0% found this document useful (0 votes)
52 views11 pages

HMW 3030 t5 GB

This document provides specifications for the HMW-3030 T5 heavy duty generator set powered by an MTU 20V4000G63L engine. Some key details include: - The generator set has a rated power of 3026kVA at 50Hz and is powered by a 20-cylinder MTU diesel engine. - The generator meets various EC directives and ISO standards for safety, emissions and noise. - It is designed to provide either prime or standby power according to ISO 8528 definitions. - Additional specifications cover the engine, generator, mounting type, and other technical details.

Uploaded by

Jeevagan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views11 pages

HMW 3030 t5 GB

This document provides specifications for the HMW-3030 T5 heavy duty generator set powered by an MTU 20V4000G63L engine. Some key details include: - The generator set has a rated power of 3026kVA at 50Hz and is powered by a 20-cylinder MTU diesel engine. - The generator meets various EC directives and ISO standards for safety, emissions and noise. - It is designed to provide either prime or standby power according to ISO 8528 definitions. - Additional specifications cover the engine, generator, mounting type, and other technical details.

Uploaded by

Jeevagan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

MODEL

HMW-3030 T5
HEAVY RANGE
Container
Powered by MTU

40FT-HC

WATER-COOLED

THREE PHASE

50 HZ

DIESEL

Generating Rates
SERVICE PRP STANDBY
Power kVA 3026 3330
Power kW 2420 2664
Rated Speed r.p.m. 1.500 01
Standard Voltage V 400/230
Rated at power factor Cos Phi 0,8

HIMOINSA Company with quality certification ISO 9001


HIMOINSA gensets are compliant with EC mark which includes the following directives:

• 2006/42/CE Machinery safety.


• 2014/30/UE Electromagnetic compatibility.
• 2014/35/UE electrical equipment designed for use within certain voltage limits
• 2000/14/EC Sound Power level. Noise emissions outdoor equipment. (amended by 2005/88/EC)
• 97/68/EC Emissions of gaseous and particulate pollutants. (amended by 2002/88/EC & 2004/26/EC)
• EN 12100, EN 13857, EN 60204

Ambient conditions of reference according to ISO 8528-1:2005 normative: 1000 mbar, 25ºC, 30% relative humidity.

Prime Power (PRP):


According to ISO 8528-1:2005, Prime power is the maximum power which a generating set is capable of delivering continuously whilst supplying a variable
electrical load when operated for an unlimited number of hours per year under the agreed operating conditions with the maintenance intervals and procedures
being carried out as prescribed by the manufacturer. The permissible average power output (Ppp) over 24 h of operation shall not exceed 70 % of the PRP.

Emergency Standby Power (ESP):


According to ISO 8528-1:2005, Emergency standby power is the maximum power available during a variable electrical power sequence,
under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage
or under test conditions for up to 200 h of operation per year with the maintenance intervals and procedures being carried out as
prescribed by the manufacturers. The permissible average power output over 24 h of operation shall not exceed 70 % of the ESP

G2 class load acceptance in accordance with ISO 8528-5:2013

HIMOINSA HEADQUARTERS:
Fábrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 [email protected] www.himoinsa.com

Manufacture facilities:
SPAIN • FRANCE • INDIA • CHINA • USA • BRAZIL • ARGENTINA

Subsidiaries:
PORTUGAL | POLAND | GERMANY | UK | SINGAPORE | UAE | PANAMA | DOMINICAN REPUBLIC | ARGENTINA | ANGOLA | SOUTH AFRICA

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
HEAVY RANGE
Container
Engine Specifications 1.500 r.p.m. Powered by MTU

ENGINE PRP STANDBY


Rated Output kW 2516 2775
Manufacturer MTU
Model 20V4000G63L
Engine Type 4-stroke diesel
Injection Type Direct
Aspiration Type Turbocharged and after-cooled
Number of cylinders and arrangement 20-V
Bore and Stroke mm 170 x 210
Displacement L 95,4
Cooling System Water
Lube Oil Specifications S10 W40
Compression Ratio 16,5
Fuel Consumption Standby l/h 639,37
Fuel Consumption 100% PRP l/h 578,23
Fuel Consumption 75 % PRP l/h 444,97
Fuel Consumption 50 % PRP l/h 313,21
Fuel Consumption 25 % PRP l/h 176,18 02
Lube oil consumption with full load 1 % of fuel consumption
Total oil capacity including tubes, L 390
filters
Total coolant capacity L 1060
Governor Type Electrical
Air Filter Type Dry
Inner diameter exhaust pipe mm 251

Generator
Generator
Manufacturer STAMFORD
Poles No. 4
Connection type (standard) Star
Mounting type S-00 21"
Insulation Class H class
Enclosure (according IEC-34-5) IP23
Exciter system Self-excited, brushless
Voltage regulator A.V.R. (Electronic)
Bracket type Double drive-shaft
Coupling system Flexible disc
Coating type Standard (Vacuum impregnation)

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
HEAVY RANGE
Container
Powered by MTU

Application Data

Exhaust System
Maximum exhaust temperature ºC 545
Exhaust Gas Flow m 3/min 510
Maximum allowed back pressure mbar 85

Necessary Amount Of Air


Intake air flow m 3 /h 11520
Cooling Air Flow m3 /s 61,29
Alternator fan air flow m3 /s 3,2

Starting System
Starting power kW 7,5 x 2
Starting power CV 10,2 x 2
Recommended battery Ah 400 03
Auxiliary Voltage Vdc 24

Fuel System
Fuel Oil Specifications Diesel
Fuel Tank L 2.000

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
HEAVY RANGE
Container
Dimensions Powered by MTU

Weight and Dimensions


(L) Length mm 12.192
(W) Width mm 2.438
(*) Weight with liquids in radiator and sump kg Ask
Fuel tank capacity L 2.000,0
04
Autonomy Hours 4
(*) (with standard accessories) STANDARD VERSION

Himoinsa has the right to modify any feature without prior notice.
Weights and dimensions based on standard products. Illustrations may include optional equipment.
Technical data described in this catalogue correspond to the available information at the moment of printing.
Industrial design under patent.

Local Distributor

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
HEAVY RANGE
Container
Powered by MTU

CONTROL PANEL MODEL


M5
Digital manual Auto-Start control panel and thermal magnetic protection (depending on current and
voltage) and differential with CEM7. Digital control unit CEM7

AS5
Automatic panel WITHOUT transfer switch and WITHOUT mains control with CEM7 unit. (*) AS5 as
optional with CEA7 unit. Automatic panel without transfer switch and WITH mains control.

CC2
Himoinsa Switching cabinet WITH display. Digital control unit CEC7

AS5 + CC2
Automatic panel WITH transfer switch and with mains control. The display will be on the genset and
on the cabinet. Digital control unit CEM7+CEC7

AC5
Automatic mains failure control panel. Wall-mounted cabinet WITH transfer switch and thermal
magnetic protection (depending on current and voltage). Digital control unit CEA7
05

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
Controller features (I) HEAVY RANGE
• : Standard Container
Powered by MTU
x : Not included
• : Optional

Generator Readings CEM 7 CEA 7 CEC 7 CEM7 + CEC7


Voltage between phases • • • •

Voltage between neutral and phase • • • •

Current intensities • • • •

Frequency • • • •

Apparent power (Kva) • • • •

Active power (Kw) • • • •

Reactive power (kVAr) • • • •

Power factor • • • •

Mains Readings CEM 7 CEA 7 CEC 7 CEM7 + CEC7


Voltage between phases x • • •

Voltage between phases and neutral x • • •

Current intensities x • • •

Frequency x • • •

Apparent power x • x x

Active power x • x x 06
Reactive power x • x x

Power factor x • x x

Engine Readings CEM 7 CEA 7 CEC 7 CEM7 + CEC7


Coolant temperature • • x •

Oil pressure • • x •

Fuel level (%) • • x •

Battery voltage • • x •

R.P.M. • • x •

Battery charge alternator voltage • • x •

Engine Protections CEM 7 CEA 7 CEC 7 CEM7 + CEC7


High water temperature • • x •

High water temperature by sensor • • x •

Low water temperature by sensor • • x •

Low oil pressure • • x •

Low oil pressure by sensor • • x •

Low water level • • x •

Unexpected shutdown • • x •

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
Controller features (II) HEAVY RANGE
• : Standard Container
Powered by MTU
x : Not included
• : Optional

Engine Protections CEM 7 CEA 7 CEC 7 CEM7 + CEC7


Fuel storage • • x •

Fuel storage by sensor • • x •

Stop failure • • x •

Battery voltage failure • • x •

Battery charge alternator failure • • x •

Overspeed • • x •

Underspeed • • x •

Start failure • • x •

Emergency stop • • • •

Alternator Protections CEM 7 CEA 7 CEC 7 CEM7 + CEC7


High frequency • • • •

Low frequency • • • •

High voltage • • • •

Low voltage • • • •

Short-circuit • • x • 07
Asymmetry between phases • • • •

Incorrect phase sequence • • • •

Inverse power • • x •

Overload • • x •

Genset signal drop • • • •

Counters CEM 7 CEA 7 CEC 7 CEM7 + CEC7


Total hour counter • • • •

Partial hour counter • • • •

Kilowatt meter • • • •

Starts valid counters • • • •

Starts failure counters • • • •

Maintenance • • • •

Communications CEM 7 CEA 7 CEC 7 CEM7 + CEC7


RS232 • • • •

RS485 • • • •

Modbus IP • • • •

Modbus • • • •

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
Controller features (III) HEAVY RANGE
• : Standard Container
Powered by MTU
x : Not included
• : Optional

Communications CEM 7 CEA 7 CEC 7 CEM7 + CEC7


CCLAN • • x •

Software for PC • • • •

Analogue modem • • • •

GSM/GPRS modem • • • •

Remote screen • • x •

Tele signal • (8 + 4) • (8 + 4) x • (8 + 4)

J1939 • • x •

Features CEM 7 CEA 7 CEC 7 CEM7 + CEC7


Alarm history • (10) / (opc. +100) • (10) / (opc. +100) • (10) / (opc. +100) • (10) / (opc. +100)

External start • • • •

Start inhibition • • • •

Mains failure start x • • •

Start under normative EJP • • x •

Pre-heating engine control • • x •

Genset contactor activation • • • • 08


Mains & Genset contactor activation x • • •

Fuel transfer control • • x •

Engine temperature control • • x •

Manual override • • x •

Programmable alarms • • x •

Genset start function in test mode • • • •

Programmable outputs • • x •

Multilingual • • • •

Special Functions CEM 7 CEA 7 CEC 7 CEM7 + CEC7


GPS Positioning • • x •

Synchronisation • • x •

Mains synchronization • • x •

Second Zero elimination • • x •

RAM7 • • x •

Remote screen • • x •

Programming timer • • x •

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
HEAVY RANGE
Container
Powered by MTU

Generator set features


Engine
· Standard air filter

· Standard fuel filter

· Standard oil filter


· Electronic management (ADEC)

· Coolant level sensor


· Exhaust gas compensator

· Diesel engine

· 4-stroke cycle
· Water-cooled

· 24V electrical system


· Radiator with blower fan

· HTW sender
· LOP sender

· Hot parts protection

· Moving parts protection 09

Alternator
· Self-excited and self-regulated

· IP23 protection
· H class insulation

Container version
· Soundproofing provided by high-density volcanic rock wool

· High mechanical resistance

· Low level of noise emissions


· Door with window to visualize control panel, alarms and measurements

· Reinforced lifting points for crane hoisting and lower ones for transportation by forklift
· Residential steel silencer with -35dB attenuation and tilting cap in the exhaust

· Fuel tank integrated in the chassis

· Anti-vibration shock absorbers


· Steel chassis

· Manual oil extraction pump


· Robust construction designed for continuous or emergency applications

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
HEAVY RANGE
Container
Powered by MTU

Generator set features


Container version
· Stainless steel fittings

· Emergency stops

· Easy access to the power connection


· Reinforced chassis for heavy range

· Easy access for chassis cleaning


· Silent-block with anti-corrosion protection between the genset and the chassis

Electrical System Container


· Control panel and emergency stop button
· Power panel

· Battery charger (standard on automatic control panels)


· Heating resistor (standard on sets with automatic control panels)

· Battery charge alternator with ground connection

· Starter battery/ies installed (cables and bracket included)


10
· Ground connection electrical installation with connection ready for ground spike (not supplied)

· 4 pole circuit breaker


· Power panel with safety protection in output terminals box (open thermal magnetic protection and alarm)

· Maintenance-free and anti-explosion battery

· Battery isolator

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
MODEL

HMW-3030 T5
HEAVY RANGE
Container
Powered by MTU
PDF Summary
Created : 28/02/2018 21:01
Author : Himoinsa
Number of pages : 11
Report Type: Data Sheet - Heavy range
Generated by: HIMOINSA Engineering Dept.
Page 1. Genset data
Page 2. Engine Specifications. Generator Specifications.
Page 3. Installation Data
Page 4. Dimensions
Page 5. Control Panel Model
Page 6. Controller features (I)
Page 7. Controller features (II)
Page 8. Controller features (III)
Page 9. Generator Features & Options
Page 10. Generator Features & Options
Page 11. PDF Summary

11

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com

You might also like