches, according to the endurance class defined in
IEC 62271‑103.

6  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Requirements
Technology

General Modular design


• Indoor switchgear under normal ambient conditions • Individual panels and panel blocks can be lined up and
according to IEC 62271‑1 extended at will – without gas work on site
• Three-pole primary enclosure, metal-enclosed • Low-voltage compartment available in 3 overall heights,
• Welded switchgear vessel, made of stainless steel, wiring to the panel via plug connectors.
with welded-in bushings for electrical connections and Panel design
mechanical components • Factory-assembled, type-tested
• Insulating gas SF6 (fluorinated greenhouse gas) • Metal-enclosed, with metal partitions
• Maintenance-free components under normal ambient • Hermetically tight, welded switchgear vessel made of
conditions according to IEC 62271‑1 stainless steel
• Three-position switch-disconnector with load-break • Maintenance-free
function and make-proof earthing function • Degree of protection
• Vacuum circuit-breaker – IP65 for all high-voltage parts of the primary circuit in the
• Cable connection with outside-cone plug-in system gas-insulated panels
– In ring-main, circuit-breaker and transformer feeders – IP2X for the switchgear enclosure
with bolted contact (M16) • Vacuum circuit-breaker with three-position disconnector
– In transformer feeders optionally with plug-in contact for disconnecting and earthing
• Wall-standing or free-standing arrangement • Three-position switch-disconnector
• Cable connection access from front • Cable connection with outside-cone plug-in system
• Installation and extension of existing switchgear at both according to DIN EN 50181
ends without gas work and without modification of • Wall-standing arrangement, optionally free-standing
existing panels arrangement
• Pressure relief downwards, optionally to the rear / upwards, • Installation and possible later extension of existing ­panels
or via pressure relief duct and optionally with pressure without gas work
absorber systems upwards • Replacement of instrument transformers without gas work,
• Earthquake-resistant design available according to as they are located outside the gas compartments
IEC/TS 62271-200, IEC 60068-2-57 and IEEE 693-2018. • Enclosure made of sendzimir-galvanized sheet steel, front
Interlocks cover powder-coated in color RAL 7035
• According to IEC 62271‑200 • Low-voltage compartment removable, plug-in bus wires
• Logical mechanical interlocks prevent maloperation • Lateral, metallic wiring ducts for control cables.
• Logical mechanical interlocks and the constructive features Instrument transformers
of the three-position switches prevent maloperation as well • Current transformers not subjected to dielectric stress
as access to the cable connection of the feeders and • Easy replacement of current transformers designed as
HV HRC fuses under voltage ring-core transformers
• Impermissible and undesired operations can be pre­vented • Metal-enclosed, plug-in voltage transformers.
by means of locking devices on the switching devices.
Vacuum circuit-breakers
Insulating system • Maintenance-free under normal ambient conditions
• Switchgear vessel filled with SF6 gas according to IEC 62271‑1
• Features of SF6 gas: • No relubrication or readjustment
– Non-toxic • Up to 10,000 operating cycles
– Odorless and colorless • Vacuum-tight for life.
– Non-inflammable
Secondary systems
– Chemically neutral
• Customary protection, measuring and control equipment
– Heavier than air
• Option: Numerical multifunction protection relay with
– Electronegative (high-quality insulator)
integrated protection, control, communication, operating
– Global Warming Potential GWP = 22,800
and monitoring functions
• Pressure of SF6 gas in the switchgear vessel
• Can be integrated in process control systems.
(absolute values at 20 °C):
– Rated filling level: 150 kPa Recycling
– Design pressure: 180 kPa The switchgear can be recycled in ecological manner in
– Design temperature of the SF6 gas: 80 °C compliance with existing legislation. Auxiliary devices such
as short-circuit indicators have to be recycled as electronic
– Operating pressure of bursting disc: ≥ 300 kPa
scrap. Batteries have to be recycled professionally. Insulating
– Bursting pressure: ≥ 550 kPa
gas SF6 has to be evacuated professionally as a reusable
– Gas leakage rate: < 0.1 % per year. material and recycled (SF6 must not be released into the
environment).

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  7
Technical data
Electrical data of the switchgear, number of operating cycles, classifications

Electrical data of the switchgear

Rated insulation level Rated voltage Ur kV 36


Rated short-duration power-frequency withstand voltage Ud:
– phase-to-phase, phase-to-earth, open contact gap kV 70
– across the isolating distance kV 80
Rated lightning impulse withstand voltage Up:
– phase-to-phase, phase-to-earth, open contact gap  kV 170
– across the isolating distance kV 195
Rated frequency fr  Hz 50 / 60
Rated normal current Ir 2) for ring-main feeders A 630
for circuit-breaker feeders A 630
for busbar A 630
for transformer feeders A Depending on the
HV HRC fuse-link
50 Hz Rated short-time withstand current Ik for switchgear with tk = 3 s up to kA 20 / 25 4)
Rated peak withstand current Ip  up to kA 63
Rated short-circuit making current Ima for ring-main feeders up to kA 63
for circuit-breaker feeders up to kA 63
for transformer feeders up to kA 50
60 Hz Rated short-time withstand current Ik for switchgear with tk = 3 s up to kA 20 / 25 4)
Rated peak withstand current Ip  up to kA 65
Rated short-circuit making current Ima for ring-main feeders up to kA 65
for circuit-breaker feeders up to kA 65
for transformer feeders up to kA 52
Filling pressure Rated filling level pre (absolute) kPa 150
(pressure values at 20 °C) Minimum functional level pme (absolute) kPa 130
Ambient air temperature T 3) Operation standard  °C –25 to +55
Storage / transport standard  °C –25 to +55
on request  °C –40 to +70
Degree of protection for gas-filled switchgear vessel IP65
for switchgear enclosure IP2X/IP3X 1)
for low-voltage compartment IP3X/IP4X 1)

Switch-disconnector / fuse combination

Switching capacity for switch-disconnector / Rated mainly active load breaking current IloadA 200
fuse combination according to IEC 62271‑105 Rated transfer current ItransferA 740 5)
Maximum transformer rating kVA 2500
Switching capacity for make-proof Rated short-circuit making current Ima 50 Hz kA 5
­earthing switch, feeder side, in transformer 60 Hz kA 5.2
feeder with HV HRC fuses Rated short-time withstand current Ik with tk = 1 skA 2

Number of operating cycles, classifications

Three-position switch-disconnector Mechanical endurance Class M1


(IEC 62271‑103) Number of mechanical operating cycles n 1000
Electrical endurance Class E3
Number of electrical operating cycles with Iload n 100
Number of short-circuit making operations with Ima n 5
Capacitive switching Class C2
(no restrikes, TD: Icc, Ilc)

1) Design option
2) The rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (according to IEC  62271‑1 )
3) Minimum and maximum permissible ambient air temperature depending on the secondary equipment used
4) Transformer feeders up to 20 kA
5) At 36 kV and 50 Hz up to 800 A

8  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Technical data
Number of operating cycles, classifications, design and construction, internal arc classification

Number of operating cycles, classifications (continued)

Earthing switch Mechanical endurance Class M0


(IEC 62271‑102) Number of mechanical operating cycles n 1000
Electrical endurance Class E2
Number of short-circuit making operations with Ima n 5
Vacuum circuit-breaker Type 1 Circuit-breaker:
(IEC 62271-100) Rated operating sequence O – 0.3 s – CO – 3 min – CO
with three-position disconnector On request O – 0.3 s – CO – 15 s – CO
Mechanical endurance Class M2
Number of mechanical operating cycles n 10,000
Electrical endurance Class E2
Capacitive switching Class C2
Number of short-circuit breaking operations with Ik n 25 or 50
Three-position disconnector:
Mechanical endurance Class M0
(DISCONNECTING and EARTHING)
Number of mechanical operating cycles n 1000
(DISCONNECTING and EARTHING)
Electrical endurance (EARTHING) Class E2
Number of short-circuit n 5
making operations with Ima (EARTHING)
Type 2 Circuit-breaker:
Rated operating sequence O – 3 min – CO – 3 min – CO
Mechanical endurance Class M1
Number of mechanical operating cycles n 2000
Electrical endurance Class E2
Capacitive switching Class C2
Number of short-circuit breaking operations with Ik n 6 or 20
Three-position disconnector:
Mechanical endurance Class M0
(DISCONNECTING and EARTHING)
Number of mechanical operating cycles n 1000
(DISCONNECTING and EARTHING)
Electrical endurance (EARTHING) Class E2
Number of short-circuit n 5
making operations with Ima (EARTHING)

8DJH 36 switchgear is classified according to IEC 62271‑200 .

Design and construction Internal arc classification (option)

Partition class PM (metal partition) Designation of the internal arc Rated voltage 36 kV
Loss of service continuity classification IAC
category for panel types IAC class for
with ­cable termination – Wall-standing arrangement IAC A FL
– Feeder panels with LSC 2 – Free-standing arrangement IAC A FLR
­disconnector (R, T, L) Type of accessibility A Switchgear in closed electrical
– Billing metering panel M, LSC 1 service location, access
cable panel K for authorized personnel only
Accessibility to compartments (according to IEC 62271-200)
(enclosure) –F Front
– Busbar compartment – Non accessible –L Lateral
– Switching-device compartment – Non accessible –R Rear (for free-standing
– Low-voltage compartment (option) – Tool-based ­arrangement)
– Cable compartment for Arc test current Up to 25 kA
panels or panel blocks Test duration 1 s
– With HV HRC fuses (T) – Interlock-controlled
– Without HV HRC fuses (R, L) – Interlock-controlled
– Cable feeder only (K) – Tool-based
– Metering panels – Tool-based
(air-insulated) (M)

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  9
Product range
Individual panels and modules

Ring-main feeder Cable feeder

Type R Type K




430 mm wide 430 mm wide
Vacuum  

circuit-breaker

Three-position
switch-disconnector

Three-position
disconnector

Capacitive voltage
detecting system

HV HRC fuse
Transformer feeder Circuit-breaker feeder


Type T Type L


500 mm wide 590 mm wide



Current transformer
on the bushing 


4MU1

Cable-type
current transformer


4MC4_30 4MU1
Cable connection
with outside cone
(not included in the
scope of supply)

Surge arrester

Plug-in voltage
transformer
Bus sectionalizer panel

Type S Type S




Disconnectable and (earthing on the right) (earthing on the left)


plug-in voltage 590 mm wide 590 mm wide
transformer

1) O nly for end panel,


on the free connection
side of the busbar

10  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Product range
Air-insulated billing metering panel type M, 1100 mm wide

Billing metering panels with cable connection on the left




Current transformer,
cast-resin insulated
 
 
 
  Voltage transformer,
cast-resin insulated

Capacitive voltage
detecting system

Billing metering panels with cable connection on the right


Fixed earthing
points for
busbar earthing


P1 and P2
are terminal
 
designations of
 
  the current
  transformer

Billing metering panels with busbar connection on both sides




       

Billing metering panels with cable connection on both sides

 
 
 
 


Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  11
Product range
Product range overview of panel blocks

Panel blocks with transformer feeders,


optionally with busbar extension

Vacuum
Components shown in dotted lines can be used optionally.
circuit-breaker

RT 1 ring-main feeder, 1 transformer feeder


Three-position
switch-disconnector
Dimensions in mm

Width Depth Height

Three-position 930 920 1600


disconnector

Capacitive voltage
detecting system

RRT 2 ring-main feeders, 1 transformer feeder

HV HRC fuse
Dimensions in mm


Width Depth Height


1360 920 1600
Cable connection
with outside cone
(not included in the
scope of supply)

Surge arrester RTR 2 ring-main feeders, 1 transformer feeder

Dimensions in mm


Width Depth Height


1360 920 1600

KRT 1 cable feeder,1 ring-main feeder,


1 transformer feeder

Dimensions in mm


Width Depth Height


1360 920 1600

12  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Product range
Product range overview of panel blocks

Panel blocks with circuit-breaker feeders,


optionally with busbar extension

Vacuum
Components shown in dotted lines can be used optionally.
circuit-breaker

RL 1 ring-main feeder, 1 circuit-breaker feeder


Three-position
switch-disconnector
Dimensions in mm


Width Depth Height


1020 920 1600
Three-position
disconnector

Capacitive voltage
detecting system

RRL 2 ring-main feeders, 1 circuit-breaker feeder

HV HRC fuse
Dimensions in mm


Width Depth Height


1450 920 1600
Cable connection
with outside cone
(not included in the
scope of supply)

RLR 2 ring-main feeders, 1 circuit-breaker feeder Surge arrester

Dimensions in mm


Width Depth Height


1450 920 1600

KRL 1 cable feeder,1 ring-main feeder,


1 circuit-breaker feeder

Dimensions in mm


Width Depth Height


1450 920 1600

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  13
Design
Overview

2 4
6
Option

9
1600 8
12

917 10

13 11

14
920
590

1020

14  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Design
Overview

1 Low-voltage compartment 7 Enclosure


• Customer-specific options in different heights 200 mm, • Hermetically tight, welded switchgear vessel made of
400 mm, and 600 mm possible stainless steel
• Enclosure made of sendzimir-galvanized sheet steel,
2 Busbar extension, modularity
switchgear front powder-coated
• Busbar extension as an ordering option
• Plug-in unit consisting of contact coupling and screened 8 SiBushing
silicone coupling • Outside-cone bushing type C with integrated
• Insensitive to pollution and condensation ­measurement of current, voltage and temperature
• Switchgear installation, extension or panel replacement
9 Current sensor
without gas work
• Single-phase inductive current sensor
3 Indicators ­according to IEC 61869‑10
• Voltage detecting systems, short-circuit / earth-fault
10 Voltage sensor
indicators and transformer monitors from various
• Voltage sensor (resistor divider)
­manufacturers
­according to IEC 61869‑11
4 Ring-main feeder
11 Cable-type current transformer
• Switch positions: CLOSED – OPEN – EARTHED
• According to IEC 61869-1 and -2
• Switching functions as a general purpose
• Designed as ring-core current transformer, 1-phase
­switch-disconnector according to IEC 62271-103 and
• Free of dielectrically stressed cast-resin parts
IEC 62271-102
• Insulation class E
• Designed as a three-position switch with the following
• Inductive type
functions: switch-disconnector and make-proof earthing
• Secondary connection via terminal strip in the panel
switch
• With manual operating mechanism, optionally with 12 Cable compartment
motor operating mechanism • Bushings according to DIN EN 50181 with outside cone
and bolted connection M16 as interface type C (standard)
5 Transformer feeder
or with outside cone and plug-in contact as interface
• High-voltage switch-fuse combination according to
type B (option for transformer feeder)
IEC 62271‑105
• HV HRC fuse-links according to DIN 43625 Connection of:
(main dimensions) with striker; “medium” version • Cable elbow plugs or cable T-plugs (see page 24)
according to IEC 60282‑1 • Thermoplastic-insulated cables (1- and 3-core cables)
– as short-circuit protection of transformers • Mounted cable clamps on cable bracket (option)
– with selectivity – if correctly selected – to upstream • Surge arresters
and downstream equipment
13 Dimension options
– 1-phase insulated
• Switchgear heights 1600 mm
6 Circuit-breaker feeder • Deep cable compartment cover
• Consisting of a vacuum switching unit with an integrated
14 Pressure relief
three-position disconnector
• Pressure relief downwards
• According to IEC 62271‑100
• Optionally upwards with duct and optionally with absorber
• Circuit-breaker type L1 with 10,000 operating cycles and
• Up to IAC A FL 25 kA / 1 s or IAC A FLR 25 kA / 1 s
type L2 with 2000 operating cycles
• With manual operating mechanism, optionally with
motor operating mechanism
• Auxiliary switch for position indication
• Closing solenoid, shunt release, c.t.-operated release,
low-energy magnetic release, undervoltage release,
circuit-breaker tripping signal, varistor module, position
switch, and operation counter (options)

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  15
Design
Panel design (examples)

Ring-main feeder
Type R Section 
1 Control board
 2 Busbar arrangement
 3 Three-position switch-disconnector
4 Pressure relief device
5 Wiring duct, removable, for protection cables

 and / or bus wires (option)
6 Switchgear vessel, filled with gas
7 Operating mechanism of switching device
  8 Bushing for cable plug with bolted contact
(M16)
9 Cable compartment cover
 10 Earthing busbar with earthing connection

11 HV HRC fuse assembly




Transformer feeder
Type T Section 




 








16  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Design
Panel design (examples)

Circuit-breaker panel type 2


Section


1 Control board
2 Low-voltage compartment (option)
3 Busbar arrangement

4 Vacuum circuit-breaker and
­three-position switch module
5 Pressure relief device

6 Wiring duct, removable, for protection cables

and / or bus wires (option)
 7 Switchgear vessel, filled with gas
8 Operating mechanism of switching devices
 9 Bushing for cable plug with bolted contact

(M16)
10 Cable compartment cover
11 Current transformer on the bushing ­(option)
 12 Earthing busbar with earthing connection
13 Low-voltage compartment
14 SIPROTEC bay controller (option)

15 Plug-in voltage transformer 4MU1
 on the busbar (option)
 16 Bushing for connection of plug-in voltage
transformers on the busbar (option)
17 Earthing facility for the plug-in
voltage transformer 4MU1 at the cable
­connection (option)
18 Bushing for connection of plug-in ­voltage
transformers at the cable connection
­(option)

19 Plug-in voltage transformer 4MU1
at the cable connection (option)

Circuit-breaker panel type 1 with 400 mm high low-voltage compartment


Section









 








 





Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  17
Design
Panel design (examples)

Billing metering panel


Section
Type M, air-insulated  
1 Sockets for voltage detecting


 system (option)
 2 Busbar connection
3 Busbar vessel, filled with gas

4 Pressure relief device
5 Current transformer
 
type 4MA7
6 Voltage transformer
type 4MR
 7 Wiring duct, removable,
for pro­tection cables
and / or bus wires (option)

8 Niche for customer-side
low-voltage equipment,
screwed cover
9 Bushings for connection of
­instrument trans­former bars
10 Instrument transformer

­compartment cover
11 Cable connection
12 Earthing busbar with earthing
 connection

Connection: busbar – busbar

Section 












Connection: cable – cable

18  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Design
Outdoor enclosure

On request, 8DJH 36 switchgear can be provided with an


outdoor enclosure with the following features:

• For outdoor applications on company grounds


• Enclosure attached to standard indoor panels
• Enclosure with three different heights (optionally with
low-voltage compartment as a 200 mm, 400 mm or
600 mm high version)
• Enclosure with three different widths for freely configu-
rable, non-extendable switchgear rows up to a switchgear
width of 2040 mm (optional combination of two enclosures
up to a switchgear width of 4080 mm)
• Internal arc classification IAC A FL or FLR to 25 kA / 1 s
according to IEC 62271‑200
• Degree of protection IP54, weatherproofing test according
to IEC 62271-1.

R-HA40-161 tif

Outdoor enclosure (front closed)

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  19
Components
Busbar extension, modularity

Features

• Busbar extension possible on all individual panels and Interconnecting the panels
panel blocks (ordering option)   
• Plug-in unit consisting of contact coupling and screened
silicone coupling
• Insensitive to pollution and condensation
• Switchgear installation, extension or panel replacement is
possible without gas work.

Every switchgear block and every individual panel is option-


ally available with busbar extension on the right, on the left,
or on both sides. This offers a high flexibility for the creation
of switchgear configurations, the functional units of which
are lined up in any order. Local installation and lining up is
done without gas work.


Lining up takes place as follows:

• By the busbar couplings on the medium-voltage side. 


Tolerances between adjacent panels are compensated by
spherical fixed contacts and the movable contact ­coupling
with degrees of freedom in all axis directions.
• By safe dielectric sealing with screened silicone couplings
that are externally earthed and adjustable to tolerances.
These silicone couplings are pressed on with a defined
Surge-proof termination
pressure when the panels are interconnected.
• On free busbar ends, screened dummy plugs are inserted, 
each of which is pressed on through a metal cover.
A common protective cover with a warning is fixed over all
three covers.
• By centering bolts for easier switchgear installation and
fixing of adjacent panels.
• By bolted panel joints with defined stops for the distances
between adjacent panels and the associated pressure for
contact pieces and silicone couplings.

Switchgear installation, extension, or the replacement of


one or more functional units requires a lateral wall distance


≥ 200 mm.


 

1 Contact piece
2 Silicone coupling
3 Tension spring for earthing
4 Centering bolt
5 Silicone dummy plug with insertable sleeve
6 Clamping cover for dummy plugs
7 Busbar termination cover

20  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Components
Current transformers, voltage transformers

Current transformers according to IEC 61869‑1 and -2

R-HA41-024b eps

R-HA41-030 eps
Cable-type current transformer and Current transformer 4MA7
Type Cable-type current transformer 4MC7033
current transformer on the bushing (1-pole)
(1-pole)
4MC4_30 (1-pole)
Features • Designed as a ring-core current transformer • Dimensions according to
• Insulation class E DIN 42600-5
• Inductive type • Insulation class E
• Cast-resin insulated
• Designed as an indoor block-type
current transformer
• Secondary connection by means
of screw-type terminals
Installa- • Outside the switchgear vessel, around the • Outside the switchgear vessel, at the bushing, • In the air-insulated metering
tion cable at the panel connection or around the cable at the panel connection panel
• Installation on the cable on site (option in circuit-breaker panel)
• Note: Installation inside or underneath the • Note: Installation inside or underneath the
panel depending on the panel type and the panel depending on the overall transformer
overall transformer height height

Voltage transformers according to IEC 61869‑1 and -3


R-HA35-184 eps

R-HA41-029 eps

Type
4MU1 (1-pole) 4MR (1-pole)

Features • Inductive type • Dimensions according to DIN 42600-3


• Connection with plug-in contact • Designed as an indoor voltage transformer
• Safe-to-touch due to metal enclosure • Cast-resin insulated
• Secondary connection by means of plugs at the • Insulation class E
voltage transformer • Secondary connection by means of screw-type terminals
• For outside-cone system type C
• Busbar voltage transformer designed for up to 80 % of the rated
short-duration power-frequency withstand voltage at rated
frequency (option)
Installa- • Arranged on the switchgear vessel in individual panels type L; • In the air-insulated metering panel
tion connection directly at the busbar
• Arranged below the switchgear vessel in individual panels type L;
can be disconnected through an SF6-insulated earthing device in
the switchgear vessel; no removal necessary for cable testing

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  21
Components
Current sensors, voltage sensors

Current sensors (make Zelisko) according to IEC 61869‑6 and -10


The current sensors are inductive current transfor­mers whose secondary winding delivers a voltage signal through a precision
shunt. At the rated primary current, this is 225 mV.

Depending on their version, the sensors have a dual accuracy class; the output signal can be equally used for measuring,
protection and, if required, earth-fault detection. The signal can be directly used by devices with low-power input
(e. g. SICAM FCM, 7SJ81, 7SY82).

R_HA40-151 tif
R_HA40-152 tif
R_HA40-147 tif

Type Ring-core current sensor SMCS-JW 1001 Ring-core current sensor Ring-core current sensor
SMCS/T-JW 1002, divisible GAE120 / SENS-JW 1003
for earth-fault detection, divisible

Voltage sensors (make Zelisko) according to IEC 61869‑6 and -11


The voltage sensors are resistor dividers which provide an output signal of 3.25 V / √3 at the rated primary voltage.
The signal can be directly used by devices with low-power input (e. g. SICAM FCM, 7SJ81, 7SY82).
R-HA3541-194 tif
R_HA40-153 tif

Type Voltage sensor SMVS-UW1001 Voltage sensor SMVS-UW1002


for symmetrical cable plugs for non-symmetrical cable plugs

22  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Components
Cable connection

Features Cable compartment

• Bushings according to





DIN EN 50181 with outside
cone and bolted connection
M16 as interface type C,
or plug-in contact as interface



type B (option in


  
transformer feeder).      
   
       
Connection of

• Cable T-plugs with bolted 




contact M16 for 630 A Panel width 430 mm (R) Panel width 500 mm (T) Panel width 590 mm (L)
• Cable elbow plugs or
cable T-plugs with plug-in
contact for 400 A (option in
transformer panel)
• Thermoplastic-insulated cables
(1-core and 3-core cables)
• Mounted cable clamps on
cable bracket (option).

Cable plugs
Connection options
• As screened (conductive)
 
design independent of the site  

altitude.

Surge arresters
   


• Pluggable on cable T-plug or


T-adapter


• The switchgear depth can be





extended when surge arresters


are mounted (depending on
the make and type)
Single cable
• Surge arresters recommended
if, at the same time, 
– the cable system is directly
connected to the overhead
line,    
– the protection zone of the 1 Cable T-plug
surge arrester at the end tower 2 Cable elbow plug
of the overhead line does not




3 Surge arrester
cover the switchgear.
4 Coupling T-plug
5 Screw-type coupling insert
Double cable

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  23
Components
Cable connection

Cable plugs for single cable connection


Cable type Cable T-plug / cable elbow plug

Make Type Cross-section mm2 Comment


Thermoplastic-insulated cables 36 kV according to IEC 60502‑2
1-core cable, Nexans M400 LR/G 1) 50 to 240 EPDM with conductive layer
PE and M400 TE/G 1) 50 to 240 EPDM with conductive layer
XLPE-insulated
M400 TB/G 50 to 240 EPDM with conductive layer
N2YSY (Cu) and
N2XSY (Cu) M440 TB/G 300 to 630 EPDM with conductive layer
or M484 TB/G 50 to 630 EPDM with conductive layer
NA2YSY (Al) and M480 TB/G 50 to 300 EPDM with conductive layer
NA2XSY (Al) Südkabel SET 36-B 1) 70 to 300 Silicone with conductive layer
SET 36 70 to 300 Silicone with conductive layer
SEHDT33 300 to 500 Silicone with conductive layer
NKT CB36-400 1) 25 to 300 Silicone with conductive layer
CB36-630 25 to 300 Silicone with conductive layer
CB36-630 (1250) 400 to 630 Silicone with conductive layer
Cellpack CTS 630A 36 kV 35 to 400 EPDM with conductive layer
TE Connectivity RSTI-68xx 25 to 300 Silicone with conductive layer, with capacitive measuring point
RSTI-69xx 300 to 630 Silicone with conductive layer, with capacitive measuring point
Prysmian FMCT-400-X 1) 25 to 300 EPDM with conductive layer
FMCTs-400-X 25 to 300 EPDM with conductive layer
Cooper Power Systems DT436 25 to 240 EPDM with conductive layer
3 M Germany 94-EE 705-6/-XX 70 to 400 Silicone with conductive layer
3-core cable, Nexans M400 TB/G 50 to 240 EPDM with conductive layer, in combination with distribution kit
PE and M480 TB/G 35 to 300 EPDM with conductive layer, in combination with distribution kit
XLPE-insulated
NKT CB36-630 35 to 300 Silicone with conductive layer, in combination with distribution kit
N2YSY (Cu) and
N2XSY (Cu) CB36-630 (1250) 400 to 630 Silicone with conductive layer, in combination with distribution kit
or TE Connectivity RSTI-68xx 35 to 300 Silicone with conductive layer, with capacitive measuring point, in
NA2YSY (Al) and combination with distribution kit RSTI-TRF0x
NA2XSY (Al)
1) Cable T-plug or cable elbow plug with plug-in contact for interface type B
Larger cable cross-sections and other cable T-plugs or cable elbow plugs on request

Mounting depth for cable plugs


The panels feature a mounting depth of 300 mm for the The mounting depth for cable plugs can be additionally
connection of cable plugs. For circuit-breaker panels with extended by means of a 105 mm or 250 mm (dimension a)
current transformers on the bushing and / or voltage trans- deep cable compartment cover. The depth of the floor cutouts
formers at the cable c­ onnection, the mounting depth is (see dimension b) is increased from 756 mm to 861 mm or
reduced to 270 mm. 1006 mm due to the deep cable compartment cover.







   

 

 


        
    

For type R For type T For type L * For type L


2) Representation for circuit-breaker panel with operating mechanism L1

* With current transformer on the bushing and / or voltage transformer at the cable connection

24  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Components
Low-voltage compartment

Features
• Overall heights Low-voltage compartment (example 500 × 600 mm)
– 200 mm, 400 mm, 600 mm
– Cover (option)
• Partitioned safe-to-touch from the high-voltage part

R-HA40-128 eps
of the panel
• Installation on the panel
– Possible per feeder
– Option for all panel types, depending on the scope
of the secondary equipment
• Customer-specific equipment
For accommodation of protection, control, measuring and
metering equipment
• Separate wiring duct on panels without
low-voltage compartment (option).
Low-voltage cables
• Control cables of the panel to the low-voltage compart-
ment via multi-pole, coded module plugs Open low-voltage compartment
• Plug-in bus wires from panel to panel in the with built-in equipment (option)
separate wiring duct on the panel (option).
















   

Switchgear height
1600 mm

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  25
Dimensions
Room planning

Switchgear installation

Wall-standing arrangement

– 1 row
– 2 rows (for face-to-face arrangement)
A wall distance of ≥ 30 mm applies to the metering panel in
switchgear with billing metering panels, as well as in
switchgear with pressure relief downwards and in switch-
gear with pressure relief duct. Then, the wall distance of
the other panel types increases to ≥ 90 mm. In switchgear

HA40-24630 eps
with pressure relief to the rear / upwards, billing metering
panels have a wall distance of 90 mm. All other panel types
have a wall distance of 150 mm.

Free-standing arrangement (option)

Switchgear extension or panel replacement


Switchgear installation with pressure relief
For switchgear extension or for panel replacement, a control ­downwards
aisle of at least 1000 mm is recommended in front of the
switchgear. For panel replacement of lined up panels, there
must be a wall distance of at least 200 mm on one side.

Control aisle

In front of the switchgear, a control aisle of at least 800 mm


is required according to IEC 62271-200.
HA40-24640 eps

Switchgear installation with pressure relief duct


and optional absorber
HA40-24650 eps

Switchgear installation with pressure relief


to the rear / upwards

26  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
Dimensions
Room planning

Pressure relief Room heights

The following type-tested versions of the pressure relief • Minimum room heights according to the table below
system are available for 8DJH 36 switchgear: • As a difference to the minimum room heights according
• Downwards into the cable basement (for individual panels to the table, a minimum room height of 2200 mm
and panel blocks, internal arc classification up to applies to all pressure relief versions in circuit-breaker
IAC A FL 25 kA 1 s or IAC A FLR 25 kA 1 s) panels with busbar voltage transformers
• To the rear / upwards (for individual panels and panel • For billing metering panels with pressure relief to the rear /
blocks, internal arc classification up to IAC A FL 20 kA 1 s) upwards and with rear duct, a minimum room height of
• Upwards through rear pressure relief duct (for individual 2400 is required.
panels and panel blocks, internal arc classification up to
IAC A FL 20 kA 1 s or IAC A FLR 20 kA 1 s)
• Upwards through rear pressure relief duct and additional
absorber (for individual panels – except billing metering
panels – and for panel blocks, internal arc classification
up to IAC A FL 25 kA 1 s or IAC A FLR 25 kA 1 s).

Switchgear installation Switchgear installation


with pressure relief with pressure relief
downwards (standard) to the rear / upwards (option)
1 Floor opening



2 Direction of pressure relief


3 Expanded metal
4 Pressure relief with and without
absorber and pressure relief duct
directed upwards at the rear

5 Divided floor cover for cable
insertion, installation on site


 6 Termination plate

 
 

  
 *** Total opening minimum 0.48 m²


  

Switchgear installation Switchgear installation


with pressure relief duct (option) with pressure relief duct
and absorber (option)




Room heights for pressure relief


  to the rear/upwards and for switch-
gear with rear pressure relief duct




  Switchgear height Room height

1650 mm ≥ 2000 mm
  1700 mm ≥ 2000 mm

     


 

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  27
ANSI design
Panel design

Panel design
• Factory-assembled, type-tested switchgear according to
IEC 62271‑200
• Fulfills the IEEE Std C37.20.7 and CSA C22.2 No. 31-18
• Cable, ring-main and circuit breaker feeders as individual
panels or in a block
• Three-pole primary enclosure, metal-enclosed
• Welded switchgear vessel made of stainless steel, with
welded-in bushings for electrical and mechanical
­components
• Installation and extension of existing switchgear assem-
blies at both ends without gas work and modifications on
panels
• Bushings with outside cone according to IEEE Std 386,
interface 13
• Cable connection access from front
• Wall-standing or free-standing arrangement
• Pressure relief downwards or optionally through pressure
relief duct with pressure absorber
• Vacuum circuit breaker
• Three-position disconnect switch in circuit breaker panel
• Three-position load-current interrupter disconnect switch
in ring-main panel.

Outdoor enclosure
• Standard switchgear equipped with an outdoor
­enclosure (option)
• Attached to standard indoor panels
• Three different widths for four feeders up to a switchgear
width of 2040 mm
• Combination of two outdoor enclosures up to a switchgear
width of 4080 mm (option)
• Weatherproofing test according to IEEE Std C37.20.9
• Enclosure category C according to IEEE Std C37.20.9.

Viewing & Lighting System


• Patented Viewing & Lighting System (VLS) for visual verifi-
cation of the switch position of the three-position switch.

UL certification
• UL certification available for USA or Canada
• UL classification as an arc-resistant switchgear according to
IEEE Std C37.20.7.

28  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
ANSI design
Electrical data of the switchgear

Electrical data of the switchgear

Rated insulation level Rated voltage Ur kV 15 27 38


Rated short-duration power-frequency withstand voltage Ud:
– phase-to-phase, phase-to-ground, open contact gap kV 36 70 80
– across the isolating distance kV 40 77 88
Rated lightning impulse withstand voltage Up:
– phase-to-phase, phase-to-ground, open contact gap  kV 95 125 170
– across the isolating distance kV 105 138 187
Rated frequency fr  Hz 50 / 60 50 / 60 50 / 60
Rated continuous current Ir 2) for main bus A 600 600 600
for circuit breaker feeders A 600 600 600
for ring-main feeders A 600 600 600
50 Hz Rated short-time withstand current Ik for switchgear with tk = 2 s up to kA 25 25 25
Rated peak withstand current Ip  up to kA 63 63 63
Rated short-circuit making current Ima for ring-main feeders up to kA 63 63 63
for circuit breaker feeders up to kA 63 63 63
60 Hz Rated short-time withstand current Ik for switchgear with tk = 2 s up to kA 25 25 25
Rated peak withstand current Ip  up to kA 65 65 65
Rated short-circuit making current Ima for ring-main feeders up to kA 65 65 65
for circuit breaker feeders up to kA 65 65 65
Filling pressure Rated filling level pre (absolute) kPa (PSI) 150 (21.76) 150 (21.76) 150 (21.76)
(pressure values at 20 °C / 68 °F) Minimum functional level pme (absolute) kPa (PSI) 130 (18.85) 130 (18.85) 130 (18.85)
Ambient air temperature T 3) Operation standard  °C –25 to +55 –25 to +55 –25 to +55
°F –13 to +131 –13 to +131 –13 to +131
Storage / transport standard  °C –25 to +55 –25 to +55 –25 to +55
°F –13 to +131 –13 to +131 –13 to +131
on request  °C –40 to +70 –40 to +70 –40 to +70
°F –40 to +158 –40 to +158 –40 to +158
Degree of protection for gas-filled switchgear vessel IP65 IP65 IP65
for switchgear enclosure IP2X/IP3X 1) IP2X/IP3X 1) IP2X/IP3X 1)
for low-voltage compartment IP3X/IP4X 1) IP3X/IP4X 1) IP3X/IP4X 1)

1) Design option
2) The rated continuous currents apply to ambient air temperatures of max. 40 °C (104 °F).
The 24-hour mean value is max. 35 °C (95 °F) (according to IEC / EN 62271-1)
3) Minimum and maximum permissible ambient air temperature depending on the
secondary equipment used

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  29
ANSI design
Viewing & Lighting System, position indication

Viewing & Lighting System


• Optical system for visual verification of the switch position
of the three-position switch 
• No auxiliary voltage supply required 
• Access from the switchgear front 
• Fixed-mounted VL-base in the panel 
• VL-module withdrawable and usable for several feeders

• Protective bag with cleaning kit available (option).

Position indication
• Mechanical position indicator for circuit breaker and
three-position switch
• Visual check of the switch position of the
three-position switch through the VLS


• Electrical position indication of the circuit breaker
via signaling lamps in the operating front.


CLOSED


OPEN


GROUND

Circuit breaker





1 VL-module
2 Switch for light source
3 Eyepiece
4 Reference images
5 Protective cover
6 Electrical position indication for circuit breaker “OPEN”
7 Electrical position indication for circuit breaker “CLOSED”

30  Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022
ANSI design
Current transformers, voltage transformers

Current transformer features


• Designed as ring-core current transformers, single-pole
• Free of dielectrically stressed cast-resin parts
(due to design)
• Inductive type 
• Climate-independent
• Secondary connection by means of a terminal strip in
the low-voltage compartment of the panel
• Cast-resin insulated.

Voltage transformer features


• Single-pole, plug-in design
• Connection system plug-in contact according to
DIN EN 50181 
• Inductive type
• Safe-to-touch due to metal enclosure
• Climate-independent
• Secondary connection by means of plugs at the voltage
transformer
• Grounding device for feeder voltage transformers 
• Primary fuse integrated in the voltage transformer
• Cast-resin insulated. 


1 Main-bus voltage transformer with primary fuse


2 Feeder voltage transformer with primary fuse
3 Feeder current transformer around the bushing
4 Feeder current transformer around the cable

Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kV, Gas-Insulated · Siemens HA 40.3 · 2022  31
Published by
Siemens AG Smart Infrastructure combines the real and digital worlds
Smart Infrastructure across energy systems, buildings and industries, enhancing
Electrification & Automation the way people live and work and significantly improving
Mozartstraße 31 C
efficiency and sustainability.
91052 Erlangen, Germany
For further information, please contact We work together with customers and partners to create
our Customer Support Center:
an ecosystem that both intuitively responds to the needs of
Phone +49 180 524 70 00
Fax +49 180 524 24 71 people and helps customers achieve their business goals.
[email protected]
siemens.com/mittelspannungsschaltanlagen It helps our customers to thrive, communities to progress
siemens.com/8DJH36 and supports sustainable development to protect our planet
Article No. SIDS-C10081-00-7600 for the next generation.
Dispo 40401
VO 210870 en KG 01.22 0.0 siemens.com/smart-infrastructure

Medium-­
voltage
systems

Status 01/2022
Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may not
always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested
performance features are binding only when they are expressly agreed upon in the concluded contract.
© Siemens 2022