(ec) te Measurements INVERSE TIME OVERCURRENT AND Types CDG11&16 The type CDG11 relay is a heavily dampea induction disc unit with an inverse definite minimum time/current characteristic. The relay gives selective phase and earth fault overcurrent protection in time graded systems to transformers, ‘a.c. machines and feeders, etc., and ensures that a minimum number of circuit breakers are tripped to clear a faulted section (see Application Sheet MS/5087). The operating coil is wound to give time/eurrent curves of the same shape on each of seven current taps which are selected by a plug setting bridge. ‘The highest current tap is automatically selected when the plug is removed, so that adjustments can be made on load without open-circuiting the current transformer. The relay has a high torque movement to ensure consistent timing even under adverse conditions, and a low burden and overshoot, Adjustment of the time setting is made by rotating a knurled moulded disc against a graduated time multiplier scale, A high set overcurrent unit (type CAG) can be fitted in the same case to provide instantaneous protection under maximum short circuit conditions (see Application Sheet MS/5087). The type CDG21 relay is either a double pole version (with two earth fault units or two over- current units) of the type CDG11, or a type CDG11 with an instantaneous unit. The type CDG31 relay is a triple pole version (with three overcurrent units or two overcurrent units and one earth fault unit in the centre) of the type CDG11. CURRENT SETTINGS Equally Spaced Tap Ranges 10-40%, 20-80% or 50-200% of 05, 10 or 5:0 amps 50 or 60Hz adjustable in seven equal steps. Graded Tap Ranges 10-40%, 20-80% or 50-200% of 05, 1:0 or 8:0 amps and 30-120% or 80-220% of 5 amp 50 or 60Hz adjustable in seven unequal steps as follows 25%, 30%, 375%, 60%, 60% 78% and 100% of top tap value. Starting Current 103-105% of current set- ting EARTH FAULT RELAY cog -. ees Type CDGI1 rolay Closing Current 115%, of current setting (117% when fitted with a mechanical operation indicator) Resetting Current The maximum current up to which the disc will completely reset is $0% of current setting TIME SETTINGS 0-1-3 seconds at 10 times current setting or 0-30 seconds at 10 times current setting (B.S.142:1966) Resetting Time With the time multiplier sot at 1.0 the resetting times of the abuve are four seconds and nine seconds respectively. Overshoot On removal of a current equal to 20 times current setting the overshoot times of the above are 0.065 second and 0:04 second respectively. OPERATING TIME IN SECS. BURDENS Standard (3VA nominal) — 2VA at current setting on lowest tap 3-5VA at current setting on highest tap Alternative with lower operating torque (1VA nominal) — (0:75VA at current setting on lowest tap 1:3VA at current setting on highest tap THERMAL RATING The relay will withstand twice the setting current continuously and 20 times the maximum setting current for three seconds. ACCURACY The relay is calibrated at 60 Hz and 20°C and falls into error class index E7-5 as given in BS. 142:1966, Frequency Error Less than 8% for frequency variation of 2 cycles; the time grading of a pro- tective system would be unaffected by this error since all the relays would be similarly affected 3 ‘TIME-CURRENT CHARACTERISTIC % INVERSE TIME RELAY CDGII q 13sec. 14 v0 05} 09 08] oe al 07 cal oe os) ed os os 3} | oz 1 or z a 20 "MULTIPLES OF PLUG SETTING CURRENT Curve reference s77ape2162 OPERATING TIME IN SEC. ‘Temperature Error For an overload equal to ten times the current setting, the percentage timing errors at +45°C and —5°C are res- pectively:— 1-3 second relay 3.0 second relay 4% and +4% 3% and +4% AUXILIARY UNITS AND OPERATION INDICATORS Shunt reinforcing or series seal in auxiliary attracted armature units with a hand reset operation indicator can be fitted. Relays suppli without an auxiliary unit have a hand reset operation indicator mechanically operated by the disc. Standard Coil Ratings (shunt) auxiliary units: 30, dic. at a nominal burden of rated. Voltage operated 410, 125 or 220 volts watts continuously TIME-CURRENT CHARACTERISTIC. INVERSE TIME RELAY COGII 3 SEC. TO 8.5.142 re (Curve reterones 677298206 07 : 7 8910 - TWDAMCK/CURKENT umes FON TYPE CDG AUATS MULTILES OF PLUG SETTING CURRENT Current operated (series) auxil FY units: Minimum operating | 0-Ssecond | Coil resistance curent in amps | __ current in ohms (ewo taps)" | rating in amps O4ando3s | igana 22 | 92 and 24 O2and20 | 22and 92 | 60 and 0-425 O6and2-4 | S2and188 | 0:20 and 00at Other coil ratings can be supplied for both types: of auxiliary unit, Contacts One or two electrically separate normally-open self or hand reset contacts are fitted which will make and carry 7500VA for 0:5 second with maxima of 30 amps and 660 volts ac.ord.c. Relays supplied without an auxiliary unit have ‘one or two pairs of normally-open self reset contacts which will make and carry 2500VA for 0:5 second with maxima of 10 amps and 660 volts a.c. or d.c. The two contact relay has a modified disc/contact assembly and is designated €DG16, CDG26 or CDG36. A.C. Trip Circuit Where a tripping supply is not available, a modified relay can be supplied which trips the circuit breaker directly using current from the line transformer. The a.¢, trip- ping circuit incorporates a current transformer and. an instantaneous unit which will safely control a.c. trip coil currents up to 150 amps at 150 volts. Applications where the trip current exceeds this value can also be catered for. CASES ‘The relays are supplied in drawout cases available for flush or projecting mounting, and finished in phenolic black as standard. These cases offer many advantages including ease of maintenance and testing. and are fitted with a contact which short circuits the associated current transformer INPEDANCEICURRENT CURVES FOR TYPE CoG meLATS Usi0 ar ) VA 9 CYCLE MULTITRAND COM MULTIPLES OF PLUG SETTING CURRENT on withdrawal of the unit. A filter is fitted which equalises the pressure inside and outside the case without admitting dust. Relays for use in exceptionally severe environ- ments can be finished to B.S.2011:20/50/56 at extra cost; standard relays are finished to B.S.2011:20/40/4 and are satisfactory for normal tropical use. a A$ al 1 | | 1 | 1 1 T erenwac er: I ae “ED nonuaLty e.osep cowract = ee NORMALLY OPEN CONTACT Connection di fam for ac. series tipping CASE DIMENSIONS oa Maximum Overall Dimensions eee eee ings of case out- + Relay Case Height Width Depth ichesfrrarat test mm | in | mm | in | mm | andmountingdetails Saari are available on coa2t 10 ov | 233 | ot | 170 | 7a | 107 | request coa2t 20 | ree | 422 | oi | 170 | 72 | 197 (ouble pote) | (Vert) 30 | 209 | 52 | ot | 170) 72 | 197 (vert) v coss1 30 ox | 235 | ame | 45a | va | 197 (Horie) “Add 2 in, (51 mm) for maximum length of 2 BA terminal studs. : ah ts INSULATION . The relay will withstand 2.0 kV r.ms. ac. 50 Hz tate, for 1 minute between all live parts and earth and ° aa ape between all circuits not intended to be connected Py Bb oda tee tegen tt sts wintna kv cms 3. HALT Stearn 50 Hz fort minute across open contacts pa INFORMATION REQUIRED WITH ORDER ts Relay type 12 sae i Current setting range Seat Current transformer secondary rating atone Srown. Characteristic (time setting) RGPARALLELED Burden "nee nse ovencunnenr morecron Trip circuit (series seal in, shunt rein- forcing or a.c.) Trip circuit curent (series seal in) * —— Trip circuit voltage (shunt reinforcing) 5 Operation indicator inscription if required Auxiliary contacts (hand or self reset) Details of instantaneous unit (CAG) if 7. required Case mounting Typical application and internal cireult diagram of type (CDG31 relay with series seal in (Our policy is one of continuous product development an the right is reserved to supply equipment wh GEC Measurements the General Electric Company Ltd St. Leonards Works Stafford ST17 4LX England > Telephone: 0785 3251 Telex: 36240 Cables: Measurements Stafford Telex th may vary slightly from that described SOT6GOGSP Printed in England

You might also like