Field Experience For Passive Power Filter For Grid-Connected
Field Experience For Passive Power Filter For Grid-Connected
I. INTRODUCTION
Industrial power systems have harmonic currents,
which occur from non-linear loads such as AC drive
switching power mode supplies (SMPS). Nowadays,
alternative energy is used in current electricity generation
systems. It is applied to the original system as shown in Fig.
1. Solar energy is an alternating current that can generate all
harmonic currents. Additionally, the amount of electricity
Fig. 2 The example of single line diagram of solar rooftop
becomes the same type of AC drives, SMPS, and solar
inverters that exceed the limits of the IEEE 519- 1992 or + -
+ -
450.0 V
200.0 A
-200.0 A
-450.0 V
,((( 106
Authorized licensed use limited to: Middlesex University. Downloaded on July 18,2020 at 16:23:02 UTC from IEEE Xplore. Restrictions apply.
International Conference on Power, Energy and Innovation (ICPEI 2019)
October 16-18, 2019, Pattaya, THAILAND
Fig. 4 The solar intensity, %THDv and %THDi of 102kWp solar rooftop
MDB7 MDB5
IV. RESULTS
Fig. 5 The solar intensity ,%THDi and current of 102kWp solar rooftop B. Improved Harmonics Distortion
In Fig. 9 and 10 are shown about voltage, current, power
The value of the reactive power demand in this system is
and harmonic without and with PPF. The comparison result
around 200-275 kVAR and the average value is 257.2 kVAR
illustrates the power quality is improved. The waveform of
as presented in Fig. 8(c). Therefore, the PPFs should be
voltage and current are improved close to sine wave as show
designed the reactive power compensation at 250 kVAR.
in Fig.11 and the improvement can be confirmed the result
There is appropriate value for solving the 5th harmonic
from harmonics spectrum that shown in Fig.12
problem that occurred in electrical system.
107
Authorized licensed use limited to: Middlesex University. Downloaded on July 18,2020 at 16:23:02 UTC from IEEE Xplore. Restrictions apply.
International Conference on Power, Energy and Innovation (ICPEI 2019)
October 16-18, 2019, Pattaya, THAILAND
a) Voltage a) Voltage
b) Current b) Current
c) Power c) Power
d) Harmonics d) Harmonics
e) %THDv e) %THDv
f) %THDi f) %THDi
Fig. 9 One day for measurement without PPFs Fig. 10 One day for measurement with PPFs
108
Authorized licensed use limited to: Middlesex University. Downloaded on July 18,2020 at 16:23:02 UTC from IEEE Xplore. Restrictions apply.
International Conference on Power, Energy and Innovation (ICPEI 2019)
October 16-18, 2019, Pattaya, THAILAND
Fig. 11 The voltage and current waveform without and with the PPFs Fig. 13 The voltage and current spectrum without and with the PPFs
V. CONCLUSION
The electrical system with solar rooftop and the
harmonic result of solar rooftop can be solved the harmonic
problems by using a PPF methods. The level of harmonic
distortion is limited in accordance with IEEE 519-1992
standard. The %THD of voltage and current are reduced to
2.4% and 9.7%, respectively. The power factor improved
close to unity. The power factor measurement represents the
ability to supply power to loads and it is a significant factor
indicates system losses. All three parameters are indicator of
the good quality of the electrical system and the confidence
of the system. Therefore, we are confident that this system
can operate with the highest efficiency. Moreover, the
extraordinary qualifications of PPFs are low cost, low
maintenance, high reliability and the PPFs installation can be
combined easily with the existing system without problems.
Fig. 12 The %THDi and %THDv without and with the PPFs REFFERENCES
[1] C. Boonseng, V. Kinnares and W. Khan-ngan, “ An Implementation
of Harmonic Filter Installations for Improved Quality and Reduced
C. Improved Harmonics Resonance Voltage and Current Distortion in UPS System”, IPEC’99
International Power Engineering Conference, Vol II, May 24-26,
PPFs installing can solve this problem, it helps to 1999.
eliminate and control the number of voltage and current [2] G. Chang, Hong-Lu Wang, So-Yung Chu, “Strategic placement and
harmonics to limit as defined standard and prevent sizing of passive filters in a power system for controlling voltage
resonance. After PPFs installation, the electrical system of distortion”, IEEE Power Engineering Society General Meeting, Jun 6-
10, 2004.
industry is not interrupted and an electronic equipments are
not damaged although the harmonic current from solar [3] Z. Chen, F. Blaabjerg and J. K. Pedersen, “A Hybrid Compensation
System with An Active Filter and Distributed Passive Filters in Power
inverter will raise up. The system can maintain the value of Systems with Dispersed Generation”, IEEE 34th Annual Conference
power factor approaches to unity. The PPFs is worth to apply on Power Electronics Specialist, Jun 15-19, 2003.
with the electrical system for industry. The integration of [4] S. Bhattacharya, Po-Tai Cheng, D.M. Divan, “Hybrid solutions for
original electrical system with solar energy system which can improving passive filter performance in high power applications”.
leads to nervous system failure. The degree of harmonic IEEE Transactions on Industry Applications, Vol. 33, No. 3, May/June
severity in the system is not combined with the passive 1997, pp. 732-747.
power filter system (PPFs) can be considered by measuring [5] C. Boonseng, B. Rapeepornpat, D. Suksawat, “ Design and Installation
of Passive Power Filter for Grid-connected Solar Rooftop
electric parameters during actual operation period at full Applications at Industrial Plants”, 2019 IEEE PES GTD Grand
loads as show in Fig. 13. The 5th harmonic were increased International Conference and Exposition Asia (GTD Asia), Mar 19-23,
from 102 A to 205 A because the solar inverter operation 2019.
causes the resonance at the 5th harmonic occurs. [6] J. C. Das, “Passive Filters-Potentialities and Limitations”, IEEE
Trans. Ind. Appl., vol40, no. 1, Jan/Feb, 2004.
109