Energy Efficient Heating
Energy Efficient Heating
an overview
CIBSE Knowledge Series: KS14
Principal authors
Phil Jones (Building Energy Solutions and
London South Bank University)
Tony Day (London South Bank University)
Editor
Ken Butcher
Director of Information
Jacqueline Balian
ISBN: 978-1-903287-98-9
This document is based on the best knowledge available at the time of publication.
However no responsibility of any kind for any injury, death, loss, damage or delay however
caused resulting from the use of these recommendations can be accepted by the
Chartered Institution of Building Services Engineers, the authors or others involved in its
publication. In adopting these recommendations for use each adopter by doing so agrees to
accept full responsibility for any personal injury, death, loss, damage or delay arising out of
or in connection with their use by or on behalf of such adopter irrespective of the cause or
reason therefore and agrees to defend, indemnify and hold harmless the Chartered
Institution of Building Services Engineers, the authors and others involved in their
publication from any and all liability arising out of or in connection with such use as
aforesaid and irrespective of any negligence on the part of those indemnified.
Printed in Great Britain by The Charlesworth Group, Wakefield, West Yorkshire, WF2 9LP
Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2 Requirements of legislation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
4 Energy efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
5 Condensing boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
9 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
10 Renewables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
In most buildings, heating and hot water account for the largest annual
consumption of delivered energy, and therefore CO2 emissions from heating
systems are often high. Providing space heating and hot water amounts to
almost half the CO2 emissions from non-domestic buildings resulting in some
37 Mt CO2/year being emitted into the atmosphere. Heating and hot water
for a typical 4000 m2 naturally ventilated office will result in 115 tonnes of
CO2 being emitted into the atmosphere.
Space heating loads are generally reducing as a proportion of the total energy
demand in buildings due to improved U-values and reduced air infiltration,
increased boiler efficiencies and improved heating controls. However, fuel
prices have increased and there is a constant need to keep costs and
environmental emissions under control whilst meeting the comfort needs of
the building occupants.
The Mayor of London’s energy hierarchy has three clear stages that provide a
structured approach to reducing energy consumption in buildings, as shown
in Figure 1. This hierarchy can be directly applied to heating by:
Figure 1:
Supply energy Use renewable
Use less energy
efficiently energy
The energy hierarchy
(’be lean’)
(’be clean’) (’be green’)
The NDHCV Guide(15) outlines the minimum provision for each type of
heating, hot water and air distribution system including:
— minimum provision for efficiency of the plant that generates heat and
hot water
— minimum provisions for the controls to ensure the system is not
generating heat or hot water unnecessarily or excessively
— a set of additional measures which may improve the efficiency of the
plant
Table 1:
— minimum provision for insulation of pipes and ducts serving space
Carbon emission factors
heating and hot water systems Source: Building Regulations Approved
— minimum provisions for acceptable specific fan power ratings serving Document L2A(8)
the minimum requirement. The installation must also have a minimum Biogas 0.025
Oil 0.265
controls package and pipework /vessel insulation levels.
Coal 0.291
Biomass 0.025
Building Regulations Part L(5) now requires the energy performance of
Grid-supplied 0.422
buildings other than dwellings to be calculated using the National Calculation electricity
Method (NCM), which for new buildings is implemented through a range of Grid-displaced 0.568
accredited software. The NDHCV Guide(15) identifies the input parameters electricity
that are required by the NCM for space heating, hot water and ventilation Waste heat 0.018
The NCM for new buildings is based on overall CO2 emissions from
buildings. Approved Document L2A(8) provides carbon emissions factors that
should be used in calculating emissions from buildings, see Table 1.
It is also very important to ensure that boiler plant is designed and maintained
for safe operation. HSE Guidance note PM5(17) requires that hot water
boilers should have an automatic control device to cut off fuel to the burners
of gas-fired plant when the boiler flow outlet temperature rises to a
predetermined temperature that might be unsafe. This control system should
keep the system temperature at least 17 °C below the temperature of
saturated steam corresponding to the pressure at the highest point of the
circulation system above the boiler. To comply with this recommendation, the
minimum system pressure should be determined from the maximum design
flow temperature.
— select fuels and tariffs that promote high efficiency, low emissions and
minimise running costs
— segregate hot water services generation wherever possible
— locate plant to minimise distribution system losses
— insulate pipework, valves, storage vessels etc. effectively
— choose efficient primary plant, such as condensing boilers
— consider energy recovery, e.g. from air exhaust streams
— distribute heat effectively by avoiding excessive pipe lengths and
system resistance
— use effective controls through good zoning, effective time control and
variable flow control where possible
— consider de-centralised heating and hot water services generation
plant on large sites to reduce standing losses and improve load
matching
but:
Figure 2 shows a simple heating system that can be used as a basic building
block. Including the following features can often help to reach a simple
energy efficient heating system:
Common header
Boiler Boiler Boiler Boiler
No 1 No 2 No 3 No 4
Compensator
Return
Seasonal efficiency
Always select the most efficient plant. Typical seasonal efficiencies of boiler
plant are shown in Table 2.
Seasonal Table 2:
Boiler/system
efficiency (%) Typical seasonal
Condensing boilers: efficiencies of boilers
— underfloor or warm water system 90 or greater
— standard size radiators, variable temperature circuit 87
(weather compensation)
— standard fixed temperature emitters (83 /72 °C flow/return) 85
Non-condensing boilers:
— modern high efficiency non-condensing boilers 82
— good modern boiler design closely matched to demand 80
— typical good existing boiler 70
— typical existing oversized boiler (atmospheric cast-iron 45–70
sectional)
Condensate
drain When low temperature return water enters the condensing heat exchanger it
cools the flue gases. If the water is less than about 55 °C the water vapour in
the flue gases is condensed and latent heat is given up. The lower the return
water temperature, the more condensation produced and the greater the
efficiency, see Figure 4.
100
1500
Condensing 1000
mode
80
Non-condensing 500
Efficiency mode
Condensate
Figure 4: 70
Operation of condensing
0
boilers 20 30 40 50 60 70
Return water temperature (°C)
There are a range of hydraulic arrangements and controls that can promote
low return temperatures, leading to condensation. The two main methods
are:
efficiencies over 90%. It is often possible to ‘design-in’ a particular low • Minimum 85% when not condensing.
• Similar capital cost to high efficiency
temperature circuit (e.g. underfloor heating in atria) in which to locate
but 30–40% over standard boilers.
the secondary heat exchanger to promote condensation. Some • Paybacks can be attractive
systems are also designed with wide temperature differentials (e.g. ΔT (3–5 years).
of 20 °C) to promote longer periods in the condensing mode. • To gain the extra efficiency we need
the right system.
• The lower the return temperature
— Weather compensated systems: the low return water temperatures the better the boiler efficiency.
occurring in ‘standard’ (i.e. 82 °C flow temperature) weather • Even greater efficiencies on low
compensated systems can be used to force condensing boilers into the temperature and wide ΔT systems.
condensing mode during milder weather, as shown in Figure 5. As the • Should consider ‘condensing systems’
rather than ‘condensing boilers’.
external temperature rises, the flow temperature is decreased, saving
energy. Locating the secondary heat exchanger in the variable
temperature part of a three-port valve, weather compensated circuit is
the most common method, as shown in Figure 6. An even simpler
approach is to directly compensate the boilers, as shown in Figure 7.
40
Return
Non-
20 condensing Condensing
0
–2 0 2 4 6 8 10 12 14 16 18 20
External temperature (oC)
Condensing boiler
primary heat exchanger
Sequencer
Compensator
Common header
Cond.
NC NC NC
prim.
Figure 6:
Sec
Weather compensation
NC = non-condensing Secondary ‘condensing’ using a 3-port valve
heat exchanger
CIBSE Knowledge Series — Energy efficient heating 9
Figure 7: Condensing boiler
Direct weather primary heat exchangers
compensation Compensator
Sequencer
Cond. Cond.
Common header
prim. prim.
NC NC
Sec. Sec.
NC = non-condensing
Secondary ‘condensing’
heat exchangers
The following criteria indicate the situations where condensing boilers may
be used to best effect.
Figure 8:
Condensate drain
Flue installation
Boiler
U traps
Metal pipe to protect
plastic drain
Flues generally need to be stainless steel with good seals to avoid condensate
leakage. Condensate will form inside the flue but should run down to a drain
at the base of the flue or back through the boiler, as shown in Figure 9.
Installation cost reductions can sometimes be realised because the flue
diameter is often smaller than a non-condensing boiler due to the smaller
amounts of combustion products, and fan driven flues. There is less natural
buoyancy due to lower flue temperatures, particularly when condensing and
a plume often occurs when the wet combustion products meet the outside
air. The plume should not present a problem but the flue outlet needs careful
siting to prevent the plume become a nuisance or having an effect on roofing
materials.
Plastic flues can be used providing they are made of the correct material and
an over-temperature limit thermostat is installed to protect the flue in case of
exposure to high discharge temperatures.
Saturated
flue gases
Less natural
buoyancy
Fall >5°
Lower flue gas
temperatures
Appliance
fan
Less volume of
flue gases
Flue drain
New buildings
Existing buildings
Using an equation from the NDHCV Guide (see NDHCV Guide for full
example), along with the weighting factors and the part load efficiencies
shown, the overall seasonal efficiency may be estimated to ensure compliance
with minimum standards.
Boiler Rating Efficiency at Boiler output (%) at Boiler efficiency (%) Table 3:
no. (kW) stated % of stated % of system as stated % of system Example calculation of
boiler output output output
seasonal efficiency
100% 30% 15% 30% 100% 15% 30% 100%
Combined heat and power (CHP) involves generating electricity on-site and
utilising the heat that is a by-product of the generation process. For a wide
range of buildings, CHP can offer an economical method of providing heat
and power which is less environmentally harmful than conventional methods.
In these buildings, CHP is often the single biggest measure for reducing
buildings-related CO2 emissions and running costs.
The CHP Quality Assurance scheme (CHPQA)(19) sets out what is meant by
‘good quality’ CHP. New installations in buildings must have a quality index
over 105 and a power efficiency over 20%. The Building Regulations now
require all new and replacement CHP plants to meet these quality criteria.
Each kW·h of electricity supplied from the average fossil fuel power station
results in the emission of around half a kilogram of CO2 into the atmosphere.
Typically, gas-fired boilers emit around one fifth of a kilogram of CO2 per unit
of heat generated. CHP has a lower carbon intensity of heat and power
production than these separate sources and this can result in around a 30%
reduction in emissions of CO2, thus helping to reduce the risk of global
warming. The environmental benefits can be clearly seen in Figures 10 and 11
below. CHP produces far less CO2 emissions with a reduced primary energy
input than conventional energy supply systems.
With over 1000 installations within UK buildings CHP is a tried and tested
technology. Government has set a target of installing 10 000 MWe of CHP by
2010, which could provide 20% of the UK’s carbon reduction target under
the Kyoto Protocol. With rising energy prices and, specifically, a widening gap
between gas and electricity prices, CHP is becoming one of the principle
technologies for providing a cost-effective low carbon solution. To be
economic it needs to be used in buildings with a significant base heat demand
and should be sized correctly in relation to this demand.
CHP can be powered by renewable fuels that can reduce carbon emissions
to zero. These include biogas produced from anaerobic digestion or from
67 kg 39 kg
270
kW·h
Delivered
Primary energy
energy
200 kW·h 160 kW heat
input
470 kW·h 100 kW electricity
Boiler
Figure 11:
Energy supply using CHP
CO2
63 kg
Delivered
energy Primary
160 kW heat energy
100 kW electricity input
325 kW·h
CHP unit
waste oils from food processing. Wood chip gasification also presents
opportunities although this is less well tried and tested. Bio-CHP is usually
more economic in larger installations to minimise the cost of fuel handling but
there are examples of small bio-CHP plants.
CHP should always be the lead ‘boiler’. There is now a range of technologies that can be used as CHP in buildings:
The best sites have a year-round heat
demand. (a) ‘micro’ CHP (up to 5 kWe)
CHP usually requires 5000 hours/year — Stirling engines
running for economic viability.
— reciprocating engines
CHP heavily depends upon heat and
power demand profiles.
The economics of CHP improve if (b) small scale (up to 1 MWe)
standby generation or boiler replacement
is undertaken.
— spark ignition
CHP should be sized according to the — micro-turbines (30–100 kWe)
base heat load, but the best economic — small scale gas turbines (typically 500 kWe)
case is often obtained by sizing the plant
slightly bigger than this.
Ensure heat is utilised in the building as (c) large scale (above 1 MWe)
savings are reduced if heat is rejected. — gas turbine
Savings depend on the hours run, — large reciprocating engine
therefore run the CHP as much as
possible to maximise savings.
Ensure that correct energy prices are (d) fuel cells.
used for feasibility studies as savings are
heavily dependent on fuel costs and
electricity prices. Most CHP in single buildings are small scale plants, normally based on gas-
Don’t rely on suppliers’ feasibility reports; fired reciprocating engines and in the form of packaged units, often in
commission a detailed independent study. modular boiler arrangements with outputs between 50 kWe and 1 MWe.
These units supply water at 82 °C suitable for space heating and hot water
systems and their part load efficiency is good. Very small non-domestic
buildings can be supplied successfully using micro-CHP whereas larger scale
(>1 MWe) installations are more likely to use gas turbines or reciprocating
engines.
The energy balance for a typical small gas-fired CHP plant is shown in Figure
12.
Generator
Gas engine
Heat pumps are devices (heat engines) that move heat from one location to
another through the input of work. Normally, a small input of electricity
results in the movement of larger amounts of heating or cooling to the point
of demand. Most often, heat pump technology is applied to moving heat from
a low temperature heat source to a heat sink at a higher temperature. Heat
pumps can produce high coefficients of performance (COPs) when operating
at low temperature differentials and a COP of 4.0 is common when operating
Coefficient of performance (COP) in heating mode. Heat pumps have found wide use in applications where ‘low
grade’ heat is available, e.g. where low grade heat from an industrial process
COP is a measure of efficiency, a COP of is being dumped, or for ventilation extract heat recovery such as in swimming
3.5 being roughly equivalent to an
efficiency of 350%; i.e. inputting one unit pools and supermarkets.
of electricity provides 3.5 units of heat
output.
Heat pumps are available in a number of different forms and exploit different
However, the term ‘efficiency’ is
inaccurate, since the electricity input sources of low grade heat. They may use the ground as a source, or water or
does not make heat, but instead moves air, all of which have different efficiencies and characteristics. Air source heat
existing heat ‘upstream’.
pumps may be used to extract heat either from outside air or from
ventilation exhaust air. When outside air is used as a heat source, the COP
tends to decline as the air temperature drops.
When used to provide heating only, the COP of heat pumps does not usually
compensate for the increased financial and environmental costs of using
electricity. Where the need for cooling has been established, e.g. in retail
outlets, reversible heat pumps can be an effective way of providing both
cooling and heating. Small split-unit heat pumps are common in small shops
and offices, but these require good interlinked controls to ensure that units
providing heating do not conflict with nearby units supplying cooling.
Reversible ground source heat pumps are now becoming a common, energy
efficient, solution to provide heating in winter (COP of, say, 4.0) and cooling
in summer (COP of, say, 3.0) in offices, for example. Ground source heat
pumps are best applied in this reversible way so that the ground is
replenished as a heat source between the seasons. Operating in heating
mode only can gradually reduce the ground temperature which will reduce
the COP.
The NDHCV Guide(15) sets minimum standards for compliance with Building
Regulations(5–7) as follows:
— heat pumps (except absorption and gas engine): COP > 2.0
— absorption heat pumps: COP > 0.5
— gas-engine heat pumps: COP > 1.0
Up to 20 2.2
21 to 60 2.4
61 to 120 2.5
Over 120 2.6
Most industrial and warehousing space is heated by either warm air or radiant
systems, both of which can be reasonably efficient, if well controlled.
The NDHCV Guide(15) sets minimum standards for compliance with Building
Regulations as follows:
See the NDHVC Guide(15) for details and for the minimum controls package.
Radiant systems:
— are more efficient because they only heat the occupants and building
fabric and do not generally raise the temperature of the internal air to
full comfort levels
— generally provide a rapid response, requiring less heat-up time at the
beginning of the day.
The radiant effect is only maintained when heater surfaces are above a
certain temperature. Hence two-stage switching, which operates above and
below the critical temperature, gives closer control than simple on /off
switching.
The NDHCV Guide(15) sets minimum standards for compliance with Building
Regulations as follows:
See the NDHVC Guide(15) for details and for the minimum controls package.
The NDHCV Guide(15) sets out minimum standards of controls for different
heat generators in order to comply with Building Regulations(5–7). Chapter 5
of CIBSE Guide F(1) covers overall control strategies; more detailed guidance
is available in chapter 10 of CIBSE Guide F and in CIBSE Guide H(3).
— increase comfort
— prevent systems running and cycling unnecessarily
— ensure the right level of service
— minimise maintenance requirements
— reduce energy consumption.
— when required
— where required
— to the temperature required,
and the boiler fires only when there is a demand for heat.
Even a well designed system can perform badly if the controls are poor.
Equally, good controls will not rescue a poorly designed heating system.
Systems should revert to safe and energy-efficient ‘off’ or ‘standby’ levels
after use, rather than default to ‘on’.
In general, sequence control will not operate correctly where the flow rate
varies as a result of individual boiler pumps or automatic isolation valves.
Systems should have:
Optimum start controls are weather dependent time-switches that vary the
start-up time in the morning to achieve the building temperature by the start
of occupancy. Heat-up times are reduced during milder weather, thus saving
around 5–10% of heating energy. Optimum stop controls turn the heating
system off early without compromising comfort in milder weather. Figure 13
shows the operation of optimum start controls and the potential energy
savings compared with a time-switch. Optimum start/stop controls can be
relatively simple using a single internal sensor and a linear delay of start-up.
24
Potential energy savings
Figure 13:
Timeswitch Operation of optimum
20 set for 6 am
Internal temperature (°C)
start control
Typical settings
16
•Maximum heat-up
period:
12 6 am to 9 am
4
04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00
Time of day
CIBSE Knowledge Series — Energy efficient heating 23
However, sophisticated self-learning units with an external sensor are now
common, providing closer control and greater savings. The greatest energy
savings from optimum start controls are likely to be gained in buildings of
lightweight construction and with heating systems of low thermal capacity.
Figure 14:
Weather compensation 80
60
Temperature (oC)
40
0
–2 0 2 4 6 8 10 12 14 16 18 20
External temperature (oC)
Most heating systems have a constant flow rate and use the same amount of
energy for pumping power throughout the year regardless of the load on the
system. Variable speed pumps can respond to the reduced demand by
decreasing the flow of the pumps so that they match the load on the system.
Considerable savings in pumping energy and improved space temperature
control can be achieved by controlling the speed of distribution system
pumps to respond to system demand. Variable speed drive controls are now
relatively cheap, giving a rapid economic payback. They also have in-built sub-
metering and can often aid commissioning/system balancing.
As shown in Figure 15, typically only 20% of full volume energy is required to
move air and water at 50% of maximum volume. Further guidance can be
found in CIBSE Guide H(3).
60
40
20
0
1 2 3 4 5 6 7 8 9 10
Hour
— wood:
• forestry, highways, railways, tree surgeons, farms
• processing waste (sawdust)
— energy crops:
• short rotation coppice (SRC)
• miscanthus, grass and hay
— agricultural waste:
• straw, chaff, chicken litter, slurry /dung
— food processing waste:
• sugar beet waste, nutshells
• spoilt batches, condemned food, process effluent
— landfill gas
— biogas from anerobic digestion
— bio-oils:
• ethanol from sugar cane
• biodiesel from waste vegetable oil.
The calorific value of some renewable sources are shown in Table 4(23).
* average
Figure 16:
Biogas to
Anerobic digester Gas holder
CHP engine
producing biogas in
combination with CHP Slurry
Heat from
CHP engine
Digester
Effluent
(to land)
Solar water heating converts solar radiation into heat that can be used
directly in hot water systems. They are widely used around the world to
provide domestic hot water, particularly where sunshine is plentiful and fuel is
The current commercial price of a typical hot water system for a house
varies from £2000 to £6000. Typically, solar collectors cost £300 to £750
per m2 to install (depending on the technology) and would produce
approximately 300 kW·h/m2 of hot water in the UK. There are some
indications that the cost of systems is falling, increasing the economic
attractiveness of systems and the range of viable applications. A collector area
of 4–5 m2 can save approximately 0.5 tonnes of CO2 emissions per year.
Civic
buildings
Houses
and flats
Community
centre
Hours per year (h) 2000 2500 2000 2500 2500 3000 3000 3750
Space heating EUI (kW·h /m2 per year) 72 141 72 141 90 168 95 181
Note: factors for converting treated floor area to net and gross are shown in Appendix A3
For new offices, good practice EUIs can be treated as the upper limit, the
aim would be that no office of any age should have an EUI greater than the
typical values. Space heating and hot water benchmarks for a range of other
buildings, e.g. hotels, mixed-use buildings, banks and agencies, are available in
chapter 20 of CIBSE Guide F(1). Where buildings provide 24-hour occupation
or have significant special end-uses such as swimming pools then EUIs will be
significantly higher than those in Table 6. Buildings with electric space heating
should be compared on the basis of CO2 emissions.
Degree-days
For product comparisons and sizing boilers, ensure that all the information is
based on either gross calorific value or net calorific value — don’t mix the
two. Heat output shown on manufacturers’ literature might be based on
either gross or net and this can make a significant difference when specifying Table 8:
equipment. Calorific values for some fuels are given in Table 8. Calorific values of fuels
Source: CIBSE Guide F(1)
In simple terms, the calorific value (CV) is the amount of heat released when Fuel Calorific value
a specific amount (weight or volume) of fuel is completely burnt in oxygen. (MJ/kg)
Most commonly used fuels (oil and gas) contain hydrogen and when burnt
this hydrogen is converted to water vapour that, when fully cooled, is Gross Net
converted to liquid water. During the process of converting water vapour to Class D fuel oil* 45.0 42.2
its liquid state a certain amount of heat is released. This is known as the Natural gas† 38.6 34.7
latent heat of condensation. The possibility exists for the measurement of LPG:
— butane 49.5 46.0
calorific value to include or to exclude the latent heat of condensation/evap- — propane 50.0 46.5
oration, thus there are two values of calorific value for a fuel. The higher Solid fuels (washed
value, including the latent heat, is the ‘gross’ CV and the lower value is the smalls):
— anthracite 29.65 28.95
‘net’ CV, see Figure 18. — dry steam coal 30.60 29.65
— coking coals 30.80 29.75
(medium volatile)
The gross CV of the fuel assumes that all the water vapour produced during
combustion has been converted to water. The efficiency of any product * to BS 2869
based on the gross CV cannot be greater than 100%. The net (lower) CV is † at 15 °C, 101.3 kPa
measured and calculated assuming that all the water vapour produced during
combustion remains as vapour. By designing an appliance which condenses
some of the water vapour (e.g. a condensing boiler), it is possible to measure
efficiencies greater than 100% using the net CV as the basis for calculation. In
the case of a natural gas appliance the efficiency based on gross CV will be
approximately 9% lower than the efficiency based on net CV.
Gross Net
100 units
calorific calorific 91 units
Heat to of heat Heat to
value value of heat
water water
84% 93%
14.1 References
1 Energy efficiency in buildings CIBSE Guide F (London: Chartered Institution of Building Services
Engineers) (2004)
2 Heating, ventilating, air conditioning and refrigeration CIBSE Guide B (London: Chartered Institution
of Building Services Engineers) (2001–2002)
3 Building control systems CIBSE Guide H (London: Chartered Institution of Building Services
Engineers) (2009)
4 Domestic heating design guide (London: Domestic Building Services Panel) (2008)
5 The Building Regulations 2000 Statutory Instruments 2000 No 2531 as amended by The Building
(Amendment) Regulations 2001 Statutory Instruments 2001 No. 3335 and The Building and
Approved Inspectors (Amendment) Regulations 2006 Statutory Instruments 2006 No. 652)
(London: The Stationery Office) (dates as indicated) (London: The Stationery Office) (2007)
(available at http://www.opsi.gov.uk/stat.htm)
6 The Building (Scotland) Regulations 2004 Scottish Statutory Instruments 2004 No. 406 (London:
The Stationery Office) (2004)
7 Building Regulations (Northern Ireland) 2000 Statutory Rules of Northern Ireland 2000 No. 389
(London: The Stationery Office) (2000)
8 Conservation of fuel and power in new buildings other than dwellings Building Regulations 2000
Approved Document L2A (London: The Stationery Office) (2006) (available at http://www.
planningportal.gov.uk/england/professionals/en/1115314231806.html) (accessed August 2008)
9 Conservation of fuel and power in existing buildings other than dwellings Building Regulations 2000
Approved Document L2B (London: The Stationery Office) (2006) (available at http://www.
planningportal.gov.uk/england/professionals/en/1115314231813.html) (accessed August 2008)
10 Technical Handbook: Domestic (Edinburgh: Scottish Building Standards Agency) (2008) (available at
http://www.sbsa.gov.uk/tech_handbooks/tbooks2008.htm) (accessed October 2008)
11 Technical Handbook: Non-domestic (Edinburgh: Scottish Building Standards Agency) (2008) (available
at http://www.sbsa.gov.uk/tech_handbooks/tbooks2008.htm) (accessed October 2008)
12 Conservation of fuel and power The Building Regulations (Northern Ireland) 1994 Technical booklet F
(London: The Stationery Office) (1998) (available at http://www.dfpni.gov.uk/index/law-and-
regulation/building-regulations/br-technical-booklets.htm) (accessed August 2008)
13 Conservation of fuel and power in dwellings The Building Regulations (Northern Ireland) 2000 Technical
booklet F1 (London: The Stationery Office) (2006) (available at http://www.dfpni.gov.uk/
index/law-and-regulation/building-regulations/br-technical-booklets.htm) (accessed August 2008)
14 Conservation of fuel and power in buildings other than dwellings The Building Regulations (Northern
Ireland) 2000: Technical booklet F2 (London: The Stationery Office) (2006) (available at http://www.
opsi.gov.uk/legislation/northernireland/ni-srni.htm) (accessed August 2008)
15 Non-Domestic Heating, Cooling and Ventilation Compliance Guide (London: NBS/Department of
Communities and Local Government) (2006) (available at http://www.planningportal.gov.uk/
uploads/br/BR_PDF_PTL_NONDOMHEAT.pdf) (accessed August 2008)
16 Building energy metering CIBSE TM39 (London: Chartered Institution of Building Services Engineers)
(2006)
17 Automatically controlled steam and hot water boilers Guidance Note PM5 (London: HSE Books)
(2000)
18 Directive 2002/91/EC of the European Parliament and of the Council of 16 December 2002 on the
energy performance of buildings (‘The Energy Performance of Buildings Directive’) Official J. of the
European Communities L1/65 (4.1.2003) (Brussels: Commission for the European Communities)
(2003) (available at http://ec.europa.eu/energy/demand/legislation/buildings_en.htm)
19 CHPQA: Quality assurance for combined heat and power (website) (London: Department for the
Environment, Food and Rural Affairs) (2007) (http//:www.chpqa.com) (accessed October 2008)
20 Combined heat and power for buildings Good Practice Guide GPG 388 (Carbon Trust) (2004)
(available at http://www.carbontrust.co.uk/publications) (accessed October 2008)
Non-domestic hot water heating systems CIBSE Applications Manual AM14 (London: Chartered
Institution of Building Services Engineers) (2009)
Council Directive 92/42/EEC of 21 May 1992 on efficiency requirements for new hot-water boilers fired
with liquid or gaseous fuels (‘The Boiler Directive’) Official J. of the European Communities L167 17–28
(22.06.1992)
The Boiler (Efficiency) Regulations 1993 Statutory Instruments 1993 No. 3083 (London: Her Majesty’s
Stationery Office) (1993)
Groundwater cooling systems CIBSE TM45 (London: Chartered Institution of Building Services Engineers)
(2008)
BS 5422: 2001: Methods for specifying thermal insulating materials on pipes, ductwork and equipment (in
the temperature range –40°C to +700°C) (London: British Standards Institution) (2001)
Brown R and Crawford Z Radiant heating BSRIA AG 3/96 (Bracknell: Building Services Research and
Information Association) (1996)
Energy use in offices Energy Consumption Guide ECG019 (Carbon Trust) (2003) (available at
http://www.carbontrust.co.uk/publications) (accessed October 2008)