Sl.
No DESCRIPTION
FEEDER-1 FEEDER-2
CIRCUIT BREAKER
1 CB OPEN 1.1 3.8
2 CB CLOSE 1.2 3.9
3 SPRING CHARGE 2.1 4.3
4 SF6 LOCKOUT 2.2 4.4
5 SF6 LOSS
6 CB AC FAIL
7 CB DC FAIL 2.3 4.5
8 CB MANUAL OPEN COMMAND STATUS
9 CB MANUAL CLOSE COMMAND STATUS
10 CB SELECTOR SWITCH IN LOCAL 3.1 4.6
11 CB SELECTOR SWITCH IN REMOTE 3.2 4.7
12 ANTIPUMPING OPERATED
ISOLATORS & EARTH SWITCHES
13 BUS ISOLATOR CLOSE 1.3 3.1
14 BUS ISOLATOR OPEN 1.4 3.11
15 LINE ISOLATOR CLOSE 1.5 4.1
16 LINE ISOLATOR OPEN 1.6 4.2
OTHERS
17 MASTER TRIP RELAY MCB FAIL
18 86 FAULTY
19 86 RESET OP STATUS 3.3 4.8
20 TRIP COIL 1 FAULTY 3.4 4.9
21 TRIP COIL 2 FAULTY 3.5 4.1
22 ADJ PANEL DC FAIL
23 AC SUPPLY FAIL
24 21 faulty 3.6 4.11
25 ADJ PANEL ETHERNET SWITCH FAULTY 1.7
26 BACKUP RELAY FAULTY 3.7 4.12
BINARY OUTPUT
CB OPEN 1.1 1.5
CB CLOSE 1.2 2.1
86 RESET 1.3 2.2
21 LED RESET 1.4 3.1
BACKUP LED RESET 1.5 3.2
LED
1 2.1
2 2.2
3 2.3
4 2.4
5 2.5
6 2.6
7 2.7
8 2.8
9 2.9
10 2.1
11 2.11
12 2.12
Sl.No DESCRIPTION
FEEDER-2
CIRCUIT BREAKER
1 CB OPEN 3.8
2 CB CLOSE 3.9
3 SPRING CHARGE 4.3
4 SF6 LOCKOUT 4.4
5 SF6 LOSS
6 CB AC FAIL
7 CB DC FAIL 4.5
8 CB MANUAL OPEN COMMAND STATUS
9 CB MANUAL CLOSE COMMAND STATUS
10 CB SELECTOR SWITCH IN LOCAL 4.6
11 CB SELECTOR SWITCH IN REMOTE 4.7
12 ANTIPUMPING OPERATED
ISOLATORS & EARTH SWITCHES
13 BUS ISOLATOR CLOSE 3.10
14 BUS ISOLATOR OPEN 3.11
15 LINE ISOLATOR CLOSE 4.1
16 LINE ISOLATOR OPEN 4.2
OTHERS
17 MASTER TRIP RELAY MCB FAIL
18 86 FAULTY
19 86 RESET OP STATUS 4.8
20 TRIP COIL 1 FAULTY 4.9
21 TRIP COIL 2 FAULTY 4.10
22 ADJ PANEL DC FAIL
23 AC SUPPLY FAIL
24 21 faulty 4.11
25 ADJ PANEL ETHERNET SWITCH FAULTY
4.12
Sl.No DESCRIPTION
CIRCUIT BREAKER
1 CB OPEN
2 CB CLOSE
3 CB SPRING CHARGED
4 CB AC FAIL
5 CB DC FAIL
6 CB MANUAL OPEN COMMAND STATUS
7 CB MANUAL CLOSE COMMAND STATUS
8 CB SELECTOR SWITCH IN LOCAL ON LCC
9 CB SELECTOR SWITCH IN REMOTE ON LCC
ISOLATORS & EARTH SWITCHES
10 BUS DS CLOSE BI
11 BUS DS OPEN BI
12 LINE ISO OPEN BI
13 LINE ISO CLOSE BI
OTHERS
14 86 RESET OP STATUS
15 TRIP COIL 1 FAULTY
16 TRIP COIL 2 FAULTY
17 ADJ PANEL DC FAIL
18 AC SUPPLY FAIL
19 MASTER TRIP RELAY MCB FAIL
20 ADJ ETHERNET SWITCH FAULTY
21 50/51 RELAY FAULTY
Sl.No DESCRIPTION
CIRCUIT BREAKER HV
1 CB OPEN 1
2 CB CLOSE 2
3 SPRING CHARGE 3
4 SF6 LOCKOUT 4
5 SF6 LOSS 5
6 CB AC FAIL 6
7 CB DC FAIL 7
8 CB MANUAL OPEN COMMAND STATUS LCC/CRP 8
9 CB MANUAL CLOSE COMMAND STATUS LCC/CRP 9
10 CB SELECTOR SWITCH IN LOCAL 10
11 CB SELECTOR SWITCH IN REMOTE 11
12 ANTIPUMPING OPERATED 12
BUS ISOLATORS & EARTH SWITCHES
13 BUS ISOLATOR CLOSE 13
14 BUS ISOLATOR OPEN 14
OTHERS
15 86 HV OPERATED 15
16 86 HV FAULTY 16
17 TRIP COIL 1 FAULTY 17
18 TRIP COIL 2 FAULTY 18
19 ADJ PANEL DC FAIL 19
20 AC SUPPLY FAIL 20
21 ADJ PANEL ETHERNET SWITCH FAULTY 21
22 DIFFERENTIAL RELAY FAULTY 22
23 LV BCU FAULTY 23
24 CTD OPERATED
CIRCUIT BREAKER LV
CB OPEN
CB CLOSE
SPRING CHARGE
SF6 LOCKOUT
SF6 LOSS
CB AC FAIL
CB DC FAIL
CB MANUAL OPEN COMMAND STATUS
CB MANUAL CLOSE COMMAND STATUS
CB SELECTOR SWITCH IN LOCAL
CB SELECTOR SWITCH IN REMOTE
ANTIPUMPING OPERATED
LINE ISOLATORS & EARTH SWITCHES
LINE ISOLATOR CLOSE
LINE ISOLATOR OPEN
86 LV OPERATED
86 LV FAULTY
TRIP COIL 1 FAULTY
TRIP COIL 2 FAULTY
ADJ PANEL DC FAIL
AC SUPPLY FAIL
ADJ PANEL ETHERNET SWITCH FAULTY
DIFFERENTIAL/OVER FLUX RELAY FAULTY
HV BCU FAULTY