(VEGA-ENG) User Manual OPR501-N - REV3
(VEGA-ENG) User Manual OPR501-N - REV3
DOOR DRIVE
OPR501-N
1
1. GENERAL INFORMATION
Power supply 230Vac ±10% (50-60Hz)
Dimension 270mm x 106mm x 45mm
Weight 0,7Kg
Degree of protection IP20
On board protection 8A
Output relay switching capacity 24VDC 3A
PINOUT
JP1 Connector for emergency power to 24Vdc (battery)
JP2 Connector for output signal
CLOSED
OPENED
OBSTRUCTED
JP6 Mains connection 230V (50/60 Hz)
JP8 NOT USED
JP10 Encoder connector
JP11 Engine connector
JP12 Keyboard plug
JP13 Engine plug
JP15 Connector for input (ONLY CLEAN CONTACT, without voltage)
OPEN
CLOSE
NUDGE
SW1 Dipswitch for default configuration
SW2 Push button:
-learn (press for 3 seconds)
-Run (open / close) (quick press).
PWR( led) Normal work GREEN
ErrorRed
OBS(led) ObstructionYellow
CE Certified
Electrical safety according to EN 60950 Conforming
2
2. CONNECTIONS (CONTROL PANEL)
DO NOT OPEN
Push button
THE COVER R SW2 Run / learn switch
Default
3
JP6 SW1
2
configurations
ON
1
INPUT ITALIAN STYLE FOR LIFTS +3.3V 19
SERIAL
L1
Power supply
CAN
GND 18
230Vac
JP8 17
CAN H
N
50/60 Hz CAN L 16
JP15 R 120 Ω
CONTROL
PANEL KEYPAD
+12 VDC
Photo.
JP12
Nudge
Close
Open
JP1 JP10 JP11 JP13 JP2
TEMP.MOT
BATTERY
ENCODER
PHOTO.
MOTOR + LED
NUDGE
CLOSE
24Vdc MOTOR CLOSED OBSTR.
COM +
OPENED
OPEN
ENC A
ENC B
ENC.
+ BAT
- BAT
GND
OBS PWR
+5V
M1
M2
26
27
15
20
21
22
23
24
25
12
13
10
11
14
5
6
7
8
9
2
3
4
1
ENCODER+MOTOR
Command common
relay reopening relay relay
Opening
Closing
BATTERY Relay signal
nudge
+
24Vdc
EMERGENCY
POWER
CONNECTIONS between
“10” and “11,12,13” in the
“JP15” connector must be
clean contacts without
tension.
ELVI 108657/FCEEJP13
Rated voltage 24 VDC
Maximum speed 220 rpm
Gear ratio 1:26
Encoder resolution (Encoder integrated in GM) 3
Degree protection IP20
Rated Torque 1.5 Nm (2.5 A)
(KAG)JP10-11 (DEFAULT)
Rated voltage 24 VDC
Maximum speed 210 rpm
Gear ratio 1:15
Encoder resolution (Encoder integrated in GM) 100
Degree protection IP20
Rated Torque 1.62 Nm
KORMAS)JP10-11
Rated voltage 24 VDC
Maximum speed 220 rpm
Gear ratio 1:15
Encoder resolution (Encoder integrated in GM) 100
Degree protection IP20
Rated Torque 5 Nm
3
3. START-UP
1. Connect the engine (JP10/ JP11/JP13).
DO NOT OPEN
Push button
THE COVER R SW2 Run / learn switch
Default
3
JP6 SW1
2
configurations
ON
1
POWER INPUT ITALIAN STYLE FOR LIFTS +3.3V 19
SERIAL
L1
220VAC Power supply
CAN
SUPPLY JP8
GND 18
230Vac CAN H 17
BE SURE TO CONNECT N
50/60 Hz CAN L 16
THE GROUND
JP15 R 120 Ω
CONTROL
PANEL KEYPAD
+12 VDC
Photo.
JP12
Nudge
Close
Open
JP1 JP10 JP11 JP13 JP2
TEMP.MOT
BATTERY
ENCODER
PHOTO.
MOTOR + LED
NUDGE
CLOSE
24Vdc MOTOR CLOSED OBSTR.
COM +
OPENED
OPEN
ENC A
ENC B
ENC.
+ BAT
- BAT
GND
OBS PWR
+5V
M1
M2
26
27
15
20
21
22
23
24
25
12
13
10
11
14
5
6
7
8
9
2
3
4
1
ENCODER+MOTOR OUTPUT INPUT
a) Check that at the power on, the doors will have to go in closing and the display will write "Door
closed".
b) If at the power on, the doors GO IN OPENING, enter in the menu " OPTIONS" and set on "Motor
rotation" the value "Reverse”. Turn Off and return at point 2.a.
DURING THIS PHASE, VERIFY THAT THE TRAVEL OF THE DOOR IS FREE FROM ANY
OBSTACLES AND THAT THE DETECTED POINT 0 ACTUALLY CORRESPONDS TO FULLY
CLOSED DOORS.
In case of operator with retractable cam, the door can be considered as completely closed, when
the retractable cam is closed.
4. SELF-LEARNING
The Self-learning function must be set-up by the installer at start-up and is required in order to
have the drive memorize the number of encoder pulses corresponding to the door clear opening.
START SELF-LEARNING
Press the SW2 push button,
for 3 seconds.
The board performs the self-learning to store the door opening data in its permanent memory, and
the door remains open, waiting for command. Self-learning procedure must be performed with
completely closed doors. During this phase, make sure that the doors travel are free. Otherwise,
repeat the operation.
4
4. COMMANDS FROM THE CONTROL BOARD OF THE
ELEVATOR
4.1 Open
The door opening can be controlled by the elevator control board through the closing of terminals (10-11)
in JP15, or through the control on the user interface or by pushbutton SW2.
The opening command is ignored in the following cases:
- Searching of Point 0;
- Self-learning phase;
- When the door closing command is active. (in order to accept the open command during the closing
phase it is necessary first interrupting the door close command);
- Alarm on;
- Door closing with Nudge;
- Door closing command from the user interface.
4.2 Close
Door closing can be controlled by the elevator control board through the closing of terminals (10-12) in
JP15 or by the command on the user interface or through pushbutton SW2.
The closing command is ignored in the following cases:
- Searching of Point 0;
- Self-learning phase;
- When the door opening command is active.(in order to accept the door closing command during the
opening phase it is necessary first interrupting the door open command).
- Alarm On;
- Door closing with Nudge;
- Door opening command from the programming pad (user interface);
- Safety reopening system is activated;
- Re-opening command from the photocell.
4.3 Nudge
In this mode, the drive performs a forced closing of the door with a safety torque corresponding to the
parameter of the safety reopening system (EN 81.1/2 compliance) and at very low speed. Nudge function is
optional and, if required, must be controlled from by control board of the elevator, after a certain number
of closing doors failed attempts. Normally, along with the nudge function, should be activated an audible
signal that warns the passengers in the car of the forced door closing. The function is controlled by closing
terminals (10-13) in JP15 and remains active only while the command stays on. Nudge can be enabled
during the opening state and while the door is in movement as well. If the command is interrupted before
to complete the door closing, the drive performs the opening or closing command from the elevator
control board. Without this command, the door remain waiting.
5
5. KEYPAD
The user interface consists of 4 buttons (ESC, ENTER, UP and DW) and an alphanumeric display to
16 characters,in two lines.
DISP801
ALLARMI/
INGRESSI
ENCODER
OPR500
1 2
A ENC-INC
STATO ALLARME S
3 SD-CARD
4
CABLE
CB6.RJ12-RJ12.0050 2 RJ12 connectors (50 cm)
Using the buttons "UP" and "DW" you can select the commands that you want to give and confirm
by pressing the ENTER key.
NOTE:
DON’T CHANGE A PARAMETER WITH THE DOOR IN
RUNNING!
6
6. PROGRAMMING MENU
NOTE:
DON’T CHANGE A PARAMETER WITH THE DOOR IN
RUNNING!
7
6.1 OPENING PROFILE AND CLOSING PROFILE
OPEN PROFILE
Speed B_a C_a
DOOR DOOR
A_a VH_a D_a
CLOSED OPENED
V1_a V2_a 100%
0%
V2_c V1_c
VH_c
Z_c A_c D_c
B_c C_c
OPENING PROFILE:
CLOSING PROFILE:
Parameters Description Default
Point D_c Start closing acceleration ramp 099
Point C_c End closing acceleration ramp 085
Point B_c Start closing deceleration ramp 030
Point A_c End closing deceleration ramp 008
Point Z_c Additional run closing for mobile coupling cam 005
Speed V1_c Starting closing speed 005
Speed VH_c Maximum closing speed 050
Speed V2_c End closing speed 003
Speed rif Speed during the initial synchronization 015
8
6.2 AUXILIARIES (“TORQUES”)
Represented by five references of current expressed in percent of the maximum
value. The maximum value of the couple's 8 A (Max Force = 340 N).
6.3 COMMANDS
-Open and Close: Door opening and closing. They have priority over the elevator
control board commands.
-Save: all interface data are stored in the permanent memory
-Default: restore all original settings. The recalled default parameters will be saved in
the permanent memory of the microprocessor (Eeprom) only by SAVE.
-Self-learning: it allows memorizing the number of encoder impulses corresponding
to the door clear opening.
6.4 OPTIONS
Safety reopening system in closing (“SEC. CL TORQUE”)
You can program the working type for the input of safety reopening system in closing:
-Slave: the board indicates the safety reopening system (relay OBSTR) to the control
panel and waits for a new command from the control panel.
-Master: the board indicates the safety reopening system (relay OBSTR) to the
control panel and reopens automatically.
9
Command type (“COMMAND MODE”)
This parameter works on opening and closing inputs (11 and 12);
MASTER: a pulse command suffices for opening and closing door operations;
SLAVE: the board need a continuous command to complete opening and closing door
operations.
6.6 LANGUAGE:
Its possible choose the language at parameter: SELECT LANGUAGE (Italian, English/german)
6.7 SOFTWARE:
Once inside the menu, you can see the current firmware version of the board that is
currently programmed.
FIRMWARE UPGRADE (OPR500):
1) Insert the "Opr500.hex" file in the Micro SD-CARD
(FAT-32 formatted).
2) Insert the micro SD-CARD in the keypad (DISP801) connected to the operator;
3) Enter the Software menu;
4) Press the ENTER key twice (quickly) to enter the Boot menu;
5) Press ENTER to start the update process
6) The update procedure has been completed.
Double
click
ESC (ENTER)
SOFTWARE Boot Updating
SOFTWARE
Opr500_vxxx ENTER
ENTER
7. FUNCTION
7.1 ENGINE HEAT PROTECTION IXT
This function is always active and protects the engine from overloads due to
mechanical hardening or obstacles hindering the normal door travel.
If the current absorbed by the engine is higher than the set level (5A) for more than 7
sec., the driver is disabled and stands by for 15 sec. , it will then close the door in low
10
speed mode. If closing fails and the current is higher than 5 A again, the above
described cycle will be repeated. After a third failed attempt, the driver will enter
the Fault state. If the obstacle is removed, after one regular cycle the counter resets
itself.
8. LED DIAGNOSTIC
“OBS” led
1: ERROR EPROM
2: OVERCURRENT
3: ENGINE NOT CONNECTED
4: ENCODER ERROR
5: IXT ERROR
6: ENGINE IN OVER TEMPERATURE
11
9. DEFAULT PARAMETRS
OPENING PROFILE :
TORQUES:
Parameters Description Max val
Default
Max Torque Maximum 095 100
Limit Torque Limit Torque 070 (Coppia Max) -5
Stat Op. Tor. Stationary opening torque 020 (Coppia Max) -5
Stat Cl. Tor. Stationary closing torque 005 (Coppia Max) -5
Sec. Cl. Tor. Security Torque in closing 055 (Coppia Max) -5
Sec. Op. Tor. Security Torque in opening 080 (Coppia Max) -5
OPTIONS:
12
10. DIMENSIONS
270 mm
106 mm
118 mm
252 mm
14 mm
12 mm
252 mm
12 mm
41 mm 77 mm
12 mm
R3
13
11. TROUBLESHOOTING:
PROBLEM Solution
The doors not move / Check that the box is powered by 220 Vac ± 10%
the doors are moving fast and Check the connections between the board and the motor
out of control / (JP 1-13).
ENC-KO error on display /
Led "PWR" (red), 3 flashes.
The doors move slowly / Repeat the self-learning procedure (Chapter 3).
ENC-INC error on display /
Led "PWR" (red), 4 flashes.
The door not open Check if the doors are opened through the appropriate
command from keypad (MenuCOMMANDOPEN).
Make sure the first row of the display if there is a letter "O"
that indicates the activation of the opening. (Jp1511
OPEN).
The door not close Check if the doors are oclosed through the appropriate
command from keypad (MenuCOMMANDCLOSE).
Make sure the first row of the display if there is a letter "C"
that indicates the activation of the closing
(Jp1512 CLOSE).
The doors move in the opposite Enter the menu and reverse the direction of rotation
direction/ changing the parameter MOTOR ROTATION:
At power move in opening MENUOPTIONS MOTOR ROTAT.REVERSE/FORWARD
The doors slow down late and Repeat the self-learning procedure (Chapter 3).
slam it in opening Enter the menu on the item OPENING PROFILE and
decrease the parameter C_a and D_a.
Verify that the belt is not too slow.
The doors slow down late and Repeat the self-learning procedure (Chapter 3).
slam it in closing Enter the menu on the item CLOSING PROFILE and
inrease the parameter B_C and A_c.
Verify that the belt is not too slow.
The doors often reveal an Check that the doors haven’t defect /locks mechanical in
obstacle (OBSTR.) closing.
Increase the “Sec. CL. Tor” parameter (Menu Torques)
Repeat the self-learning procedure (Chapter 3).
Ixt PROT error on display/ Check that the doors haven’t defect /locks mechanical in
Led "PWR" (red), 5 flashes. opening.
Increase the “Sec. OP. Tor” parameter (Menu Torques)
Repeat the self-learning procedure (Chapter 3).