PROFINET/EtherNet/IP Master Manual
PROFINET/EtherNet/IP Master Manual
User Manual
Revision 1.001
English
Page Dear customer, we thank you for your attention and we remind you that
INDEX 2 you need to check that the following document is:
UPDATED DOCUMENTATION 2
Updated
REVISION LIST 2
WARNING 2 Related to the product you own
TRADEMARKS 2
SECURITY ALERT 3 To obtain the most recently updated document, note the “document code”
EXAMPLE OF CONNECTION 4 that appears at the top right-hand corner of each page of this document.
CONNECTION SCHEME 5
CHARACTERISTICS 6 With this “Document Code” go to web page www.adfweb.com/download/
and search for the corresponding code on the page. Click on the proper
CONFIGURATION 6
“Document Code” and download the updates.
POWER SUPPLY 7
FUNCTION MODES 8
LEDS 9
ETHERNET 10 REVISION LIST:
USE OF COMPOSITOR SW67661 11
NEW PROJECT / OPEN PROJECT 12 Revision Date Author Chapter Description
SOFTWARE OPTIONS 13 1.000 13/03/2018 Ff All First release version
SET COMMUNICATION 15 1.001 10/12/2018 Ff All Revision
ETHERNET/IP ACCESS 16
PROFINET XML 17
UPDATE DEVICE 18
MECHANICAL DIMENSIONS 20
ORDERING INFORMATIONS 21 WARNING:
ACCESSORIES 21
PLC CONFIGURATION (for PROFINET) 22 ADFweb.com reserves the right to change information in this manual about
DISCLAIMER 25 our product without warning.
OTHER REGULATIONS AND STANDARDS 25 ADFweb.com is not responsible for any error this manual may contain.
WARRANTIES AND TECHNICAL SUPPORT 26
Pagina 2 di 26
RETURN POLICY 26
TRADEMARKS:
SECURITY ALERT:
GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and
safety regulation are required for each individual application. The same applies also when using accessories.
INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e.
independent limit switches, mechanical interlocks, etc.).
QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and
who have appropriate qualifications for their job.
RESIDUAL RISKS
The device is state-of-the-art and is safe. The instruments can represent a potential hazard if they are inappropriately installed and
operated by untrained personnel. These instructions refer to residual risks with the following symbol:
This symbol indicates that non-observance of the safety instructions is a danger for people that could lead to serious injury or
death and / or the possibility of damage.
CE CONFORMITY
The declaration is made by our company. You can send an email to [email protected] or give us a call if you need it.
EXAMPLE OF CONNECTION:
CONNECTION SCHEME:
CHARACTERISTICS:
CONFIGURATION:
You need Compositor SW67661 software on your PC in order to perform the following:
Define the parameter of the PROFINET;
Define the parameter of the EtherNet/IP;
Define the list of EtherNet/IP slaves connected to the converter;
Update the device.
POWER SUPPLY:
The devices can be powered between a wide range of tensions. For more details see the two tables below.
VAC VDC
Vmin Vmax Vmin Vmax
HD67661-A1 8V 24V 12V 35V
Device W/VA
HD67661-A1 4
HD67661-A1
FUNCTION MODES:
The device has got two functions mode depending of the position of the Dip2 of ‘Dip-Switch B’:
The first, with Dip2 in Off position (factory setting), is used for the normal working of the device.
The second, with Dip2 in On position, is used for upload the Project/Firmware.
For the operations to follow for the updating (see ‘UPDATE DEVICE’ section).
According to the functioning mode, the LEDs will have specifics functions (see ‘LEDS’ section).
Warning:
Dip1 of ‘Dip-Switch A’ must be at ON position to work even if the Ethernet cable is not inserted.
LEDS:
The device has got six LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.
ETHERNET:
The Ethernet connection must be made using Connector3 or Connector4 of HD67661-A1 with at least a Category 5E cable. The maximum
length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative to connections in cat.5 up to 100 Mbps. To
connect the device to an Hub/Switch is recommended the use of a straight cable, to connect the device to a PC/PLC/other is recommended
the use of a cross cable.
To configure the Converter, use the available software that runs with Windows called SW67661. It is downloadable on the site
www.adfweb.com and its operation is described in this document. (This manual is referenced to the last version of the software present on
our web site). The software works with MSWindows (XP, Vista, Seven, 8, 10; 32/64bit).
When launching the SW67661, the window below appears (Fig. 2).
Note:
It is necessary to have installed .Net Framework 4.
The “New Configuration” button creates the folder which contains the entire device’s configuration.
SOFTWARE OPTIONS:
By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.
SET COMMUNICATION:
By Pressing the “Set Communication” button from the main window for SW67661
(Fig. 2) the window “Set Communication” appears (Fig. 3).
ETHERNET/IP ACCESS:
By Pressing the “EtherNet/IP Access” button from the main window for SW67661 (Fig. 2) the window “Set EtherNet/IP Slaves Access”
appears (Fig. 4).
This section is used to define the list of the EtherNet/IP slaves to read/write with the PROFINET Master.
PROFINET XML:
UPDATE DEVICE:
If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ in ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ in OFF position;
Turn ON the device.
If you know the actual IP address of the device, you have to use this procedure:
Turn ON the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter; Figure 6: “Update device” windows
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.
Note:
When you receive the device, for the first time, you also have to update the Firmware in the HD67661 device.
Warning:
If Fig. 7 appears when you try to do the Update try these points before seeking
assistance:
Check if the serial COM port selected is the correct one;
Check if the serial cable is connected between the PC and the device;
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
If you are using the program inside a Virtual Machine, try to use in the main
Operating System;
If you are using Windows Seven, Vista, 8 or 10 make sure that you have the
administrator privileges;
In case you have to program more than one device, using the "UDP Update", you
have to cancel the ARP table every time you connect a new device on Ethernet. For
do this you have to launch the "Command Prompt" and write the command "arp -
d". Pay attention that with Windows Vista, Seven, 8, 10 you have to launch the
"Command Prompt" with Administrator Rights;
Pay attention at Firewall lock. Figure 7: “Error” window
Warning:
In the case of HD67661 you have to use the software “SW67661”: www.adfweb.com\download\filefold\SW67661.zip.
MECHANICAL DIMENSIONS:
ORDERING INFORMATIONS:
Connectors Type
1: Removable 5mm Screw Terminal
Enclosure Type
A: 1M, 35mm DIN Rail mounting
Device Family
HD67661: PROFINET / Ethernet/IP Master - Converter
ACCESSORIES:
PLC CONFIGURATION:
The configuration and commissioning of the PROFINET Converter as described on the following pages was accomplished with the help of the
TIA Portal software by Siemens. In the case of using a control system from another supplier, refer to attend to the associated
documentation.
These are the steps to follow:
1) Install the description file of the module.
2) Import the module in the network; connect the device to the PLC network and edit the parameters of IP, station name etc.
DISCLAIMER:
All technical content within this document can be modified without notice. The content of the document is a under continual renewal.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.
WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and impact of human health, which could otherwise be
caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about
recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.
CE MARKING
The product conforms with the essential requirements of the applicable EC directives.
For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]
RETURN POLICY:
If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).