115.24-NOM11 (0121) FH Series D IOM
115.24-NOM11 (0121) FH Series D IOM
Series D
INSTALLATION, OPERATION & MAINTENANCE Supersedes 115.24-NOM11 (0520) Form 115.24-NOM11 (0121)
FORM 115.24-NOM11 (0121)
TABLE OF CONTENTS
Safety Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . 1
Section One - Receipt & Initial Installation Electric Resistance Heater Assembly . . . . . . . . . . . 18
FH Series Features . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Electrical Wiring & Controls . . . . . . . . . . . . . . . . . . . 18
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Valves & Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Unpacking & Inspection . . . . . . . . . . . . . . . . . . . . . . . 3 Filters, Throwaway . . . . . . . . . . . . . . . . . . . . . . . . . 19
Handling & Installation . . . . . . . . . . . . . . . . . . . . . . . . 3 Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Drain Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Optional Item Installation . . . . . . . . . . . . . . . . . . . . . 20
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Condensate Pump . . . . . . . . . . . . . . . . . . . . . . 20
Cooling/Heating Medium Connections . . . . . . . . . . . 6 Current Switch Device . . . . . . . . . . . . . . . . . . . 21
Auxiliary Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 7 Differential Air Pressure Switch . . . . . . . . . . . . . 22
Ductwork Connections . . . . . . . . . . . . . . . . . . . . . . . 7 Discharge Air Sensor . . . . . . . . . . . . . . . . . . . . 23
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . 8 Low Temperature Cutout Control . . . . . . . . . . . 23
Electrical Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Condensate Float Switch Installation . . . . . . . . 25
Telescoping Bottom Panel . . . . . . . . . . . . . . . . . . . . . 8 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . 26
Model FHP Horizontal Fan Coil Optional
Telescoping Bottom Panel Assembly,
Typical Installation Instructions . . . . . . . . . . . . . . 9 Section Four - Inspection &
Service & Clearance Requirements . . . . . . . . . . . . 10 Start-Up Checklist
Height Restricted Application . . . . . . . . . . . . . . . . . 11 Inspection & Start-up Checklist . . . . . . . . . . . . . . . . 27
Width Restricted Application . . . . . . . . . . . . . . . . . . 12
External Space Requirements . . . . . . . . . . . . . . . . . 13 Section Five - Fan Relay Board
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Reference Wire Diagram . . . . . . . . . . . . . . . . . . . . . 30
Section Two - Start-Up Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Tools Needed for Installation/Troubleshooting . . . . 32
Cooling/Heating System . . . . . . . . . . . . . . . . . . . . . 14 Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Air System Balancing . . . . . . . . . . . . . . . . . . . . . . . 14 Test Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Motor & Fan Data . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Screw Terminal Signals . . . . . . . . . . . . . . . . . . . . . . 34
Water System Balancing . . . . . . . . . . . . . . . . . . . . . 16 Checking Wire Harnesses . . . . . . . . . . . . . . . . . . . . 35
Controls Operation . . . . . . . . . . . . . . . . . . . . . . . . . 16
ii JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
SAFETY CONSIDERATIONS
Check that the unit assembly and
component weights can be safely
The equipment covered by this manual is designed for
supported by rigging and lifting
safe and reliable operation when installed and operated
within its design specification limits. To avoid personal equipment.
injury or damage to equipment or property while
installing or operating this equipment, it is essential
that qualified, experienced personnel perform these All assemblies must be adequately
functions using good judgment and safe practices. See secured during lifting and rigging by
the following cautionary statements. temporary supports and restraints until
equipment is permanently fastened
ELECTRICAL SHOCK HAZARDS. and set in its final location.
All power must be disconnected prior
to installation and servicing this All unit temporary and permanent
equipment. More than one source of supports must be capable of safely
power may be present. Disconnect all supporting the equipment’s weight and
power sources to avoid electrocution any additional live or dead loads that
or shock injuries. may be encountered. All supports must
be designed to meet applicable local
MOVING PARTS HAZARDS. Motor codes and ordinances.
and Blower must be disconnected prior
to opening access panels. Motors can All fastening devices must be designed
start automatically, disconnect all to mechanically lock the assembly
power and control circuits prior to in place without the capability of
servicing to avoid serious crushing or loosening or breaking away due to
dismemberment injuries. system operation and vibration.
JOHNSON CONTROLS 1
FORM 115.24-NOM11 (0121)
Blower
Valve package
(factory mounted
or shipped loose)
Condensate
pump
Coils
Right or left hand coil
Removable and drain connections,
drain pan same or opposite end
Your equipment is initially protected under the All power must be disconnected before
manufacturer’s standard warranty; however, this
any installation or service should
warranty is provided under the condition that the steps
outlined in this manual for initial inspection, proper
be attempted. More than one power
installation, regular periodic maintenance, and everyday source may be supplied to a unit.
operation of the equipment be followed in detail. This Power to remote mounted control
manual should be fully reviewed in advance of any devices may not be supplied through
actual work being done on the equipment. Should the unit. Never wear bulky or loose
any questions arise, please contact your local Sales fitting clothing when working on any
Representative or the factory BEFORE proceeding. mechanical equipment. Gloves should
only be worn when required for proper
The equipment covered by this manual is available with protection from heat or other possible
a vast variety of options and accessories. Consult the injury. Safety glasses or goggles
approved unit submittal, order acknowledgement, and
should always be worn when drilling,
other manuals for details on the options and accessories
provided with the equipment on each project.
cutting, or working with chemicals
such as refrigerants or lubricants.
2 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
Never pressurize any equipment carrier. All equipment should be stored in the factory-
beyond specified operating pressures. shipping carton with internal packing in place until
Always pressure test with some inert installation.
fluid or gas such as clear water or dry
nitrogen to avoid possible damage At the time of receipt, the equipment type and
arrangement should be verified against the order
or injury in the event of a leak or
documents. Should any discrepancy be found, the local
component failure during testing. Sales Representative should be notified immediately
so that the proper action may be instituted. Should
Always protect adjacent flammable any question arise concerning warranty repairs, the
material when welding, brazing or factory must be notified BEFORE any corrective
soldering. Use suitable heat shield action is taken. Where local repairs or alterations can
material to contain sparks or drops of be accomplished, the factory must be fully informed as
solder. Have fire extinguisher available to the extent and expected cost of those repairs before
for use when welding or brazing. work is begun. Where factory operations are required,
the factory must be contacted for authorization to return
The manufacturer assumes no responsibility for personal equipment and a Return Authorization Number will be
injury or property damage resulting from improper issued. Unauthorized return shipments of equipment
or unsafe practices during the handling, installation, and shipments not marked with an authorization number
service, or operation of any equipment. will be refused. In addition, the manufacturer will not
accept any claims for unauthorized expenses.
UNPACKING & INSPECTION
CODE COMPLIANCE
All units are carefully inspected at the factory throughout
the manufacturing process under a strict detailed quality This equipment has been manufactured and certified in
assurance program, and where possible, all major accordance with UL 1995-Standard for Safety, Heating
components and subassemblies are carefully tested for and Cooling Equipment (CAN/CSA C22.2 NO 236-
proper operation and verified to be in full compliance M90) and bears the Electrical Testing Laboratories
with the factory manufacturing documents. Customer (ETL) Mark under ETL File No.: 3036742-002.
furnished components such as control valves, switches
and DDC controls are not factory tested. HANDLING & INSTALLATION
While all equipment is designed for durability and
Each unit is carefully packaged for shipment to avoid fabricated for sturdy construction and may present a
damage during normal transport and handling. The rugged appearance, great care must be taken to assure
equipment should always be stored in a dry place in the that no force or pressure be applied to the coil, piping or
proper orientation as marked on the carton. drain stub-outs during handling. Also, depending on the
options and accessories, some units could contain delicate
All shipments are made F.O.B. factory and it is the components that may be damaged by improper handling.
responsibility of the receiving party to inspect the Wherever possible, all units should be maintained in an
equipment upon arrival. Any obvious damage to the upright position and handled by the chassis as close as
carton and/or its contents should be recorded on the bill of possible to the mounting point locations.
lading and a claim should be filed with the freight carrier.
In the case of a full cabinet unit, the unit must obviously
After determining the condition of the carton exterior, be handled by the exterior casing. This is acceptable
carefully remove each unit from the carton and inspect providing the unit is again maintained in an upright
for hidden damage. At this time check to make sure that position and no impact forces are applied that may
“furnished only” items such as switches, thermostats, damage internal components, access panels, or painted
etc., are accounted for. Any hidden damage should be surfaces. The equipment covered in this manual IS NOT
recorded and immediately reported to the carrier and a suitable for outdoor installations. The equipment should
claim must be filed. In the event a claim for shipping never be stored or installed where it may be subjected
damage is filed, the unit, shipping carton, and all packing to a hostile environment such as rain, snow, or extreme
must be retained for physical inspection by the freight temperatures.
JOHNSON CONTROLS 3
FORM 115.24-NOM11 (0121)
During and after installation, special care must be taken TYPICAL CEILING INSTALLATION
to prevent foreign material such as paint, plaster, and
drywall dust from being deposited in the drain pan or
on the motor or blower wheels. Failure to do so may
have serious adverse effects on unit operation and in
the case of the motor and blower assembly, may result A
in immediate or premature failure. All manufacturers’
warranties are void if foreign material is allowed to be
deposited on the motor or blower wheels of any unit.
Some units and/or job conditions may require some form
of temporary covering during construction.
4 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
DRAIN PAN
Standard drain pans are externally insulated, single wall
galvanized steel and can be equipped with a secondary
drain connection. The FH drain pan is easily removable
for cleaning. See illustration below. Auxiliary drip pan
to catch condensed moisture from valves and piping
must be sloped toward the drain pan.
COILS
All fan coils are available in 2 or 4 pipe configurations.
Heating coils are available in reheat or preheat position.
Heating and cooling coils are available with right, left
or opposite side connections.
JOHNSON CONTROLS 5
FORM 115.24-NOM11 (0121)
COOLING/HEATING MEDIUM CONNECTIONS If coil and valve package connections are to be made
Toxic residues and loose particles with “sweat” or solder joint, care should be taken to
assure that no components in the valve package are
resulting from manufacturing and
subjected to a high temperature which may damage seals
field piping techniques such as joint or other materials. Many two-position electric control
compounds, soldering flux, and metal valves, depending on valve operation, are provided with
shavings may be present in the unit a manual-opening lever. This lever should be placed
and the piping system. Not for use with in the “open” position during all soldering or brazing
domestic or potable water systems. operations. Valve bodies should be wrapped with a wet
rag to help dissipate heat encountered during brazing.
Submittals and Product Catalogs detailing unit operation,
controls, and connections should be thoroughly If the valve package connection at the coil is made with
reviewed BEFORE beginning the connection of the a union, the coil side of the union must be prevented
various cooling and/or heating mediums to the unit. from twisting (“backed up”) during tightening to prevent
damage to the coil tubing. Over-tightening must be
All accessory valve packages should be installed as avoided to prevent distorting the union seal surface
required, and all service valves should be checked for and destroying the union. Due to the diversity of valve
proper operation. To prevent condensation accumulation packages for this product, install the valve packages with
and runoff, chilled water valve packages must be no leaks or interference between components during
insulated, or preferably, utilize a factory-provided operation and maintenance. In the case of field installed
auxiliary drip tray. valves and piping, the chilled water valve cluster (or
metering device on DX units) should be installed in
Before brazing or sweating valve such a way that any dripping or sweating is contained
packages and their components into in the auxiliary drain pan or other device. Valves and
place, it is critical to pre-check all TXV’s should be secured or supported to avoid damage
valve package clearances in relation to coil headers or distributor tubes. All valves, pipes,
to the auxiliary drain pan. If the and components must be sufficiently supported to ensure
auxiliary drain pan cannot be properly structural integrity and proper operation of the unit.
affixed to the auxiliary drain pan
After the connections are completed, the system should
support bracket, adjust valve package then be tested for leaks. Since some components are not
component angles until proper designed to hold pressure with a gas, hydronic systems
clearance is achieved. should be tested with water.
6 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
Figure 3b
JOHNSON CONTROLS 7
FORM 115.24-NOM11 (0121)
8 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
10 1/2"
264
7 [178]
10 1/2 [267]
FINISHED
CEILING LINE SCREW THE TELESCOPING PANEL TO
AIR
SHIM AS
REQUIRED
NOTE:
1. All dimensions are inches [millimeters]. All dimensions
TABLE 1: TELESCOPING BOTTOM±1/4"PANEL [6mm].WEIGHTS
Metric values(LBS./KG)
are soft conversion.
2. All drawings subject to change without prior notice.
DESCRIPTION 3. Left hand unit shown, right hand unitUNIT SIZE
opposite.
02 03
4. Mounting hardware04not provided.06 Mounting holes 08are 09 10 12
Telescoping bottom panel 10 [5] 11 [5] 12 [5] 14 [6] 16 [7] 17 [8] 20 [9] 21 [10]
located.
5. Remove solid and louvered bottom panels before mounting
frame assembly.
6. Frame assembly must be installed flat and square. Failure
to do so may result in poor bottom panel fit and improper
airflow pattern. Shim frame to support as required.
7. Telescoping skirt assembly must be field adjusted to
assure close fit to louvered bottom panel.
8. Portions of the inlet louver not directly below unit inlet
may require covering in the field on applications where
infiltration of ceiling plenum air into space is undesired.
JOHNSON CONTROLS 9
FORM 115.24-NOM11 (0121)
10 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
CORNER PANELS
SHOWN ROTATED 90°
UNIT
INSTALLED
0"
CORNER PANELS ROTATE REQUIRED CLEARANCE
ABOUT PIVOT POINT ABOVE UNIT
HALF
OPENED
FULLY
OPENED
JOHNSON CONTROLS 11
FORM 115.24-NOM11 (0121)
CORNER PANELS
SHOWN LIFTED AND
ROTATED 5°
ABIDE BY APPLICABLE
UNIT CODES AND STANDARDS
INSTALLED REGUARDING ACCESS
FOR ELECTRICAL OR
PLUMBING COMPONENTS
HALF
OPENED
FULLY
OPENED
12 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
22"
559
22"
559
TOP VIEW
TOP VIEW
OPTIONAL
SIDE ACCESS 8 1/2"
216
OPTIONAL AUXILIARY
DRIP PAN
8 1/2"
R10 1/2"
216
264
OPTIONAL AUXILIRY
CONTROL ENCLOSURE 10 1/2"
DRIP PAN
SEE NOTE 5
FRONT VIEW 267
FRONT VIEW AIR FILTER CLEARANCE
NOTES:
1. All chilledHORIZONTAL,
water piping thatLOW PROFILE
projects PLENUM
beyond the ANDpan
condensate FREE RETURN
or the optional auxiliary drip pan
must be field insulated by others.
2. Auxiliary drip pan shown above is optional, and is mounted on the outlet side of the drain pan.
NOTES:
3. Drain pan is installed with the outlet tube(s) on cooling coil connection end of coil on 4-pipe units with
1. All chilled water piping that projects beyond the condensate pan or the optional auxiliary drip pan
optional opposite end connection.
must be field insulated by others.
4. Dimensions shown on this drawing apply to standard CW and HW valve packages. Refer to the
2. Auxiliary drip pan shown above is optional, and is mounted on the outlet side of the drain pan.
Piping Package Catalog for valve package code details. Contact factory for details on valve packages
3. Drain pan is installed with the outlet tube(s) on cooling coil connection end of coil on 4-pipe units with
using non-standard or customer furnished components.
optional opposite end connection.
5. Provide sufficient clearance to access electrical components and comply with all applicable codes and
4. Dimensions shown on this drawing apply to standard CW and HW valve packages. Refer to the
ordinances.
Piping Package Catalog for valve package code details. Contact factory for details on valve packages
using non-standard or customer furnished components.
5. Provide sufficient clearance to access electrical components and comply with all applicable codes and
ordinances.
JOHNSON CONTROLS 13
FORM 115.24-NOM11 (0121)
14 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
NOTES:
1. Motor electrical data is nameplate data.
2. Watts are based on an FHP with PSC motor, 3 row coil, 12FPI, 1" throwaway filter, 0.05" ESP at 115V.
3. PSC motors are not available in 208-277V on SZ02 and SZ03.
4. Motor data is subject to change and should not be used for submittal purposes. Refer to Web-Select submittal for actual ratings.
JOHNSON CONTROLS 15
FORM 115.24-NOM11 (0121)
TABLE 3: EC MOTORS
AMPS1,3
2
UNIT FAN EC MOTOR # OF WATTS 115 VOLTS 208/230 VOLTS 277 VOLTS
SIZE SPEED HP (QTY) FANS (STD/HS) 3-SPEED 3-SPEED 3-SPEED
2-10VDC 2-10VDC 2-10VDC
(STD/HS) (STD/HS) (STD/HS)
High 32 / 45
02 Medium (1) 1/4 1 21 / 36 0.7 / 1.0 0.9 0.5 / 0.6 0.5 0.4 / 0.5 0.5
Low 14 / 26
High 35 / 59
03 Medium (1) 1/4 1 23 / 43 1.0 / 1.5 1.1 0.6 / 0.9 0.7 0.5 / 0.8 0.6
Low 16 / 33
High 50 / 75
04 Medium (1) 1/4 2 33 / 56 1.5 / 1.8 1.2 0.9 / 1.1 0.8 0.8 / 0.9 0.6
Low 21 / 41
High 104 / 132
06 Medium (1) 1/4 2 62 / 89 2.6 / 3.1 2.0 1.6 / 1.9 1.2 1.3 / 1.6 1.0
Low 36 / 62
High 91 / 122
08 Medium (1) 1/4 2 54 / 90 2.3 / 2.9 2.0 1.4 / 1.7 1.2 1.2 / 1.5 1.0
Low 31 / 62
High 119 / 182
09 Medium (1) 1/4 2 72 / 116 3.7 / 4.5 2.7 2.3 / 2.7 1.6 1.9 / 2.3 1.4
Low 39 / 77
High 142 / 207
10 Medium (2) 1/4 4 91 / 139 3.9 / 5.1 3.1 2.3 / 3.1 1.9 2.0 / 2.6 1.6
Low 54 / 104
High 143 / 209
12 Medium (2) 1/4 4 92 / 152 3.2 / 4.5 3.5 2.0 / 2.7 2.1 1.6 / 2.3 1.8
Low 56 / 105
NOTES:
1. Motor electrical data is nameplate data.
2. Watts are based on an FHP with 3-speed EC motor, 3 row coil, 12FPI, 1" throwaway filter, 0.05" ESP at 115V.
3. For neutral conductor sizing, multiply AMPS by 1.73.
4. Motor data is subject to change and should not be used for submittal. Refer to unit submittal for actual ratings.
16 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
MOTOR/BLOWER ASSEMBLY
The type of fan operation is determined by the control
components and their method of wiring, and may vary
from unit to unit. Refer to the wiring diagram for each Figure 6a
unit for that unit’s individual operating characteristics.
Motors are permanently lubricated, PSC or EC type and
do not require field lubrication.
Figure 6b
Figure 5a
Figure 6c
Figure 5b
Figure 5a-5b: Bottom panel removal Figure 6a-6c: Fan deck removal
JOHNSON CONTROLS 17
FORM 115.24-NOM11 (0121)
18 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
FILTERS, THROWAWAY to the chart on page 20 for recommended filter size for
The type of throwaway filter most commonly used on each product type and size. If the replacement filters are
fan coil units should be replaced on a regular basis. not purchased from the factory, the filters used should
The time interval between each replacement should be the same type and size as that furnished from or
be established based on regular inspection of the filter recommended by the factory. Consult the factory for
and should be recorded in the log for each unit. Refer applications using filter types other than the factory
standard or optional product.
Figure 7a Figure 7c
Figure 7b Figure 7d
JOHNSON CONTROLS 19
FORM 115.24-NOM11 (0121)
DRAIN
The drain should be checked before initial start-up and Should the growth of algae and/or bacteria be a
at the beginning of each cooling season to assure that concern, consult an air conditioning and refrigeration
the lines are clear. If it is clogged, steps should be taken supply organization familiar with local conditions for
to clear the debris so that condensate will flow easily. chemicals available to control these agents. If cleaners
are used, they should be compatible with the materials
Periodic checks of the drain should be made during the of construction for the coil, drain pan, and condensate
cooling season to maintain a free flowing condensate. pump (if applicable).
NOTES:
1. Face and free areas are in square feet [square meters].
2. Filter sizes are in inches [millimeters].
3. Free area of Johnson Controls Model FHX and
Telescoping Bottom Panel return grilles.
4. Free area of Johnson Controls Model FHX supply grille
and minimum free area allowable for a supply grille
supplied by others.
SAFETY WARNING
Risk of electric shock. Make certain
that the entire power supply to the
unit/system is disconnected before
attempting to install, service or remove
this component.
20 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
JOHNSON CONTROLS 21
FORM 115.24-NOM11 (0121)
General information
This accessory is a differential pressure switch with Assembly
a normally-open (NO) dry contact that is factory The differential air pressure switch is mounted inside
calibrated to close at a differential pressure of 0.15 the unit with double sided tape behind the filter retention
inches of water or greater. The switch measures the tab. (See figure 12a). Instructions for commissioning or
pressure differential between the unit’s fan section and replacing the differential air pressure switch:
the environmental pressure outside the unit. When the
filter is sufficiently clogged or dirty, differential pressure a. Disconnect main power on the unit.
will rise and the switch will close. b. Secure differential air pressure switch on the filter
retention tab using double sided tape. Position
Technical specifications the pressure port (marked with “+”) outside the
chassis exposed to the environment. The vacuum
Electrical port should extend inside the chassis and be open
Initial resistance <500mW to the unit’s fan section. (See figure 12b.)
3.15ma @ 125VAC c. Wire the NO relay using .187 quick connectors.
Rating d. Verify all connections before reconnecting main
10-20ma @ 5-24VDC
power.
Adjustable set point ranges in H2O
Ranges Min. Max. Proof
DISCHARGE AIR SENSOR
In H2O 0.10 0.50 5.0
Functional
Diaphragm vertical, barbed
Operating positing
fittings horizontal
-40 °F to 140 °F
Operating temp.
(-40 °C to 60 °C)
Installation
22 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
Electrical ratings
WARNING: Do not exceed the
maximum wattage, ratings, or
published operating conditions as
noted below.
Replacement instructions
Figure 13
JOHNSON CONTROLS 23
FORM 115.24-NOM11 (0121)
UNIT SIZE
COMPONENT
02 03 04 06 08 09 10 12
FHF BASE UNIT 22 [10] 25 [12] 33 [15] 43 [20] 53 [24] 60 [27] 74 [34] 83 [38]
FHP BASE UNIT 24 [11] 28 [13] 36 [16] 47 [21] 58 [26] 65 [30] 81 [37] 91 [41]
FHX BASE UNIT 56 [25] 63 [29] 75 [34] 92 [42] 108 [49] 118 [54] 141 [64] 158 [72]
1 ROW - DRY 6 [3] 7 [3] 8 [4] 10 [4] 11 [5] 13 [6] 15 [7] 17 [8]
1 ROW - WET 8 [4] 9 [4] 10 [4] 12 [5] 13 [6] 15 [7] 17 [8] 19 [9]
2 ROW - DRY 7 [3] 8 [4] 10 [4] 12 [5] 14 [6] 16 [7] 19 [9] 22 [10]
2 ROW - WET 9 [4] 10 [5] 12 [5] 14 [6] 17 [8] 19 [8] 23 [10] 27 [12]
3 ROW - DRY 8 [4] 10 [4] 12 [5] 14 [6] 17 [8] 19 [9] 23 [10] 26 [12]
COIL 3 ROW - WET 10 [5] 12 [5] 15 [7] 17 [8] 21 [10] 23 [10] 28 [13] 32 [14]
ROWS 4 ROW - DRY 9 [4] 11 [5] 13 [6] 17 [8] 20 [9] 22 [10] 27 [12] 30 [14]
4 ROW - WET 13 [6] 15 [7] 18 [8] 22 [10] 26 [12] 28 [13] 34 [15] 38 [17]
5 ROW - DRY 11 [5] 13 [6] 15 [7] 19 [9] 23 [10] 25 [11] 30 [14] 35 [16]
5 ROW - WET 17 [8] 19 [8] 22 [10] 26 [12] 31 [14] 33 [15] 39 [18] 45 [20]
6 ROW - DRY 12 [5] 14 [6] 17 [8] 21 [10] 26 [12] 28 [13] 34 [16] 39 [18]
6 ROW - WET 19 [9] 21 [10] 25 [11] 29 [13] 36 [16] 38 [17] 45 [21] 51 [23]
24 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
Ensure float switch assembly is firmly secured to the 1. Disconnect power to unit at main panel.
bracket. Ensure top of float is below rim of pan. Switch 2. Clip switch bracket onto side of pan at low end
will trip when the water level reaches a point even with and press firmly into place ensuring switch wires
top of float when float is in down position. Sensitivity are positioned up ensure float moves freely.
may be adjusted by threading switch assembly 3. Secure bracket into side of pan using self-tapping
downward out of bracket if necessary. sheet metal screw through upper hole in bracket.
4. Ensure float switch assembly is firmly secured
Test switch by lifting float with unit on. Unit should to bracket. Ensure top of float is below rim of
stop running if switch is correctly wired. Test switch pan. Switch will trip when water level reaches
sensitivity by filling pan and confirm switch stops unit a point even with top of float (when float is in
before pan overflows. down position). Sensitivity may be adjusted by
threading switch assembly downward out of
Supplier’s install instructions bracket if necessary.
5. Ensure wiring matches the wiring diagram
provided with the unit.
6. Test switch by lifting float with unit on. Unit
should stop running if switch is correctly wired.
7. Test switch sensitivity. Fill pan and confirm that
switch stops unit before pan overflows.
8. Place warning sticker on air handler or condenser
unit.
JOHNSON CONTROLS 25
FORM 115.24-NOM11 (0121)
REPLACEMENT PARTS
Factory replacement parts should be used wherever On warranty replacements, in addition to the information
possible to maintain the unit performance and previously listed, the project CO # that appears on
operating characteristics and the testing agency listings. the unit nameplate, is required. Contact local Sales
Replacement parts may be purchased through the local Representative and refr to warranty policy.
Sales Representative.
All equipment and components sold through the Parts
Contact the local Sales Representative before attempting Department are warranted under the same conditions as
any unit modifications. Any modifications not authorized the standard manufacturer’s warranty with the exception
by the factory could result in personnel injury and that the warranty period is 12 months.
damage to the unit and could void all factory warranties
and regulatory listings.
26 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
COOLING/HEATING CONNECTIONS
□ Protect Valve Package Components From Heat □ Mount valve packages
□ Connect Field Piping To Unit □ Pressure test all piping for leaks
□ Install Drain Line & Traps As Required □ Insulate all piping as required
□ Install Condensate Pan under Piping as Required
DUCTWORK CONNECTIONS
□ Install Ductwork, Fittings & Grilles As Required □ Proper supply & return grille type & size used
□ Control Outside Air For Freeze Protection □ Insulate all ductwork as required
ELECTRICAL CONNECTIONS
□ Refer to unit wiring diagram □ Connect incoming power service or services
□ All field wiring in code compliance
UNIT STARTUP
□ General visual unit & system inspection □ Record electrical supply voltage
□ Record ambient temperature □ Check all wiring for secure connections
□ Close all unit isolation valves □ Flush water systems
□ Fill systems with water/refrigerant □ Vent water systems as required
□ All ductwork & grilles in place □ All unit panels & filters in place
□ Start fans, etc. □ Check for overload condition of all units
□ Check all ductwork & units for air leaks □ Balance air systems as required
□ Record all final settings for future use □ Check piping & ductwork for vibration
□ Check all dampers for proper operation □ Verify proper cooling operation
□ Verify proper heating operation □ Reinstall all covers & access panels
JOHNSON CONTROLS 27
FORM 115.24-NOM11 (0121)
The Fan Relay Board assembly (FRBii) provides ensure that electric heat can only be energized when the
electronic control for the fan motor and various fan motor is operational. The assembly includes factory
connections for peripheral devices. The FRBii accepts provided harnesses to allow for faster installation and
incoming single phase power of nominal AC voltages improved troubleshooting by the end user.
120, 208, 240 and 277. The assembly includes a multi-
tap transformer (30VA or 50VA) that steps each of these The FRBii allows for peripheral devices (e.g., thermostat
primary voltages to 24 VAC. The assembly allows for controllers, electric heat relays, water valve actuators,
the control of a three speed fan motor, including a relay condensate drain pan float switches, air dampers) to be
for control of the neutral voltage signal path. connected by either the OEM or by the installer. The fan
relay board also includes a fuse on the secondary side
The FRBii can be connected to an external device (e.g., of the transformer to protect against incorrect wiring of
thermostat, controller, 3-speed switch) to control the external components, shorting the transformer leads.
three fan speeds. The FRBii includes logic to detect
when multiple speeds are commanded simultaneously The signals in the screw terminal block (TB1) and
and block all but the highest of the commanded speeds 18-pin black connector (J1) have a nominal voltage of
from being sent to the motor windings. A signal to 24VAC. These signals are properly insulated from line
call for electric heat from an external controller will voltage present on the assembly (J2-J5).
verify that a fan speed is selected before providing the
command signal to the external electric heat control to
28 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
INSTALLATION
MOUNTING WIRING
Important: Do not overtighten the screws. Install the wiring so it does not cause a hazard, and is
Overtightening may strip the threads and will void protected against electrical and mechanical damage. ..
the warranty.
Risk of electric shock
Using #8-3/4" screws (quantity six), install the assembly Ground the FRBii according to local,
using the provided standoffs. national, and regional regulations.
Failure to ground the FRBii may
Risk of Electric Shock result in electric shock and severe
Disconnect or isolate all power supplies personal injury or death.
before making electrical connections.
More than one disconnection or Ground the assembly from the EARTH terminal (W2)
isolation may be required to completely to the enclosure.
de-energize equipment. Contact with
components carrying hazardous Ratings
voltage can cause electric shock and 30VA – PC-01-0134
may result in severe personal injury Model(s)
PK-FCU030-0 (25-3043-7)
JOHNSON CONTROLS 29
FORM 115.24-NOM11 (0121)
30 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
JOHNSON CONTROLS 31
FORM 115.24-NOM11 (0121)
Tools needed for installation/troubleshooting: Fuse: A fuse is included on the secondary side of the
• Digital multimeter capable of measuring 30 volts transformer to protect the transformer from incorrect
AC wiring of thermostat, controller, etc. that shorts the
• Insulated 1/8" flat bladed screwdriver 24VAC and COM. The fuse is a fast-acting glass body
• Fuse puller (optional) cylindrical fuse (5x20mm). If tripped, replace the fuse
• Mini hook test clips for multimeter (optional) by removing the tripped fuse with fuse pullers and
replace using one of the below listed fuses.
HEAT Output – The HEAT output connects to an DAMP Output – The DAMP output connects to a
electric heat contactor or relay. This output represents motorized damper actuator used to control airflow
the command signal from the thermostat or controller from an external source. This output provides 24VAC
on the W1 input. The output is interlocked with the fan to energize the damper actuator. This output is
relays to ensure that a fan speed is commanded when interlocked with the fan relays to ensure that a fan speed
electric heat is requested. is commanded before energizing the damper actuator.
32 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
JOHNSON CONTROLS 33
FORM 115.24-NOM11 (0121)
34 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
Use ohmmeter to verify that ground wire has continuity To check low voltage wire harnesses:
from S1 to enclosure case. • Remove power from the unit. Unplug low voltage
harness J1 connector and disconnect connections
To check incoming power wire harness: at other end of J1 harness.
• Refer to wiring diagram. • Use ohmmeter to check continuity for each
• Remove power from the unit. Unplug power conductor, then reconnect harness to J1 connector
harness J2 or J3 connector. and to other connections.
• Unplug power wires from connections (line block,
disconnect switch, toggle switch or fuse(s)) in Before reconnecting power to unit, verify all harnesses
electrical enclosure. Verify continuity of wires, then are connected per diagram.
reconnect to J2 or J3 connector.
Use caution when inserting meter probe into plug.
To check motor harness: Excess force will damage contacts.
• Refer to wiring diagram.
• Remove power from the unit. Unplug motor harness
J4 and/or J5 connector.
• Unplug motor harness from motor connection or
PWM board (depending on type of motor). Verify
continuity of wires, then reconnect to J4 or J5
connector and to motor or PWM board.
JOHNSON CONTROLS 35
FORM 115.24-NOM11 (0121)
36 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
JOHNSON CONTROLS 37
FORM 115.24-NOM11 (0121)
38 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
Voltage or ground loss at motor Verify proper voltage and ground at motor.
Clear blockage. Verify blower rotates freely with motor
Blower blocked
disconnected.
Verify operation of thermostat or controller. If 24v unit,
Loss of fan speed command. verify fan speed command at relay board. Refer to fan
relay board troubleshooting guide.
Use amp meter to verify motor amps. Disconnect power
Motor overloaded to unit. Verify motor rotates freely by hand with blower
Fan motor starts disconnected. If not, replace motor.
but stops. [Psc Open ductwork Verify ducts sealed properly.
motor] Verify dampers, if present, are not closed. Verify there
Motor overheated due to lack are no obstructions in the discharge ductwork and/or at
of airflow the plenum opening. Verify filter is not dirty and does not
obstruct airflow.
Verify proper voltage and ground at motor power
Voltage or ground loss at motor
terminals.
Motor fault or end of life. Replace motor.
Reseat connector and verify operation. Disconnect motor
Faulty motor harness
harnesses and verify continuity. Replace motor harness.
Motor mounting bolts loose Tighten motor mounting bolts.
Motor shaft bent Replace motor.
Disconnect power from unit. Verify motor rotates freely
Motor bearing end of life
by hand with blower disconnected.
Verify static pressure per system design. Use amp meter
to verify motor amps. Disconnect power to unit. Verify
Motor overloaded
motor rotates freely with power disconnected. If not,
replace motor.
Motor end of life Use amp meter to verify motor amps. Replace motor.
Dirty filters Verify filters. Replace as needed.
Verify blower is unobstructed. Verify no duct obstruction.
Excessive fan Obstructed airflow
Verify dampers are full open.
noise
Verify ductwork is installed per smacna and ashrae
Improper duct connections
guidelines.
Static pressure too low Verify static pressure per system design.
Improperly balanced system Verify airflow through connected ductwork
Fan wheel rubbing on fan
Remover power from unit. Align wheel in housing.
housing
Remover power from unit. Align wheel in housing and
Loose fan wheel
tighten.
Inspect fan wheel to verify fins are not bent. Replace
Damaged fan wheel
blower as needed.
Imbalanced fan wheel Inspect fan wheel. Replace as needed.
JOHNSON CONTROLS 39
FORM 115.24-NOM11 (0121)
40 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
Loose motor wiring Reseat motor connector. Tighten all motor connections.
Loose control wiring Verify and/or tighten all control connections.
Verify operation of any control device such as drain pan
Intermittent control device float switch, freeze stat, thermostat, etc. When in doubt,
jumper out and verify fan operation.
[EC motor] Fan speed Refer to Fan Calibration curve on unit. Adjust speed on
adjustment outside operating PWM Controller to value that will allow motor to start.
range See instructions for Adjusting EC Motor Speed.
Fan motor
surges [EC [EC motor] Faulty PWM Verify PWM signal at motor connector. Refer to PWM
motor] signal board IOM.
Blower Set Screw loose Tighten Screw onto motor shaft.
Verify proper ductwork to unit. Verify ductwork is
Improper duct connections installed per SMACNA and ASHRAE guidelines.
Incorrectly sized ducts can cause motor surging.
Verify dampers, if present, are not closed. Verify there
ESP (external static pressure) are no obstructions in the discharge ductwork and/or at
too high the plenum opening. Verify filter is not dirty and does not
obstruct airflow.
Lack of required external static External static pressure not as designed. Adjust external
pressure static pressure to design pressure
[24V units] Three speed switch Verify three speed switch, if present, is set to desired
in wrong position. speed.
Poor voltage quality Verify input voltage within acceptable parameters.
Refer to Fan Calibration curve on unit. Adjust speed on
Speed adjustment outside fan
PWM Controller to value that will allow motor to start.
operating range
See instructions for Adjusting EC Motor Speed.
Poor Airflow Erratic speed command (in Verify 2-10V analog signal at Remote Control Input
Performance Proportional Control mode) terminals.
[ECM motor] Verify ductwork is installed per SMACNA and ASHRAE
Improper duct connections
guidelines.
Verify no obstructions. Verify all dampers are full open
Duct obstruction
while fan operates.
Improperly set dampers Verify proper inlet air to unit.
Check cleanliness of coil. Dirty coil fins will restrict
Dirty coil
airflow.
Dirty filters Check for dirty or blocked filters. Replace as needed.
Damaged or blocked blower Verify blower rotates freely. Clear blockage.
JOHNSON CONTROLS 41
FORM 115.24-NOM11 (0121)
Voltage or ground loss at motor Verify proper voltage and ground at motor.
Clear blockage. Verify blower rotates freely with motor
Blower blocked
disconnected.
Verify operation of thermostat or controller. Verify fan
Loss of fan speed command. speed command at relay board. Refer to Fan Relay board
troubleshooting guide.
Use amp meter to verify motor amps. Disconnect power
from unit. Verify motor rotates freely by hand with blower
Motor overloaded disconnected. If not, replace motor. Note: EC motors
may not rotate freely as the rotor aligns with the stator
Fan motor starts magnets.
but stops. [EC Open ductwork Verify ducts sealed properly.
motor] Verify dampers, if present, are not closed. Verify there
Motor overheated due to lack are no obstructions in the discharge ductwork and/or at
of airflow the plenum opening. Verify filter is not dirty and does not
obstruct airflow.
Verify proper voltage and ground at motor power
Voltage or ground loss at motor
terminals.
Refer to PWM board status LEDs. Verify all connections.
PWM board error or faulted
Cycle power to the board. Refer to PWM board IOM.
Motor fault or end of life. Replace motor.
Reseat connector and verify operation. Disconnect motor
Faulty motor harness
harnesses and verify continuity. Replace motor harness.
Refer to PWM board status LEDs. Verify all connections.
PWM board error or faulted
Cycle power to the board. Refer to PWM board IOM.
Verify wiring. If Fan Relay board present, verify all
Improper wiring connections
jumpers installed.
Unplug harness and re-install, making sure plugs are fully
EC wiring harness damaged or
seated. See section on checking wire harnesses, below.
improperly seated
Replace harness if damaged.
EC motor
EC motors may run at idle speed if they lose PWM signal
speed cannot be No control signal
while enabled.
adjusted
Verify PWM signal at motor connector. Refer to PWM
board IOM.
Verify dampers, if present, are not closed. Verify there
ESP (external static pressure) are no obstructions in the discharge ductwork and/or at
too high the plenum opening. Verify filter is not dirty and does not
obstruct airflow.
Motor Control failure Replace motor.
EC motor runs
in reverse,
doesn’t respond Motor Control failure Replace motor.
to speed
adjustment
42 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
JOHNSON CONTROLS 43
FORM 115.24-NOM11 (0121)
44 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
JOHNSON CONTROLS 45
FORM 115.24-NOM11 (0121)
Electric Heat Verify control voltage is at magnetic electric heat contactor control
[Solid state relay] electric heat safety
will not operate coil terminals. If power is present at coil but contactor is not
contactor fault
(cont’d) actuated, replace contactor.
CAUTION: Verify heating demand (control voltage) is at solid state relay
[Solid state relay] Solid State Relay
UNIT MAY BE control terminals. If power is present but relay is not actuated,
fault
replace relay.
EXTREMELY
HOT. TAKE
GREAT Verify DC control signal is present at controller input terminals.
[Solid state relay proportional
CARE WHEN Verify that output control voltage to solid state relay varies with
control] Heat controller fault
TROUBLE- variation in input. Replace controller if not.
SHOOTING.
Verify that thermostat or control command signal is not dropping
Loss of demand.
out. Verify voltage is present at unit during demand for heat.
Verify that signal from thermostat or control is not dropping out.
Electric Heat [24V units] Loss of demand. During demand, there needs to be 24V on 'W1' terminal of Fan
Relay board.
shuts down
unexpectedly Verify no loss of demand to unit. Verify that voltage exists on
heater contactor during demand for heat. If demand reaches unit
but not contactor, primary limit is tripped. The primary limit
CAUTION: Primary limit switch tripped.
switch(es) will auto-reset once the unit cools down. If unit is hot,
UNIT MAY BE wait for heater to cool down. This may take up to an hour. If limit
EXTREMELY trips again, verify heater is not overheating.
HOT. TAKE The secondary limit may be manually reset. If unit is hot, wat
GREAT Secondary limit switch tripped. for the heater to cool down. This may take up to an hour. Reset
CARE WHEN switch(es). If limits trip again, verify heater is not overheating.
TROUBLE- Loss of fan speed command. Heater will not operate if fan is not enabled.
SHOOTING. Verify operation of any control device such as drain pan float
Intermittent control device switch, freeze stat, thermostat, etc. When in doubt, jumper out
and verify fan operation.
Loose wiring Verify and/or tighten all wiring connections.
Verify that airflow is sufficient to provide a minimum of 70 CFM
Insufficient airflow
per kW of electric heat.
Electric heaters require even airflow across the face of the heater
Improper duct connections in order to operate properly. Verify ductwork is installed per
SMACNA and ASHRAE guidelines.
Electric heater is
Verify no obstructions. Verify all dampers are full open while
overheating Obstructed ductwork
fan operates.
Intermittent fan Verify fan motor runs continuously, providing even airflow.
CAUTION:
Incorrect voltage applied. Verify proper voltage to unit per unit label.
UNIT MAY BE
EXTREMELY Verify wiring to schematic. If Fan Coil Relay board present, verify
Improper wiring connections all jumpers and harnesses installed. Refer to Fan Coil Relay Board
HOT. TAKE
Troubleshooting Guide.
GREAT
CARE WHEN Remove power from unit. Access the heater compartment. Verify
Damaged heater elements
heating elements are undamaged.
TROUBLE-
SHOOTING. Remove thermostat or control command signal. Verify no control
Shorted magnetic heater contactor voltage to heater contactor. If electric heat continues to operate
and all wiring has been verified, replace contactor.
Remove thermostat or control command signal. Verify no control
[Solid state relay] Shorted solid
voltage to solid state relay. If electric heat continues to operate
state relay
and all wiring has been verified, replace solid state relay.
46 JOHNSON CONTROLS
FORM 115.24-NOM11 (0121)
JOHNSON CONTROLS 47
Johnson Controls is a mark and/or registered mark. Unauthorized use is strictly prohibited.