UTTAR DAKSHIN HARYANA-BLILI VITRAN NIGAM DHBVN
Specification No. CSC-121/DH/UH/P&D/2015-2016
TECHNICAL SPECIFCATION
FOR
Heat Shrink Joints & Terminations for 33 kV
Issue Month: March 2016 Common Specification Committee
(CSC Approval date 25012016 ) UHBVN & DHBVN
Page 1 of 23,
Ge.10
20
3.0
40
5.0
6.0
7.0
9.0
10.0
10
12.0
13.0
140
15.0
16.0
17.0
18.0
19.0
20.0
21.0
saz ehror sRaron fot feraaor foro wl
UITAR DAKSHIN HARYANA. BULI VITRAN NIGAM BYVN
CONTENTS
SCOPE
APPLICABLE STANDARDS
CLIMATIC CONDITIONS OF THE INSTALLATION
CABLE DATA
GENERAL TECHNICAL REQUIREMENTS
GENERAL CONSTRUCTIONS
NAME PLATE & MARKING
TESTS
TYPE TEST CERTIFICATES
PRE-DISPATCH INSPECTION
INSPECTION AFTER RECEIPT AT STORES
GUARANTEE
PACKING
TENDER SAMPLE INSTALLATION INSTRUCTION
QUALITY CONTROL
MINIMUM TESTING FACILITIES.
MANUFACTURING ACTIVITIES
SPARES, ACCESSORIES AND TOOLS
DRAWINGS
GUARANTEED TECHNICAL PARTICULARS
SCHEDULE OF DEVIATIONS
be Page 2 of 23‘3s saa efaror efteron froir ftragor forarar vif.
Ai
. UITAR DAKSHIN HARYANA’ BLILI VITRAN NIGAM /DuBvn
LEN 7
1.0 SCOPE
2.0
This specification covers the technical requirements of Design, Engineering, Manufacturing,
Testing at manufacturer's works, Packing, Forwarding and Supply of cable terminations and
joints employing Heat Shrinkable or cold shrinkable technology suitable for Straight through /
Indoor | Outdoor installation on 33kV& voltage grade in distribution system with all
accessories for efficient and trouble free operation at the site.
It is not the intent to specify completely herein all details of design and construction of
equipment / system. However, the equipment shall conform in all respects to high standards
of engineering, design and workmanship and be capable of performing in continuous
commercial operation up to vendor's guarantee in a manner acceptable to the purchaser who
will interpret the meaning of the drawings and specification and shall have the power to reject
any work or materials, which in his judgments are not in full accordance therewith,
Bidder has to submit all relevant papers, copies of type test reports as required. Failure to do
s0 may amount to the bids being considered non-responsive and outright rejection. The
information as asked for, is to be mentioned specifically and not be narrated like ‘as per
IS/IEC, relevant standard, reference to other pages of offer bid etc’
Technical data sheet annexed as has to be filed in completely and separately for
indoor/outdoor terminations and straight through joints, Copies of the documents where asked
for, are to be enclosed for each requirement.
The offer documents have to be completely filled in and submitted even if there is repetition of
the information. The offer must have a clause wise affirmation of the technical requirements,
Deviations / non-conformances/ alternatives / equivalents must be all separately listed as
deviations.
APPLICABLE STANDARDS
The offered accessories / equipment covered by this specification shall conform to the test
requirements stated in latest edition of relevant IS/IEC and other applicable standards and
shall conform to the statutory authorities.
1S-13673-2011 Patt 2 & 3 - Joints & Terminations, for
Polymeric cables for working voltages 3.3 kV up to
and including 33 kV - Type test requirements.
1S 7098-1988 (Part2) Cross linked polyethylene insulated PVC sheathed
cables from 3.3 Kv up to and including 33 KvCable.
IEC 60502-2009 Power cables with extruded insulation and their
accessories for rated voltages from 1 KV up to 30KV.
IEC 60840 Power cables with extruded insulation and
theiraccessories for rated voltages above 30 kV up
to 150kV
ASTM D 2303 Standards Methods for Liquid, _Inclined-Plane
Tracking and Erosion of Insulation Material.
IEEE 80-2000 Guide for Safety in AC Substation Grounding
IEEE 48 -2000 Testing standard for joints and terminations.
6. Page 3 of 23Z|
LEN
seq efor sftaron feo feraaor fora vi
UTTAR DAKSHIN HARYANA. BLILI VITRAN NIGAM DHBVN
3.0 CLIMATIC CONDITIONS OF THE INSTALLATION
a, Max. Ambient Temperature 60deg.C
b. Max. Daily average ambient temp. 40 deg.C
c. Min Ambient Temp Odeg. C
d. Ground Temperature 25 degC
fe. Maximum Humidity 95%
{Minimum Humidity 10%
g. Average No. of thunderstorm days per annum 50
h. Average Annual Rainfall 750 mm
i. Average No. of rainy days per annum 60
j. Thermal Resistivity of soil 150deg.Comw
k. Wind Pressure 126 kg/sq. m up to
an elevation
oft 0M
The atmosphere is generally laden with mild acid and dust in suspension during the dry
months and is subjected to fog in cold months. The design of equipment and accessories
shall be suitable to withstand seismic forces corresponding to an acceleration of 0.1 g.
4.0 CABLE DATA:
The joint kit and termination kit should be of below sizes applicable for Heat Shrink
Technology used in 3KV and
Indoor Termination for 33KV XLPE 3CX25 sq.mm cable.
Outdoor Termination for33KV XLPE 3CX25 sq.mm cable
Straight Through joint for 33KV XLPE 3CX25 sq, mm cable.
Indoor Termination for 33KV XLPE 3CX95 sq.mm cable.
Outdoor Termination for33KV XLPE 3CX95 sq.mm cable.
Straight Through joint for 33KV XLPE 3CX95 sq.mm cable.
Indoor Termination for 33KV XLPE 3CX120 sq.mm cable.
‘Outdoor Termination for33KV XLPE 3CX120sq.mm cable
Straight Through joint for 33KV XLPE 3CX120 sq.mm cable.
Indoor Termination for 33KV XLPE 3CX150 sq.mm cable.
Outdoor Termination for33KV XLPE 3CX150sq.mm cable.
Straight Through joint for 33KV XLPE 3CX150 sq.mm cable,
Indoor Termination for 33KV XLPE 3CX185 sq.mm cable.
Outdoor Termination for33KV XLPE 3CX185 sq.mm cable.
Straight Through joint for 33KV XLPE 3CX186 sq.mm cable
Indoor termination for 33kv XLPE 3CX300sq.mm cable.
‘Outdoor termination for 33kv XLPE 3CX300sq,.mm cable.
Straight through joint for 3kv XLPE 3CX300sq.mm cable.
VV V VV VV VV
Indoor termination for 33kv XLPE 3CX400 sq.mm cable.
Outdoor termination for 33kv XLPE 3CX400 sq.mm cable.
Straight through joint for 33kv XLPE 3CX400 sq,mm cable.
Indoor termination for 33kv XLPE 1CX300 sq.mm cable.
‘Outdoor termination for 3kv XLPE 1CX300 sq.mm cable.
Straight through joint for 33kv XLPE 1CX300 sq.mm cable,
be Page 4 of 23
vvvvvyvvy
Indoor termination for 33kv XLPE 1CX400 sq.mm cable.ig
LEBEN
5.0
vvvvvvvvyvY
sae efor chao feo fraaor forrar
UTTAR DAKSHIN HARYANA-SLILI VITRAN NIGAM
Outdoor termination for 3kv XLPE 1CX400 sq.mm cable.
Straight through joint for 3kv XLPE 1CX400 sq.mm cable
Indoor termination for 33kv XLPE 1CX630 sq.mm cable.
Outdoor termination for 33kv XLPE 1CX630 sq.mm cable
Straight through joint for 3kv XLPE 1CX630 sq.mm cable.
Indoor termination for 33kv XLPE 1CX1000 sq.mm cable.
Outdoor termination for 33kv XLPE 1CX1000 sq.mm cable.
Straight through joint for 33kv XLPE 1CX1000 sq.mm cable.
GENERAL TECHNICAL PARTICULARS FOR HEAT SHRINK TECHNOLOGY:
Product design shall be based on heat shrinkable part to provide function of high voltage
insulation, electrical stress control, electrical screening, sealing and environmental sealing as
necessary. Use of tapes to provide primary insulation, screening or primary stress control is
not acceptable.
Bidders shall submit evidence with their tenders that designs are based on sound engineering
principles, accumulate know how and satisfactory service experiences.
Design shall aim at minimizing number of component parts along with time and skill required
for effective installation.
5.1 STRAIGHT THROUGH JOINT/TERMINATION KIT_FOR 33KV (E)
| S.No. DESCRIPTION Unirs, 33K
1 | Hicest System Voltage kv 36
| kv 4.5 Uo
2 |AC. withstand voltage with
time duration
mins 5
3 | Impulse withstand Voltage | KV 47OKV
4 | Partial Discharge at 1.73Uo | pC <10
5 | ImpulseWithstand,1.2/50/Us | KV 1TOKV
Load Cycle Test
a)Each Cycle ~ Heating
© | Duration ae o
Temperature Deg C 100
Page 5 of 23seq efor eftenon fer fragt ferret
UTTAR DAKSHIN HARYANA BLILI VITRAN NIGAM BVN
S.No. | DescRiPrion Uns | 33KV
Cooling Duration Hrs 3
b)Number of Cycles 60
¢)Continuous phase to ground
Voltage Withstand by cous
~ — |
No water
| 7 | Water Tigntness leak From
a | the end of
the sample
| a) 3CX300
Sq.mm
Cable : 28.2
Thermal Withstand Short 2 Soa
circuit current eee paca
A Cable 37.6
©) 1CX1000
sqmm
Cable : 94.0
Dynamic short circuit 2.55 Isc for
S| withstand KA Peak | oms
4 Uo for 15
10 | DC Voltage Kv ne
| 1000 Hrs at
11 | Salt fog Hrs, | 104
|
300 Hrs at
12 | Humiaty Hs. | 3h
6.0 GENERAL CONSTRUCTIONS OF HEAT SHRINK TECHNOLOGY:
‘The material shall be constructed in accordance of the applicable standards. The kits shall be
suitable for storage without deterioration at a temperature up to 50 degrees C and shall have
Unlimited shelf life The heat shrink system of the identical type brand as offered in the bids
shall have proven performance of at least 5 years in Indian/Tropical conditions. It should be
‘supported by type test report and purchase orders of some utility
6.1 TYPE OF JOINTS AND TERMINATIONS.
Joints and Termination shall be heat shrinkable suitable for 33kV (E), three Core and
single core XLPE insulated screened and armored cables (In line with DHBVN
Specification, IS 7098-part 2, IS 13573 Part 2 &3 & IEC 60502 having compacted circular
stranded aluminum conductors of sizes 25 mm2 to 1000 mm2. Bidder shall furnish
by Page 6 of 23saa efor efraron fro ferret forerat
UTTAR HARYANA’ BLL VITRAN NIGAM IBVN
documentary evidence confirming adherence to these or the dimensions as per the type
test report, whichever is higher. Fault level as well as duration withstands capacity of
termination / jointing kits shall be matched with the parameters of cables for which the kits.
are intended to be used. Outdoor termination kits shall provide means for protecting the
exposed insulation of conductor from UV radiations.
Bidder shall furnish documentary evidence confirming adherence to these or the
dimensions as per the type test report, whichever is higher. Fault level as well as duration
withstands capacity of termination / jointing kits shall be matched with the parameters of
cables for which the kits are intended to be used. Outdoor termination kits shall provide
‘means for protecting the exposed insulation of conductor from UV radiations
6.2 CLASS OF TERMINATIONS:
The heat shrinkable cable termination shall be of Class 1 as per IEEE-<48.
Heat Shrinkable Components-General Properties:
Components shall be capable of being stored without deterioration within temperature
range of 0 Deg. C to 50 Deg. C and shall have unlimited shelf life. Sealant activated by
heat shall be used in conjunction with heat shrinkable components to provide an
environmental seal to the completed joint.
6.3 STRESS CONTROL TUBING:
6.3.1 The stress control function at the screen cut back shall be provided by @ heat
shrinkable tubing having volume resistivity of minimum 10" ohm-meter for both
terminations and joints, Also, the relative permittivity shall be minimum 18,
6.3.2 The impedance of stress control tubing shall not change over range of
temperature from 0 deg. C to 125 deg. C. The stress control tubes must have a
thermal endurance equivalent to 30 years of ie.
6.3.3 For Straight through joints prior to the installation of the stress controlling
tubing, high permittivity mastic must be applied over the ferrule, overlapping the
insulation by 3 mm. The minimum permittivity of this mastic shall be 15.
6.3.4 Atthe step caused by semi-conductive soreen cut back, high permittivity mastic
is to be provided to prevent discharge activity at the step. The minimum
permittivity of the mastic should be 15 semi-conducting paint are acceptable.
6.3.5 Silicone grease shall be provided for filing up the nicks and soratches on the
surface of XLPE insulation
‘The stress control tubes shall have a thermal endurance equivalent to 30 years of life
Bidder must submit:
‘A) Documentary evidence including graphs showing effect of temperature and
thermal ageing on impedance of stress control material offered
B) Technical explanation of how the electrical properties of material versus volume
resistivity, permittivity and AC impedance have been derived
C)_ Proof of long term accelerated and long term field usage to confirm retention of
properties with permissible limit under variation of temperature and thermal
ageing
be Page 7 of 233 sag efaror eferon fro ftrrwor forarat
G7
LHEVN
UTTAR DAKSHIN HARYANA. BLILI VITRAN NIGAM + iBYN
6.4 NON-TRACKING, EROSION AND WEATHER RESISTANT PROTECTION
644
6.4.2
6.4.3
The entire surface, from the high voltage point (lug) to the earthing point of
the XLPE core/ cable shall be non-tracking, weather and erosion resistant,
and hydrophobic in nature.
‘A heat shrinkable flexible polymeric tubing, colored red, and possessing non-
tracking erosion and weather resistant properties shall be used as an
extemal covering for the cable cores for both indoor and outdoor
terminations. Rain sheds (skirts) wherever required for providing additional
creepage shall also be of the same material as the non-tracking tube. The
tubes shall be extruded and expanded by irradiation process only.
‘The material used for manufacturing the non-tracking tubing and rain sheds
(skirts) material shall conform to the requirements of ASTM-D-2303, Moulded
tubing is not acceptable and these shall have an assessed life exceeding 40
years. Bidder must provide:-
a) Proof of track and weather resistant of polymeric material offered
through actual field studies or accelerated laboratory test/studies to
conform a minimum of 30 year expectancy. It should include tracking
and erosion resistance test to withstand ability against effects of
surface leakage currents.
b) Load cyeling tests alone, shall not be considered sufficient basis for
such life assessment.
6.5 ENVIRONMENTAL SEALING
651
652
653
‘Adhesives and sealants shall be provided in the termination and jointing kits
for environmental sealing against ingress of moisture and aggressive gases.
The adhesives and sealants shall flow due to heating of heat shrinkable
components or otherwise during installation and shall fill all voids and adhere
to metal components and cable sheaths.
For terminations: The sealing of the strands between the lug barrel and cable
termination shall be provided by:
a) Non-racking, erosion and weather resistant non-tracking sealant
coated over the inner side of heat shrinkable tubing
b)Non-tracking sealant strips
The sealants shall have unlimited shelf life.
For Joints: The outer black colored heat shrinkable flexible polymeric tubing
shall be pre-coated with adhesives to provide sealing of the exposed metallic
‘components / earth connections.
Bidder must provide information for track and erosion resistant of sealant as
per ASTM D2303 and must submit information for Dielectric strength.
6.6 PROVISION OF ADDITIONAL CREEPAGE FOR INDOOR AND OUTDOOR
‘TERMINATIONS,
Single piece, heat shrinkable weather sheds (skirts) having non-tracking, erosion and
weather resistant properties shall be supplied with the kits for providing additional
creepage. The quantity of sheds to be supplied shall depend on voltage grade and
Indoor/Outdoor application and shall be indicated along with the bid. Each shed shall
give additional creepage length of at least 100 mm. The termination should be
designed for a minimum creepage of 25mm/kV for the system voltage.
\ Page 8 of 23saq efor eftaron fro ferror fororar f
UITAR DAKSHIN HARYANA- BLILI VITRAN NIGAM z
LEN
6.7 INSULATION AND SCREEN REINSTATEMENT FOR JOINTS.
Bidder shall provide co-extruded dual-wall tubing for straight through which joints to
ensure a void-free bond between the rebuilt insulation and non-metallic screen
enables the final insulating layer to be installed complete with a conductive polymeric
screen in one step. The insulation of the cable is to be reinstated with heat shrink
tubing having an elastomeric layer, which shall provide 1.3 times the cable insulation
thickness upon shrinking. This dual walled tubing shall be co-extruded and shall be
offered with joints. Insulating Sleeves coated with conductive material shall not be
permitted. Bidder must provide:~
a) Proof that dual wall tubings are manufactured by means of co-extrusion.
b) Conformation of minimum thickness of insulation provided over the connector for
maximum size of conductor for which tubing is supplied.
©) Proof of accelerated and long term field usage to confirm the retention of key
properties within permissible limits due to thermal ageing. Minimumkey properties
before and after ageing have to be stated
6.8 FIRE RESISTANCE
The cable end terminations and straight-through joints shall be fire resistance. The
components of kts shall have flame retardant property.
6.9 EARTH/SCREEN CONTINUITY/TERMINATION SYSTEM
a) Screen continuity for each core shall be achieved by using tinned copper
mesh and earth continuity by using tinned copper braids of appropriate sizes,
b) In terminations, tinned copper braids of appropriate sizes along with copper
lugs of appropriate sizes shall be provided for the continuity of screen / armor
along with adequate holding arrangements.
c) The copper braid should withstand fault current of cable fault current capacity
without any fail
d) The armour earthing shall be part of the termination
1 Connectors
6.10 Lugs / Ferrules / Mechai
For 33kV,
‘The Mechanical connector with shear head bolts ( Hexagonal Shape) used in 33kV
cables joints & termination. The Mechanical connectors shall be suitable for
application on copper &aluminium cables / bus bars.
The requisite number of Lugs / Ferrules for compact circular stranded conductors
shall be provided for terminations / joints of XLPE Cables. Long barrel Aluminum
Ferrule should be used for Straight Through joints and Lugs for Termination,
LugiFerrule/Connector must be provided with oxidation and corrosion inhibiting
compound. The proof of same must be submitted by Bidder.
6.11 PROPERTIES OF HEAT SHRINKABLE COMPONENTS:
| - Stress Control Tube used in joints and terminations:
R Page 9 of 23saa sferor ofraron ferort ferraor ferorar
UTTAR DAKSHIN HARYANA BUILI VITRAN NIGAM IBVN
A) Electrical properties
Property Unit Required Value
Dielectric Constant | = 15 (min)
| (ASTM D-150)
Volume Resistivity | Ohm.cm Tx 40" (min)
B) Physical properties
Property Unit Required Value ]
Tensile strength Nimm 70 (Min)
(ASTM 0-412)
Ultimate % 200 (Min)
Elongation
(ASTM 0-412)
| Water Absorption % 0.3 (Max)
(ASTM D-570)
Properties after corrosion test-500 hrs @ 120°C
Tensile strength Nima’ 8 (Min)
(ASTM D-412)
Uttimate | % 50 (Min)
Elongation
(ASTM 0-412) |
Properties after solvent immersion
Tensile strength Nim’ 5 (Min)
(ASTM 0-412)
Uitimate % 7150 (Min)
Elongation
(ASTM 0-412)
Spiiting 7 No spiiting a
Fungus = Non nutrient |
Resistance
Longitudinal % 5 (Max)
change
C) Thermal properties
Property Unit Required Value
Heat shock = 30 min @ 200°C
(ASTM D-2671)
& Page 10 of 23sae eferor efyaron frat frat forerer
UTTAR DAKSHIN HARYANA- LILI VITRAN NIGAM
Properties after thermal aging, 168 hrs @ 150°C
Tensile strength
(ASTM D-412)
Nima
8 (Min)
Uttimate
Elongation
(ASTM D-412)
%
7100 (Min)
Low temperature
flexibility
(ESI 09-13, 4 hrs
@-20°C)
No cracks:
Il— Anti-Tracking/Insulating Tube used in joints and terminations:
A) Electrical properties
Property Unit Required Value _
Dielectric strength | kVimm | 78 (Min)
(ASTM D-149)
Dielectric Constant | — ~ | 3.5(Min)
(ASTM D-150)
Volume Resistivity | Ohm.cm | 24x 10™(Min)
Tracking Resistance No tracking
(ASTM D-2303)
1 hr@ 2.5kV,
1 hr @2.75 kV,
ahr @3kV&
20min @3.25 kV
B) Physical properties
Property Unit Required Value
Tensile strength Nimm? | 8 (Min)
(ASTM 0-412)
Ultimate Elongation | % ‘300 (Min) 7
(ASTM D-412)
‘Water Absorption % 0.3 (Max)
(ASTM D-570)
Properties after corrosion test-500 hrs @ 120°C
Tensile strength Nimm™ | 6 (Min)
(ASTM 0-412) |
Ultimate Elongation % 100 (Min)
(ASTM D-412) -
‘Spliting = No spiiting
Fungus Resistance | — Non nutrient
Longitudinal change | % 10 (Max) ~
BVN
he Page 11 of 23C) Thermal properties
| Property Unit ~ | Required Value
Heat shock (ASTM [=~ 30 min @ 200°C
0.2671)
Flammability (ULS4) Pass
| Properties after thermal aging, 168 hrs @ 150°C.
“Tensile strength Nimm* [7 (Min)
(ASTM D-412)
Ultimate Elongation | % 200 (Min)
(ASTM D-412)
Low temperature = No cracks 7
flexibility
(ESI 09-13, 4 hrs @
-20°C)
iBVN
Ill - Dual Wall (Insulating/semiconducting) Tube used in joints and terminations:
A) Electrical properties
Property Unit Required Value
Dielectric strength kVimm [718 (Min)
(insulating wall) |
(ASTM 0-149) |
Volume Resistivity ‘Ohm.cm | 1x 10™ min
(insulating wall)
Volume Resistivity ‘Ohm.om | 1x 10" max
(Outer semi-con layer ) |
B) Physical properties
[Property Unit | Required Value -
Tensile strength Nimm? [8 (Miny
(ASTM D-412)
"Ultimate Elongation % 200 (Min)
(ASTM D-412)
Properties afier corrosion test-500 hrs @ 120°C
Tensile strength Nimm? | 6 (Min)
(ASTM D-412)
Ultimate Elongation % 400 (Min)
(ASTM D-412)
Fungus Resistance
Non nutrient
oe Page 12 of 23sae eferor ofraron fro razor ferret
UTTAR DAKSHIN HARYANA BIJLI VITRAN NIGAM (BVN
Longitudinal change | % 10 (Max)
C) Thermal properties
Property Unit Required Value ]
Heat shock (ASTM D- | =~ 30 min @ 200°C
2671) |
Properties after thermal aging, 168 hrs @ 150°C
Tensile strength Nimm? 6 (Min)
(ASTM D-412) |
Uimate Elongation | % 700 (Min)
(ASTM D-412)
Low temperature = No cracks: |
flexibility
(ESI09-13, 4 hrs @-
20°C)
IV - Stress Control Mastic use \d terminations:
A) Electrical properties
Property Unit Required Value
Dielectric Constant |= = 9 (min)
(ASTM D-150)
Volume Resistivity | Ohmem — | 1x 10min
(insulating wall)
Dissipation factor | — 045
B) Physical properties
Property Unit Required Value
Tensile strength Nimm* 08 (Min)
(ASTM 0-412)
Uitimate Elongation % 500 (Min)
(ASTM D-412)
‘Water Absorption % 0.5 (Max)
(ASTM D-570)
he Page 13 of 23saa efaror oiraron fer fraqor fororar
UTTAR DAKSHIN HARYANA. BIJLI VITRAN NIGAM BVN
Service Temp c 90 - ]
6.12 General Kit contents of the Heat Shrink Straight through joint For 33 KV Cable:
BOM for Straight Through Joint of 33KV Cable _
Minimum Quantity for One
S.No. Description Remora
33Kv (3Core)
a) ‘Outer Insulating Heat Shrink Sleeve | 1 Set
b) Stress Control Tube 3 Nos.
i) Dual Wall Sleeve 3 Nos.
d) High permittivity Mastic Strip 18 Nos.
Mechanical connectors with Shear
®) Head bolts for 33 kV oe
D ‘Ammour/Copper Screen Earth a
Continuity Connection
i Copper Wire Mesh 2 Nos
ii Copper Binding Wire 1No.
i Tinned Copper Braid Minimum 4 No |
iv Backup ring 2.Nos
; ‘Subkit (Cleaning Solvent, Aluminum a
9 Oxide Cloth, Silicone Grease)
GI Mesh 7 VB Can for Mechanical
4) | Protection ae
i) | Instruction Sheet [ 1No.
})__| Packing Box ‘No.
6.13 General Kit contents of the Heat Shrink Straight through joint For 33 kV Cable:
BOM for Straight Through Joint of 33KV Cable
Minimum Quantity for One
ene Description Straight Through Jointing
- 33Kv (Core)
a) Outer Insulating Heat Shrink Sleeve ___1Set
by Stress Control Tube _ + Nos. |
o) Dual Wal Sleeve “Nos.
¢) High permittivity Mastic Strip 6 Nos.
Mechanical connectors with Shear
°) Head bolts for 33 kV a
? ‘ArmourlCopper Screen Earth | aan
LL Continuity Connection
i__| Copper Wire Mesh 2Nos
ii | Copper Binding Wire No.
i Tinned Copper Braid Minimum 1No |
v Backup ring 2 Nos
ge Page 14 of 23sag giaor efaron feo ferraor foro
UTTAR DAKSHIN HARYANA-BLILI VITRAN NIGAM rev
|
Subkit (Cleaning Solvent, Aluminum
9 | Oxide cioth, Silicone Grease) es
GI Mesh 7 VB Can for Mechanical |
h) | Protection ue a]
i) __| Instruction Sheet | No.
) __| Packing Box 1No.
6.14 General Kit contents of the Termination (Indoor/Outdoor) For 33 kV Cable:
BOM for Termination Kit of 33KV Cable
Minimum Quantity for One
S.No. Description Termination Kit
33kV (3Core)
a) __| Anti tracking Sleeves 3 Nos.
») | Mechanical connectors with Shear a
Head bolts(Hexagonal Shape) for 33 kV
©) _| Stress Control Sleeves 3 Nos. |
@) | Rain sheds ‘skits Oukdoor- 15 Nos. Indoor-6 |
e) High permittivity void filing Mastic 6 Nos. -
) _| Earthing set 1Set
Subkit (Cleaning Solvent, Aluminum
9 _| Oxide Cloth, Silicone Grease) | 1Set
h) | Instruction Sheet No.
i) | Packing Box No.
6.15 General Kit contents of the Termination (Indoor/Outdoor) For 33 kV Cable:
| BOM for Termination Kit of 33kV Cable
‘Minimum Quantity for One
S.No. Description Termination Kit
33kV (1 Core)
@)__| Anti tracking Sleeves 1 Nos.
») | Mechanical, connectors with Shear a
Head bolts(Hexagonal Shape) for 33 kV
°) Stress Control Sleeves ‘Nos.
4) | Rain sheds skirts Cee ee
e) __| High permittivity void filing Mastic _2Nos.
Earthing Set 1 Set
‘Subkit (Cleaning Solvent, Aluminum —
9) | Oxide Cloth, Silicone Grease) oe |
h)___| Instruction Sheet No
Co Packing Box 1No.
7.0 NAME PLATE & MARKING
be Page 15 of 23,8.0
saa efor oftaron feo fraaor foro
UTTAR DAKSHIN HARYANA BIULL VITRAN NIGAM IBYN
Following identification marking shall be provided on stress control tubes, dual wall tubes,
outer jacketing tubes (in straight through joints), breakouts, rain sheds, and non-tracking
tubes:
a) _Batch No. to co-relate with the raw materials used to manufacture the components
b) Shrink ratio
) “Stress Control” or "Conductive" as the case may be
¢) Manufacturer's name &Date of Manufacturing
“Property of DHBVN"8 “Material Code” shall be embossed suitable on the materials and on
the components wherever possible.
TESTS
All routine, acceptance & type tests shall be carried out in accordance with the relevant IS/IEC.
All routine & acceptance tests shall be witnessed by the purchaser/his authorized representative.
All the components shall also be type tested as per the relevant standards. Following tests shall
be necessarily conducted on the Joint and Termination Kits in addition to others specified in
ISIEC standards
Type Tests
(From 33kV Joint and Termination)
Series 1
a) Conductor resistance.
b) Impact (Only for Joints),
©) AC Voltage withstand Test (Air)
d) AC Voltage withstand test (under wet conditions) (for outdoor termination
only)
e) Partial Discharge.
) Impulse voltage test
9) Heat Cycle test in air and water.
h) Thermal Short Circuit Test (Screen & Conductor).
)) AC Voltage Life Test with Cyclic Current Loading (Only for Indoor /
Outdoor Terminations).
))__ Leak tightness (For Outdoor Termination only),
k) Water Tightness (for joints only)
1) Impulse Withstand
m) DC Voltage Withstand.
n) Dynamic short circuit test
0) _ Influence of humidity (For Indoor termination only).
P) Salt fog test (Only for Outdoor terminations only)
Routine Test
The bidder shall provide material wise routine test report conducted at their works
along with the standards application in their bid
a) Partial discharge test.
b) AC voltage withstand test.
) Electric Strength test for insulation tubing,
d) Elongation tests for all types of tubing
e) Tensile Strength.
be Page 16 of 23saa eieror efearon frat ferraor fororat AP
UTTAR DAKSHIN HARYANA’ BLILI VITRAN NIGAM DHBVN
LHEVN,
) Tracking and corrosion resistance test.
9) Volume Resistivity
Acceptance tests
a) Visual Inspection. The offered kits shall be free from any visible defects.
b) Physical verification of contents - all the contents shall be checked as per kit
contents list enclosed by the bidder.
©) Electric Strength test for insulation tubing.
d) Elongation tests for all types of tubing,
) Wall thickness ratio in expanded condition.
) Longitudinal change after full recovery.
q) Tracking and corrosion resistance test.
h) Verification of bill of Material
i) Tensile Strength
j) Volume Resistivity
k) Partial Discharge Test
9.0 TYPE TEST CERTIFICATES
10.0
11.0
120
The bidder shall furnish the type test certificates for the tests as mentioned above as per
the corresponding standards. All the tests shall be conducted at CPRI, Bangalore as per
the relevant standards. Type tests should have been conducted in certified Test
laboratories of CPRI, Bangalore. During the period not exceeding 5 years from the date of
opening the bid. In the event of any discrepancy in the test reports, i.e. any test report not
acceptable, same shall be carried out without any cost implication to the Purchaser.
DHBWN has rights for Surveillance test of random selected samples from third party lab for
quality checks of item
PRE- DESPATCH INSPECTION
Equipment shall be subject to inspection by a duly authorized representative of the
Purchaser. Inspection may be made at any stage of manufacture at the option of the
purchaser and the equipment if found unsatisfactory as to workmanship or material, the
same is liable to rejection. Bidder shall grant free access to the places of manufacture to
the Purchaser's representatives at all times when the work is in progress. Inspection by the
Purchaser or its authorized representatives shall not relieve the supplier of his obligation of
furnishing equipment in accordance with the specifications.
Material shall be dispatched after specific MDCC (Material Dispatch Clearance Certificate)
is issued by the Purchaser.
Following documents shall be sent along with material:
a) Test reports
b) MDCC issued by Purchaser
©) Invoice in duplicate
d) Packing list
e) Drawings & catalogue
f) Guarantee / Warrantee card
9) Delivery Challan
h) Other Documents (as applicable)
INSPECTION AFTER RECEIPT AT STORE:
‘The material received at the Purchaser store shall be inspected for acceptance and shall
be liable for rejection, if found different from the reports of the pre-dispatch inspection and
‘one copy of the report shall be sent to each PDDepartment& MM Department
GUARANTEE
Page 17 of 23,sag efor sitar feo feraaor fora
UTTAR DAKSHIN HARYANA. BILL VITRAN NIGAM iBVN
HEN
13.0
14.0
15.0
16.0
17.0
Bidder shall stand guarantee towards design, materials, workmanship & quality of process /
‘manufacturing of items under this contract for due and intended performance of the same, as
an integrated product delivered under this contract. In the event any defect is found by the
purchaser up to a period of at least 72 months from the date of commissioning and shall be for
entire duration of guarantee period Bidder shall be liable to undertake to replace/rectify such
defects at its own costs, within mutually agreed time frame, and to the entire satisfaction of the
‘Company, failing which the purchaser shall be at liberty to get it replacedirectified at bidder's
risks and costs and recover all such expenses plus the Company's own charges (@ 20% of
expenses incurred), from the bidder or from the * Security cum Performance Deposit’ as the
case may be. Bidder shall further be responsible for free replacement for another period of
THREE years from the end of the guarantee period for any ‘Latent Defects’ if noticed and
reported by the purchaser.
PACKING
Bidder shall ensure that all the equipment covered under this specification shall be
prepared for railroad transport in a manner so as to protect the equipment from damage in
transit, The material used for packing shall be environmentally friendly.
All the components shall be sealed separately and marked clearly for the purpose of
identification of each component. Each components shall be supplied in a single package as
a complete kit for one terminationijoint and shall bear the manufacturer's name and the cable
sizes or kit sizes for which it can be used, voltage grade.
TENDERSAMPLE,INSTALLATION INSTRUCTION
Bidder shall be submit the sample of material with the offer (in case of first supply to
Purchaser).
Detailed Installation instruction with drawings for all joints and termination shall be provided
by Bidder with tender documents in English Language.
QUALITY CONTROL
The bidder shall have valid ISO 9000:2001 certification for products offered. The scope
(extent) of certification should cover at least the design, development, production and
installation of products offered. The bidder shall have also valid ISO 14001: 2000
Environmental Management Systems, Bidder should provide Model No. of each kit of each
voltage grade along with dimension of each components used in the kit during the
submission of bid, Bidder should also provide material chemical Composition certificate
during the submission of bid
The bidder shall submit with the offer Quality assurance plan indicating the various stages
of inspection, the tests and checks which shall be carried out on the material of
construction, components during manufacture and bought out items and fully assembled
component and equipment after finishing. As part of the plan, a schedule for stage and
final inspection within the parameters of the delivery schedule shall be furnished. The
Purchaser's engineer or its nominated representative shall have free access to the
manufacturer's/sub-supplier’s works to carry out inspections,
MINIMUM TESTING FACILITIES
Bidder shall have adequate in house testing facilities for carrying out all routine tests,
acceptance tests as per Indian /International standards.
MANUFACTURING ACTIVITIES
‘The successful bidder shall submit bar chart for various manufacturing activities clearly
elaborating each stage, with quantity. This bar chart should be in line with the Quality
assurance plan submitted with the offer. This bar chart shall be submitted within 15 days
from the release of the order.
& Page 18 of 23sae efor efaron ferorit fraaor ferrer
UTTAR DAKSHIN HARYANA-SLILI VITRAN NIGAM BVN
18.0 SPARES, ACCESSORIES AND TOOLS
Not applicable
19.0 DRAWINGS:
After the award of the contract four (4) copies of following drawings, drawn to scale,
describing the equipment in detail shall be forwarded for approval
S.No. | Description For For Final
| Approval | Review jubmission
| Inform
[1 Technical Parameters q v
|
| 2 | Drawing showing Joints Details Y q
3 ‘Termination drawings 7 Vv
|
5 | Manual/Catalogues v im!
6 | Transport! Shipping ‘dimension Vv vy |
| drawing
[7 |@aaac Pian [od v Y
@ | Routine, Acceptance and Type 7 T —q
Test Certificates
Bidder shall be subsequently provide four (4) complete sets of final drawings, one of
which shall be auto positive suitable for reproduction, before the dispatch of the
equipment. Soft copy (Compact Disk CD) of all the drawing, GTP, Test certificates shall
be submitted after the final approval of the same to purchaser.
All the documents & drawings shall be in English language.
Instruction Manuals: Bidder shall furnish two softopies (CD) and four (4) hard copies of
nicely bound manuals (in English language) covering erection and maintenance
instructions and all relevant information and drawings pertaining to the main equipment as
well as auxiliary devices.
20. Guaranteed Technical Particulars for Heat Shrink Technology.
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF HEAT
SHRINKABLE STRAIGHT THROUGH JOINTS FOR 33kV XLPE CABLES
0 be filled
Description _by the bidder
‘Manufacturer's name & address
‘Noltage grade
Sr.
1
2.___ Sr.No. & name and country of original
3
4
‘System Voltage
be Page 19 of 23saa eferor sfteron firadt feraaor ferent
UTTAR DAKSHIN HARYANA. BIJLI VITRAN NIGAM
BVN
A.C. withstand voltage Dry(Ph./ground) in kV.
5___ [Time duration for indoor termination and straight joint__|
‘Time Duration(Mins) [
JAC. withstand voltage Wet(Ph./ground) in KV.
6 ___[Time duration for outdoor termination
‘Time Duration(Mins)
|_7___ Partial Discharge at 1.73 Uo (Pc)
8 Impulse Withstand, 1.2/50/Us (kV)
Load Cycle Test
a. Each Cycle-Heating Duration (Hrs)
Temperature(Deg C)
Cooling Duration(Hrs)
b. Number of Cycles
c. Continous phase to ground Voltage
9 Withstand(kV)
10 [Leak Tighiness
11___ [Thermal Withstand Short Circuit current 1 sec(kA)
12 Dynamic short circuit withstand(kA Peak)
13 [DC Voltage(kV)
14 [Accelerated Ageing test(30 Years)
15 (Cable Termination Instruction Manuals(Yes/No)
16 Type of kit offered _
17 Applicable standards
18 Size
19 terial of tubing / moulded parl/self amalgamating tape
fete.
20 __lInsulation time _
21 Curing time
[Time required for enerqisation after completion of
22 __ termination _
23 Special devices required if any
24 Kit storage temperature (Degree centigrade)
25 | (a)Shelf life of kit. [
(b) | Design life of kit
(©) List of contents of kit (to be furnished separately) _|
26 | Material used for stress control
27 Dielectric strength of insulation material (kV/rnm)
Material used in encapsulating compound and
environmental
ealing
(Class of kit
Whether test reports, drawings and instruction leaf lets
30__| are enclosed
31__| Volume resistivity:
34.4. [Stress control tubing
31.2. Non tracking tubing |
32 Relative permittivity
Page 20 of 23seq sor sharon feat fraqor fororar
UITAR DAKSHIN HARYANA BLILI VITRAN NIGAM
Ap
/DHBVN
32.4 ‘Stress control tubing
32.2 Non tracking tubing
33___| Water absorption
(33.1. [Stress contro! tubing
33.2. Non tracking tubing
34__| Tracking resistance
34.1. ‘Stress control tubing
34.2. Non tracking tubing
36,__| Tensile strength |
36.1. ___ [Stress control tubing
35.2. ~_[Non tracking tubing - 1
36. ultimate elongation -
36.1 _ ‘Stress control tubing _
36.2. Non tracking tubing
Note: While giving details of technical parameters above the reference
relevant ISS/international standard must be indicated
of applicable
SHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR TERMINATION
FOR 33kV XLPE CABLES(OUTDOOR/INDOOR TERMINATION KIT)
[To be filled by the
Sr. Description bidder
4 [Manufacturer's name & address
2. Isr. No. & name and country of original
3. foltage grade
4 [System Voltage _|
\A.C. withstand voltage Dry(Ph./ground) in kV.
5 [Time duration for indoor termination and straight joint
{Time Duration(Mins)
JAC. withstand voltage Wet(Ph /ground) in kV.
6 [Time duration for outdoor termination _
[Time Duration(Mins)
7 Partial Discharge at 1.73 Uo (Pc)
8 Impulse Withstand, 1.2/50/Us (kV)
lLoad Cycle Test
a. Each Cycle-Heating Duration (Hrs)
Temperature(Deg C) |
Cooling Duration(Hrs)
b. Number of Cycles
9 c._Continous phase to ground Voltage Withstand(kV) _
10 Leak Tightness.
41 [Thermal Withstand Short Circuit current 1 sec(kA)
12 Dynamic short circuit withstand(kA Peak)
13 (DC Voltage(kV) 7
44 [Accelerated Ageing test(30 Years)
15 [Cable Termination Instruction Manuals(Yes/No) _
16 [Type of kit offered
7 lApplicable standards
18 [Size _
19 _ [Material of tubing / moulded part/self amalgamating tape etc. |
20 Insulation time
be
Page 21 of 23saa efor efrarom fr foraaor ferent
UTTAR DAKSHIN HARYANA’ BUJLI VITRAN NIGAM
BVN
[Curing time
{Time required for enerqisation after completion of termination
‘Special devices required if any
Kit storage temperature (Degree centigrade)
(a)Shett life of kit.
(b) Design life of kit
25 List of contents of kit (to be furnished separately)
26 Material used for stress control :
27 Dielectric strength of insulation material (kVirnm)
Material used in encapsulating compound and environmental
28 sealing
29 (Class of kit _
Whether test reports, drawings and instruction leaf lets are
30 enclosed
31 Volume resistivity
31.4 ‘Stress control tubing
31.2. ____| Non tracking tubing
32 Relative permittivity
324 ‘Stress control tubing -
32.2. Non tracking tubing |
33 Water absorption |
33.1 ‘Stress control tubing
33.2. Non tracking tubing
4 Tracking resistance
34.4. [Stress control tubing
34.2 Non tracking tubing -
36 Tensile strength -
35.1 ‘Stress control tubing E
36.2. Non tracking tubing
36 ultimate elongation _
36.1 ‘Stress control tubing
36.2. Non tracking tubing
21. SCHEDULES OF DEVIATIONS
The bidders shall set out all deviations from this specification, Clause by Clause in this
schedule, Unless specifically mentioned in this schedule, the tender shall be deemed to
confirm the purchaser's specifications.
Note: While giving details of technical parameters above the reference of applicable
relevant |SS/international standard must be indicated
-Sd-
SE/P&D, DHBVN
‘Cum-member Secretary
CSC, UHBVN/DHBVN
b
Page 22 of 23sae eferor efraron frat frazor fororar
UTTAR DAKSHIN HARYANA BULL ViTRAN MGA = /DHBVN
(TO BE ENCLOSED WITH THE BID)
All deviations from this specification shall be set out by the Bidders, clause by Clause in this,
‘schedule. Unless specifically mentioned in this Schedule, the tender shall be deemed to
‘confirm the purchaser's specifications:
S.N Clause No. _| Details of de
We confirm that there are no deviations apart from those detailed above.
Seal of the Company
Signature
Designation
im Page 23 of 23