PM Secur TM 1109a en 220120 110143
PM Secur TM 1109a en 220120 110143
xlsm - 30/11/2011
SECUR TM
Traffic Master
lift controller
Programming manual
Compatibility:
controller board: SEC-2Q rev. 1.0 sw. rev.: 11.09A
car board: SEC-2C rev. 1.0 sw. rev.: 11.01
landing boards: SEC-2L rev. 1.0 sw. rev.: 11.01
extension boards: SEC-2IO rev. 1.0 sw. rev.: 11.01
optional board: SEC-2OPT rev. 1.0 sw. rev.: 11.02
Programming:
In order to enter in PROGRAMMING way:
· press and keep the button M for 3”; the display shows the menu 00 - “EXIT”
· press or to select the desired menu
· press M to enter in the selected menu
· (S4): scroll the parameters forwards
· (S2): scroll the parameters backwards
· (S1): increase the parameter value
· (S3): decrease the parameter value
· press M exit from the selected menu
In order to exit from the PROGRAMMING way:
· select the menu 00 - “EXIT”
· press M
· (S1): save the made modifications (User)
· press M to exit
page 1/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
en = english
menu 01 fr = francaise
01.01 Language en
BASE de = deutsch
it = italiano
01.02 Number of Floors 2 2 32 2, . . , 32 Sets the total stops of the lift.
ATTENTION:
01.04 Parking Floor 0 0,1,2, . . , 32
always 0 with hydro installations
No = no parallel call
Car = parallel only car
01.06 Par.Calls SEC-2P Car
Landings = parallel only floor
Car+Land = parallel car and floor
0m = parking disabled
ATTENTION:
01.08 Parking timer 15m 10m = 10 min.
HYDRO = 15m = 15 min. max.
15m = 15 min.
003 = 3 sec. 003 = with automatic door
01.09 Busy timer 003s
10.0 = 10 sec. 008 = with swing door
page 2/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Hydraul.
menu 02
02.01 Lift Type Hydraul. Traction/V3F
MOTOR DRIVE
Dig/Shaft
Oleo std
Idr. 3010/sft
Idr. 3010/2CH
Idr. 3010/S/2CH
Idr. 3100-E2
Idr. ALGI 4 Valve
Idr. BERINGER
02.02 Hydraulic Select Hydro std hydro std 19 Idr. MORIS Sf HYDRO ONLY
Idr. 2MC Sft
Idr. GMV GEV
Idr. ALGI AZRS
Idr.START E90 ss
DOPPIA
V3F MED
BUCHERvf
NO = without auxiliary
microlevelling motor pump
02.03 Aux. Microlevell No HYDRO ONLY
Yes = with auxiliary microlevelling
motor pump
0.50
0 50 = 0.5
0 5 sec. HYDRO ONLY
02.04 Hy. Star Time 0.00 0.00 2.50
1.00 = 1 sec. set the star starting time
HYDRO ONLY
0.50 = 0.5 sec.
02.05 Hy. HighSpeed T. 0.50 0.00 2.50 set the delay on energizing the high
1.00 = 1 sec.
speed valve
HYDRO ONLY
Set the delay between floor stop
0.10 = 0.1 sec. magnets and drive end.
02.06 Hy. Up Stop Time 0.20 0.00 2.50
1.00 = 1 sec. ATTENTION: the longer is the time
set, the wider must be the magnet
overlapping (IU-ID)
HYDRO ONLY
Set the delay between floor stop
0.10 = 0.1 sec. magnets and drive end.
02.07 Hy. Dn Stop Time 0.20 0.00 2.50
1.00 = 1 sec. ATTENTION: the longer is the time
set, the wider must be the magnet
overlapping (IU-ID)
HYDRO+MICROLIV. ONLY
0.10 = 0.1 sec. Set the delay between floor stop
02.08 Microlev. Stop T. 0.00 0.00 2.50
1.00 = 1 sec. magnets and drive end. when
microlevelling
page 3/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Trac. 2 Speeds
V3F OMRON
V3F CT-UNIDRIVE
V3F VACON
V3F CT-SP
02.10 Traction Select Trac. 2v 51 90 TRACTION ONLY
V3F SIEI
V3F VACON b/less
V3F Yo Yo
V3F ZETADYN
V3F gen.
TRACTION ONLY
0.50 = 0.5 sec. Set time between direction signal
02.11 Direction Time 0.50 0.00 2.50
1.00 = 1 sec. and speed signal (run order) to
inverter
TRACTION ONLY
Set the time between the direction
0.20 = 0.2 sec.
02.12 Start Time 0.20 0.00 2.50 control and the speed control (run)
1.00 = 1 sec.
to inverter
TRACTION ONLY
Set the delay between floor stop
0.10 = 0.1 sec. magnets and drive end.
02.13 Stop Time 0.20 0.00 2.50
1.00 = 1 sec. ATTENTION: the longer is the time
set, the wider must be the magnet
overlapping (IU-ID)
TRACTION ONLY
0.50 = 0.5 sec.
02.14 Zero Speed Time 04.0 0.00 05.0 Set the max. time allowed at zero
01.0 = 1 sec.
speed
TRACTION ONLY
00.5 = 0.5 sec.
02.15 Brake Time 00.5 0.00 05.0 Set brake off delay time when V3F-
01.0 = 1 sec.
Closed Loop
page 4/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
ATTENTION!
SLOW = inspection in low speed For installations with nominal speed
02.20 Inspection Speed Fast FAST = inspection in high speed exceeding to 0.63m/s always set LOW
NOT ACTIVE on installation V3F
V.isp = (Fn x 0.63)/Vn
I = Intermediate
02.22 Slow Speed L L = Slow Sets the level speed code output
H = High
I = Intermediate
02.23 Int. Slow Speed I + L L = Slow Sets the low speed output
H = High
I = Intermediate
02.24 Int.High Speed I + H L = Slow Sets the medium speed output
H = High
I = Intermediate
02.25 High Speed H L = Slow Sets the high speed output
H = High
I = Intermediate
02.26 Reset Speed I + L + H L = Slow Sets the reset high speed output
H = High
I = Intermediate
02.27 Inspection Speed I L = Slow Sets the inspection speed output
H = High
I = Intermediate
02.28 Short Floor Speed I + L L = Slow Sets the short floor speed output
H = High
No = function disabled
02.29 Releveling Tract No
Yes = function enabled
No = function disabled
02.30 Enable 2val. Sic No
Yes = function enabled
page 5/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Side A
P:01 Side A Side B
P:02 Side B Side A+B WITH 2 ENTRANCES ONLY
P:03 Side A+B Selectiv
No open
page 6/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
YES = open the doors After the reset open the door or
03.14 Open After Reset YES
NO = don't open the doors don't open the doors
page 7/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
None
Pulse = closing impulse at the
3A.10 Run Close Cmd. Assent departure (see 3A.11)
Always ON = active command during
the close and in run
page 8/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
page 9/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Absent
Impulse = closing impulse at the
3B.10 Run Close Cmd. Absent departure (see 3A.11)
Always ON = active command during
the close and in run
page 10/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
04.06 Priority Floor 00 NOT USE NOT USE NOT USE NOT USE NOT USE NOT USE
04.07 Priority D. Side Side A NOT USE NOT USE NOT USE NOT USE NOT USE NOT USE
NO = function disabled
04.11 Serial Pres. NO WITH SERIAL LDG. CALLS ONLY
Yes = function enabled
page 11/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
NO = function disabled
YES = function enabled (beep in
04.13 Beeper No
car/floor)
Side A
04.16 Visitor Side Side A Select the entrance visitors side
Side B
No = function disabled
FCU = control of:
- limit switch maintenance
04.18 EN81/21 Enable No
- floor doors lock
EU = control only of the floor doors
lock
page 12/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
NO = function disabled
FIDo = fire recall and parking with
menu 05
05.01 Fire Homing NO door open Function enabled by input P7/1
FIRE
FIDc = fire recall and parking with
door closed
NO
ITALY
2 Keys
BELGIUM
CHINA
05.02 Fire Type No UK Function enabled by input P7/2
HONG KONG
AUSTRALIA
EN8172
EN8172-CC
Side A
05.04 Fire Side 1 Side A Side B Set the fire evacuation side
Side A+B
Side A
05.06 Fire Side 2 Side A Side B Set the fire evacuation side
Side A+B
NO = function disabled
05.07 FPD - U36 NO
Yes = function enabled
Enables the short interfloor
menu 06 NO = function disabled calculation function (SFD)
06.01 Short Floors NO
SHORT FLOORS Yes = function enabled DO NOT USE THIS MENU IF DIGITAL
SHAFT
page 13/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
page 14/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
page 15/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
ATTENTION:
menu 12
12.01 Total Runs - read only The total run counter it reset
COUNTERS
against "Charge DEFAULT"
HYDRO ONLY:
12.03 Up Level Counts - read only Shows the levelling number up
direction
menu 13
13.01 Back to menu -
PASSWORD
PIN:---- = no password
13.02 Change value PIN:---- Allows to insert a password code
PIN:0000 = password enabled
S2 = no
13.03 Remove password - Allows to cancel the password
S4 = ok
Single
menu 14
Duplex
DUPLEX/GROUP 14.01 Group Logic Single Select the installation group type
3-plex
4-plex
00 = installation 1
01 = installation 2 Sets the installation number inside
14.02 Group ID 00 00 03
02 = installation 3 the group
03 = installation 4
page 16/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
30.05 Night Start Time 00:00 Sets the start night time
30.06 Night End Time 00:00 Sets the end night time
NO = function disabled
30.08 Gong No Sets gong sound before floor message
Yes = function enabled
page 17/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
NO = function disabled
30.09 Photocell No Asks for leave the doors free
Yes = function enabled
NO = function disabled
30.10 Overload No Asks to unload the car
Yes = function enabled
page 18/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Car floor
Car state
- Last occurred alarm
Alarm Ð
Date - time
Car floor
Car state
- Next to last occurred alarm
Alarm Ð
Date - time
PwOn = Supply
Up_V = Fast up dir.
Up_L = Slow up dir.
Dn_V = Fast down dir.
Dn_L
Dn L = Slow down dir.
dir
Stop = Still
InAp = Opening
Aper = Doors open
InCh = Closing
Chiu = Door closed
CAR STATUS codes
F_Op = Door open in fireman's drive
page 19/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Error codes
Abbreviations on error code beginning indicate position inside functional drawings of the device which is probably related to the current error.
E.G."02B6 Sic. SUPPLY" indicates that safety circuit supply is missing. Check at page 2, section B6.
Abbreviation "Err." indicates a generic or software error, which is not strictly related to functional drawings.
99.xx 01F5 Oil Temper. Terminals P6/1 - P6/2 open (OIL T) Check oil temperature.
99.xx Oil Pressure Terminals P6/3 - P6/4 open (OIL P) Check oil pressure.
99.xx Motor Therms Terminals P6/7 - P6/8 open (MOT T) Check motor temperature.
SEC-2S Board
Check the level landing door
99.xx 0000 Sec.SWING • LED SWING off
contacts
• RL4 relay not energised
SEC-2S board
99.xx 0000 Sec.CAR-D • LED CAR-DOORS off Check the safety car door contacts
• relè RL5 not energised
SEC-2S board
during the run: Check the safety landing doors locks
99.xx 03G4 Sec.Locks
• LOCKS Led's off contact
• RL6 relay not energised
page 20/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Inverter fauld
99.xx 04H5 V3F ready Terminals P5/4 -P5/6 open
Check inverter diagnostic
The high speed remote control switch Check the correct high speed remote
99.xx OUT HIGH Fault
is not energised control switch TH
Check the safety circuit board SEC-
2S it has to be correctly connected
99.xx SEC-3S not conn. SEC-2S board not connected
through the flat cable SCB to the
SEC-2Q board
Check:
• magnets positioning IU, ID, IZ
Error noticed from the security
• Sensor wiring and functioning IU,
99.xx 05C3 DZSM Fault module for re-levelling on open
ID, IZ
doors and/or preopen doors
To restore: CLEAR
3sec.
Mistake revealed from the door zone Check if the door zone magnet is
99.xx Missing door zone
sensor IZ p
positioned
Check:
• travelling cable wiring (XC1/XQ1)
99.xx 06D3 CAN Car off Car serial receiving interrupted
• CAN terminations (SEC-2Q board -
dip sw. SW1/XQ1 - ON)
page 21/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
99.xx 06G5 Machine Room Terminals P6/5 - P6/6 open (MRM T) Check machine room temperature
Further (EN81/21) door limit switch Check the contact and positioning
99.xx 24B1 EN81-21 FCU
contact not functioning wiring FCU
Check:
Serial receiving from floor nodes • shaft serial wiring (CAN2)
99.xx 0000 CAN ext off
interrupted. • CAN2 terminations - see page 90 on
funct. dwg.
page 22/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Check:
• that current value of parm.1,09
"T.Run Superv." is enough for a
Drive time supervision elapsed
complete run between adjacent
during re-levelling
99.xx Run Time floors.
01.07 "T run Superv."
• that no obstacle is compromising
the regular car movement
to reset:
press CLEAR 3sec.
3sec
page 23/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
Status codes
Below listed messages refers to particular and temporary situations.
These messages are not registered into the error memory log.
Halt = INST. Due to an error the lift is not able
BLOCK to re-start.
pp
The lift is supplied y an emergency
by g y
EMER = EMERGENCY battery drive for of net voltage
missing.
page 24/25
PM_SECUR_TM_11.09A_MANUALE_DI_PROGRAM-IT-FR-EN DE 14.11.xlsm - 30/11/2011
param. display default value factory value user value min. value max. value possibilities note
FT-A = Photocel.A
A Photocell is intercepted
FT-B = Photocel.B
page 25/25