Krom Schroder BCU 460 465
Krom Schroder BCU 460 465
Technical Information · GB
6 Edition 07.12
• Automatic burner control unit, ignition transformer, indicators and operating controls
in a space-saving metal housing which replaces the local burner control cabinet
• For directly ignited burners of unlimited capacity in intermittent or continuous
operation pursuant to EN 746-2
• Flame control by UV, ionization or a further option of using the furnace
chamber temperature
• Display of the program status, unit parameters and flame signal; manual
mode for burner adjustment and for diagnostic purposes
• Visualization and adaptation to the specific application via the PC programming
and diagnostic software BCSoft to simplify logistics management.
• Spacious connection chamber with plug-in terminal blocks and plug-in cable
glands for quick installation and servicing
• Air valve control on BCU..L relieves the furnace control
• Optional PROFIBUS DP interface for easy transmission of activation signals
and feedbacks via fieldbus cable
• EC type-tested and certified
• Certified for systems up to SIL 3 and compliant with PL e
Contents
Burner control units BCU 460, BCU 465 . . . . . . . . . . . . . . . . 1 3.1.14 BCU 465..B1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.1.15 BCU 465T..B1..E1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.1.16 BCU 465T..B1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3.2 BCU..P with 16-pin industrial plug connector . . . . . . . 32
1.1 Examples of application . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3.3 PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
1.1.1 BCU 460: Modulating-controlled burner . . . . . . . . . . . . . . . . 7 3.3.1 Safety-related control signals . . . . . . . . . . . . . . . . . . . . . . . 33
1.1.2 BCU 460..L: Two-stage-controlled burner . . . . . . . . . . . . . . 8 3.3.2 BCSoft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
1.1.3 BCU 460..L: Single-stage-controlled radiant tube burner . . 9 3.3.3 Configuration, Master-Slave procedure . . . . . . . . . . . . . . 34
1.1.4 BCU 465..L: Single-stage-controlled burner with 3.3.4 Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
pneumatic 3.3.5 Network technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
air/gas ratio control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.3.6 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1.1.5 BCU 465..L: Single-stage-controlled burner . . . . . . . . . . . . . 11 3.3.7 Bus communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1.1.6 BCU 460..B1 for PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . 13
1.1.7 BCU 460..D: High temperature equipment . . . . . . . . . . . . 13 3.4 BCU 460 program sequence . . . . . . . . . . . . . . . . . . . . 37
2 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3.5 BCU 465 program sequence . . . . . . . . . . . . . . . . . . . 39
2.1 Certified pursuant to SIL . . . . . . . . . . . . . . . . . . . . . . . . . 14 3.6 Program status and fault messages . . . . . . . . . . . . . 42
2.2 EC type-tested and certified . . . . . . . . . . . . . . . . . . . . . 14 4 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2.3 CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 4.1 Scanning the parameters . . . . . . . . . . . . . . . . . . . . . . . 45
2.4 FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 4.2 Flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.2.1 Burner flame signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2.5 PROFIBUS User Organization . . . . . . . . . . . . . . . . . . . . 15 4.2.2 Switch-off threshold of the flame amplifier . . . . . . . . . . . . 46
2.6 Approval for Russia . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 4.2.2 High temperature operation in the case of BCU..D2 or
3 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 BCU..D3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
4.2.3 UVS check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3.1 Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.1 BCU 460..E1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 4.3 Behaviour in start-up position/standby . . . . . . . . . . . 50
3.1.2 BCU 460 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 4.3.1 Flame-simulation check in start-up position/standby . . . 50
3.1.3 BCU 465..E1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 4.3.2 Position indicator input on BCU 465T..O (POC) . . . . . . . . . 51
3.1.4 BCU 465 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 4.3.3 Minimum burner pause time tBP . . . . . . . . . . . . . . . . . . . 52
3.1.5 BCU 465T..E1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 4.4 Behaviour during start-up . . . . . . . . . . . . . . . . . . . . . . 53
3.1.6 BCU 465T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 4.4.1 Safety time on start-up tSA . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.1.7 BCU 460..P..E1 with industrial plug connector . . . . . . . . . . 22 4.4.2 Minimum burner on time tB . . . . . . . . . . . . . . . . . . . . . . . 53
3.1.8 BCU 460..P with industrial plug connector . . . . . . . . . . . . 23 4.4.3 Flame proving period tFS . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.1.9 BCU 465..P..E1 with industrial plug connector . . . . . . . . . . 24 4.4.4 Burner start-up attempts . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.1.10 BCU 465..P with industrial plug connector . . . . . . . . . . . . 25 4.5 Behaviour during operation . . . . . . . . . . . . . . . . . . . . 55
3.1.11 BCU 460..B1..E1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 4.5.1 Safety time during operation tSB for V1 and V2 . . . . . . . . . 55
3.1.12 BCU 460..B1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.5.2 Fault lock-out or restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
3.1.13 BCU 465..B1..E1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 4.5.3 Immediate fault lock-out after installation fault . . . . . . . . 56
1 Application The BCU 465..L is fitted with air flow monitoring and pre- and
The burner control units BCU 460 and BCU 465 control, ignite post-ventilation for use on recuperative burners.
and monitor gas burners for intermittent or continuous opera- The program status, the unit parameters and the level of the
tion. As a result of their fully electronic design, they react quickly flame signal can be read directly from the unit. The burner
to various process requirements and are therefore suitable can be controlled manually for commissioning and diagnostic
for frequent cycling operation. purposes.
They can be used for directly ignited industrial burners of un- If the local requirements on the burner control unit change, the
limited capacity. The burners may be modulating or stage- PC software BCSoft can be adjusted to the unit parameters of
controlled. The BCU is installed near the burner to be monitored. the application by using the optical interface.
On industrial furnaces, the BCU reduces the load on the cen- ▼
tral furnace control by taking over tasks that only relate to the
burner, for example it ensures that the burner always ignites
in a safe condition after it has been restarted.
The optional air valve control on the BCU..L assists the furnace
control for cooling, purging and capacity control tasks.
Hardening furnace
with lots of industri-
al burners located
side-by-side
DI
BCU 460 6 3 5 4
19
18
µC
17
16
12 9
VG..L GIK
BIO
BIC
DK+GT M
DI P A
6 3 5 22 23 4
19
18
µC
17
16
BCU 460..L 12 26 9
VG..N GIK..B
BIO
BIC
VR..R
L1, N, PE
DI P
PLC
DI P A
6 3 5 22 23 4
19
18
µC
17
16
BCU 460..L 12 26
VG..L
BICR
VR..R
19
18
µC
17
16
BCU 465..L 12 26 21
VG..L
BICR
VR..R
DI P A
6 3 5 22 23 4
19
18
µC
17
16
BCU 465..L 12 26 21
VG..L EKO
GEH
BICR
VR..R
LEH EKO
L1, N, PE
DI P
PLC
DI P A
6 3 5 22 23 4
19
18
µC
17
16
BCU 465..L 12 26 21
VG..L
BICR
VR..R
40 41 42 43 44 45 46 47
µC
88 F3
O N1
230V~
I N1 c1 v1 N1 v2 N1 n s l
c2 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 26 27 30 31 32 33 34 35 36 37 38 50 51
max. 2 A, max. 2 A,
253 V 253 V
A
Z I V1 V2
ϑ DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
1
UVS 2
3
3 Function
3.1 Connection diagrams
3.1.1 BCU 460..E1
For cable selection and wiring, see page 68 (Project plan-
ning information).
For the explanation of symbols, see page 83 (Legend).
40 41 42 43 44 45 46 47
µC
88 F3
O
230V~
I N1 c1 v1 N1 v2 N1 n s l
c2 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 26 27 30 31 32 33 34 35 36 37 38 50 51
max. 2 A, max. 2 A,
253 V 253 V
A
Z I V1 V2
ϑ DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
1
UVS 2
3
40 41 42 43 44 45 46 47
C
88 F3
O N1
230V~
I v1 N1 v2 N1 n s m l
c2 N1 c1 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
max. 2 A, max. 2 A,
253 V 253 V
A
Z I V1 V2
ϑ DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
1
UVS 2
3
40 41 42 43 44 45 46 47
C
88 F3
O
230V~
I v1 N1 v2 N1 n s m l
c2 N1 c1 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
max. 2 A, max. 2 A,
253 V 253 V
A
Z I V1 V2
ϑ DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
1
UVS 2
3
40 41 42 43 44 45 46 47
C
88 F3
O N1
230V~
I v1 N1 v2 N1 n s m l
c2 N1 c1 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
max. 2 A, max. 2 A,
253 V 253 V
OCS**
Digital input*
A
Z I V1 V2
ϑ DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
* = BCU 465T..D2
= BCU 465T..D3
** = BCU 465T..O
1
UVS 2
3
40 41 42 43 44 45 46 47
C
88 F3
O
230V~
I v1 N1 v2 N1 n s m l
c2 N1 c1 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
max. 2 A, max. 2 A,
253 V 253 V
OCS**
Digital input*
A
Z I V1 V2
ϑ DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
* = BCU 465T..D2
= BCU 465T..D3
** = BCU 465T..O
1
UVS 2
3
40 41 42 43 44 45 46 47
µC
88 max. 2 A, max. 2 A,
F3
O N1 253 V
230V~
253 V
I N1 c1 v1 N1 N1 n s l
c2 v2 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 26 27 30 31 32 33 34 35 36 37 38 50 51
16 15 14 8 7 6 12 11 10 9 4 3
Z I V1 V2
DI P A 7 8 9 7 8 9 10 11
8 7 6 4 3
16 15 14 12 11 10 9
1
UVS 2
PE 3
L1
N
40 41 42 43 44 45 46 47
µC
88 max. 2 A, max. 2 A,
F3
O 253 V
230V~
253 V
I N1 c1 v1 N1 N1 n s l
c2 v2 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 26 27 30 31 32 33 34 35 36 37 38 50 51
16 15 14 8 7 6 12 11 10 9 4 3
Z I V1 V2
DI P A 7 8 9 7 8 9 10 11
8 7 6 4 3
16 15 14 12 11 10 9
1
UVS 2
PE 3
L1
N
40 41 42 43 44 45 46 47
C
88 max. 2 A, max. 2 A,
F3
O N1
230V~
253 V 253 V
I v1 N1 v2 N1 n s m l
c2 N1 c1 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
16 15 14 8 7 6 12 11 10 9 4 3
Z I V1 V2 p
DI P A 7 8 9 7 8 9 10 11
8 7 6 4 3
16 15 14 12 11 10 9
1
UVS 2
PE 3
L1
N
40 41 42 43 44 45 46 47
C
88 max. 2 A, max. 2 A,
F3
O
230V~
253 V 253 V
I v1 N1 v2 N1 n s m l
c2 N1 c1 l N1
1 2 3 4 5 6 PE 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
16 15 14 8 7 6 12 11 10 9 4 3
Z I V1 V2 p
DI P A 7 8 9 7 8 9 10 11
8 7 6 4 3
16 15 14 12 11 10 9
1
UVS 2
PE 3
L1
N
40 41 42 43 44 45 46 47
µC
88 F3
230V~
O
I N1 c2 N1 c1 v1 N1 v2 N1 s
l N1
l
1 2 5 6 PE 7 8 9 10 11 12 13 14 15 18 19 20 22 26 27 30 31 32 33 34 35 36 37 38 50 51
max. 2 A,
253 V
Z I V1 V2
DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
BCU..B1/1
2A 2B 1A 1B
ON ON
OFF OFF
1
UVS 2
3
PROFIBUS-DP
40 41 42 43 44 45 46 47
µC
88 F3
230V~
O
I N1 c2 N1 c1 v1 N1 v2 N1 s
l N1
l
1 2 5 6 PE 7 8 9 10 11 12 13 14 15 18 19 20 22 26 27 30 31 32 33 34 35 36 37 38 50 51
max. 2 A,
253 V
Z I V1 V2
DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
BCU..B1/1
2A 2B 1A 1B
ON ON
OFF OFF
1
UVS 2
3
PROFIBUS-DP
40 41 42 43 44 45 46 47
C
88 F3
230V~
O
I N1 c2 N1 c1 v1 N1 v2 N1 s
l N1 m l
1 2 5 6 PE 7 8 9 10 11 12 13 14 15 18 19 20 21 22 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
max. 2 A,
253 V
Z I V1 V2
DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
BCU..B1/1
2A 2B 1A 1B
ON ON
OFF OFF
1
UVS 2
3
PROFIBUS-DP
40 41 42 43 44 45 46 47
C
88 F3
230V~
O
I N1 c2 N1 c1 v1 N1 v2 N1 s
l N1 m l
1 2 5 6 PE 7 8 9 10 11 12 13 14 15 18 19 20 21 22 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
max. 2 A,
253 V
Z I V1 V2
DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
BCU..B1/1
2A 2B 1A 1B
ON ON
OFF OFF
1
UVS 2
3
PROFIBUS-DP
40 41 42 43 44 45 46 47
C
88 F3
230V~
O
I N1 c2 N1 c1 v1 N1 v2 N1 s
l N1 m l
1 2 5 6 PE 7 8 9 10 11 12 13 14 15 18 19 20 21 22 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
max. 2 A,
253 V
OCS**
Digital input*
Z I V1 V2
DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
BCU..B1/1
* = BCU 465T..D2
= BCU 465T..D3
2A 2B 1A 1B
** = BCU 465T..O ON ON
OFF OFF
1
UVS 2
3
PROFIBUS-DP
40 41 42 43 44 45 46 47
C
88 F3
230V~
O
I N1 c2 N1 c1 v1 N1 v2 N1 s
l N1 m l
1 2 5 6 PE 7 8 9 10 11 12 13 14 15 18 19 20 21 22 25 26 27 28 29 30 31 32 33 34 35 36 37 38 50 51
max. 2 A,
253 V
OCS**
Digital input*
Z I V1 V2
DI P
L1 (L1)
N (L2)
PE
7 8 9 7 8 9 10 11
BCU..B1/1
* = BCU 465T..D2
= BCU 465T..D3
2A 2B 1A 1B
** = BCU 465T..O ON ON
OFF OFF
1
UVS 2
3
PROFIBUS-DP
3.3 PROFIBUS DP
BCU..B1 features the same scope of functions and performance
of a BCU® without a PROFIBUS connection.
PROFIBUS is a manufacturer-independent, open fieldbus stand-
L1, N, PE
ard for diverse applications.
DI P
PROFIBUS DP is a bus variant for communication between
SPS automation systems and distributed peripherals at the field
PLC
level, optimized for speed and low connection costs.
BUS
API
On PROFIBUS DP, the individual bus stations are connected
via a 2-core shielded cable as standard.
PROFIBUS DP
The bus system transfers the control signals for starting, re-
BCU..B setting and for controlling the air valve to purge the furnace
or kiln or for cooling in start-up position and heating during
1– 6 BUS operation from the control system (PLC) to the BCU..B1. In the
opposite direction, it sends operating status, the level of the
flame signal and the current program status.
1
3.3.1 Safety-related control signals
BCU..B Signals from the safety interlocks and digital input are trans-
ferred independently of the bus communication by separate
1– 6 BUS cables. The air valve used to purge the furnace or kiln can
either be activated via the PROFIBUS or via a separate cable
to terminal 22. The purging process must be monitored by
2
further measures, e.g. flow monitoring.
BCU..B
1– 6 BUS
1
2
/
power supply for the bus terminator is provided by the BCU.
0 – 25.5 µA 2
255 steps
255 steps
Reserved
The bus terminator can be connected in the bus connection 3 A on
0 – 25.5 µA
plug. 4 P on
4 ϑ2
5 Reserved
6 Reserved
7 Reserved
▼
BCU03
460, BCU 465 · Edition 07.12 37
Flame proving period tFS
max. 3 start-up attempts
or fault lock-out
Function > BCU 460 program sequence
The burner can also be started manually
with the aid of the switch on the BCU.
03 Flame proving period tFS Voltage must be applied continuously
running (P23) to terminals 1, 4 and 5 in order for this
to occur.
In the event of flame failure: The BCU can also be operated in Manual
fault lock-out
mode for start-up.
04 The air valve can also be set to Start-up without flame signal
Operation signalling
contact closes open with V2 or to be activated If no flame is detected during the safety
and V2 opens externally (display A4 ) via pa- time tSA, either a fault lock-out occurs or
rameter 30. up to two further start-up attempts occur.
In the event of flame failure: The required functions and, if applicable,
restart or the number of start-up attempts must be
fault lock-out specified when ordering. (Parameter 10,
“Burner start-up attempts”).
Behaviour in the event of flame failure
04 Controlled shut-down during operation
via ϑ signal
If the flame fails during operation, either
an immediate fault lock-out or a restart
00 If min. burner on time tB occurs. This procedure can be set via the
has elapsed: optical interface (parameter 12, “Burner
operation signalling
contact opens, restart”).
V1 and V2 close,
min. burner pause time tBP
starts to elapse (P21)
If parameter P15 = 0:
flame simulation check
BCU 465T..B1
BCU 460..B1
BCU 465..B1
BCU 465T
BCU 460
BCU 465
Program status DISPLAY Fault message (flashing)
BCU 465T..B1
BCU 460..B1
BCU 465..B1
BCU 465T
BCU 460
BCU 465
Program status DISPLAY Fault message (flashing)
= standard, = available.
* Adjustable using BCSoft software and a PC opto-adapter
** Please quote in your order
0 = Function inactive,
1 = Function active.
04 04 88
1
5
4 ϑ
6 DI
7
9
12 V1
14 V2
16-17
18-19
t
BCU 465T..O
12 21 14 mA
V1
V2
OCS
PLC
04 00 01 02 03 04 88
1
5
4 ϑ DI P A
7 6 3 5 22 23 4
9
12 V1 19
18
14 V2 µC
16-17 17
18-19 16
tSA
VG..N GIK..B
An immediate restart of the burner after a controlled shut-down
is prevented by the pause time. The pause time starts when BIO
BIC
the burner is switched off. If a start-up signal (ϑ) is applied
VR..R
before expiry of this time, start-up is delayed until the end of
the pause time.
After the pause time, the burner is started if the start-up signal
(ϑ) is applied.
The minimum burner pause time tBP serves to adapt the pro-
gram sequence to the requirements of the application.
The time should be set such that the system can be moved to
ignition position, i.e. air valves or butterfly valves can be closed
and, possibly, gas can be flared off, before a restart occurs.
00 02 02 88 00 02 88
1 1
5 5
4 4 ϑ
7 7
9 9
12 V1 12 V1
14 V2 14 V2
16-17 16-17
18-19 18-19
tZ t tZ tZ t
t SA tSA tSA
If no flame forms or, in the case of BCU 465, if the air flow fails If several start-up attempts are set at the works and if the BCU
during start-up, a fault lock-out is performed after expiry of detects an installation fault during start-up, it closes valve V1
time tSA. The display blinks and shows the cause of the fault. after the safety time tSA has expired and attempts to start up
again. After the last programmed start-up attempt has been
completed, the burner control unit conducts a fault lock-out.
The display blinks and shows the cause of the fault.
1x
04 04 88 04 01 02 03 04 88
1 1
5 5
4 ϑ 4 ϑ
7 7
9 9
12 V1 12 V1
14 V2 14 V2
>2 s 16-17
16-17
18-19 18-19
t tFS t
tSB tSB tZ
tW tSA
4.6 Air valve control on BCU..L 4.6.3 Air valve opens in the case of external activation (not
Parameter 30, “Air valve control” during start-up)
Parameter 31, “Air valve can be activated externally on start-up”
00 A0 02 03 A4 88
Parameter 32, “Air valve closed/can be activated in the event 1
5
of malfunction” 4 ϑ
7
The BCU..L features an adjustable air valve control. The display 9
12 V1
shows that purging is currently being carried out with P0 . A 14 V2
indicates that the air valve is being activated for cooling or 23 A
26
heating. The BCU supports the following functions: 16-17
18-19
4.6.1 Purge tZ tFS t
In the case of multiple burner applications, burners with me- tSA
chanical combustion air supply are used. The air for combus-
tion and pre-purge is supplied by a central fan controlled by
a separate logic. This logic determines the purging time. Parameter 30 = 0: The air valve opens if it is activated exter-
The BCU..L supports centrally-controlled pre-purge or post- nally by input 23.
purge. The BCU..L is informed that purging is currently being Parameter 31 = 0: The air valve remains closed during start-up
performed by input 22. It then opens the air valve, regardless even if it is activated externally.
of the status of the other inputs (purging has priority). The These settings are required on burners on which the gas/air
display indicates P0 . ratio is controlled by a pneumatic air/gas ratio control system
For purging, the safety interlock (limits) must activate input 5 link and which also need to be started at low fire, e.g. on
and input 22 of the BCU. two-stage-controlled burners, see page 8 (BCU 460..L:
Two-stage-controlled burner). In this case, activation of the
4.6.2 Cooling in start-up position/standby
air valve during burner start via input 23 must be prevented.
The air valve can be activated externally by input 23 for cooling
in the start-up position. During activation of the air valve, the External control allows switchover between low fire and high
display shows A0 , indicating that cooling is currently being fire during operation.
carried out.
Parameters 30 and 31 determine the behaviour of the air valve
during burner start.
19
18
Parameter 36 tKN = 0: Without low fire over-run, the gas circuit µC
17
is closed immediately owing to the quick-closing gas valve in 16
BCU 460..L 12 26 9
the case of On/Off control. The air circuit closes more slowly.
The air flowing in during the closing time increases the O2
VG..N GIK..B
percentage in the combustion chamber.
BIO
Parameter 36 tKN = 5, 15 or 25 s: The air valve is closed with BIC
deactivated start-up signal (ϑ). The gas valve remains open VR..R
for tKN. This means that the burner, after deactivation of the
start-up signal (ϑ), is initially adjusted down to low fire and A4 00 88
then switched off completely. 1
5
Using the low fire over-run function reduces the O2 percentage 4 ϑ
7
in the furnace atmosphere. 9
12 V1
Flame control is still operational. 14 V2
23 A
Can be used only in the case of a pneumatic air/gas ratio 26
16-17
control system and On/Off control. 18-19
Its must be ensured that no excess gas occurs. tKN t
4.7 Extended air control with BCU 465..L Check of the HIGH signal (pressure switch contact closed)
For use on recuperative burners, the BCU 465..L features an The air must flow and a HIGH signal must be applied to the
extended air control which meets the specific requirements pressure switch during pre-purge. If the HIGH signal is not
of such burners. applied, the BCU performs a fault lock-out after expiry of the
testing time (as long as the safety time on start-up). Error mes-
4.7.1 Air flow monitoring during purging (BCU 465..L) sage: P , no air flow.
Parameter 06
This parameter determines whether the air flow is monitored
during pre-purge.
Parameter 06 = 0: The air flow is not monitored during pre-
purge.
Parameter 06 = 1: The air flow is monitored during pre-purge
(pressure switch signal at terminal 21), i.e.
Check of the LOW signal (pressure switch contact open)
No air may flow before pre-purge. A LOW signal must be ap-
plied to the pressure switch. If the LOW signal is not applied,
the BCU performs a fault lock-out after expiry of a delay time
(as long as the flame simulation delay time tLV). Error message:
0 , “no flow” state check failed.
After the start-up signal (ϑ) has been applied and after the
flame simulation check and “no flow” state check have been
conducted successfully, the air valve is opened. Start-up of
the burner commences as usual with no interruption of the
air after expiry of the programmable pre-ventilation time tVL.
(Parameter setting for this example sequence:
P15 = 1, P23 = 0, P30 = 1, P37 > 0), see page 44 (Param-
eters). The gas valve does not open until the pressure switch
has switched.
The air valve remains open for the programmed time after the
start-up signal (ϑ) has been deactivated. The burner control
unit closes the air valve after expiry of the post-ventilation
time tNL.
40 41 42 43 44 45 46 47
6.11 BCU and BCU..E1 C
88 F3
O
230V~
BCU I c2 N c1 v1 N v2 N
l N m l
The BCU is
1 available
2 3 4 as
5 a replacement
6 PE unit 7for8existing
9 10 11 systems
12 13 14 15 5 21 22 23 28 29 30 31 32 33 34 35 36 37 38 50 51
in which a BCU is already in operation.
BCU..E1
We recommend using the BCU..E1 when planning new systems.
It features a new power management scheme for simplified
installation and control. The power for the ignition transformer A
and valves is supplied via the phase (terminal
Z I
1) andV1must
V2
ϑ DI P
no longer be supplied by the safety interlocks. No effort and
expenditure is thus required for coupling contactors and their L1 (L1)
N (L2)
safety devices. PE
Unit replacement 7 8 9 7 8 9 10 11
6.13 PROFIBUS DP In addition, it must be ensured that all cables leading to and
from the BCU® be installed as far away as possible from
6.13.1 Safety-related control signals cables emitting strong fields (e.g. frequency converter cables).
Signals from the safety interlocks and digital input are trans-
ferred independently of the bus communication by separate 6.13.4 Unit replacement
cables. A BCU..B1 (for PROFIBUS) may only be replaced by a BCU..B1.
The purge signals can be transferred via the bus communica- BCUs without a PROFIBUS connection may not be replaced
tion or by a separate cable. by a BCU..B1.
PROFIBUS DP
6.14 Third gas valve (can be shut down) on The following application describes a two-stage-controlled
BCU 460..L and BCU 465 burner without a pneumatic air/gas ratio control system. V2
and the air valve are activated simultaneously. However, V2
Units with air valve control have an additional contact (terminal
may not be activated during purging.
50/51), which closes at the same time as the air valve.
This can be used to activate a third gas valve. To do this, the ϑ
output of valve V1 or V2 must be used as auxiliary energy (as L1 4 BCU 460..L
19/20
a result of the required flame monitoring). 3
18
A
23 51
N
12 26 9 12 50
13 14 15 50 51 V1 V2
VG..N
V2 V3
VG..N BIO
BIC
VR..R
Bibliography
– PROFIBUS Specification, EN 50170 Vol. 2 (version 1.0).
Order No.: 74919469 – Installation Guideline for PROFIBUS DP/FMS, available
from the Profibus User Organization (PUO).
– PROFIBUS Technology and Application, Order No.: 4.001,
available from the PUO.
– M. Popp, The New Rapid Way to PROFIBUS DP, a textbook
for system operators.
– M. Popp, PROFIBUS DP Principles, Tips and Tricks for Us-
ers.
– www.profibus.com
m mm
212 m 174
45
230 mm
mm
185 mm
ø 4mm
9.1 BCU..B1
External fuse: 12 A per zone.
9.2 PROFIBUS DP
Manufacturer ID: 0x05DB.
ASIC type: SPC3.
SYNC- and FREEZE-capable.
Baud rate detection: automatic.
Min. cycle time: 0.1 ms.
Diagnostic bytes: 6 (DP Standard).
Parameter bytes: 7 (DP Standard).
0.177"
If the flame fails during operation, the valve outputs are dis- gas valve V2 is opened. It remains open until the burner is
40 41 42 43 44
switched off or a fault is signalled.
connected within the safety time tSB. µC
88 F3
O
The default safety time during operation t in accord-
230V~
I SB N1 c1 v1 N1 v2 N1 n s
c2 l N1
ance with EN 298 is 1 second. In accordance with
1 2 3 4 5 6 PE 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 26 27 30 31 32 33 34
EN 746-2, the safety time of the installation during 7opera-
tion (including closing time of the valves) may not exceed 3 s.
Note the requirements of the Standards! max. 2 A, max. 2 A,
253 V 253 V
Remarks
sdcdscdsc Kromschröder AG
Michael Rehkamp
[email protected]
Osnabrück
Contact
Elster GmbH The current addresses of our international agents are
Postfach 2809 · 49018 Osnabrück available on the Internet:
Strotheweg 1 · 49504 Lotte (Büren) www.kromschroeder.de/index.php?id=718&L=1
Germany
T +49 541 1214-0
F +49 541 1214-370 We reserve the right to make technical modifications
03250539
[email protected] in the interests of progress.
www.kromschroeder.com Copyright © 2012 Elster Group
www.elster.com All rights reserved.