DIRECT EXPANSION COMPRESSED AIR DRYERS

Operators Manual

DD36 DD54 DD72


DD108 DD144 DD180
DD216 DD280 DD340

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 1-8
- EN -
CONTENTS

1. GENERAL INFORMATION
1.1 Functional description 2
1.2 Safe use of the dryer 2

2. INSTALLATION
2.1 Acceptance and transportation 3
2.2 Installation site 3
2.3 Installation 3

3. START UP
3.1 Control panel 4
3.1.1 Keys function 5
3.1.2 Condensate discharge parameters programming 5
3.1.3 Anomaly warning 6
3.1.4 Remote signalling alarm 6
3.2 Before start up 6
3.3 Start up 7

4. MAINTENANCE, TROUBLESHOOTING AND DISMANTLING


4.1 Maintenance 7
4.2 Troubleshooting 7
4.3 Dismantling 9

ATTACHMENTS TO THIS MANUAL

A) Refrigerant circuit

B) Electric circuit diagram

C) Technical data sheet

D) Correction factors

E) Dryer dimensions

F) Basic spare parts

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved
Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved
- EN -
INTRODUCTION
This manual is an integral part of the dryer you bought, and must remain with the machine even if this will be resold.
It is highly recommended that the qualified*personnel for installation maintenance and/or control will fully comply with the contents
of this manual and the prevention and safety rules in force in the country where the system will be used. In this way, not only the
usage of the machine will be rational, but also the service will result cost effective.
In case your dryer will present any kind of problem, please contact your local authorizedOMI distributor.
Please note that, when necessary, the use of original spare parts will ensure efficiency and long duration to your dryer.
Due to the continuous technological evolution,OMI reserves the right to modify the specifications contained in this manual without
giving previous notice.

SYMBOLS AND LABELS USED IN THE MANUAL AND ON THE DRYER

Air inlet. Air outlet.


or or or or or or
Read the Operators manual before attempt to
Pay particular attention to components or systems
start up the machine and to perform any service
under pressure.
operation on the dryer.

Pay particular attention to the indications


Pay particular attention to hot surfaces.
preceded by these symbols.

Installation, maintenance, and/or control


Pay particular attention to the risk of electric
operations preceded by these symbols must be
shock.
performed exclusively by qualified personnel*.

Condensate drain point. Rotation direction of the fan.

Pay particular attention to the risk of moving


Explosion risk.
parts

Attention: Before performing any


maintenance operation on this
machine, do not forget to disconnect
the electric supply, to completely
discharge air pressure, and to refer to
the Operators manual

- Turn main power switch on position 1.


- Wait for 8 hours before starting the dryer.

* Qualified personnel must be trained and certified in accordance with local laws and regulations.
WARRANTY
The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in material and
workmanship for a period of twelve months from the date of placing the Equipment in operation or eighteen months from the date of
shipment from the factory, whichever shall first occur. The Purchaser shall be obligated to promptly report any failure to conform to
this warranty, in writing to the Company in said period, whereupon the Company shall, at its option, correct such nonconformity, by
suitable repair to such equipment or, furnish a replacement part F.O.B. point of shipment, provided the Purchaser has stored,
installed, maintained and operated such Equipment in accordance with good industry practices and has complied with specific
recommendations of the Company. Accessories or equipment furnished by the Company, but manufactured by others, shall carry
whatever warranty the manufacturers have conveyed to the Company and which can be passed on to the Purchaser. The Company
shall not be liable for any repairs, replacements, or adjustments to the Equipment or any costs of labor performed by the Purchaser or
others without Company's prior written approval.
Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 1–9
The effects of corrosion, erosion and normal wear and tear are specifically excluded. Performance warranties are limited to those
specifically stated within the Company's proposal. Unless responsibility for meeting such performance warranties are limited to
specified tests, the Company's obligation shall be to correct in the manner and for the period of time provided above.
THE COMPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED OR
IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, ARE HERBY DISCLAIMED.
Correction by the Company of nonconformities whether patent or latent, in the manner and for the period of time provided above,
shall constitute fulfillment of all liabilities of the Company for such nonconformities whether based on contract, warranty negligence,
indemnity, strict liability or otherwise with respect to or arising out of such Equipment.
The Purchaser shall not operate Equipment which is considered to be defective, without first notifying the Company in writing of
its intention to do so. Any such use of Equipment will be at Purchaser's sole risk and liability.
Note that this isOMI standard warranty. Any warranty in force at the time of purchase of the equipment or negotiated as part of the
purchase order may take precedence over this warranty.

1. GENERAL INFORMATION
1.1 FUNCTIONAL DESCRIPTION
OMI refrigerated air dryers remove moisture from compressed air. Moisture is detrimental to pneumatically operated appliances,
controls, instruments, machinery and tools.
Compressed air enters the patented aluminum heat exchanger where it is cooled down to the dew point temperature in two
different stages: In the first air/air sector compressed inlet air is cooled thanks to the colder compressed air coming out counterflow
from the condensate separator. In the second refrigerant / air sector, compressed air temperature is further lowered to the dew point
temperature. During this two stages almost all the oil and water vapours contained in compressed air are condensed to liquid and
successively be separated from the compressed air in the condensate separator and drained out by the automatic drain. At this point
the obtained cold air re-enters counterflow the initial air / air exchanger and it is reheated by the inlet hot air with the consequence of
energy recovering and also reduction of the relative humidity contained in the outflowing air.
This dryer can be easily installed into various pneumatic systems in which dry air is required or desired. Please refer to Principles
of Operation for complete operating details.
The dryer comes provided with all the control, safety and adjustment devices, therefore no auxiliary devices are needed.
A system overload not exceeding the maximum operative limits can worsen the operational performance of the dryer (high
dew point), but it will not affect its safety.
The electric diagram (attachment B) shows the minimum protection degree IP 42.
Improper grounding can result in electrical shock and can cause severe injury or death.
This product must be connected to a grounded, metallic, permanent wiring system or an equipment-grounding terminal or
lead on the product.
All grounding must be performed by a qualified electrician and comply with national and local electrical codes.
In the event of an electrical short circuit, grounding reduces the risk of electric shock by providing an escape wire for the
electric current.
Ground must be established with a bare grounding wire sized according to the voltage and minimum branch circuit
requirements.
Ensure good bare metal contact at all grounding connection points, and ensure all connections are clean and tight.
Check grounding connections after initial installation and periodically thereafter to ensure good contact and continuity has
been maintained.
Check with a qualified electrician or service technician if the grounding instructions are not completely understood, or if in
doubt as to whether the product is properly grounded.

1.2 USE OF THE MACHINE IN SAFE CONDITIONS


This system has been designed and manufactured in compliance with the European safety directive in force, therefore any
installation, use and maintenance operations must be performed respecting the instructions contained in this manual.
Because an air dryer is pressurized and contains rotating parts, the same precautions should be observed as with any piece of
machinery of this type where carelessness in operation or maintenance could be hazardous to personnel. In addition to obvious
safety rules that should be followed with this type of machinery, safety precautions as listed below must be observed.

1. Only qualified personnel shall be permitted to adjust, perform maintenance or repair this air dryer.
2. Read all instructions completely before operating unit.
3. Pull main electrical disconnect switch and disconnect any separate control lines, if used, before attempting to work
or perform maintenance on the unit.
4. Do not attempt to service any part while machine is in an operational mode.
5. Do not attempt to remove any parts without first relieving the entire air system of pressure.
6. Do not attempt to remove any part of the refrigeration system without removing and containing refrigerant in
accordance with the EPA and local regulations.
7. Do not operate the dryer at pressures in excess of its rating.
8. Do not operate the dryer without guards, shields and screen in place.
9. Inspect unit daily to observe and correct any unsafe operating conditions.

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 2–9
2. INSTALLATION
2.1 ACCEPTANCE, UNPACKING AND HANDLING
Upon receiving your OMI air dryer, please inspect the unit closely. If rough handling is detected, please note it on your delivery
receipt, especially if the dryer will not be uncrated immediately. Obtaining the delivery person's signed agreement to any noted
damages will facilitate any insurance claims by the customer.
It is mandatory to keep the dryer always in vertical position, as indicated by the symbols present on the packaging. For handling, use
devices having sufficient capacity for the weight of the machine.
Remove the packaging after having positioned the dryer in the installation site. Dispose the various packaging materials in
compliance with the relevant rules locally in force.
If not in use, the dryer can be stored in its packaging in a dust free and protected site between 32°F (0°C) and 120 °F (50 °C), and a
specific humidity not exceeding 90 %. Should the stocking time exceed 12 months, please contact your localOMI authorized
distributor.
Under no circumstances should any person attempt to lift heavy objects without proper lifting equipment (i.e., crane, hoist, slings or
fork truck). Lifting any unit without proper lifting equipment, may cause serious injury. Use fork lift channels where provided.

2.2 INSTALLATION SITE


While preparing a proper site for the installation of the dryer, please take into account the following requirements
 The machine must be protected from atmospheric agents and not directly exposed to sun light.
 A seating base flat and capable to hold the weight of the machine.
 Ambient temperature complying with the nominal data of the dryer.
 The dryer should be located in a clean area, without forced air draft that can affect the fan control system.
 Make sure to leave sufficient clearance (20 inches, 500 mm) around the dryer in order to allow an adequate
cooling of the machine and for maintenance and/or control operations.

The incoming air must be free from smoke or flammable vapours which could lead to explosion or fire risks.

2.3 INSTALLATION
Before attempting any installation operation, make sure that
 No parts of the air system are under pressure.
 No parts of the system are electrically powered.
 Tubing to be connected to the dryer are free of impurities.
 All interconnecting piping has been tightened.
After having verified the points listed above, you can proceed to the installation of the machine.
1. Connect the dryer to the compressed air lines. If not already existing, we suggest to install a by-pass allowing to
isolate the machine from the plant, thus to facilitate eventual maintenance operations.
2. Perform the electrical connection in accordance with any local laws and regulations after reviewing the dryer
electrical specifications and wiring diagram.
3. Check the condensate drainage assembly, and connect the drain flexible hose to the draining line, keeping in
mind that the condensate separated by the dryer may contain oil, therefore, in order to dispose of it in
compliance with the local rules in force, we suggest installing a water-oil separator having adequate
capacity.
4. Power the dryer after having checked that the nominal voltage and line frequency are constant and matching the
nominal values of the machine. The user must provide the installation with an adequate line protection
and a ground terminal complying with the electrical rules locally in force.

In order to optimise the use of the dryer, we suggest to place it in such a way that all the control instruments of the
machine will result easily visible.
A suitably sized prefilter must be installed before the dryer. Failure to install and maintain a proper prefilter will
void the dryer warranty. The rating for this filter must be at least 10 micron.

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 3–9
3. START UP
Ensure that the dryer is by−passed, or there is no load on the cooler.
Switch on the main electrical isolation switch (if present). The control panel will show the message OFF, indicating that the line and
control voltages are available.
Start sequence
The dryer will initially start by pressing and holding the local ON/OFF button. The start sequence will progress only if there are no
active alarms. The compressor motor will start AFTER 120 SECONDS. The fan motor will start simultaneously with the compressor
for DD280-340 models, after 30 seconds for smaller models.
Stop sequence
The dryer can be stopped locally from the control panel. After having pressed the ON/OFF switch for 1 second, the compressor and
the fan motor keep on running for further 10 seconds in order to re-balance the internal pressures. The dryer can be also stopped due
to an alarm or energy saving condition (ESA or ES2). Any alarm will de−energize the compressor, fan motor can still running, it
depends on the type of alarm (see Display indications chapter). If the shutdown is due to an alarm, a message will blink on display
indicating the reason for the shutdown. Energy saving condition (ESA or ES2) occurs when the dew point stands below the set value
for a long time in order to save energy and avoid heat exchanger freezing. This situation can happen when ambient temperature is
low and there is no compressed air load.
Variable speed fan control
A patented microprocessor allows to adjust dryer’s cooling capacity by changing the fan motor speed. If the dew point is greater than
the set value, the fan speed is increased, if the dew point is smaller than the set value, the fan velocity is decreased. The range can
be from 0 to 100% and the higher is the fan speed, the faster the fan LED blinks, you can read the exact value by pressing the UP
button. If the velocity is 100% you will read FL (Full Load). Under load standard condition the fan speed is usually at 100%, if there is
no load the fan velocity can oscillate between 0 and 20%.
In models DD280-340, in order to adjust the greater dryer’s cooling capacity, a hot gas by-pass valve cooperates with the variable
speed system.
3.1 CONTROL PANEL
The dryers are provided with an electronic control system. All adjustments and resets can be performed by means of the digital panel
located on the front of the dryer. The control panel is composed of 5 keys (ON/OFF, TEST, SET, DOWN and UP) and a 3 digit
display, with three signalling LEDs indicated by icons (PIC 1)
PIC. 1

DISPLAY VISUALIZATION AND SIGNALLING LEDS


DISPLAY DESCRIPTION LED STATUS DESCRIPTION

the unit is in ENERGY SAVING mode ON Compressor energized

the unit is ON with low load Blinking Programming mode activated

the unit is ON with normal load ON Condensate drain energized

ON Speed of the fan = 100%


the unit is ON with normal-high load
Blinking Speed of the fan < 100%
the unit is ON with high load OFF Fan not running

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 4–9
3.1.1 KEYS FUNCTION
TEST: When pushed for 3 sec. during normal operation, it activates the condensate drain.
(Not used on No loss condensate drain)
SET: When pushed and released during normal operation, it displays the parameter C1.
When pushed for 10 seconds, it allows to enter the C8 and C9 condensate drain parameters programming menu (see
relevant table).
When pushed after having set new configuration values, it stores the applied modifications.
DOWN: When pushed while setting the drain set point, it decreases the displayed value of one unit per second, during the
first 10 seconds, than of one unit every 0,1 sec.
When pushed for 10 seconds during normal operation, it starts an automatic test cycle of the controller.
UP: When pushed while setting the drain set point, it increases the displayed value of one unit per second, during the first
10 seconds, than of one unit every 0,1 sec.
ON / OFF: Pressed, it activates or deactivates the dryer. When the dryer is deactivated, the display shows OFF.

NOTE: when the controller is in the OFF position, some parts of the dryer may still be energized. Therefore,
for safety purposes, disconnect the electrical power before performing any operation on the machine.

3.1.2 CONDENSATE DISCHARGE PARAMETERS PROGRAMMING


Push the SET key for 10 seconds to enter the parameters configuration menu: the display will show in sequence
the set point value, the code of the first modifiable parameter (C8) and its value).
Only if strictly necessary, use the UP and/or DOWN keys to change the displayed parameter value.
Press the SET key to store the previously changed parameter value or to browse the parameters without changing
them.
15 seconds after the last performed operation, the controller will return automatically to the normal operation
mode.

PARAMETER DESCRIPTION RANGE DEFAULT SET VALUE

Delay between condensate


C8 discharges
1 ÷ 240 (min) 1

Time required for condensate DD36-180 DD216 DD280-340


C9 1 ÷ 240 (sec)
discharge 1 2 3

NOTE: Changes entered for timing values will be effective only after exiting the programming, while changes to other
variables will be immediately effective.
Please remember that eventual changes to the configuration parameters of the machine could negatively affect its
efficiency. Thus, changes have to be performed by a person familiar with the operation of the dryer.

WARNING FOR USER:


IT’S FORBIDDEN TO ATTEMPT TO MODIFY THE OTHER CONFIGURATION PARAMETERS OF THE ELECTRONIC
CONTROLLER WITHOUT AUTHORIZATION AND COLLABORATION OFOMI’S AUTHORIZED DISTRIBUTOR.

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 5–9
3.1.3 DISPLAY INDICATIONS
The controller is capable of recognizing certain types of anomalies in the drying circuit. In such cases, a message will blink on the
display, alternated to the current dew point value.

MESSAGE
CAUSE OUTPUTS ACTIONS
(BLINKING)

High dew point value Alarm output ON Resettable by switching off the
HtA
(delayed alarm) Refrig. Compressor output OFF dryer.
Very high dew point value Fan output ON If problem persists call your local
Ht2 Drain cycle standard OMI distributor.
(immediate alarm)
Resettable by switching off the
Alarm output ON
dryer. May require replacing the
Interruption or short circuit on the Refrig. Compressor output OFF
PF1 faulty probe.
PTC probe input line Fan output OFF
If problem persists call your local
Drain cycle standard
OMI distributor.
ESA Alarm output OFF
The automatic Energy saving Refrig. Compressor output OFF No action necessary.
mode activated due to low load Fan output OFF Automatic Reset
ES2 Drain cycle standard
Alarm output ON
Refrig. Compressor output OFF
ASt Activated after repeated alarms Call your local OMI distributor.
Fan output ON
Drain cycle standard
Note: PF1 has priority on all other messages.

3.1.4 REMOTE SIGNALING ALARM (OPTIONAL)


The dryer control board is equipped with a dry contact for a remote alarm signal. This is normally open
contact: when an alarm is detected, this contact is closed.
Proceed as follows to activate a remote alarm output:
1. The User must review the diagram below.
2. Disconnect the dryer from electrical power supply, remove cover and left side panel.
3. Connect the alarm circuit to the terminal blocks (See PIC.2).
4. Replace cover, left side panel and reconnect power.

Alarm Output relays electric features:


Max. 250VAC / 3A – AC 15 (Amp. Inductive)

PIC.2

The activation of the above function is at the User’s discretion. The User will purchase all necessary installation material.
Any operation which needs access to the dryer must be carried out by qualified personnel.

3.2 BEFORE START UP

Before starting the machine, make sure that all operating parameters correspond to the nominal data.
The dryer is supplied already tested and preset for normal operation, and it doesn’t require any calibration.
Nevertheless, it’s necessary to check the operating performances during the first working hours.

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 6–9
3.3 START UP
The operations specified below must be performed after the first start up and at each start up after a prolonged
inactive period of time due to maintenance operations, or any other reason.
1. Make sure that all instructions contained in chapters INSTALLATION SITE and INSTALLATION have been
observed.
2. Ensure dryer by-pass is open and air inlet/outlet valves closed. (if existing).
3. Activate power supply and press the ON/OFF switch on the control panel for at least 1 second.
(note there is a 2 minute delay before the dryer will start after the dryer is turned on).
4. Wait 5 to 10 minutes until machine has achieved its standard operating parameters.
5. Slowly open the air outlet valve and successively open the air inlet valve.
6. If existent, close the air by-pass valve.
7. Check if the condensate drain is working properly.
8. Check if all connecting pipes are properly tightened and fixed.

Before disconnecting the dryer from electrical power supply, use ON/OFF switch to stop the
dryer. Otherwise wait 10 minutes before switching the dryer on again, in order to allow freon
pressure to rebalance.

4. MAINTENANCE, TROUBLESHOOTING AND DECOMMISSIONING

4.1 MAINTENANCE

Attention! Perform pressure test with inert gases only (helium, nitrogen).

Before attempting any maintenance operation, make sure that:


1. No parts of the system are under pressure.
2. No parts of the system are electrically powered.
 WEEKLY OR EVERY 40 HOURS OF OPERATION
 Verify the temperature on the control panel display is acceptable.
 Visually check if the condensate is drained regularly.
 Clean the filter mesh of the condensate drain system.
 MONTHLY OR EVERY 200 HOURS OF OPERATION
 Clean the condenser with compressed air, taking care not to damage the condenser fins..
 At the end of the above mentioned operations, check if the dryer is working properly.
 Check the condition of any filters installed with the dryer. Replace elements as needed.
 YEARLY OR EVERY 2000 HOURS OF OPERATION
 Check if the flexible tube used for condensate drainage is damaged and replace it if necessary.
 Check if all connecting pipes are properly tightened and fixed.
 At the end of the above mentioned operations, check if the dryer is working properly.

4.2 TROUBLESHOOTING
NOTE: FOLLOWING BEHAVIORS ARE NORMAL CHARACTERISTIC OF OPERATION AND NOT TROUBLES
 Variable speed of the fan.
 Display of message ESA and ES2 in case of operation without load or low load.
 A 2 minute delay for dryer to start after pressing the on/off switch.
Troubleshooting and eventual control and/or maintenance operations must be performed by qualified
personnel.
For maintaining the refrigerating circuit of the machine, contact a refrigeration engineer.

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 7–9
TROUBLE DISPLAY POSSIBLE CAUSE REMEDY

No power in the line. Restore the power in the line.


Control panel
display is Problems with cabling. Check cabling; if the trouble persists, replace it.
blank Check the electronic control board; if the trouble persists,
Problems with the electronic control board.
replace it.

The dryer is off. Turn it on by pressing the ON/OFF switch for 1 second.

Dryer in stand-by. Wait 2 minutes after the dryer is switched on.


Check if the compressed air inlet/outlet is connected
Compressed air inlet/outlet inverted.
properly.
The flow rate and/or temperature of the air
entering the dryer are higher than the Restore the nominal conditions.
nominal values.
The ambient temperature is higher than the
Restore the nominal conditions.
nominal values.
The condenser is dirty. Clean the condenser.
Clean the condensate drainage system filter mesh.
Replace the coil of the drainage solenoid valve if burned.
Condensate drain is not functioning. Clean or replace the drainage solenoid valve if
Pic.3 clogged/jammed.
Check the C8 and C9 parameters of the electronic control
board; if the trouble persists, replace it.
The temperature control probe is positioned
Check the probe; if the trouble persists, replace it.
WATER IN THE SYSTEM

improperly or faulty.
Problems with cabling or with the electronic Check the cabling and the electronic control board, if the
control board. trouble persists, replace them.
Activation of compressor’s internal thermal Wait one hour and check again. If the fault persists: stop
protection. dryer and call your localOMI distributor.
Problems with the electrical components of
Check the electrical components of the compressor.
the compressor.
Defective compressor. Replace the compressor.
The flow rate and/or temperature of the air
entering the dryer are higher than the Restore the nominal conditions.
nominal values.
The ambient temperature is higher than the
Restore the nominal conditions.
nominal values.
The condenser is dirty. Clean the condenser.
The temperature control probe is positioned
Check the probe; if the trouble persists, replace it.
improperly or faulty.
Fan pressure switch defective or burned out
Turn off the dryer and call your localOMI distributor.
(if present).
High pressure switch defective or burned out
Turn off the dryer and call your localOMI distributor.
(if present).
Gas leakage in the refrigerating circuit. Turn off the dryer and call your localOMI distributor.
Defective fan. Replace the fan.
Protection fuse burned out (if present). Replace the fuse.
The temperature control probe is positioned
Check the probe; if the trouble persists, replace it.
improperly or faulty.
Gas leakage in the refrigerating circuit
Turn off the dryer and call your localOMI distributor.
without load.
The temperature control probe is positioned
Check the probe; if the trouble persists, replace it.
improperly or faulty.

Series of alarms very close to each other. Call your localOMI distributor.

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 8–9
TROUBLE DISPLAY POSSIBLE CAUSE REMEDY

Check the probe; if the trouble persists, replace it.


Check the electronic control board; if the trouble persists,
LOW PRESSURE IN THE LINE

Ice formation in the evaporator.


replace it.
Contact our Service Centre to check the gas charge.
Check if the compressed air inlet/outlet is connected properly.
Check if the connecting tubing is clogged; in case proceed
Clog. accordingly.
Check if any valves are closed.
Check the condition of any filter.
Drainage solenoid valve jammed, clean or replace it.
Verify the condensate drainage times set on the electronic control
Air flows continuously through the
board (C8 and C9).
condensate drainage.
Check the signal from the control board: if it is continuous,
replace the control board.

IMPORTANT:
The temperature control probe is extremely delicate. Do not remove the probe from its position. In case of any kind of
problem, please contact your localOMI distributor

Pic.3

Filter mesh

4.3 DECOMMISSIONING
In case of necessity, decommission the machine and the relevant packaging in compliance with the
rules locally in force.
Pay particular attention to the refrigerant, as it contains part of the refrigerating compressor lubricating
oil. Always contact a waste disposal and recycling facility.

Cod. 710.0167.01.00 Rev0B – 06.2014 © Copyright 2014 OMI Srl - All rights reserved 9–9