The document summarizes a new switch mode power supply model called the S8VK-T. It is a 3-phase power supply that offers high efficiency, wide operating temperature range, and compact size. It has input voltage ranges from 380-480VAC for worldwide applications and 450-600VDC. Power output ratings include 120W, 240W, 480W, and 960W models with 24V output.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views19 pages

Catálogo Fuentes OMRON

The document summarizes a new switch mode power supply model called the S8VK-T. It is a 3-phase power supply that offers high efficiency, wide operating temperature range, and compact size. It has input voltage ranges from 380-480VAC for worldwide applications and 450-600VDC. Power output ratings include 120W, 240W, 480W, and 960W models with 24V output.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

New Product

Switch Mode Power Supply

S8VK-T (120/240/480/960 W Models)


Worldwide 3-phase Power Supply
Resistant in tough environments
Easy and fast installation
The most compact class on the market
• Wide input range for worldwide applications:
380 to 480 VAC (320 to 576 VAC)
• Possible for 2-phase input usage*:
380 to 480 VAC (340 to 576 VAC)
*When using the 960 W at 2-phase input, the power rating is 768 W.
• DC input can be available*:
450 to 600 VDC (450 to 810 VDC)
*Excluding 960 W
• High efficiency 91% typ. at 480 W model
• Wide operation temperature range: –40 to 70°C
• Power Boost function at 120% Refer to Safety Precautions for All Power Supplies and Safety
!
• Meets LR maritime standards Precautions on page 12.

• EMS: Conforms to EN 61204-3


EMI: EN61204-3 Class B
• RoHS Compliant
• Three years Warranty
Note: Three years warranty conditions: Rated input voltage, 80% load,
Ambient operating temperature: 40°C, Standard mounting

Model Number Structure


Model Number Legend
S8VK- T@@@@@
1 2

1. Power Ratings 2. Output voltage


120: 120 W 24: 24 V
240: 240 W
480: 480 W
960: 960 W

Ordering Information
Note: For details on normal stock models, contact your nearest OMRON representative.
Power ratings Input voltage Output Voltage Output current Boost Current Model number
120 W 24 V 5A 6A S8VK-T12024
2-phase and 3-phase
240 W 380 to 480 VAC 24 V 10 A 12 A S8VK-T24024
480 W 450 to 600 VDC 24 V 20 A 24 A S8VK-T48024
3-phase
24 V 40 A 48 A
380 to 480 VAC
960 W S8VK-T96024
2-phase
24 V 32 A -
380 to 480 VAC

1
S8VK-T
Specifications
Ratings, Characteristics, and Functions
Power rating 120 W 240 W
Item Output voltage 24 V 24 V
Efficiency 3-phase, 400 VAC input *11 89% typ. 89% typ.
3-phase, 380 to 480 VAC (allowable range: 320 to 576 VAC)
Voltage range *1 2-phase, 380 to 480 VAC (allowable range: 340 to 576 VAC)
450 to 600 VDC (allowable range: 450 to 810 VDC) *8
Frequency *1 50/60 Hz (47 to 63 Hz)
Input Current 3-phase, 400 VAC input *11 0.38 A typ. 0.69 A typ.
Power factor - -
Leakage current 3-phase, 400 VAC input 3.5 mA max./1.3 mA typ. 3.5 mA max./1.4 mA typ.
Inrush current (for a
3-phase, 400 VAC input 28 A typ. 29 A typ.
cold start at 25°C) *2
Rated output current 5A 10 A
Boost current 6A 12 A
Voltage adjustment range *3 22.5 to 29.5 VDC (with V.ADJ) (guaranteed)
Ripple & Noise
3-phase, 400 VAC input *11 160 mV p-p max. at 20 MHz of bandwidth 190 mV p-p max. at 20 MHz of bandwidth
voltage *4
Output Input variation influence *13 0.5% max.
Load variation influence *12 1.5% max.
Temperature
3-phase, 400 VAC input 0.05%/°C max.
variation influence
Start up time *2 3-phase, 400 VAC input *11 700 ms typ. 600 ms typ.
Hold time *2 3-phase, 400 VAC input *11 30 ms typ. 20 ms typ.
Overload protection Yes, automatic reset Yes, automatic reset
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on
Overvoltage protection
Additional the input again) *5
functions Series operation Yes (For up to two Power Supplies, external diodes are required.)
Parallel operation Yes (Refer to Engineering Data) (For up to two Power Supplies)
Output indicator Yes (LED: Green), lighting from 80% to 90% or more of rated voltage
3.0 kVAC for 1 min. (between all input terminals and output terminals) cutoff current 20 mA
Withstand voltage 2.5 kVAC for 1 min. (between all input terminals and PE terminal) cutoff current 20 mA
Insulation 1.0 kVAC for 1 min. (between all output terminals and PE terminal) cutoff current 30 mA
Insulation resistance 100 MΩ min. (between all output terminals and all input terminals / PE terminal) at 500 VDC
–40 to 70°C (However, only startup is guaranteed for between –40°C to –25°C. (3-phase only))
Ambient operating temperature
(Derating is required according to the temperature.) (with no condensation or icing)
Storage temperature –40 to 85°C (with no condensation or icing)
Environment
Ambient operating humidity 0% to 95% (Storage humidity: 0% to 95%)
Vibration resistance 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
MTBF 135,000 hrs min.
Reliability
Life expectancy *10 10 years min.
Weight 700 g max. 1,000 g max.
Construction Cooling fan No
Degree of protection IP20 by EN / IEC 60529
Harmonic current emissions Conforms to EN 61000-3-2
Conducted Emission Conforms to EN 61204-3 Class B EN 55011 Class B
EMI
Radiated Emission Conforms to EN 61204-3 Class B EN 55011 Class B
EMS Conforms to EN 61204-3 high severity levels
UL Listed: UL 508 *7
UL UR: UL 60950-1 (Recognition)
UL Listed: UL 508 *7
cUR: CSA C22.2 No.60950-1
EN: EN 50178
Standards Approved Standards *6 CSA: CSA C22.2 No.60950-1
Lloyd’s standards *9
EN: EN 50178, EN 60950-1
ANSI/ISA 12.12.01 *7
Lloyd’s standards *9
ANSI/ISA 12.12.01 *7
SELV (EN 60950-1/EN 50178/UL 60950-1)
SELV (EN 50178), PELV(EN 60204-1, EN 50178)
PELV (EN 60204-1, EN 50178)
Conformed Standards Safety of Power Transformers (EN 61558-2-16)
Safety of Power Transformers (EN 61558-2-16)
EN 50274 for Terminal parts
EN 50274 for Terminal parts
SEMI Conforms to F47-0706 (3-phase, 380 to 480 VAC input)

Note: Refer to page 4 for notes 1 to 13.

2
S8VK-T

Power rating 480 W 960 W (768 W *18)


Item Output voltage 24 V 24 V
Efficiency 3-phase, 400 VAC input *11 91% typ. 92% typ.
3-phase, 380 to 480 VAC
(allowable range: 320 to 576 VAC) 3-phase, 380 to 480 VAC
2-phase, 380 to 480 VAC (allowable range: 320 to 576 VAC)
Voltage range *1
(allowable range: 340 to 576 VAC) 2-phase, 380 to 480 VAC
450 to 600 VDC (allowable range: 340 to 576 VAC)
(allowable range: 450 to 810 VDC) *8
Input Frequency *1 50/60 Hz (47 to 63 Hz)
Current 3-phase, 400 VAC input *11 1.2 A typ. 2.1 A typ.
Power factor - -
Leakage current 3-phase, 400 VAC input 3.5 mA max./1.0 mA typ. 3.5 mA max./1.2 mA typ.
Inrush current (for a
3-phase, 400 VAC input 28 A typ.
cold start at 25°C) *2
Rated output current 20 A 40 A at 3-phase (32 A at 2-phase)
Boost current 24 A 48 A at 3-phase (Not possible at 2-phase)
Voltage adjustment range *3 22.5 to 29.5 VDC (with V.ADJ) (guaranteed) 22.5 to 29.5 VDC (with V.ADJ) (guaranteed) *14
Ripple & Noise voltage *4 3-phase, 400 VAC input *11 130 mV p-p max. at 20 MHz of bandwidth 90 mV p-p max. at 20 MHz of bandwidth
Input variation influence *13 0.5% max.
Output
Load variation influence *12 1.5% max.
Temperature
3-phase, 400 VAC input 0.05%/°C max.
variation influence
Start up time *2 3-phase, 400 VAC input *11 500 ms typ. 700 ms typ.
Hold time *2 3-phase, 400 VAC input *11 20 ms typ. 20 ms typ.
Overload protection Yes, automatic reset
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on
Overvoltage protection
the input again) *5
Additional
functions Series operation Yes (For up to two Power Supplies, external diodes are required.)
Parallel operation Yes (Refer to Engineering Data) (For up to two Power Supplies)
Output indicator Yes (LED: Green), lighting from 80% to 90% or more of rated voltage
3.0 kVAC for 1 min. (between all input terminals and output terminals) cutoff current 20 mA
Withstand voltage 2.5 kVAC for 1 min. (between all input terminals and PE terminal) cutoff current 20 mA
Insulation 1.0 kVAC for 1 min. (between all output terminals and PE terminal) cutoff current 30 mA
Insulation resistance 100 MΩ min. (between all output terminals and all input terminals / PE terminal) at 500 VDC
–40 to 70°C (However, only startup is guaranteed for between –40°C to –25°C. (3-phase only))
Ambient operating temperature
(Derating is required according to the temperature.) (with no condensation or icing)
Storage temperature –40 to 85°C (with no condensation or icing)
Environment
Ambient operating humidity 0% to 95% (Storage humidity: 0% to 95%)
Vibration resistance 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
MTBF 135,000 hrs min.
Reliability
Life expectancy *10 10 years min.
Weight 1,600 g max. 2,700 g max.
Construction Cooling fan No
Degree of protection IP20 by EN / IEC 60529
Harmonic current emissions Conforms to EN 61000-3-2 *15
Conducted Emission Conforms to EN 61204-3 Class B EN 55011 Class B *16
EMI
Radiated Emission Conforms to EN 61204-3 Class B EN 55011 Class B *16
EMS Conforms to EN 61204-3 high severity levels
UL Listed: UL 508 *7
UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No.60950-1
Standards Approved Standards *6 CSA: CSA C22.2 No.60950-1
EN: EN 50178, EN 60950-1
Lloyd’s standards
ANSI/ISA 12.12.01 *7
SELV (EN 60950-1/EN 50178/UL 60950-1)
PELV (EN 60204-1, EN 50178)
Conformed Standards
Safety of Power Transformers (EN 61558-2-16)
EN 50274 for Terminal parts
SEMI Conforms to F47-0706 (3-phase, 380 to 480 VAC input) *17

Note: Refer to page 4 for notes 1 to 18.

3
S8VK-T

*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 7 to 8 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 29.5 VDC of the voltage adjustment range.
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. A characteristic when the ambient operating temperature is between –25 to 70°C.
*5. Refer to Overvoltage Protection on page 8 for the time when input voltage shuts off and input turns on again.
*6. To meet safety standards, the S8VK-T must be protected with an external circuit-breaker or a fuse.
Be sure to use an external circuit-breaker or a fuse. Refer to Precautions for Safe Use on page 13 for details.
*7. The following supplementary Fuse/Circuit Breaker must be installed in accordance with NEC.:
Model FAZ-D5/3-NA, FAZ-D5/3-RT or FAZ-D5/3-DU, EATON INDUSTRIES (AUSTRIA) GMBH (E235139), Model KLKD5, LITTELFUSE INC.
(E10480)
*8. Safety Standards for a DC Input
The following standards apply to a 450 to 600 VDC input: UL 60950-1, EN 50178, EN 60950-1, and Lloyd's standards.
*9. In the case of using side-mounting bracket (S82Y-VK10S, S82YVK20S), Lloyd's Standards are not applicable.
*10. The value is when rated output current is 50% or less, the ambient operating temperature is 40°C or less, standard mounting, and rated input
voltage.
*11. The value is when both rated output voltage and rated output current are satisfied.
*12. 380 to 480 VAC input, in the range of 0 A to the rated output current.
*13. This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at
the rated output voltage and rated output current.
*14. Use at 26.4 VDC or lower for 2-phase input.
*15. The S8VK-T Power Supply conforms to EN 61000-3-2 under the following conditions for 2-phase input.
480 W: rated output voltage, and 65% or less of rated output current
960 W: rated output voltage, and 45% or less of rated output current
*16. The S8VK-T Power Supply conforms to EMI under the following conditions for 2-phase input.
480 W: Conforms to class B: rated output voltage, and 65% or less of rated output current/
Conforms to class A: rated output voltage, and 65% to 100% of rated output current
960 W: Conforms to class B: rated output voltage, and 45% or less of rated output current/
Conforms to class A: rated output voltage, and 45% to 100% of rated output current
*17. 480 W: rated output voltage, and 50% or less of rated output current.
960 W: rated output voltage, and 92.5% or less of rated output current.
*18. When using 2-phase input. Refer to 2-Phase Input Operation For 960 W Model in Precautions for Safe Use on page 16 for details.

4
S8VK-T
Connections
Block Diagrams
S8VK-T12024 (120 W)
S8VK-T24024 (240 W)

L1 +V

INPUT L2 Noise filter DC OUTPUT

L3 Rectifier lnrush Smoothing Rectifier/ −V


current circuit smoothing
protection circuit
Drive
control
circuit

Voltage
detection circuit
Overcurrent Overvoltage
detection circuit detection circuit
Photocoupler

S8VK-T48024 (480 W)
S8VK-T96024 (960 W)

L1 +V

INPUT L2 Noise filter DC OUTPUT

L3 Rectifier lnrush Smoothing Rectifier/ −V


current circuit smoothing
protection circuit
Drive
control
circuit

Voltage
detection circuit
Overcurrent Overvoltage
detection circuit detection circuit
Photocoupler

5
S8VK-T
Construction and Nomenclature
Nomenclature
120 W Model 240 W Model 480 W Model
S8VK-T12024 S8VK-T24024 S8VK-T48024

3 3

4 4 4

5 5 5

1 2 1 2 1 2 3

960 W Model
S8VK-T96024

4
5

1 2 3

Note:
A: The output current can use 100% of the rated output current.
B: Overcurrent protection limits the output current to 80% of the rated
6
output current.

No. Name Function


1 Input terminals (L1), (L2), (L3) Connect the input lines to these terminals. *1
2 Protective Earth terminal (PE) / Ground Connect the ground line to this terminal. *2
3 DC Output terminals (−V), (+V) Connect the load lines to these terminals.
4 Output indicator (DC ON: Green) Lights while a direct current (DC) output is ON.
5 Output voltage adjuster (V.ADJ) Use to adjust the voltage.
6 Operation Switch *3 *4 To operate in parallel or 2-phase input, set the switch to the "B" side. (960 W model only).
*1. For wiring, refer to Wiring in Precautions for Safe Use on page 13.
*2. This is the protective earth terminal specified in the safety standards. Always ground this terminal.
*3. For parallel operation, refer to Parallel Operation in Precautions for Safe Use on page 15.
*4. For 2-phase input, refer to 2-Phase Input Operation For 960 W Model in Precautions for Safe Use on page 16.

6
S8VK-T
Engineering Data
Derating Curve
120 W (S8VK-T12024) 960 W (S8VK-T96024): Standard mounting
Load ratio (%)

Load ratio (%)


120 120
B

100 100 C
A
A
B
80 C 80

60 60

40 40

20 20

0 0
−40 −25 −10 0 10 20 30 40 50 60 70 80 −40 −25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C) Ambient temperature (°C)

Note: This is the guaranteed value for startup. (3-phase only) Note: This is the guaranteed value for startup. (3-phase only)

A. Standard mounting A. 3-Phase (340 VAC or over to 576 VAC or lower)


B. Face-up mounting at 480 VAC or lower or 678 VDC or lower For less than 340 VAC, it is possible to use with output voltage at
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower 28.5 VDC or lower and load rate 60% or lower.
B. 2-Phase (380 VAC or over to 576 VAC or lower, and output voltage
240 W (S8VK-T24024) 26.4 VDC or lower)
C. 2-Phase (360 VAC or over to 380 VAC or lower, and output voltage
26.4 VDC or lower)
Load ratio (%)

120
For 340 VAC or over to less than 360 VAC, it is possible to use with
output voltage at 26.4 VDC or lower, and whichever is the smaller of
100 A the load rate 60% or lower or the value of C.
B
80 C
960 W (S8VK-T96024): Face-up mounting
Load ratio (%)

120
60
100 D
E
40
F
80

20
60
0
−40 −25 −10 0 10 20 30 40 50 60 70 80
40
Ambient temperature (°C)

Note: This is the guaranteed value for startup. (3-phase only) 20

A. Standard mounting
B. Face-up mounting at 480 VAC or lower or 678 VDC or lower 0
−40 −25 −10 0 10 20 30 40 50 60 70 80
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower
Ambient temperature (°C)
480 W (S8VK-T48024)
Note: This is the guaranteed value for startup. (3-phase only)
Load ratio (%)

120
D. 3-Phase (340 VAC or over to 576 VAC or lower)
For less than 340 VAC, it is possible to use with output voltage at
100 A 28.5 VDC or lower and load rate 60% or lower.
B
E. 2-Phase ( 380 VAC or over to 480 VAC or lower, and output voltage
26.4 VDC or lower)
80 C F. 2-Phase (Over 480 VAC to 576 VAC or lower)
For 340 VAC or over to less than 380 VAC, it is possible to use with
output voltage at 26.4 VDC or lower, and whichever is the smaller of
60
the load rate 60% or lower or the value of F.

40

20

0
−40 −25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)

Note: This is the guaranteed value for startup. (3-phase only)

A. Standard mounting
Over 528 VAC: the derating is 0.21%/VAC
Over 746 VAC: the derating is 0.16%/VDC
B. Face-up mounting at 480 VAC or lower or 678 VDC or lower
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower

7
S8VK-T

Mounting Overvoltage Protection


Consider the possibility of an overvoltage and design the system so
(A) Standard (Vertical) mounting (B) Face-up mounting that the load will not be subjected to an excessive voltage even if the
feedback circuit in the Power Supply fails. If an excessive voltage that
is approximately 130% of the rated voltage or more is output, the
output voltage is shut OFF. Reset the input power by turning it OFF
for at least five minutes and then turning it back ON again.

Output voltage (V)


Overvoltage protection
+30% operating
(approx.)
29.5 V

Overload Protection
The load and the power supply are automatically protected from Rated output Variable range
overcurrent damage by this function. voltage
22.5 V
Overload protection is activated if the output current rises above
121% of the rated current.
When the output current returns within the rated range, overload
protection is automatically cleared.
Output voltage (V)

0V

The values shown in the above diagram is for reference only.


Note: Do not turn ON the power again until the cause of the
overvoltage has been removed.

Intermittent operation Inrush Current, Startup Time, Output Hold Time

Input ON Input OFF


0 50 100
AC input
Output current (%) voltage

The values shown in the above diagrams are for reference only.

Note: 1. Internal parts may occasionally deteriorate or be damaged Inrush current on input application
if a short-circuited or overcurrent state continues during AC input
current
operation.
2. Internal parts may possibly deteriorate or be damaged if the
Power Supply is used for applications with frequent inrush 90% 96.5%
current or overloading at the load end. Do not use the Power
Output
Supply for such applications. voltage
Startup time Hold time

Note: Twice the input current or above will flow during the parallel
operation or redundant system.
Therefore, check the fusing characteristics of fuses and
operating characteristics of breakers making sure that the
external fuses will not burn out and the circuit breakers will not
be activated by the inrush current.

Reference Value
Value
Reliability 120 W: 390,000 h
(MTBF) 240 W: 350,000 h
480 W: 280,000 h
960 W: 260,000 h
MTBF stands for Mean Time Between
Failures, which is calculated according to the
probability of accidental device failures, and
Definition
indicates reliability of devices.
Therefore, it does not necessarily represent a
life of the product.
Life expectancy 10 years. Min.
The life expectancy indicates average
operating hours under the ambient
temperature of 40°C and a load rate of 50%.
Definition
Normally this is determined by the life
expectancy of the built-in aluminum electrolytic
capacitor.

8
S8VK-T
Dimensions (Unit: mm)

S8VK-T12024 (120 W) (1) 122.2±1


40±1 117.8
6.35 112.2
(4)

104.6 125±1

6.35

4.7 (10)
Rail Stopper 19.8 (Sliding: 7.5 max.)

S8VK-T24024 (240 W) (1) 150±1


60±1 145.6
6.35 140 (4)

104.6 125±1

6.35

4.7 (10)
Rail Stopper 19.8 (Sliding: 7.5 max.)

(1) 150±1
S8VK-T48024 (480 W)
145.6
95±1 140 (4)

125±1

52.3 6.35 6.35

19.8
4.7 (10)
(26.8) (Sliding: 7.5 max.)
30 25 Rail Stopper

S8VK-T96024 (960 W)
(1) 180±1
175.6
135±1 170 (4)

125±1

47.9 10.16 10.16

19.8
4.7 (10)
(36.7) (Sliding: 7.5 max.)
41.78 32.95 Rail Stopper

9
S8VK-T

DIN Rail (Order Separately)


Note: All units are in millimeters unless otherwise indicated.

Mounting Rail (Material: Aluminum)


PFP-100N
PFP-50N
7.3±0.15
4.5
35±0.3 27±0.15

15 25 25 25 25 15(5) * 1
10 10
1,000 (500) *
* Values in parentheses are for the PFP-50N.

Mounting Rail (Material: Aluminum)


PFP-100N2
16

4.5
35±0.3 27 24 29.2

15 25 25 25 25 15 1 1.5
10 10
1,000

End Plate
PFP-M
10
6.2
1.8
M4×8 pan-
head screw 1
50 35.5 35.5
1.8

11.5

10 1.3
M4 spring washer 4.8

Note: If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.

10
S8VK-T

Mounting Brackets
Name Model Qty used
Front-mounting bracket (for 120, 240 and 480 W models) S82Y-VK10F 1
Front-mounting bracket (for 960 W model) S82Y-VK10F 2
Side-mounting bracket (for 120 W model) S82Y-VK10S 1
Side-mounting bracket (for 240 W model) S82Y-VK20S 1
Note: Be sure to use the accessory screws.
Mounting screw tightening torque (recommended): 4.43 to 5.31 lb-in (0.5 to 0.6 N·m)

Type Model Dimensions Appearance

120 W model 240 W model

For 960W type


4-4.5 dia.±0.1

Front-mounting
bracket 140±0.1 150
(for 120, 240, S82Y-VK10F 960 W model
480 W and 960 W
models)

25±0.1
64±0.1
5.4
38
t = 2.0

Left-side mounting Right-side mounting


73
40 49 50±0.1 15.5±0.1

4-4.5 dia.±0.1

Side-mounting
bracket S82Y-VK10S 140±0.1
Left-side mounting Right-side mounting
125 150
(For 120 W model) (DIN Rail) * (DIN Rail) *

t = 2.0

Left-side mounting Right-side mounting

73
40 59 50±0.1 15.5±0.1

4-4.5 dia.±0.1

Side-mounting
bracket S82Y-VK20S 140±0.1
125 150 Left-side mounting Right-side mounting
(For 240 W model) (DIN Rail) * (DIN Rail) *

t = 2.0

* You can mount the side of the Power Supply to a DIN Rail by removing the DIN Rail Back-mounting Bracket and then attaching a Side-mounting
Bracket to the Power Supply.

11
S8VK-T
Safety Precautions
Warning Indications
Indicates a potentially hazardous
situation which, if not avoided, may
CAUTION result in minor or moderate injury or in
property damage.
Supplementary comments on what to
Precautions for
do or avoid doing, to use the product
Safe Use safely.
Supplementary comments on what to
Precautions for do or avoid doing, to prevent failure to
Correct Use operate, malfunction or undesirable
effect on product performance.

Meaning of Product Safety Symbols

Used to warn of the risk of electric shock under


specific conditions.

Used to warn of the risk of minor injury caused by


high temperatures.

Used for general mandatory action precautions


for which there is no specified symbol.

Used to indicate prohibition when there is a risk of


minor injury from electrical shock or other source
if the product is disassembled.

!CAUTION
Minor electric shock, fire, or Product failure may
occasionally occur. Do not disassemble, modify, or
repair the Product or touch the interior of the
Product.

Minor burns may occasionally occur. Do not touch


the Product while power is being supplied or
immediately after power is turned OFF.

Fire may occasionally occur. Tighten terminal screws


to the specified torque.
S8VK-T12024, S8VK-T24024, S8VK-T48024:
4.43 to 5.31 lb-in (0.5 to 0.6 N•m)
S8VK-T96024:
10.62 to 13.28 lb-in (1.2 to 1.5 N•m)

Minor injury due to electric shock may occasionally


occur. Do not touch the terminals while power is
being supplied.

Minor electric shock, fire, or Product failure may


occasionally occur. Do not allow any pieces of metal
or conductors or any clippings or cuttings resulting
from installation work to enter the Product.

If the external breaker or fuse is tripped, the


equipment may have been seriously damaged.
Do not turn ON the input again.

12
S8VK-T

Precautions for Safe Use


Wiring
• Connect the ground completely. A protective earthing terminal • Use the following material for the wires to be connected to the
stipulated in safety standards is used. Electric shock or malfunction S8VK-T to prevent smoking or ignition caused by abnormal loads
may occur if the ground is not connected completely. or phase failure.
• Minor fire may possibly occur. Ensure that input and output • Wire the input as shown in the following figures depends on your
terminals are wired correctly. power distribution system. Do not connect the neutral line in a
• Do not apply more than 75-N force to the terminal block when 3-phase, 4-wire system.
tightening it. TN-S TN-C 2-phase

• Be sure to remove the sheet covering the Product for machining


before power-ON so that it does not interfere with heat dissipation.
• To comply with safety standards and to ensure equipment safety,
connect the input to the S8VK-T through one of the following
Breakers or Fuses.

Power circuit-breakers
FUSE
Model Input Power circuit-breakers L1 L1 L1
L2 L2 L2
Circuit breaker Conforming UL/CE L3 L3 (L3)
3-phase 480 V, 5 A, characteristic D, 3-pole, or N PEN PE
S8VK-T12024 equivalent breaker PE

S8VK-T24024
Fuse Conforming UL/CE 600 V, 5 A TT IT DC
2-phase/DC
Fast Acting or identical function fuse
Circuit breaker Conforming UL/CE
3-phase 480 V, 5 A, characteristic D, 3-pole, or
S8VK-T48024 equivalent breaker
S8VK-T96024
Fuse Conforming UL/CE 600 V, 10 A
2-phase/DC
Fast Acting or identical function fuse
Note: Do not use the S8VK-T96024 with a DC input. FUSE
L1 L1 +
L2 L2
L3 L3 -
N PE

Recommended Wire Type/Cross-sectional Area and Stripping Length


INPUT OUTPUT PE / Ground
Wire tripping
Model American Solid Wire American Solid Wire American Solid Wire Length
Wire Gauge /Stranded Wire Wire Gauge /Stranded Wire Wire Gauge /Stranded Wire
0.35 to 6 mm2 0.75 to 6 mm2
S8VK-T12024 AWG22 to 10 AWG18 to 10
/0.35 to 4 mm2 /0.75 to 4 mm2
0.35 to 6 mm2 2.5 to 6 mm2 2.5 to 6 mm2
S8VK-T24024 AWG22 to 10 AWG14 to 10 AWG14 to 10 8 to 10 mm
/0.35 to 4 mm2 /2.5 to 4 mm2 /2.5 to 4 mm2
0.5 to 6 mm2 4 to 6 mm2
S8VK-T48024 AWG20 to 10 AWG12 to 10
/0.5 to 4 mm2 /4 mm2
1.5 to 16 mm2 10 to 16 mm2 2.5 to 16 mm2
S8VK-T96024 AWG16 to 6 AWG8 to 6 AWG14 to 6 13 to 16 mm
/1.5 to 16 mm2 /10 to 16 mm2 /2.5 to 16 mm2

• The wire insertion hole, and applicable screwdriver of the terminal block are as follows.
Wire Insertion Hole
Applicable Screwdriver
(Refer to the diagram on the right)
Model
Driver
W L No. Length
Diameter
S8VK-T12024 L
S8VK-T24024 2.9 2.9 #2 4.9 mm max. 10 mm min.
S8VK-T48024
W
S8VK-T96024 5.4 5 #2 5.1 mm max. 12 mm min.

Installation Environment doubled for each drop of 10°C. The life of the Power Supply can
• Do not use the Power Supply in locations subject to shocks or thus be increased by reducing its internal temperature.
vibrations. In particular, install the Power Supply as far away as
possible from contactors or other devices that are a vibration
Ambient Operating and Storage Environments
source. For usage onboard a ship, always attach an End Plate • Store the Power Supply at a temperature of −40 to 85°C and a
(PFP-M) to both sides of the Power Supply to hold the Power humidity of 0% to 95%.
Supply in place. • Do not use the Power Supply in areas outside the derating curve
• Install the Power Supply well away from any sources of strong, otherwise, internal parts may occasionally deteriorate or be
high-frequency noise and surge. damaged.
• Use the Power Supply at a humidity of 0% to 95%.
Operating Life • Do not use the Power Supply in locations subject to direct sunlight.
• The life of a Power Supply is determined by the life of the • Do not use the Power Supply in locations where liquids, foreign
electrolytic capacitors used inside. Here, Arrhenius Law applies, matter, or corrosive gases may enter the interior of Products.
i.e., the life will be cut in half for each rise of 10°C or the life will be

13
S8VK-T

Mounting Power Boost Function


• Take adequate measures to ensure proper heat dissipation to For All Models
increase the long-term reliability of the Product. Be sure to allow Power Boost is a function that can output the temporary repeated
convection in the atmosphere around devices when mounting. Do boost current larger than the rated current.
not use in locations where the ambient temperature exceeds the However, it should meet the following four Boost current conditions.
range of the derating curve. 1. Time that the boost current flows: t1
• When cutting out holes for mounting, make sure that cuttings do 2. The maximum value of the boost current: lp
not enter the interior of the Products. 3. The average output current: lave
4. The time ratio of the boost current flow: Duty
*1
Note: Boost current conditions
• t1 ≤ 10 s
• Ip ≤ Rated boost current
• lave ≤ Rated current
t1
Duty= × 100 [%] ≤ 30%
t1 + t2

[A]
*2 *1. Convection of air

output current
*1 Ip: Boost current
*2. 20 mm min.
Rated current

• Improper mounting will interfere with heat dissipation and may lave: Average current
occasionally result in deterioration or damage of internal parts. Use
the Product within the derating curve for the mounting direction that
is used.
t1 t2
Overload Protection
• Internal parts may possibly deteriorate or be damaged if a
• Do not allow the boost current to continue for more than 10
short-circuited or overcurrent state continues during operation.
seconds.
• Internal parts may possibly deteriorate or be damaged if the Power
Also, do not let the duty cycle exceed the boost current conditions.
Supply is used for applications with frequent inrush current or
These conditions may damage the Power supply.
overloading at the load end. Do not use the Power Supply for such
• Ensure that the average current of one cycle of the boost current
applications.
does not exceed the rated output current.
• The DC ON indicator (green) flashes if the overload protection
This may damage the Power Supply.
function operates.
• Lessen the load of the boost load current by adjusting the ambient
Charging a Battery temperature and the mounting direction.
• Power Boost Function is not possible for the S8VK-T 960 W at
If you connect a battery as the load, install overcurrent control and
2-phase input or in parallel operation.
overvoltage protection circuits.

Output Voltage Adjuster (V.ADJ) Series Operation


• The output voltage adjuster (V.ADJ) may possibly be damaged if it Two power supplies can be connected in series.
is turned with unnecessary force. Do not turn the adjuster with
excessive force. L1 +V
• After completing output voltage adjustment, be sure that the output
L2
capacity or output current does not exceed the rated output
capacity or rated output current. L3 −V
Load

DIN Rail Mounting


To mount the Block on a DIN Rail, hook portion (A) of the Block onto L1 +V
the rail and press the Block in direction (B). L2

L3 −V
(A)
Note: 1. The diode is connected as shown in the figure. If the load is
short-circuited, a reverse voltage will be generated inside
the Power Supply. If this occurs the Power Supply may
possibly deteriorate or be damaged. Always connect a
(B) diode as shown in the figure.
To dismount the Block, pull down portion (C) with a flat-blade Select a diode having the following ratings.
screwdriver and pull out the Block. Type Schottky Barrier diode
Dielectric strength (VRRM) Twice the rated output voltage or above
Forward current (IF) Twice the rated output current or above
2. Although Products having different specifications can be
connected in series, the current flowing through the load
must not exceed the smaller rated output current.
30 mm min.

(C)
Rail stopper

14
S8VK-T

Making Positive/Negative Outputs Parallel Operation


• The outputs are floating outputs (i.e., the primary circuits and Parallel operation is used when the output current from one Power
secondary circuits are separated). You can therefore make Supply is insufficient for the load. Power Supplies are connected in
positive and negative outputs by using two Power Supplies. parallel to increase the output current.
You can make positive and negative outputs with any of the Two Power Supplies can be connected in parallel.
models. 1. Parallel operation is possible only if the standard mounting and
If positive and negative outputs are used, connect Power Supplies 3-phase input is used.
of the same model as in the following figure. (Combinations with Maintain an ambient temperature of between -25 and 40°C.
different output capacities or output voltages can be made. 2. For parallel operation, always use two Power Supplies with the
However, use the lower of the two maximum rated output currents same capacity.
as the current to the loads.) 3. Use the output voltage adjusters (V. ADJ) to adjust the difference
in the output voltages between the two Power Supplies to 50 mV
or less.
L1 +V +V 4. If the output current from the two Power Supplies is not balanced,
the Power Supply with the higher output voltage will operate in an
L2

Load
overcurrent protection state, which will extremely reduce its
L3 −V service life. After you adjust the difference in the output voltages
between the two Power Supplies, make sure that the currents are
0V
well balanced.
L1 +V 5. The length and thickness of each wire connected to the load and
Load

each unit must be the same so that there is no difference in the


L2 voltage drop value between the load and the output terminals of
L3 −V −V
each Power Supply.
6. For Parallel Operation with units 120 W, 240 W S8VK-T Power
Supplies, connect diodes or S8VK-R to the outputs of each unit if
• Depending on the model, internal circuits may be damaged due to sudden load variation influence occurs in the ambient operation
startup failure when the power is turned ON if loads such as a environment.
servomotor or operational amplifier may operate in series. Refer to the S8VK-R datasheet (Catalog No.: T059) for S8VK-R
Therefore, connect bypass diodes (D1, D2) as shown in the specifications and the model number for each capacity.
following figure.
If the list of models that support series connection of outputs says S8VK-T S8VK-R

that an external diode is not required, an external diode is also not L1 +V +V


required for positive/negative outputs.

Load
L2 IN 1

L3 −V −V
L1 +V

D1 S8VK-T
L2
Load

L1 +V
L3 −V
L2 IN 2
Load

L3 −V
L1 +V
Load

L2 D2
7. The internal parts may occasionally be deteriorated or broken. Be
sure to set the OPERATION SWITCH to B when using S8VK-T
L3 −V 480 W, 960 W for Parallel Operation.
For Parallel Operation with units 960 W S8VK-T Power Supplies,
connect diodes to the outputs of each unit if sudden load variation
• Use the following information as a guide to the diode type, influence occurs in the ambient operation environment.
dielectric strength, and current.
Type Schottky Barrier diode L1 +V
Load

Dielectric strength (VRRM) Twice the rated output voltage or above L2


Forward current (IF) Twice the rated output current or above L3 −V

L1 +V

L2

L3 −V

• Use the following information as a guide to the diode type,


dielectric strength, and current.
Type Schottky Barrier diode
Dielectric strength (VRRM) Twice the rated output voltage or above
Forward current (IF) Twice the rated output current or above

15
S8VK-T

Backup Operation In Case There Is No Output Voltage


Backup operation is possible if you use two Power Supplies of the The possible cause for no output voltage may be that the overcurrent
same model. or overvoltage protection has operated. The internal protection may
Even if one Power Supplies fails, operation can be continued with the operate if a large amount of surge voltage such as a lightening surge
other Power Supply. occurs while turning ON the power supply.
Make sure that the maximum load does not exceed the capacity of In case there is no output voltage, please check the following points
one Power Supply. before contacting us:
For backup operation, connect the S8VK-R for 120 W, 240 W, and • Checking overload protected status:
480 W. Check whether the load is in overload status or is short-circuited.
Refer to the S8VK-R datasheet (Catalog No.: T059) for S8VK-R Remove wires to load when checking.
specifications and the model number for each capacity. • Checking overvoltage or internal protection:
Turn the power supply OFF once, and leave it OFF for at least
S8VK-T S8VK-R 5 minutes. Then turn it ON again to see if this clears the condition.
L1 +V +V
2-Phase Input Operation For 960 W Model

Load
L2 IN 1
The internal parts may occasionally be deteriorated or broken. Be sure
L3 −V −V to set the OPERATION SWITCH to B when using S8VK-T 960 W at
2-phase input.
S8VK-T
L1 +V

L2 IN 2

L3 −V
Note:
For 960 W, always connect diodes to the output sides of the two A: The output current can use 100%
Power Supplies as shown in the following diagram. of the rated output current.
B: Overcurrent protection limits the
A output current to 80% of the rated
D1
output current.
L1 +V
Load

L2

L3 −V

B
D2
L1 +V

L2

L3 −V

• Use the following information as a guide to the diode type,


dielectric strength, and current.
Type Schottky Barrier diode
Dielectric strength (VRRM) Twice the rated output voltage or above
Forward current (IF) Twice the rated output current or above

• Increase the output voltage setting of Power Supply A and Power


Supply B by the drop in the forward voltage (VF) of diodes D1 and
D2 .
Also, the diodes will cause a power loss equivalent to the Power
Supply output current (IOUT) times the diode forward voltage (VF).
Therefore, cooling measures must be implemented so that the
temperature of the diodes decreases to the catalog value or lower.
• Because of the load power and power loss due to the diodes, do
not exceed the rated power of one Power Supply (rated output
voltage × rated output current).

16
S8VK-T
Period and Terms of Warranty
Warranty Period
The product warranty is valid for a period of three years from the date of shipment from the factory.

Terms of Warranty
The warranty is valid only for the following operating conditions.
1. Average ambient operating temperature of the product: 40°C max.
2. Average load rate: 80% max.
3. Mounting method: Standard mounting
* The maximum ratings must be within the derating curve.

If the product fails for reasons attributable to OMRON within the above warranty period, OMRON will repair or replace the faulty part of the product
at the place of purchase or the place where the product delivered without charge.
This warranty does not cover the following types of failures.

(1) Failures that result from handling or operation of the product under conditions or in environments that are not given in this document and
not given in any other specifications exchanged between OMRON and the customer
(2) Failures that originate in causes other than the delivered product itself
(3) Failures caused by disassembly, modification, or repair of the product by anyone other than OMRON
(4) Failures caused by applications or uses for which the product was not originally intended
(5) Failures caused by factors that could not be anticipated with the scientific or technical knowledge available when the product was shipped
(6) Failures caused by other causes for which OMRON is not responsible, such as natural disasters and other acts of God
This warranty is limited to the individual product that was delivered and does not cover any secondary, subsequent, or related damages.

Recommended Replacement Periods and Periodic Replacement for


Preventive Maintenance
The recommended replacement period for preventive maintenance is greatly influenced by the application environment of the product. As a
guideline, the recommended replacement period is 7 to 10 years.*
To prevent failures or accidents that can be caused by using a product beyond its service live, we recommend that you replace the product as early
as possible within the recommended replacement period.
However, bear in mind that the recommended replacement period is for reference only and does not guarantee the life of the product.

Many electronic components are used in the product and the product depends on the correct operation of these components to achieve the original
product functions and performance.
However, the influence of the ambient temperature on aluminum electrolytic capacitors is large, and the service life is reduced by half for each
10°C rise in temperature (Arrhenius law).
When the capacity reduction life of the electrolytic capacitor is reached, the product failures or accidents may occur.
We therefore recommend that you replace the product periodically to minimize product failures or accidents in advance.
* The recommended replacement period applies under the following conditions: rated input voltage, load rate of 50% max., ambient temperature
of 40°C max., and the standard mounting method. (The fan is excluded for models with fans.)

This product model is designed with a service life of 10 years minimum under the above conditions.

17
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.

Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.

Limitation on Liability; Etc.


OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.

Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.

Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.

Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.

Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.

Errors and Omissions.


Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation Industrial Automation Company Authorized Distributor:
Kyoto, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V. OMRON ELECTRONICS LLC
Wegalaan 67-69, 2132 JD Hoofddorp 2895 Greenspoint Parkway, Suite 200
The Netherlands Hoffman Estates, IL 60169 U.S.A.
Tel: (31)2356-81-300/Fax: (31)2356-81-388 Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2014-2016 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,