0% found this document useful (0 votes)
3K views22 pages

1900/65A Equipment Monitor Manual

This document provides installation instructions for connecting a Bently Nevada 1900/65A general purpose equipment monitor. It describes connecting transducers and sensors to the monitor module in both safe and hazardous areas using non-incendive wiring as well as wiring through safety barriers or galvanic isolators. Connection details are given for vibration and temperature input channels along with power and signal output wiring. Safety guidelines and approvals information is also included.

Uploaded by

Rabah Amidi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3K views22 pages

1900/65A Equipment Monitor Manual

This document provides installation instructions for connecting a Bently Nevada 1900/65A general purpose equipment monitor. It describes connecting transducers and sensors to the monitor module in both safe and hazardous areas using non-incendive wiring as well as wiring through safety barriers or galvanic isolators. Connection details are given for vibration and temperature input channels along with power and signal output wiring. Safety guidelines and approvals information is also included.

Uploaded by

Rabah Amidi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

Installation Manual

Bently Nevada* Asset Condition Monitoring

1900/65A General Purpose


Equipment Monitor
Field Wiring Diagrams

Part Number 173089-01


Rev. H (01/14)
1900/65A General Purpose Equipment Monitor Installation Manual

© 2005 - 2014 Bently Nevada, Inc.


All rights reserved.

The information contained in this document is subject to change without notice.

* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General


Electric Company.
Bently Nevada, Proximitor, Velomitor

Printed in USA. Uncontrolled when transmitted electronically

Contact Information

The following contact information is provided for those times when you cannot contact
your local representative:

Mailing Address 1631 Bently Parkway South


Minden, Nevada USA 89423
USA
Telephone 1.775.782.3611
1.800.227.5514
Fax 1.775.215.2873
Internet www.ge-mcs.com/bently

ii
Additional Information
Notice:
This manual does not contain all the information required to operate and maintain
the product. Refer to the following manuals for other required information.

1900/65A Datasheet (Part Number 173401-01)


Description, Features, Specifications, Ordering Options, Approvals, Accessories
1900/65A Manual (Part Number 173400-01)
System Description, Receiving and Handling Instructions, Installation, Configuration,
Maintenance, Troubleshooting

Product Disposal Statement


Customers and third parties, who are not member states of the European Union, who are
in control of the product at the end of its life or at the end of its use, are solely
responsible for the proper disposal of the product. No person, firm, corporation,
association or agency that is in control of product shall dispose of it in a manner that is
in violation of any applicable federal, state, local or international law. Bently Nevada, Inc.
is not responsible for the disposal of the product at the end of its life or at the end of its
use.

1900/65A Hazardous Area Approvals


Throughout this document where Division 2, Division 1, Zone 1, and Zone 0 are used the
following agency approvals exist:

North American:
Ex/AEx nA [L] IIC
Class 1 Div. 2 Groups A,B,C,D
T4 @-20°C ≤ Ta ≤ 70°C
Vn = 18 to 36 Vdc @ Imax = 1A
per drawing 173089
European:
II 3G Ex nA [nL] IIC T4
@-20°C ≤ Ta ≤ 70°C
Sira 06 ATEX 4053X
IECEx SIR 06.0012X
per drawing 173089

iii
1900/65A General Purpose Equipment Monitor Installation Manual

Contents

1. Connection Overview..................................................................................... 1
1.1 System Connections ........................................................................................................................ 1
1.2 Transducer Connections ................................................................................................................ 2
1.3 Transducer Connection with Barriers ...................................................................................... 4
1.4 Transducer Connection with Galvanic Isolators ................................................................. 5
1.5 Power and Signal Output Connections ................................................................................... 6
2. Non-Incendive Field Wiring Details ............................................................ 9
2.1 Vibration Channel Connections .................................................................................................. 9
2.2 Temperature Channel Connections ........................................................................................10
3. I.S. Field Wiring Details (Safety Barriers)..................................................11
3.1 Vibration Channel Connections ................................................................................................11
3.2 Temperature Channel Connections ........................................................................................12
4. I.S. Field Wiring Details (Galvanic Isolators) ............................................13
4.1 Vibration Channel Connections ................................................................................................13
4.2 Temperature Channel Connections ........................................................................................14
5. Appendix.........................................................................................................15

iv
Section 1 — Connection Overview

1. Connection Overview
1.1 System Connections

Figure 1-1: 1900/65A Monitoring System


1
1900/65A General Purpose Equipment Monitor Installation Manual
1.2 Transducer Connections
Safe or Division 2 / Zone 2 Area

Figure 1-2: 1900/65A Monitoring System


1. 1900/65A Display Module
2. 1900/65A Monitor Module
3. Electrostatic Hazard: Wipe display with a damp cloth only.
4. Display to Monitor wiring
5. Temperature channels may be connected to unapproved thermocouples or RTDs located
in a Class I Division 2 Groups A,B,C,D and Zone 2 IIC,IIB,IIA areas.
6. Temperature channel wiring recommendations:
a. 1900/65A to Thermocouple - Thermocouple extension cable must be of the same
type as thermocouple. Recommended positive (RP) and negative (RN) extension
wire gauge for proper operation is shown in Table 1-1.
Table 1-1: Thermocouple Connections
AWG for Cable Length ft [m] Color Code
Thermocouple
100 [31] 500 [152]# 1000 [305]# RP RN
Type J 22 14 12 White Red
Type K 20 12 10 Yellow Red
Type E 24 16 14 Purple Red
Type T 20 12 10 Blue Red

#Note that signal terminals on 1900/65A monitor will accept a 16AWG maximum
conductor.

2
Section 1 — Connection Overview
b. 1900/65A to RTD – Use twisted shielded pair or triad with stranded conductors
and insulating sheath. Wire gauge is shown in Table 1-2.
Table 1-2: RTD Connections
AWG for Cable Length ft [m]
RTD Type
100 [31] 500 [152] 1000 [305]
Pt, Ni 28 26 22
Cu 26 18 16

7. Vibration channel wiring recommendations:


a. 1900/65A to standard Bently Nevada* vibration transducer – Use 16 to 22 AWG
twisted shielded pair or triad with stranded conductors and insulating sheath.
Cable length is not to exceed 1000ft [305m].
b. For non-standard transducers, consult systems integrator or field applications
engineer
8. Non-Incendive (limited energy) wiring between 1900/65A monitor and
transducers/sensors. See Table 5-1 in the appendix for channel parameters.
9. Temperature channel sensors, e.g., Thermocouple and RTD sensors.
10. Vibration channel transducers, e.g., Proximitor* transducers, Velomitor* transducers,
Accelerometers, etc.

3
1900/65A General Purpose Equipment Monitor Installation Manual
1.3 Transducer Connection with Barriers
Safe or Division 2 / Zone 2 Area Division 1 / Zone 0 or 1 Area

Figure 1-3: Connection with Barriers


1. For I.S. installations using external barriers, disconnect single point earth system
connection by removing the jumper located inside the 1900/65A monitor under the
protective cap. For intrinsically safe (I.S.) external barrier installations, system common to
barrier I.S. ground impedance must not exceed 1Ω. Continuity between the shield of the
field wiring from the hazardous area and the I.S. earth should be verified.
2. Connect shields to I.S. earth at barrier ground.
3. External barriers installed in a safe area must be approved.
4. Refer to Table 5-2 in the appendix for external barrier parameters.
5. Wiring recommendations: 1900/65A to barrier and barrier to standard Bently Nevada
transducer – use 16 to 22 AWG twisted shielded pair or triad with stranded conductors
and insulating sheath. Cable length is not to exceed 1000 ft [305m].
6. Separate all I.S. wiring from non-I.S. wiring by a minimum of 2 in [50 mm]. When
installing systems over one another, take care to ensure separation of I.S. and non-I.S.
wiring.
7. Each channel is a separate I.S. circuit and must be wired separately from other channels.
Use a separate screened cable for each channel or a cable containing wiring for many
channels with each cable separated from other channel wiring by an earthed screen.
8. Temperature channels may be connected to unapproved thermocouples or RTDs located
in a Class I Division 1 Groups A,B,C,D; Class II Division 1 Groups E,F,G; and Class III Division
1 areas when connected through the safety barriers or equivalent recommended in
Table 5-2. For Division 1 / Zone 0 or Zone 1, non-grounded thermocouples or RTDs are
required.

4
Section 1 — Connection Overview

1.4 Transducer Connection with Galvanic Isolators


Safe or Division 2 / Zone 2 Area Division 1 / Zone 0 or 1 Area

Figure 1-4: Connection with Galvanic Isolators


1. Connect shields for the wiring between the 1900/65A monitor and the galvanic isolators
to earth at the 1900/65A monitor and the single point ground jumper should be installed.
The jumper is located inside the 1900/65A monitor under the protective cap
2. Connect shields for incoming field cables to earth at the galvanic isolator rail or at the
entry into the 1900/65A monitors weatherproof enclosure.
3. Galvanic isolators installed in a safe area must be approved.
4. Refer to Table 5-3 in the appendix for galvanic isolator parameters.
5. Wiring recommendations: 1900/65A to galvanic isolator and galvanic isolator to
standard Bently Nevada transducer – use 16 to 22 AWG twisted shielded pair or triad
with stranded conductors and insulating sheath. Cable length is not to exceed 1000 ft
[305m].
6. Separate all I.S. wiring from non-I.S. wiring by a minimum of 2 in [50 mm]. When
installing systems over one another, take care to ensure separation of I.S. and non-I.S.
wiring.
7. Each channel is a separate I.S. circuit and must be wired separately from other channels.
Use a separate screened cable for each channel or a cable containing wiring for many
channels, with each cable separated from other channel wiring by an earthed screen.
8. Temperature channels may be connected to unapproved thermocouples or RTDs located
in a Class I Division 1 Groups A,B,C,D; Class II Division 1 Groups E,F,G; and Class III Division
1 areas when connected through the galvanic isolators or equivalent recommended in
Table 5-3. For Division 1 / Zone 0 or 1 areas, non-grounded thermocouples or RTDs
must be used.

5
1900/65A General Purpose Equipment Monitor Installation Manual

1.5 Power and Signal Output Connections


Safe or Division 2 / Zone 2 Area

Figure 1-5: 1900/65A Monitor Module, dimensions are centimeters (inches)


1. +24 Vdc Power Input
2. To minimize ground loop problems, connect earth ground and system common only at
the 1900/65A or other single point ground. For I.S. installations using external barriers,
disconnect single point earth system connection by removing the jumper located inside
the 1900/65A monitor under the protective cap. For intrinsically safe (I.S.) external barrier
installations, system common to barrier I.S. ground impedance must not exceed 1Ω.

6
Section 1 — Connection Overview
3. Relays 1-3
4. Relays 4-6
5. Wire gauge and type selected per local code requirements. Power terminals can accept
12AWG maximum.
Power Input requirements: 18-36 Vdc, 1.0A Maximum
Must follow Division 2 / Zone 2 wiring methods.
6. Install the 1900/65A only in a housing that is acceptable with the local authority having
jurisdiction for Division 2 / Zone 2 installations. See Figure 5-1 in the appendix for more
housing requirements.
7. Communications
8. 4-20 mA Outputs
9. Ethernet
10. Inhibit/Trip Multiply
11. Reset
12. Transducer Buffered Outputs
13. Do not connect or disconnect the buffered outputs except when de-energized or area is
known to be non-hazardous.

7
1900/65A General Purpose Equipment Monitor Installation Manual

8
Section 2 — Non-Incendive Field Wiring Details

2. Non-Incendive Field Wiring Details


2.1 Vibration Channel Connections
Safe or Division 2 / Zone 2 Area

Figure 2-1: Vibration Channel Connections


1. Connect shields to earth at 1900/65A end only.
2. Components are shown for single channel only (i.e., one transducer to one monitor
channel). Connect other channels similarly.
3. Use non-Incendive wiring between 1900/65A monitor and transducers.
4. Wiring is shown cut away for clarity.
5. Refer to Table 5-1 in the appendix for non-incendive parameters.
6. Refer to specific transducer datasheet for maximum cable length.
7. 3-wire non-incendive devices.
8. 2-wire non-incendive devices. When using BN 2-wire velocity transducers (190501,
330500, 330525 and 330750), the white wire goes to COM/A and the black wire goes to
SIG/B.
9. Signal monitor transducer side view.

See datasheet at http://www.ge-mcs.com/download/monitoring/173401.pdf for


supported vibration input transducers.

9
1900/65A General Purpose Equipment Monitor Installation Manual

2.2 Temperature Channel Connections


Safe or Division 2 / Zone 2 Area

Figure 2-2: Temperature Channel Connections

1. Connect shields to earth at 1900/65A end only.


2. Components are shown for single channel only (i.e., one transducer to one monitor
channel). Connect other channels similarly.
3. Use non-Incendive wiring between 1900/65A monitor and transducers.
4. Wiring is shown cut away for clarity.
5. Refer to Table 5-1 in the appendix for non-incendive parameters.
6. Temperature channels may be connected to unapproved thermocouples or RTDs located
in a Class I Division 2 Groups A,B,C,D and Zone 2 IIC, IIB, IIA areas.
7. Ungrounded thermocouples (not supplied by BN).
8. 2-wire RTD (not supplied by BN).
9. 3-wire RTD (not supplied by BN).
10. Signal monitor transducer side view.

See datasheet at http://www.ge-mcs.com/download/monitoring/173401.pdf for


supported temperature input transducers.

10
Section 3 — I.S. Field Wiring Details (Safety Barriers)

3. I.S. Field Wiring Details (Safety


Barriers)
3.1 Vibration Channel Connections
Safe or Division 2 / Zone 2 Area Division 1 / Zone 0
or Zone1 Area

Figure 3-1: Vibration Channel with Barrier connections


1. Components are shown for single channel only (i.e., one transducer to one monitor
channel). Connect other channels similarly.
2. Use non-Incendive wiring between 1900/65A monitor and barriers.
3. Join cable shields to terminate at the barrier ground as shown. Use insulated shields.
Verify continuity between the shield of the field wiring from the hazardous area and the
I.S. earth.
4. Independent connection to system earth.
5. Wiring is shown cut away for clarity.
6. Refer to Table 5-2 in the appendix for external barrier parameters.
7. 3-wire non-incendive devices.
8. 2-wire non-incendive devices. When using BN 2-wire velocity transducers (190501,
330500, 330525 and 330750), the white wire goes to COM/A and the black wire goes to
SIG/B.
9. MTL 796(-), BN# 02245002, or equivalent.
10. MTL 728(-), BN# 02295055, or equivalent.
11. Signal monitor transducer side view.
See datasheet at http://www.ge-mcs.com/download/monitoring/173401.pdf for
supported vibration input transducers.

11
1900/65A General Purpose Equipment Monitor Installation Manual
3.2 Temperature Channel Connections
Safe or Division 2 / Zone 2 Area Division 1 / Zone 0
or Zone1 Area

Figure 3-2: Temperature Channel with Barrier connections


1. Components are shown for single channel only, (i.e., one transducer to one monitor
channel). Connect other channels similarly.
2. Use non-incendive wiring between 1900/65A monitor and barriers.
3. Join cable shields to terminate at the barrier ground as shown. Use insulated shields.
Verify continuity between the shield of the field wiring from the hazardous area and the
I.S. earth.
4. Independent connection to system earth.
5. Wiring is shown cut away for clarity.
6. Refer to Table 5-2 in the appendix for external barrier parameters.
7. Bently Nevada does not supply thermocouples or 3-wire RTDs. Temperature channels
may be connected to unapproved thermocouples or RTDs located in a Class I Division 1
Groups A,B,C,D; Class II Division 1 Groups E,F,G; and Class III Division 1 areas when
connected through the external barriers recommended in Table 5-2 or equivalent. For
Division 1 / Zone 0 or 1 areas, use non-grounded thermocouples or RTDs.
8. Signal monitor transducer side view.

See datasheet at http://www.ge-mcs.com/download/monitoring/173401.pdf for


supported temperature input transducers.

12
Section 4 — I.S. Field Wiring Details (Galvanic Isolators)

4. I.S. Field Wiring Details (Galvanic Isolators)


4.1 Vibration Channel Connections
Safe or Division 2 / Zone 2 Area Division 1 / Zone 0
or Zone1 Area

Figure 4-1: Vibration Channel with Galvanic Isolator connections


1. Components are shown for single channel only (i.e., one transducer to one monitor channel).
Connect remaining channels similarly.
2. Galvanic isolators require external +24Vdc power.
3. Use non-incendive wiring between 1900/65A monitor and galvanic isolators. Connect cable shields
for this wiring to earth at the 1900/65A monitor. Use insulated shields.
4. Connection to system earth.
5. Wiring is shown cut away for clarity.
6. Refer to Table 5-3 in the appendix for galvanic isolator parameters.
7. 3-wire non-incendive devices.
8. 2-wire non-incendive devices. When using BN 2-wire velocity transducers (190501, 330500, 330525
and 330750), the white wire goes to COM/A and the black wire goes to SIG/B.
9. Install jumper between terminals 2 and 3.
10. P&F Isolator KFD2-VR4-Ex1.26, BN# 172436, or equivalent.
11. MTL Isolator 5031, 5531 or equivalent.
12. Signal monitor transducer side view.
NOTE: When using P&F Isolator KFD2-VR4-Ex1.26 and velomitor, you must configure the /65A as
“Nonstandard” and “3-Wire -24 Volt”, otherwise it will not work.
See datasheet at http://www.ge-mcs.com/download/monitoring/173401.pdf for supported
vibration input transducers.

13
1900/65A General Purpose Equipment Monitor Installation Manual
4.2 Temperature Channel Connections
Safe or Division 2 / Zone 2 Area Division 1 / Zone 0
or Zone1 Area

Figure 4-2: Temperature Channel with Galvanic Isolator connections


1. Components are shown for single channel only (i.e., one transducer to one monitor
channel). Connect remaining channels similarly.
2. Galvanic isolators require external +24Vdc power.
3. Use non-incendive wiring between 1900/65A monitor and galvanic isolators. Connect cable
shields for this wiring to earth at the 1900/65A monitor. Use insulated shields.
4. Connection to system earth.
5. Wiring is shown cut away for clarity.
6. Refer to Table 5-3 in the appendix for galvanic isolator parameters.
7. Bently Nevada does not supply thermocouples and 3-wire RTDs. Temperature channels
may be connected to unapproved thermocouples or RTDs located in a Class I Division 1
Groups A,B,C,D; Class II Division 1 Groups E,F,G; and Class III Division 1 areas when
connected through the galvanic isolators recommended in Table 5-3 or equivalent. For
Division 1 / Zone 0 or 1 areas, non-grounded thermocouples or RTDs must be used.
8. Install jumpers between terminals 1 and 3 and terminals 2 and 5.
9. P&F Isolator KFD2-RR-Ex1, BN# 172431, or equivalent.
10. MTL Isolator 5082, 5582 or equivalent.
11. P&F Isolator KFD2-VR-Ex1.50M, BN# 172435, or equivalent.
12. MTL Isolator 5081, 5581 or equivalent
13. Signal monitor transducer side view.

See datasheet at http://www.ge-mcs.com/download/monitoring/173401.pdf for supported


temperature input transducers.

14
Section 5 — Appendix

5. Appendix
Typical Housing
(Bently Nevada P/N 168944 Shown)

Figure 5-1: Typical Housing, dimensions are centimeters (inches)

1. Install the 1900/65A monitoring system in a suitable enclosure with an IP54 / Type 4 rating
for all outdoor and Division 2 / Zone 2 installations.
2. Install conduit above this height to avoid internal mounting hardware. Never install conduit
through the top of the housing.
3. Mounting holes, 4 places, 8.4 (0.33) DIA.

15
16
Non-Incendive Parameters (per channel, all channels must be kept separate)

Ca(nF) La(mH) Co(nF) Lo(mH)


Terminal
I/O Type Signal Uo(V) Io(mA) Ci(nF) Li(µH)
Number
IIC IIB IIA IIC IIB IIA IIC IIB IIA IIC IIB IIA

Ch 1 J6, 5-8

2 Wire Ch 2 J6, 1-4


transducer 23.9 45.5 12 60 200 200 200 1 1 1 188 188 188 1 1 1
Inputs Ch 3 J6, 13-16

Ch 4 J6, 9-12

Ch 1 J6, 5-8

3 Wire Ch 2 J6, 1-4


Transducer 23.9 45.5 12 60 200 200 200 1 1 1 188 188 188 1 1 1
Inputs Ch 3 J6, 13-16

Ch 4 J6, 9-12

Ch 5 J8, 5-8

Ch 6 J8, 1-4
Thermocouple
5 0.5 4 20 1000 1000 1000 1 1 1 996 1000 1000 1 1 1
Inputs
Table 5-1: Non-incendive parameters

Ch 7 J8, 9-12
1900/65A General Purpose Equipment Monitor Installation Manual

Ch 8 J8, 13-16

Ch 5 J8, 5-8

Ch 6 J8, 1-4
RTD
5 0.913 4 20 1000 1000 1000 1 1 1 996 1000 1000 1 1 1
Inputs
Ch 7 J8, 9-12

Ch 8 J8, 13-16
External Barrier Parameters (per channel, all channels must be kept separate)
Circuit Parameters Channel Parameters
per Channel
Worst Case Combined Co Lo
See Uo R Io Po Suggested
Section Device Circuit MTL Barrier
Parallel Series Uo Io Po IIC IIB IIA IIC IIB IIA
Number Models
V Ω mA mW
V Ω mA V Ω mA V mA mW nF nF nF mH mH mH

Proximitor Power 26 298 87 566 796-


unit 7096-
3.1 23.4 169.6 138 27.2 690 39.5 27.2 138 821 89 690 2300 2.1 8.4 16.8
or 7196-
Accel. Signal 20 392 51 255 7796-

Velomitor 728-
unit 7028-
3.1 Power 28 300 93 651 28 300 93.4 28 300 93.4 28 93.4 651 83 650 2150 4.62 18.5 37
or 2 Wire 7128-
Accel. 7728-

Power 10 50 200 500


760ac
3.2 TC 10 25 400 11.2 100 112 11.2 400 1000 1840 12600 54000 0.25 1 2
7760ac
Power 10 50 200 500

Power 3 10 300 225


755ac
7055ac
3-Wire
3.2 Signal 3 10 300 225 7056ac 3 5 600 3 20 150 3 600 450 40000 1000 1000 0.11 0.44 0.88
RTDs
7755ac
7756ac
Signal 3 10 300 225
Table 5-2: External Barrier parameters

I.S. equipment certified for connection to individual barrier circuits: Choose barrier circuit parameters
(Vmax/Rmin or Uo/Io or Voc/Isc) and cable in accordance with the control drawing of the I.S. device.
I.S. equipment with entity parameters: Match certified I.S. equipment parameters with barrier channel
parameters such that the following conditions are met:
Vmax or Ui is ≥ Voc or Uo
Ii or Imax is ≥ Io or Isc
Ca or Co is ≥ Ci + Ccable

17
Section 5 — Appendix

La or Lo is ≥ Li + Lcable
18
Galvanic Isolator Parameters (per channel, all channels must be kept separate)
Circuit Parameters Channel Parameters
per Channel
See Worst Case Combined Co Lo
Section Device Circuit Uo R Io Po
Number Parallel Series Uo Io Po IIC IIB IIA IIC IIB IIA
V Ω mA mW
V Ω mA V Ω mA V mA mW µF µF µF mH mH mH

Proximitor Power 25.2 280 90 570


unit
4.1 24.55 272.4 90.12 26.4 10.3K 2.6 26.4 90.2 595 0.096 0.74 2.48 4.9 19.7 39
or
Accel. Signal 1.2 10K 0.12 0.036

Velomitor
unit
4.1 Power 1.2 10K 0.12 0.036 1.2 10K 0.12 1.2 10K 0.12 1.2 0.12 0.036 100 1000 1000 1000 1000 1000
or 2 Wire
Accel.

4.2 TC Power 5.5 2292 2.4 3.3 5.5 2292 2.4 5.5 2292 2.4 5.5 2.4 3.3 100 1000 1000 15 60 120

Power
4.2 RTD and 12.4 730 17 53 12.4 730 17 12.4 729 17 12.4 17 53 1.24 7.9 30 138 554 1100
Signal
Table 5-3: Galvanic Isolator parameters
1900/65A General Purpose Equipment Monitor Installation Manual

I.S. equipment certified for connection to individual galvanic isolator circuits: Choose galvanic isolator
circuit parameters (Vmax/Rmin or Uo/Io or Voc/Isc) and cable in accordance with the control drawing of the
I.S. device.
I.S. equipment with entity parameters: Match certified I.S. equipment parameters with galvanic isolator
channel parameters such that the following conditions are met:Vmax or Ui is ≥ Voc or Uo
Ii or Imax is ≥ Io or Isc
Ci + Ccable ≤ Ca or Co
Li + Lcable ≤ La or LoSee section 4 for suggested galvanic isolator models for the different channel types.

You might also like