0% found this document useful (0 votes)
35 views3 pages

Release Notes 9442

This document provides release notes for firmware versions of products CPU 9442/3x and PM 9445/3x. The most recent version is SWU 01.01.03 from May 23, 2023 which fixes a bug in the calculation of current in Zone 1 for PM modules. Earlier versions provided various bug fixes and new features related to firmware updates, redundancy, temperature compensation, and other improvements. Known issues remain with certain module configurations and updating older PM modules.

Uploaded by

OUGOUAG
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views3 pages

Release Notes 9442

This document provides release notes for firmware versions of products CPU 9442/3x and PM 9445/3x. The most recent version is SWU 01.01.03 from May 23, 2023 which fixes a bug in the calculation of current in Zone 1 for PM modules. Earlier versions provided various bug fixes and new features related to firmware updates, redundancy, temperature compensation, and other improvements. Known issues remain with certain module configurations and updating older PM modules.

Uploaded by

OUGOUAG
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Product Information

CPU 9442/3x and PM 9445/3x - Firmware Release Notes


SWU 01.01.03 Release Date 23.05.2023
New Features -- --
Bugfix PM • Correct calculation of current in Zone 1 PM
Known Bugs CPU • 9468/ and 9469/ with 8AO + 4 HV or 8 AO + 8 HV does not work
- Configure module as 8AI/AO + HART PV
Remarks Firmware identical to version SWU 01.00.25, only PM firmware changed

SWU 01.01.02 Release Date 16.05.2023


New Features -- -- EN
Bugfix PM • Update of all power module firmware versions to this version is possible
Known Bugs CPU • 9468/ and 9469/ with 8AO + 4 HV or 8 AO + 8 HV does not work
- Configure module as 8AI/AO + HART PV
PM • Current of Zone 1 PM not correct. Maintenance LED can be switched on
- Update to 01.01.03
Remarks Firmware identical to version SWU 01.00.25, only PM firmware changed

SWU 01.01.01 Release Date 03.05.2023


New Features -- --
Bugfix PM • use correct temperature correction in current measurement PM zone 2
Known Bugs CPU • 9468/ and 9469/ with 8AO + 4 HV or 8 AO + 8 HV does not work
- Configure module as 8AI/AO + HART PV
PM • PM with FW < 01.00.25 cannot be updated and will switch of power.
- restarted using separate power supply (using SWU 99.00.00)
- updated to 01.00.25 prior
- If updated once to 01.01.01 or later, any update is possible
Remarks Firmware identical to version SWU 01.00.25, only PM firmware changed

SWU 01.01.00 Release Date 04.04.2023


New Features PM • Improved load balancing in redundant mode
• Switch output off faster if power is disconnected
• add support for new PM Z1
• Use constant output voltage while in boot mode
Bugfix PM • Problem with firmware update solved. Some PM got stuck in download mode
and switched output off
Known Bugs CPU • 9468/ and 9469/ with 8AO + 4 HV or 8 AO + 8 HV does not work
- Configure module as 8AI/AO + HART PV
PM • PM with a FW < 01.00.25 cannot be updated and will switch of power.
- PM can be restarted with a separate power supply
(use SWU 99.00.00)
- If system is updated to 01.00.25 prior, it can be updated to 01.01.00
• Skipped temperature compensation of current measurement PM zone 2, values
in webserver too high
Remarks Firmware identical to version SWU 01.00.25, only PM firmware changed

Firmware Release Notes


Series 9442/3x and 9445/3x 2023-05-23 PI00 III en 01
Product Information

SWU 01.00.25 Release Date 23.11.2022


New Features CPU • Password reset
PM • Switch off red. PM while other PM is in update.
• Serial firmware download of redundant PM
Bugfix CPU • Improved redundancy switching
• Webserver
- Show DI instead of DO, fix text
- Correct display of CPU zone 1
PM • Fixed power on problem
• Serial firmware download
• Switch off PWR OUT LED if power supply of PM is removed
Known Bugs CPU • 9468/ and 9469/ with 8AO + 4 HV or 8 AO + 8 HV does not work
- Configure module as 8AI/AO + HART PV
Remarks

SWU 01.00.24 Release Date 28.03.2022


New CPU • HART communication over backup CPU
Features • Add support for virtual COM port EN
• Add OPC UA demo mode in standard CPU
• Add NTP support
• Add global data (field station name, location, comments….) available in both
redundant CPU
• Add support for IOM redundancy
• Add PROFINET extensions
• Improved Web diagnostics
• Licenses loadable via webserver
• Add support for HEX decoders of socket (9496\)
Bugfix CPU • Extend PROFINET to 1024 Bytes
• Boot from sockets from factory (empty sockets)
PM • Improve PM redundancy
Known Bugs PM • Power on problem may occur
Remarks --

SWU 01.00.23 Release Date 26.10.2020


New Features -- --
Bugfix CPU • Optimize timeout on backplane
Known Bugs -- --
Remarks --

SWU 01.00.22 Release Date 22.09.2020


New Features CPU • Webserver extended history
• Webserver timesync with PC
• IS1+ Virtual Com port support
Bugfix PM • no maintenance alarm of red. PM, with a switched off PM
Known Bugs CPU • Update from SWU 01.00.21 requires a power on to show correct PM information
Remarks No official release

Firmware Release Notes


Series 9442/3x and 9445/3x 2023-05-23 PI00 III en 01
Product Information

SWU 01.00.21 Release Date 09.07.2020


New Features CPU • PROFIBUS DP
• New PROFINET stack
Bug Fixes CPU • Webserver
Known Bugs -- --
Remarks --

SWU 01.00.18 Release Date 19.03.2020


New Features CPU • PROFIBUS DP
Bugfix CPU • PROFIBUS DP
• Webserver
Known Bugs -- --
Remarks --

SWU 01.00.17 Release Date 11.02.2020


New Features -- --
Bugfix CPU • Synchronization between redundant CPU
• Webserver
Known Bugs -- --
Remarks --

SWU 01.00.16 Release Date 11.09.2019


New Features -- --
Bugfix CPU • Synchronization between redundant CPU EN
Known Bugs CPU • HART over PROFIBUS DP not working
• No slave startup on PROFIBUS DP
• RS485 only point to point connection
Remarks --

SWU 01.00.11 Release Date 06.02.2019


New Features CPU • All protocols implemented
Bugfix CPU • Synchronization between redundant CPU
Known Bugs CPU • No HART communication on inactive CPU
• No update of inactive CPU if other CPU is active
• RS485 only point to point connection
Remarks --

Support: [email protected]
+49 7942 943-4123
r-stahl.com

Firmware Release Notes


Series 9442/3x and 9445/3x 2023-05-23 PI00 III en 01