Mitsubishi Electric PLFY-P VBM-E Service Manual Eng
Mitsubishi Electric PLFY-P VBM-E Service Manual Eng
December 2012
No. OCH413
REVISED EDITION-D
TECHNICAL & SERVICE MANUAL
Indoor unit
[Model names] [Service Ref.]
PLFY-P32VBM-E PLFY-P32VBM-E.UK PLFY-P32VBM-E1.UK Revision:
• PLFY-P32/40/50/63/80/
PLFY-P32VBM-ER2.UK PLFY-P32VBM-ER3.UK 100/125VBM-ER3 have
been added in REVISED
PLFY-P40VBM-E PLFY-P40VBM-E.UK PLFY-P40VBM-E1.UK EDITION-D.
PLFY-P40VBM-ER2.UK PLFY-P40VBM-ER3.UK • Some descriptions have
been modified.
PLFY-P50VBM-E PLFY-P50VBM-E.UK PLFY-P50VBM-E1.UK
PLFY-P50VBM-ER2.UK PLFY-P50VBM-ER3.UK • Please void OCH413
REVISED EDITION-C.
PLFY-P63VBM-E PLFY-P63VBM-E.UK PLFY-P63VBM-E1.UK
PLFY-P63VBM-ER2.UK PLFY-P63VBM-ER3.UK Note:
• This manual does not cover
PLFY-P80VBM-E PLFY-P80VBM-E.UK PLFY-P80VBM-E1.UK outdoor units.
When servicing them, please
PLFY-P80VBM-ER2.UK PLFY-P80VBM-ER3.UK refer to the outdoor unit’s
PLFY-P100VBM-E PLFY-P100VBM-E.UK PLFY-P100VBM-ER2.UK service manual.
• RoHS compliant products
PLFY-P100VBM-ER3.UK have <G> mark on the spec
name plate.
PLFY-P125VBM-E PLFY-P125VBM-E.UK PLFY-P125VBM-ER2.UK
PLFY-P125VBM-ER3.UK
CONTENTS
1. TECHNICAL CHANGES......................... 2
2. SAFETY PRECAUTION..........................3
3. PART NAMES AND FUNCTIONS.......... 5
4. SPECIFICATIONS.................................13
5. 4-WAY AIR FLOW SYSTEM................. 18
6. OUTLINES AND DIMENSIONS............ 21
7. WIRING DIAGRAM............................... 22
8. REFRIGERANT SYSTEM DIAGRAM...... 24
9. TROUBLESHOOTING.......................... 25
Model name 10 . SPECIAL FUNCTION........................... 34
indication
11. DISASSEMBLY PROCEDURE............. 41
INDOOR UNIT
PLFY-P32VBM-ER2.UK PLFY-P32VBM-ER3.UK
PLFY-P40VBM-ER2.UK PLFY-P40VBM-ER3.UK
PLFY-P50VBM-ER2.UK PLFY-P50VBM-ER3.UK
PLFY-P63VBM-ER2.UK PLFY-P63VBM-ER3.UK
PLFY-P80VBM-ER2.UK PLFY-P80VBM-ER3.UK
PLFY-P100VBM-ER2.UK PLFY-P100VBM-ER3.UK
PLFY-P125VBM-ER2.UK PLFY-P125VBM-ER3.UK
INDOOR CONTROLLER BOARD (I.B) has been changed. (S/W version up)
PLFY-P32VBM-E1.UK PLFY-P32VBM-ER2.UK
PLFY-P40VBM-E1.UK PLFY-P40VBM-ER2.UK
PLFY-P50VBM-E1.UK PLFY-P50VBM-ER2.UK
PLFY-P63VBM-E1.UK PLFY-P63VBM-ER2.UK
PLFY-P80VBM-E1.UK PLFY-P80VBM-ER2.UK
PLFY-P100VBM-E.UK PLFY-P100VBM-ER2.UK
PLFY-P125VBM-E.UK PLFY-P125VBM-ER2.UK
INDOOR CONTROLLER BOARD (I.B) has been changed. (S/W version up)
PLFY-P32VBM-E.UK PLFY-P32VBM-E1.UK
PLFY-P40VBM-E.UK PLFY-P40VBM-E1.UK
PLFY-P50VBM-E.UK PLFY-P50VBM-E1.UK
PLFY-P63VBM-E.UK PLFY-P63VBM-E1.UK
PLFY-P80VBM-E.UK PLFY-P80VBM-E1.UK
FAN MOTOR (MF) has been changed.
TURBO FAN, NUT and WASHER have been changed.
OCH413D 2
2 SAFETY PRECAUTION
Cautions for units utilizing refrigerant R410A
Do not use refrigerant other than R410A. Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
If other refrigerant (R22 etc.) is used, chlorine in refrige- a flame, poisonous gases will be released.
rant can cause deterioration of refrigerant oil etc.
OCH413D 3
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
Unit
Gravimeter
OCH413D 4
3 PART NAMES AND FUNCTIONS
Filter
Air outlet
Liquid pipe
Gas pipe
i-see sensor
(option)
Vane
Air intake
(Intake grille)
OCH413D 5
3-2. WIRELESS REMOTE CONTROLLER
display
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.
display
SET TEMP. display indicates the desired
temperature which is set.
“ ”“ ” display
AMPM
Displays the order of timer operation.
NOT AVAILABLE
display “ ”“ ” display
ON/OFF TEMP Displays whether timer is on or off.
The vertical direction of air flow is indicated.
display
FAN SPEED display indicates which fan
buttons
speed has been selected. SET TEMPERATURE button sets any desired
room temperature.
FAN AUTO STOP
ON/OFF button
The unit is turned ON and OFF alternately MODE VANE AUTO START
each time the button is pressed. TIMER CONTROL buttons
CHECK LOUVER h AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be
FAN SPEED SELECT button automatically stopped at the preset time.
Used to change the fan speed. TEST RUN min AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
MODE SELECT button SET RESET CLOCK
LOUVER button
CHECK-TEST RUN buttons
Changes left/right airflow direction.
Only press this button to perform an (Not available for this model.)
inspection check or test operation.
Do not use it for normal operation.
CLOCK button
VANE CONTROL button
RESET button
Used to change the air flow direction.
SET button
OCH413D 6
3-3. WIRED REMOTE CONTROLLER <PAR-30MAA/PAR-31MAA>
Wired remote controller function
* The functions which can be used are restricted according to the model.
: Supported : Unsupported
PAR-30MAA/PAR-31MAA
Function PAR-21MAA
Slim City multi
Body Product size H × W × D (mm) 120 × 120 × 19 120 × 130 × 19
LCD Full Dot LCD Partial Dot LCD
Backlight
Energy-saving Energy-saving operation schedule
Automatic return to the preset temperature
Restriction Setting the temperature range restriction
Function Operation lock function
Weekly timer
On / Off timer
High Power
Manual vane angle
Function buttons
Function guide
F1 F2 F3 F4
OCH413D 7
The main display can be displayed in two different modes: "Full" and "Basic".
The factory setting is "Full". To switch to the "Basic" mode, change the setting on the Main display setting.
Fri Fri
Operation mode
Indoor unit operation mode appears here. Appears when the buttons are locked.
Preset temperature
Preset temperature appears here.
Appears when the On/Off timer or Night setback function is
Clock (See the Installation Manual.) enabled.
Current time appears here.
Fan speed
Appears when the Weekly timer is enabled.
Fan speed setting appears here.
Most settings (except ON / OFF, mode, fan speed, temperature) can be made from the Menu screen.
OCH413D 8
Menu structure
Timer
On / Off timer
Auto-Off timer
Filter information
Error information
Weekly timer
Energy saving
Auto return
Schedule
Night setback
Restriction
Temp. range
Operation lock
Maintenance
Auto descending panel
Manual vane angle
Initial setting
Main / Sub
Clock
Main display
Contrast
Display details
Auto mode
Administrator password
Language selection
Service
Service menu
Test run
Drain pump test run
Input maintenance info.
Function setting
Lossnay (City Multi only)
Check
Self check
Maintenance password
Remote controller check
OCH413D 9
Main menu list
Setting and display items Setting details
Vane · Louver · Vent. Use to set the vane angle.
(Lossnay) • Select a desired vane setting from f ve different settings.
Use to turn ON / OFF the louver.
• Select a desired setting from "ON" and "OFF."
Use to set the amount of ventilation.
• Select a desired setting from "Off," "Low," and "High."
High power Use to reach the comfortable room temperature quickly.
• Units can be operated in the High-power mode for up to 30 minutes.
Timer On/Off timer Use to set the operation On/Off times.
• Time can be set in 5-minute increments.
* Clock setting is required.
Auto-Off Use to set the Auto-Off time.
timer • Time can be set to a value from 30 to 240 in 10-minute increments.
Filter information Use to check the f lter status.
• The f lter sign can be reset.
Error information Use to check error information when an error occurs.
• Error code, error source, refrigerant address, unit model, manufacturing number, contact
information (dealer's phone number) can be displayed.
* The unit model, manufacturing number, and contact information need to be registered in
advance to be displayed.
Weekly timer Use to set the weekly operation On / Off times.
• Up to eight operation patterns can be set for each day.
* Clock setting is required.
* Not valid when the On/Off timer is enabled.
Energy Auto return Use to get the units to operate at the preset temperature after performing energy-save
saving operation for a specif ed time period.
• Time can be set to a value from 30 and 120 in 10-minute increments.
* This function will not be valid when the preset temperature ranges are restricted.
Schedule Set the start/stop times to operate the units in the energy-save mode for each day of the
week, and set the energy-saving rate.
• Up to four energy-save operation patterns can be set for each day.
• Time can be set in 5-minute increments.
• Energy-saving rate can be set to a value from 0% or 50 to 90% in 10% increments.
* Clock setting is required.
Night setback Use to make Night setback settings.
• Select "Yes" to enable the setting, and "No" to disable the setting. The temperature range and
the start/stop times can be set.
* Clock setting is required.
Restriction Temp. range Use to restrict the preset temperature range.
• Different temperature ranges can be set for different operation modes.
Operation Use to lock selected functions.
lock • The locked functions cannot be operated.
Maintenance Auto Auto descending panel (Optional parts) Up / Down you can do.
descending
panel
Manual Use to set the vane angle for each vane to a f xed position.
vane angle
Initial setting Main/Sub When connecting two remote controllers, one of them needs to be designated as a sub
controller.
Clock Use to set the current time.
Main display Use to switch between "Full" and "Basic" modes for the Main display.
• The default setting is "Full."
Contrast Use to adjust screen contrast.
OCH413D 10
Setting and display items Setting details
Initial setting Display Make the settings for the remote controller related items as necessary.
details Clock: The factory settings are "Yes" and "24h" format.
Temperature: Set either Celsius (°C) or Fahrenheit (°F).
Room temp. : Set Show or Hide.
Auto mode: Set the Auto mode display or Only Auto display.
Auto mode Whether or not to use the AUTO mode can be selected by using the button.
This setting is valid only when indoor units with the AUTO mode function are connected.
Administrator The administrator password is required to make the settings for the following items.
password • Timer setting • Energy-save setting • Weekly timer setting
• Restriction setting • Outdoor unit silent mode setting • Night set back
Language Use to select the desired language.
selection
Service Test run Select "Test run" from the Service menu to bring up the Test run menu.
• Test run • Drain pump test run
Input Select "Input maintenance Info." from the Service menu to bring up the Maintenance
maintenance information screen.
The following settings can be made from the Maintenance Information screen.
• Model name input • Serial No. input • Dealer information input
Function Make the settings for the indoor unit functions via the remote controller as necessary.
setting
LOSSNAY This setting is required only when the operation of City Multi units is interlocked with
setting LOSSNAY units.
(City Multi only)
Check Error history: Display the error history and execute delete error history.
Refrigerant leak check: Refrigerant leaks can be judged.
Smooth maintenance: The indoor and outdoor maintenance data can be displayed.
Request cord: Details of the operation data including each thermistor temperature and error
history can be checked.
Self check Error history of each unit can be checked via the remote controller.
Maintenance Take the following steps to change the maintenance password.
password
Remote When the remote controller does not work properly, use the remote controller checking
controller function to troublushoot the problem.
check
OCH413D 11
3-4. WIRED REMOTE CONTROLLER <PAR-21MAA>
“Sensor” indication
Display Section
Displayed when the remote controller
Day-of-Week sensor is used.
For purposes of this explanation,
Shows the current day of the week.
all parts of the display are shown.
During actual operation, only
the relevant items will be lit. Time/Timer Display
Shows the current time, unless the simple or Auto Off “Locked” indicator
timer is set. Indicates that remote controller but-
If the simple or Auto Off timer is set, the time to be tons have been locked.
switched off is shown.
Identifies the current operation
Shows the operating mode, etc. “Clean The Filter” indicator
*Multilanguage display is available. To be displayed on when it is time to
clean the filter.
Operation Section
Temperature setting buttons ON/OFF button
Down
Fan Speed button
Up
Ahead
BACK MONITOR/SET DAY CHECK TEST
Airflow Up/Down button
Timer On/Off button PAR-21MAA CLOCK OPERATION CLEAR
(Set Day button)
Louver button
( Operation button)
To return operation
Opening the number
cover
Ventilation button
Built-in temperature sensor ( Operation button)
To go to next operation
number
Note:
● “PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
● “NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
OCH413D 12
4 SPECIFICATIONS
4-1. SPECIFICATIONS
Model PLFY-P32VBM-E PLFY-P40VBM-E PLFY-P50VBM-E PLFY-P63VBM-E
Power source 1-phase 220-240V 50Hz, 1-phase 220V 60Hz
Cooling capacity 1 kW 3.6 4.5 5.6 7.1
(Nominal) 1 kcal / h 3,100 3,900 4,800 6,100
1 Btu / h 12,300 15,400 19,100 24,200
2 kcal / h 3,150 4,000 5,000 6,300
Power input kW 0.03 0.04 0.04 0.05
Current input A 0.22 0.29 0.29 0.36
Heating capacity 3 kW 4.0 5.0 6.3 8.0
(Nominal ) 3 kcal / h 3,400 4,300 5,400 6,900
3 Btu / h 13,600 17,100 21,500 27,300
Power input kW 0.02 0.03 0.03 0.04
Current input A 0.14 0.22 0.22 0.29
External finish Galvanized steel sheet
External dimension H × W × D mm 258 x 840 x 840
in. 10-3/16 x 33-1/8 x 33-1/8
Net weight kg (lb) 22 (49) 22 (49) 22 (49) 23 (51)
Decoration panel Model PLP-6BA PLP-6BA PLP-6BA PLP-6BA
External finish MUNSELL (6.4Y 8.9/0.4)
Dimension mm 35 x 950 x 950
H×W×D in. 1-3/8 x 37-7/16 x 37-7/16
Net weight kg (lb) 6 (13)
Heat exchanger Cross fin (Aluminum fin and copper tube)
FAN Type × Quantity Turbo fan × 1 Turbo fan × 1 Turbo fan × 1 Turbo fan × 1
External Pa 0 0 0 0
static press. mmH2O 0 0 0 0
Motor type DC motor
Motor output kW 0.050 0.050 0.050 0.050
Driving mechanism Direct-drive
Airflow rate m3 / min 11 - 12 - 13 - 14 12 - 13 - 14 - 16 12 - 13 - 14 - 16 14 - 15 - 16 - 18
(Low-Mid2- L/s 183 - 200 - 217 - 233 200 - 217 - 233 - 267 200 - 217 - 233 - 267 233 - 250 - 267 - 300
Mid1-High) cfm 388 - 424 - 459 - 494 424 - 459 - 494 - 565 424 - 459 - 494 - 565 494 - 530 - 565 - 636
Noise level (Low-Mid2-Mid1-High) dB <A> 27 - 28 - 29 - 31 27 - 28 - 30 - 31 27 - 28 - 30 - 31 28 - 29 - 30 - 32
(measured in anechoic room)
Insulation material PS
Air filter PP honeycomb
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A CITY MULTI
Diameter of Liquid mm (in.) :6.35 (:1/4) Flare :6.35 (:1/4) Flare :6.35 (:1/4) Flare :9.52 (:3/8) Flare
refrigerant pipe Gas mm (in.) :12.7 (:1/2) Flare :12.7 (:1/2) Flare :12.7 (:1/2) Flare :15.88 (:5/8) Flare
Field drain pipe size mm (in.) O.D. :32 (VP-25)
Standard Document Installation Manual, Instruction Book
attachment Accessory
Installation Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
Note : 1 Nominal cooling conditions 2 Nominal cooling conditions 3 Nominal heating conditions Unit converter
Indoor : 27DB/19WB (81°FDB/66°FWB) 27DB/19.5WB (81°FDB/67°FWB) 20DB (68°FDB) kcal/h = kW × 860
Outdoor : 35DB (95°FDB) 35DB (95°FDB) 7DB/6WB (45°FDB/43°FWB) Btu/h = kW × 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min × 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
OCH413D 13
Model PLFY-P80VBM-E PLFY-P100VBM-E PLFY-P125VBM-E
Power source 1-phase 220-240V 50Hz, 1-phase 220V 60Hz
Cooling capacity 1 kW 9.0 11.2 14.0
(Nominal) 1 kcal / h 7,700 9,600 12,000
1 Btu / h 30,700 38,200 47,800
2 kcal / h 8,000 10,000 12,500
Power input kW 0.07 0.15 0.16
Current input A 0.51 1.00 1.07
Heating capacity 3 kW 10.0 12.5 16.0
(Nominal ) 3 kcal / h 8,600 10,800 13,800
3 Btu / h 34,100 42,700 54,600
Power input kW 0.06 0.14 0.15
Current input A 0.43 0.94 1.00
External finish Galvanized steel sheet
External dimension H × W × D mm 258 x 840 x 840 298 x 840 x 840
in. 10-3/16 x 33-1/8 x 33-1/8 11-3/4 x 33-1/8 x 33-1/8
Net weight kg (lb) 23(51) 27(60) 27(60)
Decoration panel Model PLP-6BA PLP-6BA PLP-6BA
External finish MUNSELL (6.4Y 8.9/0.4)
Dimension mm 35 x 950 x 950
H×W×D in. 1-3/8 x 37-7/16 x 37-7/16
Net weight kg (lb) 6(13)
Heat exchanger Cross fin (Aluminum fin and copper tube)
FAN Type × Quantity Turbo fan x 1 Turbo fan x 1 Turbo fan x 1
External Pa 0 0 0
static press. mmH2O 0 0 0
Motor type DC motor
Motor output kW 0.050 0.120 0.120
Driving mechanism Direct-drive
Airflow rate m3 / min 16 - 18 - 20 - 22 21 - 24 - 27 - 29 22 - 25 - 28 - 30
(Low-Mid2- L/s 267 - 300 - 333 - 367 350 - 400 - 450 - 483 367 - 417 - 467 - 500
Mid1-High) cfm 565 - 636 - 706 - 777 742 - 848 - 953 - 1024 777 - 883 - 989 - 1059
Noise level (Low-Mid2-Mid1-High) dB <A> 30 - 32 - 35 - 37 34 - 37 - 39- 41 35 - 38 - 41 - 43
(measured in anechoic room)
Insulation material PS
Air filter PP honeycomb
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A CITY MULTI
Diameter of Liquid mm (in.) :9.52 (:3/8) Flare :9.52 (:3/8) Flare :9.52 (:3/8) Flare
refrigerant pipe Gas mm (in.) :15.88 (:5/8) Flare :15.88 (:5/8) Flare :15.88 (:5/8) Flare
Field drain pipe size mm (in.) O.D. :32 (VP-25)
Standard Document Installation Manual, Instruction Book
attachment Accessory
Installation Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
Note : 1 Nominal cooling conditions 2 Nominal cooling conditions 3 Nominal heating conditions Unit converter
Indoor : 27DB/19WB (81°FDB/66°FWB) 27DB/19.5WB (81°FDB/67°FWB) 20DB (68°FDB) kcal/h = kW × 860
Outdoor : 35DB (95°FDB) 35DB (95°FDB) 7DB/6CWB (45°FDB/43°FWB) Btu/h = kW × 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min × 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions 1, 3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specification may be subject to change without notice. subject to rounding variation.
OCH413D 14
4-2. ELECTRICAL PARTS SPECIFICATIONS
Service Ref. PLFY-P32VBM-E.UK PLFY-P40VBM-E.UK PLFY-P50VBM-E.UK PLFY-P63VBM-E.UK
Symbol PLFY-P32VBM-E 1.UK PLFY-P40VBM-E1.UK PLFY-P50VBM-E1.UK PLFY-P63VBM-E1.UK
PLFY-P32VBM-ER2.UK PLFY-P40VBM-ER2.UK PLFY-P50VBM-ER2.UK PLFY-P63VBM-ER2.UK
Parts name PLFY-P32VBM-ER3.UK PLFY-P40VBM-ER3.UK PLFY-P50VBM-ER3.UK PLFY-P63VBM-ER3.UK
Room temperature
thermistor TH21 Resistance 0/15k, 10/9.6k, 20/6.3k, 25/5.4k, 30/4.3k, 40/3.0k
Liquid pipe thermistor TH22 Resistance 0/15k, 10/9.6k, 20/6.3k, 25/5.4k, 30/4.3k, 40/3.0k
Gas pipe thermistor TH23 Resistance 0/15k, 10/9.6k, 20/6.3k, 25/5.4k, 30/4.3k, 40/3.0k
Fuse
(Indoor controller board) FUSE 250V 6.3A
MSBPC20M04
Vane motor MV
DC12V 300/phase
PLD-12230ME-1
Drain pump DP
INPUT 12/10.8W 241/Hr
Linear expansion valve LEV DC12V Stepping motor drive port dimension :5.2 (0~2000pulse)
EDM-40YGME
Power supply terminal
block TB2 (L, N, ) Rated to 330V 30A *
Transmission terminal
TB5 (M1, M2, S) Rated to 250V 20A *
block
MA remote controller
TB15 (1, 2) Rated to 250V 10A *
terminal block
* Note: Refer to WIRING DIAGRAM for the supplied voltage.
OCH413D 15
Service Ref. PLFY-P80VBM-E.UK
PLFY-P100VBM-E.UK PLFY-P125VBM-E.UK
PLFY-P80VBM-E1.UK
Symbol PLFY-P100VBM-ER2.UK PLFY-P125VBM-ER2.UK
PLFY-P80VBM-ER2.UK
PLFY-P100VBM-ER3.UK PLFY-P125VBM-ER3.UK
Parts name PLFY-P80VBM-ER3.UK
Room temperature
thermistor TH21 Resistance 0/15k, 10/9.6k, 20/6.3k, 25/5.4k, 30/4.3k, 40/3.0k
Liquid pipe thermistor TH22 Resistance 0/15k, 10/9.6k, 20/6.3k, 25/5.4k, 30/4.3k, 40/3.0k
Gas pipe thermistor TH23 Resistance 0/15k, 10/9.6k, 20/6.3k, 25/5.4k, 30/4.3k, 40/3.0k
Fuse
(Indoor controller board) FUSE 250V 6.3A
MSBPC20M04
Vane motor MV DC12V 300/phase
PLD-12230ME-1
Drain pump DP INPUT 12/10.8W 241/Hr
Linear expansion valve LEV DC12V Stepping motor drive port dimension :5.2 (0~2000pulse)
EDM-80YGME
Power supply terminal
block TB2 (L, N, ) Rated to 330V 30A *
Transmission terminal
TB5 (M1, M2, S) Rated to 250V 20A *
block
MA remote controller
TB15 (1, 2) Rated to 250V 10A *
terminal block
* Note: Refer to WIRING DIAGRAM for the supplied voltage.
PLFY-P63VBM-ER2.UK 28-29-30-32
PLFY-P63VBM-ER3.UK
PLFY-P80VBM-E(1).UK
PLFY-P80VBM-ER2.UK 30-32-35-37
Measurement location PLFY-P80VBM-ER3.UK
PLFY-P100VBM-E.UK
* Measured in anechoic room. PLFY-P100VBM-ER2.UK 34-37-39-41
PLFY-P100VBM-ER3.UK
PLFY-P125VBM-E.UK
PLFY-P125VBM-ER2.UK 35-38-41-43
PLFY-P125VBM-ER3.UK
OCH413D 16
4-4. NC CURVES
PLFY-P125VBM-E.UK
PLFY-P125VBM-ER2.UK
PLFY-P125VBM-ER3.UK
External static pressure : 0Pa
Power source : 220,230,240V, 50Hz / 220V, 60Hz
High 50/60Hz Middle2 50/60Hz
Low 50/60Hz Middle1 50/60Hz
70.0
Octave band pressure level (dB) 0dB=20Pa
65.0
60.0
NC-60
55.0
50.0
NC-50
45.0
40.0
NC-40
35.0
30.0
NC-30
25.0
20.0
Approximate minimum
15.0 audible limit on NC-20
continuous noise
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
OCH413D 17
5 4-WAY AIR FLOW SYSTEM
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set up the switches
(SWA, SWB) on the circuit board to the appropriate setting.
• Correspondence of ceiling heights to numbers of air outlets
SWA SWB
3 2
2 3 CN43
1 4
SW1
ON
OFF
1 2 3 4 5 6 7 8 9 10 CN82
3456
2 3
7 8
7 8
D
BC
4 4 789A
5 6 5 6
./ .
(10ths DIGIT) (1s DIGIT) (BRANCH No.)
PLFY-P32/40/50/63/80VBM-E.UK
PLFY-P32/40/50/63/80VBM-E1.UK
PLFY-P32/40/50/63/80VBM-ER2.UK
PLFY-P32/40/50/63/80VBM-ER3.UK
SWA
SWB Silent Standard High ceiling
4 direction 2.5m 2.7m 3.5m
3 direction 2.7m 3.0m 3.5m
2 direction 3.0m 3.3m 3.5m
PLFY-P100/125VBM-E.UK
PLFY-P100/125VBM-ER2.UK
PLFY-P100/125VBM-ER3.UK
SWA
SWB Silent Standard High ceiling
4 direction 2.7m 3.2m 4.5m
3 direction 3.0m 3.6m 4.5m
2 direction 3.3m 4.0m 4.5m
OCH413D 18
5-2. BRANCH DUCT HOLE AND FRESH AIR INTAKE HOLE
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when
required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figures marked with * in the drawing below represent the dimensions of the main unit excluding those of the optional multi
function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise, condensation and dripping may occur.
120
Indoor unit
*158
Branch duct hole diagram :100 cut
(view from either side) out hole
90 100 100 90
Ceiling
100
130
Drain pipe
70°
Refrigerant pipe
*155
*167
14-:2.8 burring hole
350
:175 burring hole pitch :150 cut out hole
Multiple remote
controller adapter
PAC-SA88HA-E
CN51
OCH413D 19
5-4. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS
l PLFY-P32/40/50/63/80VBM-E.UK
PLFY-P32/40/50/63/80VBM-E1.UK
PLFY-P32/40/50/63/80VBM-ER2.UK
PLFY-P32/40/50/63/80VBM-ER3.UK
Multi function casement + Standard filter Multi function casement + High efficiency filter
50 50
0 0
Static pressure[Pa]
Static pressure[Pa]
-50 -50
2 - inlet
2 - inlet
-100 -100
-150 -150
1 - inlet
1 - inlet
-200 -200
0 1 2 3 4 5 6 0 1 2 3 4 5 6
Airflow rate [m3/min] Airflow rate [m3/min]
2 PLFY-P100/125VBM-E.UK Qa
PLFY-P100/125VBM-ER2.UK
PLFY-P100/125VBM-ER3.UK
Multi function casement + Standard filter Multi function casement + High efficiency filter
50 50
0 0
Static pressure[Pa]
Static pressure[Pa]
-50 -50
2 - inlet
-100 -100
2 - inlet
-150 -150
1 - inlet 1 - inlet
-200 -200
0 2 4 6 8 0 2 4 6 8
Airflow rate [m3/min] Airflow rate [m3/min]
0
Static pressure[Pa]
-50
-100
-150
-200
0 2 4 6 8
Airflow rate [m3/min]
OCH413D 20
6 OUTLINES AND DIMENSIONS
PLFY-P32/40/50/63/80/100/125VBM-E.UK
PLFY-P32/40/50/63/80VBM-E1.UK
PLFY-P32/40/50/63/80/100/125VBM-ER2.UK
PLFY-P32/40/50/63/80/100/125VBM-ER3.UK Unit : mm
Ceiling hole
20~45 860~910 20~45
810
Detail connecting of branch duct(Both aspects)
Fresh air Suspension bolt pitch 90 100 100 90 Cut out hole
20~45
intake hole 160
100
130
(7.5)
160
70°
* 155
167
Indoor/outdoor unit connecting *
terminal block
Ceiling hole
terminal block
860~910
Branch duct hole
605
840
620
Burring hole pitch Burring hole
For MA-Remote controller
terminal block :150
Cut out hole
160
24
D
C
90
(7.5)
Burring hole
3-:2.8
Burring hole pitch
20~45
1 60 284 377
Drain pipe
connected to VP-25 ( Connected the attached
flexible pipe or socket. ) Cut out hole
120°
Keep approximately :100
2
158
10 to 15 mm space
between unit ceiling *
and ceiling slab.
A
B
*
190
Ceiling
156
170
105
140
* * *
* *
In case of standard grille : PLP-6BA/PLP-6BAMD
Suspension bolt
50~70
+5
35
Ceiling Auto-grille
* Indoor unit/Outdoor unit
17
Max. 4.0m
Emergency Up/Down switch<Down> L.L Filter
Air intake hole
Air outlet hole
950
500
597
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
500 83 36
4. Electrical box may be removed for the service purpose.
36
Air outlet hole Make sure to slack the electrical wire little bit for control/power wires connection.
950 5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional
Corner pocket multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions * marked on the figure.
3) The optional high efficiency filter must be used jointly with optional multi-functional
Indoor unit Indoor unit casement.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/water dew.)
8. As for necessary installation/service space, please refer to the left figure.
1000 mm
or more
OCH413D 21
7 WIRING DIAGRAM
PLFY-P32/40/50/63/80/100/125VBM-E.UK
PLFY-P32/40/50/63/80VBM-E1.UK
PLFY-P32/40/50/63/80/100/125VBM-ER2.UK
[LEGEND]
SYMBOL NAME SYMBOL NAME SYMBOL NAME
I. B INDOOR CONTROLLER BOARD TB2 TERMINAL POWER SUPPLY OPTION PART
CN27 CONNECTOR DAMPER TB5 BLOCK TRANSMISSION W.B PCB FOR WIRELESS REMOTE CONTROLLER
CN32 REMOTE SWITCH TB15 MA-REMOTE CONTROLLER BZ BUZZER
CN51 CENTRALLY CONTROL TH21 THERMISTOR ROOM TEMP. DETECTION LED1 LED (OPERATION INDICATION : GREEN)
CN52 REMOTE INDICATION (0 / 15k, 25 / 5.4k) LED2 LED (PREPARATION FOR HEATING : ORANGE)
FUSE FUSE (T6.3AL250V) TH22 PIPE TEMP. DETECTION / LIQUID RU RECEVING UNIT
LED1 POWER SUPPLY (I. B) (0 / 15k, 25 / 5.4k) SW1 EMERGENCY OPERATION (HEAT / DOWN)
LED2 POWER SUPPLY (I. B) TH23 PIPE TEMP. DETECTION / GAS SW2 EMERGENCY OPERATION (COOL / UP)
SW2 SWITCH CAPACITY CODE (0 / 15k, 25 / 5.4k)
SW3 MODE SELECTION A. B ADDRESS BOARD
SW4 MODEL SELECTION SWA SWITCH CEILING HEIGHT SELECTOR
SWE DRAIN PUMP (TEST MODE) SWB DISCHARGE OUTLET NUMBER
X1 AUX. RELAY DRAIN PUMP SELECTOR
DP DRAIN PUMP SWC OPTION SELECTOR
FS DRAIN FLOAT SWITCH SW1 MODE SELECTION
LEV LINEAR EXPANSION VALVE SW11 ADDRESS SETTING 1s DIGIT
MF FAN MOTOR SW12 ADDRESS SETTING 10ths DIGIT
MV VANE MOTOR SW14 BRANCH NO.
<fig. *1> The black square (■) indicates a switch position. POWER SUPPLY
A.B (RED) 4 MODELS SW2 MODELS SW2 ~/N 220-240V 50Hz
ADDRESS
CN43 ON ON BLU TB5 TO OUTDOOR UNIT 220V 60Hz
P32 OFF P80 OFF M1 BC CONTROLLER
GRILLE SWA SWB 1 BLU REMOTE CONTROLLER BREAKER
SW1 8 1 2 3 4 5 6 1 2 3 4 5 6 M2
3 2 DC24-30V (16A)
ON 2 3 ON ON S (SHIELD)
MV MV MV MV OFF 1 4 P40 OFF P100 OFF
(RED)
12345678910 1 2 3 4 5 6 1 2 3 4 5 6
M M M M SW12 SW11 SW14
ADDRESS FUSE(16A)
0 1 0 1 SWC E F0 1 2 CN82 P50
ON
P125
ON TB2
9 9
OFF OFF RED
PULL BOX
BLU L
BCD
3456
2 3
2 3
7 8
7 8
5 6
4
5 6
4 789A 1 2 3 4 5 6 1 2 3 4 5 6
TB15 3 U.B
4 5 6 BLU 1 M
TO MA-REMOTE CNB BZ
BLU 2 CONTROLLER MS 1~
WHT
YLW
ORN
BLU
RED
BRN
DC8.7-13V 3~
I-SEE M SW1 LED2
DP
3 1
SENSOR t° t° t° MF 5 3 1
MT CN3G
CN3A
M SW2 LED1
I-SEE SENSOR CORNER PANEL * Be sure to turn off the power AUTOMATIC FILTER ELEVATION PANEL
(OPTIONAL PART) RU
LEV W.B TH22 TH23 FS TH21 source and then disconnect (OPTIONAL PART)
fan motor connector.
NOTES: (Failure to do so will cause
trouble in Fan motor.)
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15.
(Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, : terminal block, : connecter.
6. The setting of the SW2 dip switches differs in the capacity. For the detail, refer to fig *1.
LED2 Power supply for MA-Remote controller Power supply for MA-Remote controller on Lamp is lit.
OCH413D 22
PLFY-P32/40/50/63/80/100/125VBM-ER3.UK
LEGEND
SYMBOL NAME SYMBOL NAME SYMBOL NAME
I. B INDOOR CONTROLLER BOARD DP DRAIN-UP MACHINE A. B ADDRESS BOARD
CN27 CONNECTOR DAMPER FS DRAIN FLOAT SWITCH SWA SWITCH CEILING HEIGHT SELECTOR
CN32 REMOTE SWITCH LEV LINEAR EXPANSION VALVE SWB DISCHARGE OUTLET NUMBER
CN51 CENTRALLY CONTROL MF FAN MOTOR SELECTOR
CN52 REMOTE INDICATION MV VANE MOTOR SWC OPTION SELECTOR
CH100 IT TERMINAL TB2 TERMINAL POWER SUPPLY SW1 MODE SELECTION
FUSE FUSE(T6.3AL250V) TB5 BLOCK TRANSMISSION SW11 ADDRESS SETTING 1s DIGIT
LED1 POWER SUPPLY(I. B) TB15 MA-REMOTE CONTROLLER SW12 ADDRESS SETTING 10ths DIGIT
LED2 POWER SUPPLY(I. B) TH21 THERMISTOR ROOM TEMP. DETECTION SW14 CONNECTION NO.
SW2 SWITCH CAPACITY CODE (0°C / 15kΩ, 25°C / 5.4kΩ) OPTION PART
SW3 MODE SELECTION TH22 PIPE TEMP. DETECTION / LIQUID W.B PCB FOR WIRELESS REMOTE CONTROLLER
SW4 MODEL SELECTION (0°C / 15kΩ, 25°C / 5.4kΩ) BZ BUZZER
SWE DRAIN-UP MACHINE(TEST MODE) TH23 PIPE TEMP. DETECTION / GAS LED1 LED(OPERATION INDICATION : GREEN)
X1 AUX. RELAY DRAIN WATER LIFTING-UP MACH. (0°C / 15kΩ, 25°C / 5.4kΩ) LED2 LED(PREPARATION FOR HEATING : ORANGE)
RU RECEIVING UNIT
SW1 EMERGENCY OPERATION(HEAT / DOWN)
SW2 EMERGENCY OPERATION(COOL / UP)
7 8 9
BC E
2 3 4
2 3 4
3456
D
PULL BOX
5 6 5 6 789A
P63 OFF BLU
N
10ths 1s BRANCH 1
1 2 3 4 5 6 GRN/YLW
5 5 5 5 DIGIT DIGIT No. TO NEXT
INDOOR UNIT
8 4 See fig:+1 I.B
CN32 1 3 5
(WHT) J42 J41 SW3 SW4 SW2
ON ON CND
20 18 16 14 12 10 8 6 4 2 (BLK)
OFF OFF
19 17 15 13 11 9 7 5 3 1 1 3 1 8 1 4 1 2 3 4 5 6 7 8 910 12345 123456 2 1
Pair No. ADDRESS ADDRESS M-NET
VANE CNV
I-SEE SENSOR (WHT) CN81 CN42 SWE CN2M
MOTOR CN6Y (RED) (RED) (BLU)
1 (RED) 6 MA REMOCON LED2 1 8
CN3A OFF ON
(BLU) CN100 +2
1 3 (WHT) 3 +
I-SEE SENSOR WIRELESS
CN90 AUTO GRILLE CN25
CN4Y CN3G
1 (WHT) 9 (WHT)
1 (WHT) 4 (BLK) 1 2
LEV CN60 1 3
1 (WHT) 6 LED1
INTAKE FAN X1
LIQUID/GAS FLOAT SW CN20 CN27 CNMF AUTO
CN52 +2 CN51 +2 CN41 CN44 CN4F (RED) (RED) (WHT) GRILLE
1 (GRN) 5 1 (WHT) 5 1 (WHT) 4 1 (WHT) 4 1 (WHT) 4 1 2 1 2 7 4 1 D.U.M 3 1 3 1 POWER
CNP CNAC
9 (BLU) (WHT)
TB15 3 U.B
6
4 5 ORN TO MA-REMOTE CNB BZ MS
1 M
CONTROLLER 3~
WHT
ORN
YLW
ORN
BLU
RED
BRN
2 1~
DC8.7-13V
I-SEE M SW1 LED2 MF DP
t° t° t° 3 1 CN3A
SENSOR + Be sure to turn off the source power CN3G
MT SW2 5 3 1
M LED1 and then disconnect fan motor connector.
I-SEE SENSOR CORNER PANEL RU (Failure to do so will cause trouble in Fan motor) AUTOMATIC FILTER ELEVATION PANEL
(OPTION PART) W.B TH22 TH23 FS TH21
LEV (OPTION PART)
NOTES:
+2 IT terminal IT terminal
PAC-IT51AD-E PAC-IT52AD-E
1 5
1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
1 5
2.In case of using MA-Remote controller, please connect to TB15.(Remote controller wire is non-polar.)
1 4 5 8 1 4 5 8
3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4.Symbol [S] of TB5 is the shield wire connection.
CN100(WHT) CN100(WHT)
1 3 5 1 5 5.Symbols used in wiring diagram above are, : terminal block, : connecter.
CN51(WHT) CN52(GRN)
6.The setting of the SW2 dip switches differs in the capacity. For the detail, refer to fig<+1>.
In connecting optional IT terminal, use
either CN51 or CN52 which is not connected.
Be careful for connector colors.
LED on indoor board for service
Mark Meaning Function
Main Power supply(Indoor unit:220-240V)
LED1 Main power supply
power on → lamp is lit
LED2 Power supply for
MA-Remote controller
Power supply for MA-Remote controller
on → lamp is lit
OCH413D 23
8 REFRIGERANT SYSTEM DIAGRAM
PLFY-P32/40/50/63/80/100/125VBM-E.UK
PLFY-P32/40/50/63/80VBM-E1.UK
PLFY-P32/40/50/63/80/100/125VBM-ER2.UK
PLFY-P32/40/50/63/80/100/125VBM-ER3.UK
Gas pipe
Unit : mm(inch)
Capacity PLFY-P32/40VBM-E PLFY-P50VBM-E PLFY-P63/80VBM-E
PLFY-P100/125VBM-E
Item PLFY-P32/40VBM-E1 PLFY-P50VBM-E1 PLFY-P63/80VBM-E1
OCH413D 24
9 TROUBLESHOOTING
9-1. HOW TO CHECK THE PARTS
PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E1.UK
PLFY-P32/40/50/63/80/100/125VBM-ER2.UK PLFY-P32/40/50/63/80/100/125VBM-ER3.UK
Parts name Check points
Room temperature Disconnect the connector then measure the resistance with a tester.
thermistor (TH21) (At the ambient temperature of 10 - 30)
Liquid pipe thermistor
(TH22) Normal Abnormal
Gas pipe thermistor (Refer to Thermistor characteristic graph.)
(TH23) 4.3k~9.6k Open or short
Vane motor (MV) Measure the resistance between the terminals with a tester.
(At the ambient temperature of 20 - 30)
White
Connector Normal Abnormal
MV Red - Yellow (-, -,
-, -)
Orange Red - Blue (-
, -,
- , -)
300 Open or short
Red Red - Orange (-
, -,
-, -)
Blue Yellow Red - White (-, -,
-
, -)
Drain pump (DP) Measure the resistance between the terminals with a tester.
YLW
(Winding temperature 20)
1 Normal Abnormal
3 290 Open or short
YLW
i-see sensor Turn on the indoor unit with the black plastic tape on the outside of i-see sensor controller board.
(Option) With electricity being turned on, measure the power voltage between connectors with tester.
i-see sensor rotates and pull out the connector of motor for i-see sensor.
Black plastic tape
4 3 2 1
i-see sensor (At the ambient temperature of 10 - 40)
i-see sensor connector Normal Abnormal
4 3 2 1
Blue BlackPink Brown (–)—
(+) DC 1.857V~ 3.132V Other than the normal
(+)—(–) DC 0.939V~ 1.506V Other than the normal
NOTE : Be careful not to discharge static electricity into electronics.
Vane motor for Measure the resistance between the terminals with a tester.
i-see sensor (Option) (At the ambient temperature of 20 - 30)
White Connector Normal Abnormal
MV Red - Yellow
Red - Blue
Orange 250 Open or short
Red - Orange
Red Red - White
Blue Yellow
Linear expansion Disconnect the connector then measure the resistance valve with a tester.
valve(LEV) Blue
Normal Abnormal Refer to 9-1-3.
M Brown
White-Red Yellow-Brown Orange-Red Blue-Brown
Open or short
Yellow
200 $10%
White Red Orange
OCH413D 25
9-1-1. Thermistor
Resistance (k)
30
Thermistor R0=15k' ± 3% 20
Fixed number of B=3480 ± 2%
1 1
Rt=15exp { 3480( )} 10
273+t 273
0: 15k' 0
10: 9.6k' -20 -10 0 10 20 30
Temperature ()
40 50
20: 6.3k'
25: 5.4k'
30: 4.3k'
40: 3.0k'
DC12V
Blue Red 5
4 Drive circuit
:4 Blue 4 :4
M Brown
6
:2 Orange 3 :3
Yellow
:1 5 :3 2
1 Yellow 2 :2
3
White Red Orange
White 1 :1
Connector(CN60)
OCH413D 26
<Output pulse signal and the valve operation>
Output
Output
(Phase) Closing a valve : 1 → 2 → 3 → 4 → 1
1 2 3 4 Opening a valve : 4 → 3 → 2 → 1 → 4
{1 ON OFF OFF ON
The output pulse shifts in above order.
{2 ON ON OFF OFF • When linear expansion valve operation stops, all output phase
become OFF.
{3 OFF ON ON OFF • At phase interruption or when phase does not shift in order, motor
does not rotate smoothly and motor will lock and vibrate.
{4 OFF OFF ON ON
2 Linear expansion valve operation • When the switch is turned on, 2200 pulse closing valve signal will be
sent till it goes to point A in order to define the valve position.
Open
D C When the valve moves smoothly, there is no sound or vibration
occurring from the linear expansion valves; however, when the pulse
number moves from E to A or when the valve is locked, more sound
can be heard than in a normal situation.
Valve position (capacity)
• Sound can be detected by placing the ear against the screw driver
handle while putting the screw driver tip to the linear expansion
valve.
Close
Open
Outdoor unit R410A model : 1400 pulse
Outdoor unit R22/R407C model : 2000 pulse
A Opening a valve
all the way
E
Close
B
Pulse number
3 Troubleshooting
Valve does not close To check the linear expansion valve, operate the indoor unit If large amount of refriger-
completely. in fan mode and at the same time operate other indoor units ant is leaked, exchange
in cooling mode, then check the pipe temperature <liquid the linear expansion valve.
pipe temperature> of the indoor unit by the
outdoor multi controller board operation
monitor. During fan operation, linear expan-
sion valve is closed completely and if there
Thermistor
(Liquid pipe) is any leaking, detecting temperature of
Linear the thermistor will go lower. If the detected
expansion temperature is much lower than the tem-
valve perature indicated in the remote controller,
it means the valve is not closed all the way.
It is not necessary to exchange the linear expansion valve, if
the leakage is small and not affecting normal operation.
Wrong connection Check the color of lead wire and missing terminal of the con- Disconnect the connector
of the connector or nector. at the controller board,
contact failure then check the continuity.
OCH413D 27
9-1-3. DC Fan motor (fan motor/indoor controller board)
Is the resistance
No Yes Replace the fan motor.
Is the fuse normal? between the terminals of
Replace the indoor controller board.
drain pump normal?
Yes
Wiring contact check No
Contact of fan motor connector (CNMF) Replace the drain pump.
Yes
Is there contact failure? Wiring recovery
No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit board.
TEST POINT
: VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC 310~340 V
TEST POINT : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC 15 V
Yes
Is the voltage normal? Replace the fan motor.
No OK
Check the operation of fan. END
Replace indoor
NG
controller board
Replace indoor controller board.
OK
Check the operation END
NG
Replace the fan motor.
OCH413D 28
9-2. FUNCTION OF DIP SWITCH The black square (■) indicates a switch position.
Operation by switch Effective
Switch Pole Function Remarks
ON OFF timing
Thermistor <Room temperature
1 detection> position Built-in remote controller Indoor unit Address board
2 Filter clogging detection Provided Not provided <Initial setting>
ON
3 Filter cleaning 2,500hr 100hr OFF
1 2 3 4 5 6 7 8 9 10
Note :
4 Fresh air intake Effective Not effective *1 Fan operation at Heating
Switching remote Indicating fan operation mode
SW1 5 Thermo ON signal display ON/OFF
display Under *2 Thermo ON operation
Function
suspension at Heating mode
setting 6 Humidifier control Always operated while the heat in ON +1 Operated depends on the condition *2
Airflow set in case of *3
7 Low *3 Extra low *3
thermo OFF SW1-7 SW1-8
8 at heating mode Setting air flow *3 Depends on SW1-7 OFF OFF Extra low
ON OFF Low
9 Auto restart function Effective Not effective OFF ON Setting air flow
ON ON Stop
10 Power ON/OFF by breaker Effective Not effective
ON ON ON
Set while the unit is off.
P32 P63 P125
OFF OFF OFF
SW2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 Before <Initial setting>
Capacity
power
code 1~6 ON ON Set for each capacity.
setting P40 P80 supply
OFF OFF
1 2 3 4 5 6 1 2 3 4 5 6 ON
ON ON
P50 P100
OFF OFF
1 2 3 4 5 6 1 2 3 4 5 6
1 Heat pump/Cooling only Cooling only Heat pump Indoor controller board
Set while the unit is off.
2 Louver/humidifier +6 Available Not available <Initial setting>
ON
3 Vane Available Not available OFF
1 2 3 4 5 6 7 8 9 10
Vane swing function in heating
4 (wave-flow) Available Not available
Note :
SW3 *4 SW3-5, 6
5 Vane horizontal angle
Second setting *4 First setting *4 Under
Function
suspension *5 Please do not use SW3-9,
setting 10 as trouble might be
6 Vane horizontal angle Third setting *4 Depends on SW3-5
caused by the usage
Changing the opening of condition.
7 linear expansion valve Effective Not effective *6 SW3-2 setting
Only for PLFY-P·VBM, SW
is used to change whether
8 Sensible temperature correction Not effective Effective the humidifier functions or
not. (Fixed the louver
9 Superheat setting temperature *5 — — function less.)
SW4 When replacing the indoor controller board, make sure to set the switch to the Indoor controller board
Model initial setting, which is shown below. Before
Selection
(Setting power
for
1~5 ON supply
PLFY OFF ON
series) 1 2 3 4 5
Note : *4 SW3-5,6
SW3-5 SW3-6 Vane setting Initial setting Setting Vane position
OFF OFF Set up
Standard Standard
ON OFF Set up ● Less draft * Upward position than the standard
OFF ON Set up Less smudging Downward position than the standard
ON ON unused — —
* Be careful of smudge on ceiling.
OCH413D 29
Effective
Switch Pole Operation by switch timing Remarks
Address board
78
23
23
SW12 45 6 45 6
(for over 10) at "0", and match SW11 (for 1 to 9) 90 1 90 1
10ths digit with "3".
78
78
23
23
10 1 45 6 45 6
address
setting Before
power
supply Address board
ON
Rotary switch
SW14 How to set branch numbers SW14 (Series R2 only) <Initial setting>
SW14 F01 Match the indoor unit’s refrigerant pipe with SW14
23
BCDE
Branch
the BC controller’s end connection number.
45 6
F01
No.
789A
23
BCDE
Setting 789A
OCH413D 30
Effective
Switch Pole Operation by switch timing Remarks
• To operate each indoor unit by each remote controller when installed 2 indoor <Initial setting>
units or more are near, Pair No. setting is necessary. Pattern A