Đồng hồ đo áp xuất bình dầu điều tốc

This document is an operation manual for MPM/MDM series transmitting controllers. It provides specifications for the controllers including measured ranges, power supply, output signals, environmental tolerances, accuracy, and relay specifications. It also describes the construction materials, pressure and differential pressure ports, and outlines of different models including the MPM484C, MDM484C, MPM460, and MDM460. Installation, calibration, communication protocols, and the company's responsibilities are also briefly covered.

Uploaded by

Dinh Van Quang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
124 views20 pages

Đồng hồ đo áp xuất bình dầu điều tốc

This document is an operation manual for MPM/MDM series transmitting controllers. It provides specifications for the controllers including measured ranges, power supply, output signals, environmental tolerances, accuracy, and relay specifications. It also describes the construction materials, pressure and differential pressure ports, and outlines of different models including the MPM484C, MDM484C, MPM460, and MDM460. Installation, calibration, communication protocols, and the company's responsibilities are also briefly covered.

Uploaded by

Dinh Van Quang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

MPM/MDM Transmitting Controller

series operation manual


V2.0
Contents

1.Introduction........................................................................................... 1

2.Safety alarm...........................................................................................2

3.Specification..........................................................................................2

4.Outline construction...........................................................................4

5. Electric connection............................................................................9

6. Calibration...........................................................................................11

7.Installation........................................................................................... 13

8.Communication protocol................................................................15

9.Responsibility.....................................................................................17

Our company reserves the right to modify this manual due to product

technique and process updates. If any information is modified, we will not

make further notice.

Please pay attention to the latest version.

Our company reserves the right of final interpretation of this manual.

I
Thanks for selecting our products. Please read this manual carefully

before operation.

1. Introduction

MPM/MDM series transmitting controllers are multi-functional

instruments for pressure, differential pressure and level measurement

and control which consists of MPM/MDM484C, MPM/MDM460,

MPM460W, MPM/MDM484ZL. This series of products are all-electronic

structure, which can measure, display and control on-site pressure,

differential pressure and level. It could output standard signals, and

realize network transmission and remote setting and calibration for

transmitting controllers’ parameters based on RS485 (Modbus RTU

protocol) bus. With easy operation and calibration, it is widely used in

various industries like hydro-power, tap water, water treatment,

petroleum, chemical industry, metallurgy, etc. It can realize the

measurement, display and control of pressure, differential pressure and

liquid level of fluid medium.

Features

 High-precision AD conversion circuit, microprocessor processing data

 Convenient for networking and data transmission, long-distance

calibration and setup available

1
 Main and secondary screens are displayed simultaneously (484C

has main screen only)

 Parameters setting and calibration by keys, easy to operate

 Analog output and RS485 interface (Modbus RTU protocol) available

 Max. 8-way control (460 series), high controlling accuracy

 Return difference setting for each controlling contact to avoid contact

chattering, stable operation

2. Safety alarm

Please read this manual carefully before operation and make

the connection according to the electrical definition of each

product.

Do not calibrate the transmitter when there is no standard

pressure source. If you need to adjust it, please operate it by

professional persons

Please do not touch the corrugated diaphragm with your

hands or sharp objects to avoid damaging the sensor.

In case of strong interference, the housing should be well

grounded.

3. Specification
Measured range:

Level: 0m~1m…200mH2O (only MPM460W)

2
Pressure: -100kPa…0kPa~10kPa…100MPa

Differential pressure: 0kPa~50kPa…3.5MPa

Overpressure:

Level: 1.5 times FS

Pressure: 1.5 times FS or 110MPa (min. value is valid)

Differential pressure: static pressure ≤20MPa

Power supply: 220V AC/110~370V DC/24V DC

Output signal:

Analog output: 4mA~20mA DC,0mA~10/20mA DC,

0/1V~5/10V DC

Digital output: RS485 interface (Modbus RTU protocol)

Environmental temp.: -10℃~60℃

Media temp.: -10℃~80℃

Storage temp.: -40℃~80℃ (460W wetted parts -20℃~80℃)

Relative humidity: 0%~80%

Vibration: acceleration≤3g, frequency 0Hz~300Hz

Shock: ≤10g

Stability: ≤±0.3%/year

Max. Power consumption: ≤3.5W (460 series 5~8 relay ≤5W)

Accuracy: ≤±0.25%FS (typ.) ≤±0.5%FS (max.)

Relay load: 240V/3A AC or 30V/3A DC

Contact life: >100000 times

Main screen: 0.56” (460 series, 484C series) or 0.8” (484ZL series)

3
Secondary screen: 0.36” (460 series,484ZL series)

Display range: -1999~9999 (red highlight LED)

Digital part: sampling rate:10 times/s

Relay qty.:1~5 (484C series,484ZL series) 1~8(460 series)

Installation method: vertical and Horizontal

mounting (MPM484ZL, MPM484C), submersible

Protection: IP65:MPM460(W) and MDM460 display housing

IP68:MPM460W sensor

4. Outline construction

4.1. Construction material

Pressure port: stainless steel

Diaphragm: 316L stainless steel

Electric housing: stainless steel(484C, 484zl front shell)

aluminium alloy (460,484zl bottom shell)

Seal method: NBR, full-welded

4.2. Pressure port

Standard gauge: M20x1.5 male .etc

Standard differential pressure: G1/4 female

Standard level(460W): sensor part is submersible transducer

4.3. Outline

a) MPM/MDM484C series

4
49

kPa

φ100
(160)
(60)
SW27
2

22

φ6
M20×1.5

MPM484C Pressure Transmitting Controller

49

kPa
φ100
(160)

φ27
G1/4
(60)
φ40
φ30

8
22
13 33 13

MDM484C Differential Pressure Transmitting Controller

5
3-φ3.5 EQS
49
°

120
120

°
kPa

φ100
φ130
22

33
2

M20×1.5

SW27
φ6
2
φ116 (60)

MPM484C Pressure Transmitting Controller (Horizontal mounting)

b) MPM460, MDM460, MPM460W outline

(175)
60
125
27 15

MPa
80
SW24
(150)

φ27
12

M20×1.5
MPM460 Pressure Transmitting Controller

6
(175)
125 60
27 15

KPa

80
SW24
(162)

φ27

G1/4
φ30
φ40

8
13 33 13 22

MDM460 Differential Pressure Transmitting Controller


( 175)
125 ( 175)
125

m H 2O
80
(110)

m H 20
80
SW24

SW24

φ 27

φ 18

SW36
SW48

M42× 1.5 φ 140


L
L(length)

57.5
(100)

φ 26

φ 26

MPM460W Transmitting Transmitter MPM460WK Transmitting Controller

7
c) MPM484ZL, MDM484ZL: 15 50

terminal
MPa

φ150
cover name

(220)
plate

SW27
68
22

φ6
M20×1.5

MPM484ZL Pressure Transmitting Controller


15 50

terminal
MPa
φ150

cover name
(240)

plate

φ27
(90)

G1/4
φ30
φ40

8
22
13 33 13
MDM484ZL Differential Pressure Transmitting Controller (vertical mounting)

8
3-φ6 EQS
15 50
°

120
120

°
cover

MPa
terminal

φ180
φ150
M20×1.5

SW27
name

50
plate

φ6
22
(68) 2
φ168

MPM484ZL Pressure Transmitting Controller (horizontal mounting)

Note: The pressure port dimension of controllers for vertical and horizontal

mountings is the same.

5. Electric connection

5.1 MPM/MDM484C series

1, 2, 3: NC, NO and COM of relay 1;

4, 5, 6: NC, NO and COM of relay 2;

19, 20, 21: NC, NO and COM of relay 3;

13,14,15: NC, NO and COM of relay 5;

9
16,17,18: NC, NO and COM of relay 4;

7, 8: analog output terminal;

9,10: RS485 communication terminal;

11,12: AC/DC supply terminal;

Notes: if the relay qty. is <2, there is no dotted box part (13~24).

5.2 MPM460, MPM460W, MDM460 inner electric connection

Note: 1. After the wiring is completed, lock the cable and restore the front panel as it

is to maintain the original protection level of the product.

2.Wire diameter of connection terminal is 0.2 mm2~1.5mm2.

5.3 MPM/MDM484ZL

10
10,11,12: NO, COM and NC of relay 1;

4, 5, 6: NO, COM and NC of relay 2;

4, 5, 6: NO, COM and NC of relay 3;

1, 2, 3: NO, COM and NC of relay 4;

22, 23, 24: NO, COM and NC of relay 5;

7, 8, 9: NO, COM and NC of relay 2;

13, 14: RS485 communication terminal;

15, 16: analog output terminal;

17, 18: 24VDC supply terminal;

19: connected to housing ;

20, 21: 220VAC supply terminal.

Note:

1. please do not use AC 220V and DC 24V at the same time;

2. if there is no need for terminal’s function in purchase order, the

terminal will not connect with any circuit. It’s null;

3. Terminal 19# is for grounding, if necessary, please connect

grounding wire reliably;

4. please power on after checking system and circuit.

6. Key Calibration
6.1. Indicator and key introduction

Indicator includes main indicator and deputy indicator (not including

484C series). Main indicator displays current measuring pressure value

11
at measurement status; displays current parameter virtual value at setup

status. In all states, the secondary display shows the current system

status or limit value and cannot be changed individually. There are three

keys on frond board, ▲, SET, and ▼ keys.

6.2 Key operation flow


Relay 4
PASS or 1993 Unit Unit AL-4 control
point

Addr Address Relay 4


AL4F Property

Relay 5
bAUd Baud rate AL-5 control
point

-dP- Decimal Relay 5


Point AL5F Property

Zero Relay 6
P-SL Display AL-6 control
point

P-SH Full span Relay 6


Display AL6F Property
XXXX

Zero output Relay 7


P-OL Display control
AL-7
point
Full span
P-OH output Relay 7
AL7F Property
Display

Relay 1 Relay 8
AL-1 control AL-8 control
point point

Relay 1 Relay 8
AL1F AL8F
Property Property

Relay 2 common
AL-2 control S--c Hysterisis
point
Second
Relay 2 F--L screen
AL2F Property Display
Relay 3 Return
AL-3 control FAct Factory
point

Relay 3
AL3F Property -End END

long press key“Set”for 3s normal measurement

12
Note:

1.MPM484ZL has no“AL-6” to“AL-8F”; MPM484C has no“AL-6”to“AL-8F”,“F--L” and

deputy display. All the information will be shown on main display if it has no deputy

display;

2.Baud rate: 0/1200,1/2400,2/4800,3/9600,4/19200,5/38400,6/57600,7/115200;

3.Relay property: “0” indicates the lower limit alarm, “1” indicates upper limit alarm;

4. “Zero output display” and “span output display” Used to adjust the output analog

quantity, The default is consistent with "zero display" and "full display";

5. "Common hysterisis" : it is used to eliminate the jitter of pressure at the critical

point of limit value, and the default value is 0;

6. "Second screen display": 0(default) Display "U--U"; 1~5(484ZL)/1~8(460) display

the corresponding limit value, 6 and 7(484ZL)/ 9 and 10 (460) display the zero

display and full span value;

7."Return factory" : set "1" and press the "confirm" button, the meter will immediately

restore the factory Settings, the default is "0" FAct indicates menu entering, “1”

means “restore to factory”. Default is “0”.

7. Installation
7.1 MPM484C, MPM460, MPM484ZL

The pressure port for MPM484C, MPM460, MPM484ZL controllers is

M20x1.5 male waterline seal. For flush diaphragm transmitting controller,

pressure port is G1/2 male with seal cushion. The controller could be

installed to flange connector on measuring tube directly. Please add

13
cut-off valve between flange connector and tube for easy installation and

repair.

There is one nylon protection cap on the pressure port of flush

diaphragm type controllers. Please do not take off the cap to protect

diaphragm if the user does not install.

Please mount controller to pressure port M20X1.5 female, the screw

depth should be less than 20mm (there should be a seal-ring on the type

face). Pressure port G1/2 female’s depth should be no less than 15mm.

Please do not wrap tape on pressure port G1/2 male to seal. This would

affect product stability or damage product.

7.2 MDM484C, MDM484ZL, MDM460

The pressure ports for standard MDM484A, MDM484ZL differential

pressure controller are two G1/4 female. Marked with “+“ is high (positive)

pressure side; marked with “-“ is low (negative) pressure side. The

transmitter should be connected to process tube together with 3 valve

manifolds by pressure leading tube. Pressure leading tube’s high

(positive) pressure side connects to pressure port marked “+”; pressure

leading tube’s low (negative) pressure side connects to pressure port

marked “-”. Please make two pressure port horizontal for right installation

position, and make indicator facts to worker directly.

For normal operation and easy installation, please install 3 valve

14
manifolds between controller and measuring point; pressure port G1/4

male’s length should be no more than 12mm, and sealed by seal

cushion.

Note:

(1) process operation pressure should be no more than 20MPa.

(2) the measured media differential pressure should not exceed upper limit

pressure.

(3) Open 3 valve manifold to prevent that one single pressure acts on transmitting

controller to protect product.

(4) Media should be compatible with construction material.

(5) Pressure port marked with “+” and ”-”. This will keep correct connection.

7.3 MPM460W

Standard MPM460W level transmitting controller is submersible type and

the installation direction is vertical down.

8. Communication protocol
The products uses standard Modbus RTU protocol (03: read register,

06: set single register).

Table 8.1 Data format

Fun. CRC
Start Add. Date End
code check

T1–T2–T3–T4 8 BITS 8 BITS n x 8 BITS 16 BITS T1–T2–T3–T4

Table 8.2 Common register list

15
Registe Register Register
Name Name Name
r add. add. add.
2nd limit 6th limit
Add. 0001 0014 001C
character value
3rd limit 6th limit
baud rate 0002 0016 001D
value character
Real-time 3rd limit 7th limit
000F 0017 001E
value character value
Decimal 4th limit 7th limit
0010 0018 001F
point value character
1st limit 4th limit 8th limit
0011 0019 0020
value character value
1st limit 5th limit 8th limit
0012 001A 0021
character value character
2nd limit 5th limit common
0013 001B 0015
value character hysterisis
Deputy User set Return to
0022 0025 0027
display set save factory

Table 8.3 Common used register sample

Register
Explanation Send command Answer command
addr.

Read addr. 00 03 00 01 00 01 D4 1B 05 03 02 00 05 89 87
0001
Change addr. 05 06 00 01 00 02 58 4F 02 06 00 01 00 02 59 F8

Read pressure
000F 02 03 00 0F 00 01 B4 3A 02 03 02 03 F9 3C F6
value

0027 Return to factory 02 06 00 27 00 01 F8 32 02 06 00 0F 00 66 39 D0

Read pressure 02 03 04 03 E9 00 02 99
000F 02 03 00 0F 00 02 F4 3B
data 42

16
Analysis: byte number:0x04(4) 1:03 E9 (1001) 2:00 02 (2)
Pressure value =1001*0.01=10.01

Note: The pressure value read is hexadecimal number, convert it to decimal number,

divided by the decimal point value (0: divided by 1; 1: divided by 10; 2: divided by

100; 3: divided by 1000) and then get real-time pressure values.

9. Responsibility
Within one year from the delivery date, we shall repair or replace the

instrument with any quality fault caused by material parts or our

manufacturing technique free of charge. For non-quality malfunction

during user’s operation, we are in charge of repair. But the material cost

and the shuttle transportation fees should be borne by users.

17