Technical data sheet                                                            BF24-TN-ST
Spring-return actuator, combined with
thermoelectric tripping device BAT (72°C), for
fire and smoke dampers 90° in ventilation
and air-conditioning systems, with connection
plugs for simple integration in control and
monitoring systems or bus networks via
communication and power supply units
• Torque motor 18 Nm / 12 Nm
• Nominal voltage AC/DC 24 V
• Control Open/close
• Mechanical interface Form fit 12x12 mm,
non-continuous hollow shaft
 Technical data
                                Electrical data    Nominal voltage                                AC/DC 24 V
                                                   Nominal voltage frequency                      50/60 Hz
                                                   Nominal voltage range                          AC 19.2...28.8 V / DC 21.6...28.8 V
                                                   Power consumption in operation                 7W
                                                   Power consumption in rest position             2W
                                                   Power consumption for wire sizing              10 VA
                                                   Power consumption for wire sizing note         Imax 8.3 A @ 5 ms
                                                   Auxiliary switch                               2 x SPDT
                                                   Switching capacity auxiliary switch            1 mA...3 A (0.5 A inductive), DC 5 V...AC 250 V
                                                   Switching points auxiliary switch              5° / 80°
                                                   Connection supply / control                    Cable with connector plug 1 m, 2 x 0.75 mm²
                                                                                                  (halogen-free)
                                                   Connection auxiliary switch                    Cable with connector plug 1 m, 6 x 0.75 mm²
                                                                                                  (halogen-free)
                                                   Connection plug                                Supply / control: 3-pole plug, suitable for
                                                                                                  communication and power supply units (see
                                                                                                  "Accessories")
                                                                                                  Auxiliary switch: 6-pole plug, suitable for
                                                                                                  communication and power supply units (see
                                                                                                  "Accessories")
                                                   Cable length thermoelectric tripping device    1 m
                              Functional data      Torque motor                                   18 Nm
                                                   Torque fail-safe                               12 Nm
                                                   Direction of motion motor                      selectable by mounting L/R
                                                   Manual override                                with position stop
                                                   Angle of rotation                              Max. 95°
                                                   Angle of rotation note                         incl. 5° initial spring tension
                                                   Running time motor                             <120 s / 90°
                                                   Running time fail-safe                         16 s @ 20°C
                                                   Sound power level, motor                       45 dB(A)
                                                   Sound power level, fail-safe                   63 dB(A)
                                                   Mechanical interface                           Form fit 12x12 mm, non-continuous hollow
                                                                                                  shaft
                                                   Position indication                            Mechanical, with pointer
                                                   Service life                                   Min. 60'000 safety positions
                                                   Probe length                                   65 mm
                                   Safety data     Response temperature thermal fuse              Duct outside temperature 72°C
                                                                                                  Duct inside temperature 72°C (colour black)
                                                   Protection class IEC/EN                        III, Safety Extra-Low Voltage (SELV)
                                                   Protection class auxiliary switch IEC/EN       II, reinforced insulation
www.belimo.com                                    BF24-TN-ST • en-gb • 2023-03-03 • Subject to change                                       1/5
                                                    Technical data sheet                                                            BF24-TN-ST
                                   Safety data    Degree of protection IEC/EN                      IP54
                                                                                                   IP protection in all mounting positions
                                                  EMC                                              CE according to 2014/30/EU
                                                  Low voltage directive                            CE according to 2014/35/EU
                                                  Certification IEC/EN                             IEC/EN 60730-1 and IEC/EN 60730-2-14
                                                  Type of action                                   Type 1.AA.B
                                                  Rated impulse voltage supply / control           0.8 kV
                                                  Pollution degree                                 3
                                                  Ambient humidity                                 Max. 95% RH, non-condensing
                                                  Ambient temperature normal operation             -30...50°C
                                                  Ambient temperature safety operation             The safety position will be attained up to max.
                                                                                                   75°C
                                                  Storage temperature                              -40...50°C [-40...122°F]
                                                  Servicing                                        maintenance-free
                                       Weight     Weight                                           2.8 kg
                                                           Safety notes
                                                 • The device must not be used outside the specified field of application, especially not in aircraft
                                                   or in any other airborne means of transport.
                                                 • The actuator is adapted and installed on the fire and smoke damper by the damper
                                                   manufacturer. For this reason, the actuator is only supplied directly to safety damper
                                                   manufacturers. The manufacturer then bears full responsibility for the proper functioning of
                                                   the damper.
                                                 • The two switches integrated in the actuator are to be operated either on power supply voltage
                                                   or at safety extra-low voltage. The combination power supply voltage/safety extra-low voltage
                                                   is not permitted.
                                                 • The device may only be opened at the manufacturer's site. It does not contain any parts that
                                                   can be replaced or repaired by the user.
                                                 • The device contains electrical and electronic components and must not be disposed of as
                                                   household refuse. All locally valid regulations and requirements must be observed.
 Product features
                           Mode of operation      The actuator moves the damper to the operating position at the same time as tensioning the
                                                  return spring. The damper is turned back to the safety position by spring energy when the
                                                  supply voltage is interrupted.
                Thermoelectric tripping device    Complies with the specific requirements of the standard ISO 10294-4.
                                                  BAT: If the ambient temperature of 72°C is exceeded, the duct outside temperature fuse will
                                                  respond. If the duct inside temperature of 72°C is exceeded, then the duct inside temperature
                                                  fuse will respond. When one of the thermal fuses responds, the supply voltage is interrupted
                                                  permanently and irreversibly.
                                                  The LED is on when
                                                  - supply voltage is available
                                                  - the thermal fuses are OK and
                                                  - the test switch is not pressed.
                                                  The temperature fuse for the ambient temperature protects the actuator from overheating and
                                                  cannot be replaced. The actuator must be replaced when the duct outside temperature fuse is
                                                  triggered. The temperature fuse for the duct inside temperature can be replaced, see section
                                                  "Accessories".
                                                  The function of the system (interruption of the supply voltage) can be checked by pressing the
                                                  test button.
                                                  Note: The function of the thermal fuses and the control key is only warranted if the actuator is
                                                  connected to the supply voltage (LED on).
www.belimo.com                                   BF24-TN-ST • en-gb • 2023-03-03 • Subject to change                                         2/5
                                               Technical data sheet                                                             BF24-TN-ST
                          Manual override     Without power supply, the actuator can be operated manually and fixed in any required
                                              position. It can be unlocked manually or automatically by applying the supply voltage.
                                Signalling    Two microswitches with fixed settings are installed in the actuator for indicating the damper
                                              end positions. The electrical contacts of these microswitches are equipped with a gold/silver
                                              coating that permits integration both in circuits with low currents (mA range) and in ones with
                                              larger-sized currents (A range) in accordance with the specifications in the data sheet. It should
                                              be noted with this application however that the contacts can no longer be used in the
                                              milliampere range after larger currents have been applied to them, even if this has taken place
                                              only once.
                                              The position of the damper blade can be read off on a mechanical position indication.
                   Standards / Regulations    The design of the actuator is based on the specific requirements from the European standards:
                                              - EN 15650 Ventilation for buildings – Fire dampers
                                              - EN 1366-2 Fire resistance tests on service installations
                                              (Part 2: Fire dampers)
                                              - EN 13501-3 Fire classification of construction products and building elements
                                              (Part 3: Classification using data from fire resistance tests on products and elements used in
                                              building service installations: fire resisting ducts and fire dampers)
           Recommendation for application     The regular operational check (open/close control of the fire damper) enhances the safety of
                                              people, animals, property and the environment. Unless other requirements are stipulated – e.g.
                                              in the damper manufacturer's operating instructions – Belimo recommends the performance of
                                              a monthly operational check. Fire damper actuators from Belimo are designed in accordance
                                              with service life specifications contained in the technical data sheet for regular operational
                                              checks. Notes for regular operational checks can be found in the European Product Standard for
                                              Fire Dampers (EN 15650) under "Maintenance information".
                               Connection     The actuator is equipped with connection plugs. This allows it to be integrated into control and
                                              monitoring systems (e.g. SBS-Control) or bus networks (e.g. MP-Bus solutions) via
                                              communication and power supply units (see "Accessories").
 Parts included
                                              Hand crank
                                              Pointer
                                              Protective bag
                                              Form fit insert 12/10 mm
www.belimo.com                               BF24-TN-ST • en-gb • 2023-03-03 • Subject to change                                         3/5
                                                      Technical data sheet                                                            BF24-TN-ST
 Accessories
                           Electrical accessories    Description                                                               Type
                                                     Communication and power supply unit for fire damper actuators 24 V        BKN230-24
                                                     with connector
                                                     Communication and power supply unit for fire damper actuators 24 V        BKN230-24-C-MP
                                                     with connector
                                                     Communication and power supply unit for fire damper actuators 24 V        BKN230-24-MOD
                                                     with connector
                                                     Communication and power supply unit for fire damper actuators, Control    BSIA24-48
                                                     by pulse release
                                                     Communication and power supply unit for fire damper actuators, Control    BSIA24-48-R
                                                     by interrupt release
                                                     Auxiliary switch 2 x SPDT                                                 SN2-C7
                                                     Blanking cover for BAT (without thermal fuse for duct inside              ZBAT0
                                                     temperature), Multipack 20 pcs.
                                                     Spare tripping element for BAT, Duct inside temperature 72°C (colour      ZBAT72
                                                     black)
                                                     Spare tripping element for BAT, Duct inside temperature 72°C (colour      ZBAT72/9
                                                     black)
                                                     Spare tripping element for BAT, Duct inside temperature 95°C (colour      ZBAT95
                                                     grey)
                                                     Spare tripping element for BAT, Duct inside temperature 95°C (colour      ZBAT95/9
                                                     grey)
                                                     Spare tripping element for BAT, Duct inside temperature 120°C (colour     ZBAT120
                                                     orange)
                                                     Spare tripping element for BAT, Duct inside temperature 140°C (colour     ZBAT140
                                                     red)
                     Mechanical accessories          Description                                                               Type
                                                     Bracket for SN2-C7 for BF                                                 ZSN-BF
                                                     Adapter, for form fit 12 mm on round shaft 18 mm, L = 33 mm               ZA18-BF
                                                     Adapter, for form fit with clamp for round shaft 10...20 mm / square      ZK-BF
                                                     10...16 mm
                                                     Pointer 12x12 mm                                                          ZZ12-B
                                                     Hand crank 40 mm                                                          ZK1-B
                                                     Hand crank 70 mm                                                          ZK2-B
                                                     Protective bag with wire, Multipack 100 pcs.                              ZSD-B.1
 Electrical installation
                                                     Supply from isolating transformer.
                                                     Parallel connection of other actuators possible. Observe the performance data.
                                                     Combination of power supply voltage and safety extra-low voltage not permitted at the both
                                                     auxiliary switches.
 Wiring diagrams
 AC/DC 24 V, open/close
                                                                             Plug connection to
                                                                             communication and power
                                                                             supply units:
                                                                             Application examples for
                                                                             integration into monitoring and
                                                                             control systems or into bus
                                                                             networks can be found in the
                                                                             documentation of the connected
                                                                             communication and power
                                                                             supply unit (see "Accessories").
www.belimo.com                                      BF24-TN-ST • en-gb • 2023-03-03 • Subject to change                                      4/5
                   Technical data sheet                                BF24-TN-ST
 Dimensions
www.belimo.com   BF24-TN-ST • en-gb • 2023-03-03 • Subject to change        5/5