FM Global Vs NFPA Vs TCVN

This document provides parameters for fire protection systems for a warehouse including: - An automatic wet sprinkler system using ESFR sprinklers with a maximum ceiling height of 12m, sprinkler area spacing of 9m2, and minimum operating pressure of 3.5 bar. - An indoor hose system with a hose stream demand of 950 L/m and a required water volume of 57 m3. - A fire water tank with a total required water volume of 357 m3. - A fire pump with a flow rate of 5950 L/m.

Uploaded by

beo beo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
455 views3 pages

FM Global Vs NFPA Vs TCVN

This document provides parameters for fire protection systems for a warehouse including: - An automatic wet sprinkler system using ESFR sprinklers with a maximum ceiling height of 12m, sprinkler area spacing of 9m2, and minimum operating pressure of 3.5 bar. - An indoor hose system with a hose stream demand of 950 L/m and a required water volume of 57 m3. - A fire water tank with a total required water volume of 357 m3. - A fire pump with a flow rate of 5950 L/m.

Uploaded by

beo beo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Param

No. Description
FM Global
A Warehouse
I Wet Automatic sprinkler System
- Non-combustible
- Class 1
1 Class of Hazzad - Class 2
- Class 3
- Class 4 / unexpanded plastic
2 Max. Ceiling height (m) 12
3 Max. protection area for calculation (m 2) n/a
4 Density (L/s/m2) n/a
5 Type sprinkler ESFR - K22.4(320) pendent - Quick Response
6 Max. Sprinkler area spacing (m 2) 9
7 Max. Sprinkler linear spacing (m) 3
8 No. of Design sprinkler 9
9 Water supply Duration (minutes) 60
10 Minimum operating pressure (bar) 3.5
11 Sprinkler demand (L/m) 5000
12 Sprinkler required (m3) 300

II Indoor hose cabinet


1 Hose stream demand (L/m) 950
2 Water supply Duration (minutes) 60
3 Indoor hose required (m3) 57
III Outddor fire hydrant
1 Outdoor fire hydrant demand (L/m) N/a
2 Water supply Duration (minutes) N/a
3 Outdoor fire hydrant required (m 3)

IV Volume of Fire water tank


1 Total water demand 357
Estimate diameter of main pipe from main
water meter to water tank is 100mm, velocity
2
is 2m/s, Volume of supplement water into
tank is (m3)
3 Volume of water tank 357
V Fire pump
1 Flow of fire pump (L/m) 5950
Parameter
NFPA TCVN

- Non-combustible
- Class 1
- Class 2 Ordinary - Group 3
- Class 3
- Class 4 / unexpanded plastic
14 20
288
0.29
ESFR - K22.4(320) pendent - Quick Response No recommend
9 12
3 4
12 24
60 60
2.8
6000 5000
360 300

950 900
60 60
57 54

N/a 3600
N/a 180
648

417 1002

170

417 832

6950 9500
Remark

FM Global: FM 8-9
NFPA: NFPA 13
VN Standard: TCVN 7336:2003

FM Global: FM 8-9
NFPA: NFPA 13
VN Standard: TCVN 7336:2003

FM Global: FM 2-0, FM 8-9


NFPA: NFPA 13
TCVN 7336:2003

FM Global: FM 2-0, FM 8-9


NFPA: NFPA 13
VN Standard: QCVN 06:2021/BXD

FM Global: FM 2-0, FM 8-9


NFPA: NFPA 13
VN Standard: QCVN 06:2021/BXD

Follow TCVN 2622:1995, In calculations on the volume of a


fire fighting water reservation container, it is allowed to
include the water amount that is continuously added in water
tank, even the fire extinguishing time is three hours.