INVERSE TIME OVERCURRENT
AND
Types CDG11&16
The type CDG11 relay is a heavily dampea
induction disc unit with an inverse definite
minimum time/current characteristic. The relay
gives selective phase and earth fault overcurrent
protection in time graded systems to transformers,
‘a.c. machines and feeders, etc., and ensures that
a minimum number of circuit breakers are tripped
to clear a faulted section (see Application Sheet
MS/5087).
The operating coil is wound to give time/eurrent
curves of the same shape on each of seven current
taps which are selected by a plug setting bridge.
‘The highest current tap is automatically selected
when the plug is removed, so that adjustments
can be made on load without open-circuiting the
current transformer.
The relay has a high torque movement to ensure
consistent timing even under adverse conditions,
and a low burden and overshoot, Adjustment of
the time setting is made by rotating a knurled
moulded disc against a graduated time multiplier
scale,
A high set overcurrent unit (type CAG) can be
fitted in the same case to provide instantaneous
protection under maximum short circuit conditions
(see Application Sheet MS/5087).
The type CDG21 relay is either a double pole
version (with two earth fault units or two over-
current units) of the type CDG11, or a type
CDG11 with an instantaneous unit.
The type CDG31 relay is a triple pole version
(with three overcurrent units or two overcurrent
units and one earth fault unit in the centre) of the
type CDG11.
CURRENT SETTINGS
Equally Spaced Tap Ranges
10-40%, 20-80% or 50-200% of 05, 10 or
5:0 amps 50 or 60Hz adjustable in seven equal
steps.
Graded Tap Ranges
10-40%, 20-80% or 50-200% of 05, 1:0 or
8:0 amps and 30-120% or 80-220% of 5 amp
50 or 60Hz adjustable in seven unequal steps
as follows 25%, 30%, 375%, 60%, 60%
78% and 100% of top tap value.
Starting Current 103-105% of current set-
ting
EARTH FAULT RELAY
cog
-. ees
Type CDGI1 rolay
Closing Current 115%, of current setting
(117% when fitted with a mechanical operation
indicator)
Resetting Current The maximum current up
to which the disc will completely reset is $0% of
current setting
TIME SETTINGS
0-1-3 seconds at 10 times current setting or
0-30 seconds at 10 times current setting
(B.S.142:1966)
Resetting Time With the time multiplier sot
at 1.0 the resetting times of the abuve are four
seconds and nine seconds respectively.
Overshoot On removal of a current equal to
20 times current setting the overshoot times of
the above are 0.065 second and 0:04 second
respectively.OPERATING TIME IN SECS.
BURDENS
Standard (3VA nominal) —
2VA at current setting on lowest tap
3-5VA at current setting on highest tap
Alternative with lower operating torque
(1VA nominal) —
(0:75VA at current setting on lowest tap
1:3VA at current setting on highest tap
THERMAL RATING
The relay will withstand twice the setting current
continuously and 20 times the maximum setting
current for three seconds.
ACCURACY
The relay is calibrated at 60 Hz and 20°C and
falls into error class index E7-5 as given in
BS. 142:1966,
Frequency Error Less than 8% for frequency
variation of 2 cycles; the time grading of a pro-
tective system would be unaffected by this error
since all the relays would be similarly affected
3 ‘TIME-CURRENT CHARACTERISTIC
% INVERSE TIME RELAY CDGII
q 13sec.
14 v0
05} 09
08] oe
al 07
cal oe
os)
ed os
os
3}
| oz
1 or
z a 20
"MULTIPLES OF PLUG SETTING CURRENT
Curve reference s77ape2162
OPERATING TIME IN SEC.
‘Temperature Error For an overload equal to
ten times the current setting, the percentage
timing errors at +45°C and —5°C are res-
pectively:—
1-3 second relay
3.0 second relay
4% and +4%
3% and +4%
AUXILIARY UNITS AND
OPERATION INDICATORS
Shunt reinforcing or series seal in auxiliary
attracted armature units with a hand reset
operation indicator can be fitted. Relays suppli
without an auxiliary unit have a hand reset
operation indicator mechanically operated by the
disc.
Standard Coil Ratings
(shunt) auxiliary units: 30,
dic. at a nominal burden of
rated.
Voltage operated
410, 125 or 220 volts
watts continuously
TIME-CURRENT CHARACTERISTIC.
INVERSE TIME RELAY COGII
3 SEC. TO 8.5.142
re
(Curve reterones 677298206 07 :
7 8910
-TWDAMCK/CURKENT umes FON TYPE CDG AUATS
MULTILES OF PLUG SETTING CURRENT
Current operated (series) auxil
FY units:
Minimum
operating | 0-Ssecond | Coil resistance
curent in amps | __ current in ohms
(ewo taps)" | rating in amps
O4ando3s | igana 22 | 92 and 24
O2and20 | 22and 92 | 60 and 0-425
O6and2-4 | S2and188 | 0:20 and 00at
Other coil ratings can be supplied for both types:
of auxiliary unit,
Contacts One or two electrically separate
normally-open self or hand reset contacts are
fitted which will make and carry 7500VA for 0:5
second with maxima of 30 amps and 660 volts
ac.ord.c.
Relays supplied without an auxiliary unit have
‘one or two pairs of normally-open self reset
contacts which will make and carry 2500VA for
0:5 second with maxima of 10 amps and 660
volts a.c. or d.c. The two contact relay has a
modified disc/contact assembly and is designated
€DG16, CDG26 or CDG36.
A.C. Trip Circuit Where a tripping supply is
not available, a modified relay can be supplied
which trips the circuit breaker directly using
current from the line transformer. The a.¢, trip-
ping circuit incorporates a current transformer and.
an instantaneous unit which will safely control
a.c. trip coil currents up to 150 amps at 150 volts.
Applications where the trip current exceeds this
value can also be catered for.
CASES
‘The relays are supplied in drawout cases available
for flush or projecting mounting, and finished in
phenolic black as standard. These cases offer
many advantages including ease of maintenance
and testing. and are fitted with a contact which
short circuits the associated current transformer
INPEDANCEICURRENT CURVES FOR TYPE CoG meLATS
Usi0 ar ) VA 9 CYCLE MULTITRAND COM
MULTIPLES OF PLUG SETTING CURRENT
on withdrawal of the unit. A filter is fitted which
equalises the pressure inside and outside the case
without admitting dust.
Relays for use in exceptionally severe environ-
ments can be finished to B.S.2011:20/50/56
at extra cost; standard relays are finished to
B.S.2011:20/40/4 and are satisfactory for normal
tropical use.
a
A$
al
1
|
|
1
|
1
1
T erenwac er: I
ae
“ED nonuaLty e.osep cowract
=
ee NORMALLY OPEN CONTACT
Connection di
fam for ac. series tippingCASE DIMENSIONS oa
Maximum Overall Dimensions eee eee
ings of case out-
+ Relay Case Height Width Depth ichesfrrarat test
mm | in | mm | in | mm | andmountingdetails
Saari are available on
coa2t 10 ov | 233 | ot | 170 | 7a | 107 | request
coa2t 20 | ree | 422 | oi | 170 | 72 | 197
(ouble pote) | (Vert)
30 | 209 | 52 | ot | 170) 72 | 197
(vert) v
coss1
30 ox | 235 | ame | 45a | va | 197
(Horie)
“Add 2 in, (51 mm) for maximum length of 2 BA terminal studs.
: ah ts INSULATION
. The relay will withstand 2.0 kV r.ms. ac. 50 Hz
tate, for 1 minute between all live parts and earth and
° aa ape between all circuits not intended to be connected
Py Bb oda tee tegen tt sts wintna kv cms 3.
HALT Stearn 50 Hz fort minute across open contacts
pa INFORMATION REQUIRED WITH ORDER
ts Relay type
12 sae i Current setting range
Seat Current transformer secondary rating
atone Srown. Characteristic (time setting)
RGPARALLELED Burden
"nee nse ovencunnenr morecron Trip circuit (series seal in, shunt rein-
forcing or a.c.)
Trip circuit curent (series seal in)
* —— Trip circuit voltage (shunt reinforcing) 5
Operation indicator inscription if required
Auxiliary contacts (hand or self reset)
Details of instantaneous unit (CAG) if
7. required
Case mounting
Typical application and internal cireult diagram of type
(CDG31 relay with series seal in
(Our policy is one of continuous product development an the right is reserved to supply equipment wh
GEC Measurements the General Electric Company Ltd
St. Leonards Works Stafford ST17 4LX England >
Telephone: 0785 3251 Telex: 36240 Cables: Measurements Stafford Telex
th may vary slightly from that described
SOT6GOGSP Printed in England