Mechanical Works Technical Specifications University Baghdad
Mechanical Works Technical Specifications University Baghdad
SPECIFICATION
Technical Requirements
DRAFT
AFCEE Iraq Interim Construction Standards 2 Mechanical Services
CONTENTS
a) General: The water chiller shall use a halocarbon refrigerant and complete with
cooler, condenser, compressor, electric motor, instrument and gauge panel,
operating and safety controls, vibration isolation bases and all required auxiliaries.
Assembled units shall be pressure and leak tested, then evacuated, charged with
refrigerant and lubricating oil and given an operating test before shipment.
According to ARI standard or ASME code.
c) The motor shall be suitable for 3 phase 400 volts and 50Hz with main power
factor of 0.91 at full load 0.8 at 20% capacity.
e) Cooler and Condenser: Cooler and condenser shall be shell and tube type
designed for 10atm water side working pressure, with replaceable integral
seamless finned copper tubes mechanically expanded into steel tube sheets.
Intermediates tube supports shall be provided to prevent motion between the
tubes. Cooler shall be provided with properly designed baffles and eliminates of
anti-corrosive durable materials to prevent carry-over of refrigerant. Condenser
shall be provided with adequate gas distribution passages and a perforated plate
impingement baffle.
f) Insulation: Evaporator section with all associated piping and water heads and
motor casing shall be factory insulated with closed cell foam insulation. No
condensation of water vapor shall be allowed at all external cold parts of the
machine.
g) Controls: Automatic control system shall be electric type. All safety and control
devices shall be suitable for 220v, single phase, 50Hz AC. Provide control panel
of an approved design, completely factory wired and contains, at minimum, the
following built-in devices:
The control console also contains safety controls for high oil temperature,
high motor temperature, and low oil pressure to prevent the machine from
operating if one of the safety controls registers abnormal conditions. All safety
controls, except the low oil pressure, shall be arranged in a lockout circuit
provided with reset push-button and individual pilot lights on the face of the
panel.
A suitable capacity controller shall be provided with a load limit device to
limit the current to the compressor motor to a safe maximum, and a demand
limiter device from 40% to 100% full load current. Provide pump starter
interlocks, pressure stat or flow switches so that unit cannot operate unless full
flow is provided in condenser and cooler water circuits.
h) Capacity Control: Capacity control system for each unit shall consist of
automatically controlled cast bronze variable inlet guide vanes which provide
continually variable capacity from 10% to 100% output.
Vanes shall be driven by an electric operator under the control of the water
temperature thermostat. System includes automatic stopping at minimum return
water temperature and automatic re-starting. Provide a timing device to prevent
more than two starts in one hour period. Main motor is protected against overload
operation by regulating inlet guide vanes through the current limiting device.
i) Purge System: Provide a purge system for each unit. System shall consist of
motor driven compressor and an electrically heated oil separator, suction pressure
regulating valve, automatic on-off electronic device, SERVICE valve, condenser
and sectionalized separator drum permitting separation of the non-condensable
gasses and water. A valve relieves non-condensables to atmosphere and a float
valve returns refrigerant to the evaporator. The purge system shall be provided
only when a sub-atmospheric refrigerant is used.
l) Pipe Connection: The machine has water boxes of flanged pipe connection in the
piping adjacent to the machine to allow removal of headers for inspection,
cleaning, or removal tubes. Two 15mm valved connection shall be provided in
water lines at machine side or the condenser and evaporator shut-off valves for
future chemical cleaning.
m) Installation: Unit shall be set on a flat level suitably reinforced concrete pad as
shown or drawings – spring type or corrugated rubber pads isolators shall be used
between the unit and the floor.
a) Type: The electric hot water boiler shall be a complete package, factory
assembled, and ready to be connected to service wiring and water piping.
b) Capacity: The capacity shall be as shown on the drawings and indicated in the
schedule.
e) Tank: Tank shall be fully isolated with a minimum of 2" (50mm) fiberglass
insulation and equipped with a steel jacket having a minimum of 18 gauge steel
with enamel finish. Tank shall be unconditionally guaranteed for twenty years
against all defects in workmanship and materials and shall be constructed and
stamped in accordance with the latest applicable ASME code and pressure vessel
inspectors.
f) Valves and Connections: The boiler vessel shall be equipped with flanged inlet
and outlet. All valves shall be rated not less than 150 psig (10.55 kgm/cm2) and
have replaceable seats.
g) U.l. Label: The complete package shall be supplied with U.L. certification and
labeling.
h) Operation: The hot water circulating pump shall start first manually, then the
electric heater(s) are energized. The heating element of the electric water boiler
shall be interlocked to prevent energized when the hot water circulating pump is
not operating.
3- Cooling Tower
a) General: Cooling tower shall be of the type, and have the capacity, shown on the
schedule. It shall be complete with casing, basin, hot water distribution, float
valve, fan(s), drain connection, overflow connection, bleed off connection and
suitable mounting base. Tower shall be treated for corrosion protection coat.
b) Casing: Casing shall be manufactured of steel not lighter than 16 gauge, hot dip
galvanized after fabrication. Construction shall be welded or bolted with stainless
steel or hot dip galvanized steel bolts.
d) Fill: Tower fill shall be manufactured of hot dip galvanized steel or polyvinyl. Fill
shall be free to expand and contract without deformation or warping. It shall be
suitably supported to eliminate sagging.
e) Fan: Fan shall be of the type shown on the schedule, constructed of hot dip
galvanized steel (after fabrication) or aluminum and suitably mounted. Fan shall
be statically and dynamically balanced at the factory. Fan drive shall be as
specified on the schedule. Fan bearings shall be of the heavy duty type and
mounted in an accessible location. Bearings shall be provided with accessible
lubrication fittings. All fans, drives and motors shall be provided with guards and
screens.
f) Collection Basin: Basin shall be constructed of heavy 10 gauge (or heavier) steel
plates and shall be hot dip galvanized after fabrication. Basin shall be provided
with float valve assembly, overflow, drain and screened non-cavitating pump
suction.
h) Motor: Motor shall be suitable for outdoor use and with isolation class "F" for
high ambient temperature. Drives shall be v belt taper lock sheaves selected for
150% of the motor horse power. Galvanized steel drive guards shall be provided
on-all belt drives.
j) Supports: Tower shall be provided with suitable weather and corrosion protected
mounting base manufactured of steel I-beam or channels.
k) Capacity: Rated capacity shall be based on 4400 watts (15000 btu/hr), heat
rejection capacity for each rated ton of refrigeration.
4-(A) Split Type Air Conditioner with Air Cooled Condensing Unit
a) Unit: The air conditioner shall be a split-type air conditioner for application with
R-22 refrigerant, and shall be composed of a cooling unit and a condensing unit,
with one or two refrigeration cycles, electrical and enclosing cabinets. Optional
accessories shall also be provided upon customer request. The condensing unit
shall be completely weather proof for outdoor installation, and the cooling unit
shall be designed for indoor installation. The condensing unit and the cooling unit
shall be properly assembled, internally piped and wired, and thoroughly tested
and holding charged with R-22 refrigerant at the factory.
c) Condensing Unit:
4. Condenser fan and condenser fan motor: The condenser fan shall be the
aluminum propeller type, dynamically and statically balanced, and the condenser
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 9 Mechanical Services
fan shall be directly driven by a motor for up-flow air discharge. The motor shall
be permanently lubricated, and protected from water invasion.
5. Condenser: The air cooled coil shall be the multi pass, cross-finned tube type,
equipped with high efficient aluminum fins, mechanically bonded to oxygen-free
copper tubes. The coil shall be cleaned, dehydrated and tested for leakage at the
factory.
d) Cooling Unit:
1. Evaporator: The evaporator shall be the multi pass cross-finned tube type,
equipped with high efficient aluminum fins, mechanically bonded to seamless,
oxygen free copper tubes. The fins shall be spaced at max. 12 fins per 25.4 mm.
the coil shall be cleaned, dehydrated, and tested for leakage at the factory.
2. Evaporator fan and evaporator fan motor: The evaporator fan shall be the
forward-curved, multi-blade centrifugal type, statically and dynamically
balanced, and v-belt or direct-drive fan motor. The evaporator fan motor shall be
permanently lubricated.
e) Control: All electrical control devices, except for the field-supplied room
thermostat assembly, shall be enclosed in a weatherproof location of the unit. In
addition to the compressor protection devices, the unit shall be provided with
fuses for the control circuit, and auxiliary relays.
a) Capacity: The total cooling capacity of the air-cooled split air conditioners shall
be indicated on drawings.
b) Indoor Unit
4. Evaporator Coil: The evaporator coil shall be the multi-pass cross-finned tube
type, equipped with aluminum plate fins, mechanically bonded to seamless
oxygen-free copper tubes. The fins shall be spaced at more than 12 fins per
25.4 mm. the coils shall be cleaned, dehydrated and tested for leakage at the
factory.
c) Evaporator Fan Section: The evaporator fan(s) shall be the forward curved
centrifugal type, statically and dynamically balanced, and belt driven by a motor
or with direct drive type fan motor. The fan motor shall be permanently
lubricated.
1. Filters – washable filters shall be equipped at the air intake of the unit.
3. Control – the unit shall be equipped with operation switch(es), pilot lamp(s) and
a thermostat mounted on the unit control panel. The operation switch shall
include a OFF-ON-COOL (HEAT) three position push button switch and a
COOL-HEAT selection switch. The operation control shall conform to manual
starting, automatic continuous operation whenever the thermostat requires and
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 11 Mechanical
Services
the protection devices allow, and a manual resetting system after activation of a
protection device.
d) Outdoor Unit
1. Cabinet - the cabinet shall be constructed of finished steel, baked with synthetic
resin paint. The fan guard wire net shall be mounted on the top of the unit.
4. Condenser Fan and Motor – The condenser fan(s) shall be the aluminum
propeller type, statically and dynamically balanced, and each fan shall be
directly driven by a motor for up-flow air discharge. The motors shall be
permanently lubricated, and shall be protected from water invasion.
a) The contractor shall finish and install air cooled through the wall air conditioner
in the buildings as indicated on the drawings.
b) Total cooling capacity for each shall be as indicated on the drawings. Unit
temperature according to climatic conditions given in the specifications.
c) Total heating capacity for each shall be as indicated on the drawings. Heaters
shall be electric type.
d) Controls shall be factory wired and completely enclosed within the unit, fan
control shall be 2 or 3-positions switch for high medium and low fan speeds for
cooling and heating. Exhaust vent control shall be to close the vent, or opened to
introduce fresh air to the room.
e) The compressor shall be rubber shock mounted and internally spring mounted for
quiet operation and vibration isolation. The compressor shall be hermetically
sealed steel case and sprayed with black epoxy paint.
f) Evaporator and condenser coils shall have copper as the primary surface and
aluminum fins for the secondary surface acopillary restrictor shall be the metering
device for the refrigeration system.
g) Evaporator and condenser fans shall be direct driven with a common motor.
Evaporator fan shall be centrifugal type and condense fan shall be propeller type.
h) Air deflectors shall be provided on the discharge air grille for adjustment of
supply air in vertical and horizontal directions.
a) The unit shall be of the completely self contained horizontal with factory wired
controls and factory assembled components and piping. The unit shall be
completely weather proof for outdoor installation. Unit shall include air-cooled
condenser, direct expansion evaporator, supply air fan, hermetic compressor,
expansion valve, liquid line sight glass, filter drier, control panel, electric heater,
complete charge of refrigerant R-22, and all operating and safety controls.
c) Casing: The casing shall be constructed of zinc coated steel, phosphatized with
epoxy resin prime and finished with enamel for weather proof protection. All
cabinet panels shall be 16 gauge steel. Removable panels shall provide access to
all working parts. Supply air fan enclosure shall be lined with 25 mm fiber glass
coated with heavy layer of betchumastic material.
d) Condenser Fan and Motor: The unit shall be furnished with direct driven
propeller type fans arranged for vertical discharge. Condenser fan motor shall be
totally enclosed, weather proof type insulated and shall be of the permanently
lubricated type, resiliently mounted. Each fan shall have a safety guard and
integral water slinger device.
e) Compressor: The unit compressor shall be of the hermetic design with external
spring isolators and crank case heater.
f) Coils: Condenser and evaporator coils shall be constructed of aluminum plate fins
mechanically bonded to copper tubes.
g) Fan: The indoor air fan shall be of the forward curved centrifugal type double
inlet, belt driven by an electric motor, bearings shall be of the permanently
lubricated type. Motor shall be provided with variable pitch pulley.
h) Filters: The unit shall be provided with 25 mm thick washable filters. Filters
media shall be non-ferrous wire mesh. If the unit is not provided with a filter box
in the return air duct. Air velocity through the filters shall not exceed 2.5 m/sec.
i) Heaters: The unit heater shall be of the electric resistance type. Each heater
assembly shall include circuit breakers, contactors, manual reset high temperature
limiting device and air flow switch.
j) Control: The unit shall be supplied with a remote, wall mounted control
thermostat. This device shall include manual adjustable room thermostat, suitable
for heating and cooling, On-Off switch, Heat-Cool selector switch. The operation
of the indoor supply fan shall be effected by the On-Off switch. Cooling cycle
operation shall be under the control of the room thermostat and the satisfaction of
all cooling safety devices. Heating cycle shall be under the control of the room
thermostat and the satisfaction of all the heating safety devices. An interlock shall
be provided to ensure the operation of the cooling or heating cycles only if the
indoor supply fan is energized.
7- Cold Rooms
Construction of Cold Rooms: The construction of the cold stores shall be vermin, insect
and termite proof. Shall consist of:
a) Walls and Ceilings: Shall be insulated with 100mm thickness polyurethane foam
(K factor 0.0224 watts/ m o C) internally and externally finished in white plastic
covered 24 gauge sheet steel except where built into structural frame.
c) Construction – shall be in sectional panels with male and female edges, locked
together by an interior operated gear/cam locking device, 3 per side section edge
and 2 or 3 per top and bottom. Corners shall be made with purpose-made section
panels (no join between sections at corner). All joint between sections shall be
suitably sealed with a non-hard setting mitic or similar. Bungs shall be provided
in the locking device access holes.
strip type heated door seal. Locks shall be provided on all doors and shall be of
the staple lock type with quick release service for internal use.
Galvanized door cills shall be provided to protect the cold store edges. The
deep freeze store shall have a pressure relief valve mounted in a wall panel
section adjacent to the door for pressure equalization purposes. All stores shall be
fitted with a bulkhead lighting fitting with protective glass cover and switched
from outside the cold stores. A 100mm dial thermometer located outside the store
and mounted adjacent to the door with remote sensing bulb suitably located
within the store shall be provided on each door. Doors shall be labeled with an
engraved aluminum plate stating the cold store chamber, store function and
normal operating temperature.
e) Evaporators: Each cold store shall be provided with a 1/240/50 fan assisted,
ceiling mounted. The evaporator shall be suitable for and matched to a
compressor unit with remote air cooled condenser connected by refrigerant mains.
The evaporators shall have plastic covered steel casings containing
copper/aluminum finned coils, propeller fan or fans, drip tray, automatic de-frost
or de-frost cycle as required, dual thermostatic temperature control of fans (two
thermostats), 25 mm condensate drain to drainage channel (heated tracer cable on
deep freeze and meat cold store) and fain-safe thermostat on de-frost heaters. Fan
motors shall be drip-proof induction type with an insulation class to suit
application.
g) Condensers: All condenser fans shall be the induction type drip proof running at
1425 rpm and shall have a class of insulation to suit the operating temperatures.
Units shall be suitable for a 3/400/50 electrical supply. The condensers shall be
mounted on a purpose-made steel frame partition fixed across the compressor
room to provide an inlet plenum chamber and discharge air chamber which shall
discharge to outside the compressor room.
h) Refrigerant pipe work: Refrigerant pipe work shall be in standard copper tube to
BS. 2017/C with all welded fittings and complete with sight glasses, dryers and
pipe work insulation section of the specification.
i) Controls: The wall mounted control(s) constructed to match all other motor
starter control panels specified elsewhere, shall be provided with direct on line
starters, run and trip lights and On-Off auto rotary switches for the control of the
complete cold store refrigeration equipment, including the wall mounted extract
fans. The cold store shall be integrally wired back to a central externally located
terminal block for the main electrical connection of fans, lighting and heater
tapes, etc.
a) Type: The humidifier shall be of the steam grid type with distributors located in
the ductwork and the separator mounted outside the duct work.
c) Distribution pipe: The distribution pipe shall be of the stainless steel steam
jacketed type with air foil upstream and team outlets downstream. The
distribution pipe shall be approximately as long as the duct is wide to assure even
distribution across the face of the air stream.
The distribution pipe shall be of such a design that any condensate formed
in the pipe between the humidifier and the manifold instantly reevaporates when it
reaches the section heated by the jacket. The manifold shall be complete with
internal stainless steel silencing mesh to prevent whistling of the steam.
d) Trap: Provide and install a condensate drip trap of the inverted bucket type, size
and piping as recommended by the manufacturer.
e) Humidifier Body: The humidifier body shall be complete with steam jacketed
valve, steam jacketed reevaporating chamber and muffling screen. The body shall
be constructed of steel and shall be suitable for 860 Kpa working pressure.
f) Strainer: Provide and install a 0.045 inch perforated strainer ahead of the
humidifier body.
g) Control: The control of the humidifier shall be as shown on the drawings. The
control valve shall be interlocked with a sail switch to prevent steam from
entering when there is no air flow in the duct.
h) Mounting: The humidifier body shall be supported from the building structure in
an approved manner and shall not be supported from the ductwork unless
additional supports are provided.
i) Piping: Run the stream supply pipe from the steam header to the humidifier as
follows:
1. Take steam supply line from the top of the supply main, never from the side or
bottom. If several humidifiers take steam from a single supply line, be sure to
trap the end of the run-out.
3. Clean piping – after running the supply line, blow down at full steam pressure
to eliminate dirt and pipe cuttings.
a) Type: The pump shall be of the centrifugal base mounted type, specially designed
and constructed for quiet operation.
c) Pump: The pump shall be of the horizontally split case, double suction design,
making possible complete servicing without breaking piping or motor
connections. The motor to pump connection shall be of the flexible coupler type.
The pump shall use a mechanical rotating type carbon seal and shall face against a
tungsten carbide insert. The pump shall be equipped with oil lubrication sleeve
bearings for smooth and quiet operation.
d) Motor: The motor shall be drip proof, 1450 rpm and shall be specially selected
for quiet operation and shall be so stamped. The current characteristics shall be as
shown on the schedule. The horse power of the motor shall be of such a size to
ensure non-overloading of the motor throughout the capacity range of the pump.
e) Base: The base shall be of size suitable for the pump, motor, and shaft, and shall
be constructed of cast iron or welded steel.
f) Installation: A concrete base, 20 cm (8") higher than the surrounding floor shall
be provided. Construct the base and install as shown by the detail on the
drawings. The pump base shall be set on a vibration elimination pad designed for
resilient material moulded of neoprene 8 mm (5/16") thick, across ribbed
construction.
g) Lubrication: After completion of the system and before startup of the pump, the
pump shall be lubricated in strict accordance with the manufacturer's instructions.
A metal instruction plate shall be attached to the pump in a location where it is
clearly visible. These instructions shall indicate the recommended lubricant, the
points of lubrication and the recommended frequency of lubrication.
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 17 Mechanical
Services
h) Pump Alignment: The contractor shall check, test and start each pump and shall
have the pump manufacturer align the pump with a dial indicator within 0.05 mm
(0.002"). Discharge and suction pressure readings shall be recorded and
forwarded to record purposes.
a) Type: The pump shall be of the centrifugal base mounted type, especially
designed and constructed for quiet operation.
c) Pump: Shall be of the vertically split case, end suction design, making possible
complete servicing without the need to disturb the connecting pipe-work and
pump foundation. Motor to pump connection shall be of the flexible coupler type.
The pump shall use a mechanical rotating type carbon seal and shall face against a
tungsten carbide insert. The pump shall be equipped with oil lubricated bronze
sleeve bearings for smooth and quiet operation.
d) Motor: Shall be drip proof, 1450 rpm and shall be specially selected for quiet
operation and shall be so stamped. The current characteristics shall be as shown
on the schedule. The horse power of the motor shall be of such a size to ensure
non-overloading of the motor throughout the capacity range of the pump.
e) Base: Shall be of a size suitable for the pump, motor, and shaft, and shall be
constructed of cast iron or welded steel.
f) Installation: A concrete base, 20 cm (8") higher than the surrounding floor shall
be provided. Construct the base and install as shown by the detail on the
drawings. The pump base shall be set on a vibration elimination pad designed for
resilient material moulded of neoprene 8 mm (5/16") thick, across ribbed
construction.
g) Lubrication: After completion of the system and before startup of the pump, the
pump shall be lubricated in strict accordance with the manufacturer's instructions.
A metal instruction plate shall be attached to the pump in a location where it is
clearly visible. These instructions shall indicate the recommended lubricant, the
points of lubrication and the recommended frequency of lubrication.
h) Pump Alignment: The contractor shall check, test and start each pump and shall
have the pump manufacturer align the pump with a dial indicator within 0.002"
(0.05 mm). Discharge and suction pressure readings shall be recorded and
forwarded to record processes.
11- Piping
a) Pipe Material – all system piping, except as noted below shall be black steel,
class B, schedule 40, or equivalent with 10.5 kg/cm2 (15 psi). Steel welding
fittings and neck welding flanges were connected to valves or other flanged
equipment. Condensate drain piping shall be galvanized steel of adequate size to
carry away the condensate at the rate it is formed, and piping less than 65mm
diameter shall be screwed, and 65 mm diameter and above shall be welded.
b) Pipe workmanship:
1. All piping shall be installed straight and parallel or perpendicular to the
building construction.
2. Piping shall be pitched to allow air to be vented to system high points and to
allow the system to be drained at the low points. Provide drain pipes at the
base of each riser and at all low points and wherever required to permit
complete draining of all lines.
3. Make all changes in sizes and directions of piping with fittings. Do not use
mitre fittings, face or flush bushings, close nipples, street elbows or bendings.
6. Piping shall be installed with bonds and offsets to take the expansion. Wherever
this is not possible for physical reasons, expansion joints shall be used.
7. Use unions and/or flanges to allow easy dismantling and maintenance of the
piping system.
8. All water pipe rises shall be furnished with 300mm long dirt pocket, equipped
with hose gate valve.
c) Pipe Installation:
and avoid interference with other work. Due to small scale of drawings, the
required offsets, fittings, valves, drains, etc.., may not be indicated. The contractor
shall refer to and carefully check architectural, structural, electrical, and
mechanical drawings and details, note locations of walls partitions, ceiling,
beams, columns, etc.., and arrange the piping installation accordingly and furnish
all necessary fittings, offsets, valves, etc.., required to meet such conditions.
Piping shall be run as straight and direct as possible, in general forming right
angles with or parallel with walls or other piping and neatly spaced. Piping shall
be installed with approved offsets around obstruction, necessary expansion joints,
expansion bends wherever required pipe installation shall be in accordance with
the procedure established in the American Standard Code for pressure piping.
Eccentric reducers shall be used where required to permit proper drainage and
venting of pipe lines. Drain valves shall be provided in all piping system at low
points and where otherwise indicated on the drawings. Low points of water shall
be provided with 15mm valve, nipple and 15mm hose coupling. Air vents shall be
provided in all high points of piping systems. Piping shall be erected in such a
manner as to provide for expansion and contraction shall be provided at inlet and
outlet of every cooling and heating coil.
d) Pipe connections:
2. Install all inlet and outlet piping to coils, pumps, gate valves, strainers, control
valves and other equipment at full line size with the reduction being made to the
size of tapping of the equipment being served.
3. All flange joints shall be made up with compressed type asbestos gaskets. Gasket
shall be 1.6mm thick.
1. Support, anchor and guide all piping to preclude failure or deformation. Construct
and install hangers, supports, anchor guides and accessories to the approval of the
engineer. Do not use wire, tape, or metal bands. Hanging pipes from other pipes
will not be permitted.
4. Supports spacing and hanger rods diameter shall conform to the following
schedule:
5. Hangers shall consist of galvanized steel, rods, lock nuts swivels, couplings,
brackets as shown on the drawings.
f) Pipe Sleeves:
1. Provide all pipe openings through walls, partitions and slabs with sleeves having
and internal diameter of at least 50mm larger than the outside diameter of the
pipe.
3. Fill the space between the outside of insulation (or pipe) and inside of sleeve with
fiberous asbestos or water tight mastic
Pipe Tests:
a) Scope: All piping installed on the project unless specifically shown otherwise
shall be hydraulically tested as specified herein. Refrigeration piping, if used on
the project, shall be tested as specified under refrigeration piping. The contractor
shall provide all equipments required to make the tests specified herein.
c) Test to be performed: The contractor shall fill the pipe to be tested with water
and bring the section up to pressure with a test pump. The tests shall be conducted
by the contractor in the presence of the consultant or his representative. These
tests shall be conducted before any insulation is installed and any insulation
installed prior to these tests shall be removed. Gauges used in the tests shall have
been recently calibrated with a dead weight tester.
d) Duration of Tests: All these tests shall apply full test pressure to the piping for a
minimum of twenty-four hours.
e) Pressure of Tests: All tests shall be conducted at the water working pressure of
the pipe installed. When class B or medium weight pipe is used, the test pressure
shall be 1.5 times the working pressure indicated on the schedules.
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 21 Mechanical
Services
f) Inability to Hold Pressure: When the test pressure has fallen over 5% during the
twenty-four hours test period, the point of leakage shall be found, repaired and the
test repeated. This procedure shall be followed until the piping system has been
proven absolutely tight.
h) Delicate Controls: When delicate control mechanisms are installed in the piping
system, they shall be removed during the tests to prevent shock damage. This
does not apply to control valves.
i) Leaks: Leaks developing subsequent to these tests shall not be repaired by mastic
or other temporary means. All leaks shall be repaired by removal of the valve,
fitting, joint or section that is leaking and installing new material with joints as
specified herein before.
12- Valves
b) Gate Valves: Gate valves shall be of the wedge disc type, permit straight line
flow, complete shutoff and designed so that when the valve is wide open it can be
packed under pressure. Valves 50 mm (2") and smaller shall be bronze, with
screwed ends and non-rising stem. The valve shall have a deep stuffing box for
long contact with the stem, packing gland and filled with high quality packing.
Valves 65 mm (2.5") through 100 mm (4") shall be iron body bronze valves for
working pressure of 1034 kN/m2 (150psi) and iron valves for working pressure
862 kN/m2 (125psi) when installed in class B piping.
c) Check Valves: Check valves shall be horizontal swing type with two piece
hinges, disc and seat shall be bronze or with composition face, depending on
service. Valves 50 mm (2") and smaller shall be bronze, with screwed ends, have
full area Y pattern body and integral seats. Valves 65 mm (2.5") and larger shall
be cast iron body brass mounted and with flanged ends. Working pressure for
check valves shall be 862 kN/m2 when installed in class B piping. Check valves at
pump discharge shall be non-slam or silent check. Valve disc shall close before
line flow can reverse to eliminate slam and water hammer due to check valve
closure.
d) Globe Valves (Regulating Valves): Shall permit control of flow rate from full
flow to complete shut-off and shall be designed that when the valve is wide open
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 22 Mechanical
Services
it can be repacked under pressure, and have a deep stuffing box with gland and
filled with high quality packing. Valves 50 mm (2") and smaller shall be bronze,
with screwed ends, unions bonnet, and with stainless steel plug type disc and seat
of not less than 500 Brinnel hardness. Valves 65 mm (2.5") and larger shall be
cast iron body bronze mounted with flanged ends, yoke bonnet and disc guide.
Working pressure for valves shall be 10.5 kg/cm2 when installed in class B
schedule 40 piping.
e) 3-Way Valves and 2-Way Valves: Two and three way valves shall be globe
type. Valves up to 50 mm (2") size shall be bronze with screwed connections and
valves 65mm (2.5") and larger shall be cast iron, bronze or stainless steel trim
with flanged connections. Two way valves shall be of equal flow characteristics
while three way valves shall have linear flow characteristics. Valves shall have a
constant total flow throughout plug travel. All valves shall be provided with
spring loaded, self adjusting to flow packing and renewable seats.
f) Relief Valves: Relief valves shall be of self closing type with test lever, and arms
with copper float, and shall be of the globe type, single seated dead and service
suitable for a pressure of 5 atmosphere, with screwed ends.
g) Butterfly Valves: Butterfly valves shall be of the rotary disc type, permit straight
line flow, complete shut-off and designed so that when the valve is wide open it
can be packed under pressure. Valves 50 mm (2") and smaller shall be bronze,
with screwed ends. The valve shall have a deep stuffing box for long quality
packing. Valves 65 mm (2.5") and larger shall be cast iron body, bronze trim with
flanged ends, bolted bonnet. All valves shall be suitable for a steam working
pressure of 10.5 kg/cm2 when installed in class B schedule 40 piping.
a) Fittings:
1. Fittings for welded pipes shall be of the butt welding type with beveled ends
and shall be seamless steel. Fittings shall have the same wall thickness and
schedule as the attached pipe.
2. welding neck or slip on flanges shall be of forged steel with 1.6mm raised
face and shall be suitable for a working pressure equal to or greater than the
working pressure of accompanying pipe.
b) Unions: Unions shall be provided at the following locations and where shown on
drawings:
Unions shall not be concealed in walls, partitions or ceiling. Types and quality
of unions used shall be as described in item covered under 'fittings'.
c) Joints:
1. Joints on galvanized steel pipes shall be screwed type for sizes 50mm and
smaller.
2. Threads shall be cut to the full thickness of disc. After joining, not more than
two threads shall be left outside. Compound used shall be of approved make
and shall be applied smoothly. After inspection and final approval, the
exposed threads shall be coated with red lead.
3. Each piece of pipe shall be carefully reamed prior to erection and carefully
inspected before installation.
4. Joints on pipes of sizes 65mm and larger shall be welded type. All welding
shall be done by the metallic arc process. Before welding, the base material
shall be cleaned of all slag, oil, grease, scale and rust. Edges and surfaces of
the parts to be joined by welding shall be well prepared for the type of weld to
be used. Each completed layer of weld shall be thoroughly cleaned with
hammer and wire brush before the next layer of weld is laid. Any sweating of
joint under hydrostatic test shall cause for its rejection and removal.
The "Y" type strainer in sizes 2" (50mm) and smaller shall be bronze and shall
have screwed connections. Strainers in sizes 2.5" (65mm) and larger shall be cast iron
and shall have flanged connections. Screens shall be bronze, monel metal or stainless
steel with perforations as follows:
The free area of each screen shall not be less than 3 times the area of the strainer
inlet pipe. The "Y" type strainer shall be installed where shown on drawings. Strainer
shall be suitable for a working pressure of 10.5 kg/cm2.
Duplex strainer shall be disc valve type. The strainer body shall be cast iron or
fabricated carbon steel, rated for not less than 10.5 kg/cm2. The basket shall be stainless
steel with perforated backing. Pressure drop across the strainer body shall be not more
than 0.07 kg/cm2 (1 psi) when the basket is 2/3 dirty at maximum system flow rate.
Where necessary, provide reducing fittings from strainer flange size to pipe size.
Provide a differential pressure gauge across the strainer or a pressure gauge with 0.0175
kg/cm2 (0.25 psi) graduations fitted with two way brass cock. Provide manual air vent
cocks in cap of each strainer.
A flexible connector shall be installed at inlet and outlet ports of all units
wherever shown on the drawings. Corrugated inner tubing shall be of stainless steel
construction. Outer shield shall be stainless steel wire braid. Flanges shall be of stainless
steel construction.
b) Pressure gauges: Contractor shall provide pressure gauges of the Bourden tube
type with 100 mm diameter dial, case shall be of drawn steel with friction fit steel
ring, both finished black. Range of pressure gauge shall be as required for the
service and pressure in the system so that measured variable shall be at about mid-
range of gauge scale. Accuracy shall be within 1% numbers shall be black on a
white background. Each gauge shall have a shut-off cock. All pressure gauges
shall be calibrated before supply and certificate of the laboratory where calibrated
submitted. They shall be installed at the following locations: on supply and return
of all chillers, condensers and boilers. On suction and delivery of all pumps,
wherever else indicated in the specifications. Gauge connections at inlet and
outlet of every coil.
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 25 Mechanical
Services
c) Water Flow Meters: – contractor shall supply water flow meters as shown on the
drawings. The meter shall be designed for the accurate measurement of water
flow rate in pipe sizes ranging from 20mm (0.75 inch) diameter to the largest
diameter pipe given in the bill of quantities and for flow rate ranging from 4m3/hr
to the largest flow rate as in the bill of quantities. The above meter shall consist of
the following components:
1. Orifice flanges with orifice plate for inserting into the main pipeline in which
the meter is required to be installed.
3. A range orifice or orifices for insertion into the by-pass. Pipeline, alternatively
venturi tube assembly may be supplied.
4. Rota meter of suitable calibration in order to read the water flow directly for
any flow rate within the range specified above. The rotameter shall be used at
the start-up of the plant to measure and fix design flow rates of water to all the
air handling units, chillers, condensers, cooling towers, etc.., wherever
necessary regulation of flow will be done by means of 6mm (0.25 inch) thick
stainless steel orifice plate at inlet of each equipment. The plate will be fixed
permanently between flanges after regulation at design quantity is achieved.
After regulation is done, the meter will be removed and an adapter installed
which should be easily removable to enable the meter to be reinstalled for
checking flow wherever required. For this purpose the contractor shall include
for the supply and installation of orifice plates/venturi tube assembly, flanges,
adapter and all necessary accessories. The accuracy of the flow meter shall be
with ±1%.
18 - Air Vents
Automatic air vent on pumps, mains, high points of system and where indicated
on the drawings shall be of ball float construction. Vent inlet shall be not less than 20mm
(0.75") TPS. Outlet shall be not less than 7.5mm (0.25") TPS. Orifice shall be 3.175mm
(1/8"). Float and trim shall be of stainless steel construction. Vent shall be fitted with try-
cock (discharge valve) which normally stays open. Vent shall discharge air at any
pressure up to 10.5 kg/cm2 (150psi).
Unit shall be used to monitor filter performance in the fresh air duct to A.H.U. it
shall be constructed of two parts, lower part shall be made of plastic and shall contain
two pressure chambers separated by a diaphragm. The upper part shall contain the
electrical connections. The membrane shall transfer the differential pressure to a lever
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 26 Mechanical
Services
which activates the contact of the snap element. Switching point shall be continuously
adjustable with an adjustment screw, adjustment range AP shall be 0.3 – 2m bar (30 –
200 PA).
ﻣﻔﻘﻮدة113 ﺻﻔﺤﺔ
Safe pressurizing agent such as dry nitrogen shall be used with adequate gauges
and pressure regulators to maintain a safe operation. Compressed air, oxygen or
acetylent shall not, under any circumstances, be used for pressure testing. No
attempt shall be made to repair a leak while the system is under pressure, should a
leak be found, the pressure shall first be relieved, and then the joint shall be taken
apart, cleaned and remade as a new joint.
After the system has been proven tight by the soap suds test, all nitrogen
shall be discharged to atmosphere and the system shall be charged with small
quantity of refrigerant. The entire system shall then be checked will halide or
electronic leak detector.
a) Open Type
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 27 Mechanical
Services
1. Type - the fill tank shall be of the horizontal type for roof mounting.
4. Closed Type – tank shall be designed with the required air volume to take the
maximum expansion. Tank shall be tightly constructed with no leaks. It shall be
tested at 1.5 the design pressure for 24 hours before commissioning.
6. Piping – piping connections for the tank shall be as indicated on the drawings.
Piping shall be complete with air release fittings, drain and all other components as
shown on the drawings.
b) Closed Type
1. Type – pressurized closed expansion tank shall be furnished and erected to serve as
feeding system for chilled water circuit and hot water circuit and to allow for the
expansion of water. The tank shall be supplied complete as an integral system
comprising of expansion vessel, feed booster pump, make-up water storage tank,
pressure switches and gauges. Tank shall be factory assembled, wired and tested.
4. Motor – shall be totally enclosed type, drip proof, fan cooled, squirrel cage with
suitable insulation to withstand high ambient temperature of 45oC.
- Pressure switch,
- Motor starter with overload,
- Pressure relief valve,
- Connection for recharging with air.
b) Duct Workmanship
1. All duct work shall be constructed and erected in a workmanlike manner. Ducts
shall be straight and smooth on their side with neatly finished joints, air tight and
shall be free from vibration under all conditions of operation. The internal ends of
slip joints shall be made in the direction of air flow. The ducts shall be securely
attached to the building construction in an approved manner.
2. Change in dimensions and shape of ducts shall be gradual. All duct sizes shall fall
within the limiting dimensions indicated on the drawings unless otherwise
approved.
3. Curved elbows, unless otherwise specified on the drawings, shall have a center line
radius equal to 1.5 times the width of the duct.
4. Air turns shall be installed in all abrupt elbows and shall consist of curved metal
blades or vanes, arranged to permit the air make the turns without appreciable
turbulence. They shall be the manufacturer's standard product and shall be quiet
when the system is in operation.
5. Configuration of ducts shall be as shown by the detail on the drawings. Ducts shall
be cross broken for strength and rigidity.
6. Duct throats shall be of same velocity as the main duct to which branch connection
is made.
7. Plenums or suction chambers shall be U.S. standard gauge 18, with galvanized iron
angles and rivets for seam connection and stiffening. Connections of plenums and
air chambers to walls and floors shall be made with galvanized angles anchored to
wall or floor construction with anchor bolts, with sheet metal bolted or riveted to
angles. Mastic clear shall be installed at connection to floor and connection of
angles sheet metal to provide airtight joints.
8. Provide handle operated access doors in plenums and chambers from both sides.
Access plates in ducts for access to dampers shall be U.S. standard gauge 18 and
made airtight by means of felt strips. Size shall be 305mm×305mm (12"×12")
unless limited by the duct size. Doors shall be provided with cam latcher. Access
openings in false ceiling shall be coordinated with other trades to provide access to
all hidden doors.
9. Provide adequate space around duct to assure proper support and allow the
installation of duct insulation.
10. Furnish test well made-up of a brass nipple welded into the duct or casing and a
cap on the downstream side of each coil and fan.
Sheet steel gauges and transverse joints shall correspond to size of ducts and shall
be as follows:
c) Hangers and Supports – hangers shall be adjustable type and spaced not more
than 2m apart and at all changes of directions. The hanger shall consist of two
threaded bars and bottom support angle. The steel bars shall be fixed to ceiling in
an approved manner. Support details shown on drawings shall be adhered to.
d) Circular Ducts – all ductwork, fittings and all associated hangers supports
dampers, flexible joints sealants, insulation access and testing shall conform to the
recommendation of SMACNA. (ASHRAE) all raw edges of ductwork, formed
seams, welds and rivets shall be painted two coats of aluminum paint at works.
All sheet metal ductwork and fittings shall be manufactured in best quality strip
mill cold reduced sheet continuously hot dipped galvanized. All circular and oval
ductwork and fittings shall be constructed from spiratly wound sheet galvanized
steel and shall have the following thickness and where required, flanges of stated
sizes:
Sheet thickness
Nominal diameter mm Stiffering or angle flange sizes mm
mm
Up to 200 0.6 25×25×3
Over 200 and up to 750 0.8 25×25×3
Over 750 and up to 1000 1.0 30×30×A at 1250mm centers
Over 1000 1.2 40×40×A at 1250mm centers
Fastening shall be at 150mm center and of the mechanically closed rivet type
which do not protrude into the air space other than the rivet head on all flanges
and joints, etc. ??ld steel nuts and bolts electro plated sherardized or ???dmium
plated shall be used. Ductwork sealant shall be of the non-hardsetting mastic type
which retain its adhesion and elasticity throughout the temperature range of 0oC to
70oC and shall be applied to all joints by pressure using an injection gun or placed
into the joints prior to construction such that the sealant is under pressure or
erection of the joints.
a) Splitter Dampers - at all places as shown on drawings where branch ducts take
off a main trunk, furnish and install splitter dampers of 16 gauge galvanized iron
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 31 Mechanical
Services
securely fastened to a square operating road, and with the edges lined with felt.
Where same are exposed in finished parts of the building, they shall be nickel
plated. If duct is enclosed in a plaster furring, the operating handle shall be
extended and the damper regulator installed on the face of the plaster.
b) Turning Vanes – all turning vanes shown on the plans shall be factory fabricated,
ready to install and securely supported in place. The vans shall be of the type that
can be custom cut easily with a metal cutting blade. Pressure loss shall be not
greater than 20% of velocity head. Turning vanes made by contractor are not
acceptable. With installation for 90o bends with equal widths of duct on each side
of bend, vane bar length shall equal duct width×1.4 and vane length shall equal
duct height.
c) Duct Silencer
1. Type – the silencers shall be of the rectangular or circular type suitable for use in
low pressure ductwork.
2. General – noise within the ductwork of the air handling system shall be
satisfactorily controlled by the installation of prefabricated sound traps. Silencers
must be manufactured in suppliers own facilities under his own quality control.
5. Pressure Drop – shall not exceed the value of 0.25 inch water gauge (6.5mm).
6. Pressure Taps – pressure taps and caps shall be installed at the inlet and outlet to
each sound trap. Each pressure tap shall have an identifying tag to indicate the
position of the pressure reading.
d) Fire Dampers – at points where ducts for ventilation and air conditioning
purposes pass through an intended fire separation in a building and where the
penetration occurs through floors or walls and where shown on drawings a fire
damper shall be installed by the contractor into the duct air ways. Approved fire
dampers shall have the following performance characteristics:
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 32 Mechanical
Services
2. Fire damper shall provide the maximum practical barrier to passage of air when
in the closed position.
3. Fire dampers shall remain in the closed position under fire conditions.
7. Fire dampers shall possess 1.5 hour standard fire protection rating. Rating shall
be certified by fire resistance index (UL-1974).
a) Pipe Insulation
2. Insulation shall have factory applied jacket and vapor barriers and secured with
plastic bands at all joints, at center of each section and where sections abut fittings.
3. Insulation shall only be applied to piping after all testing has been accomplished,
successfully.
4. All valves shall be provided with a galvanized sheet metal box that will encompass
the entire body except for the gland and the hand wheel. The box shall be stuffed with
an insulating material of the same thermal conductivity and construction as that of the
pipe.
5. All insulated piping subject to movement shall be provided with protection shields at
all hanger locations. Shields shall be of galvanized iron extending on each side of the
hanger for a distance equal to the diameter of the insulation and shall extend up the
sides of the insulation to the center of the pipe.
6. Insulate strainers to permit removal of the basket without disturbing the insulation of
the strainer body.
7. Pipe insulation shall be sectional glass fiber block moulded to conform to pipe, with
minimum density of 48 Kg per cubic meter and a maximum K-factor of 0.25 at a mean
temperature of 24oC. The temperature range shall be from 1.7 o C to 150 o C.
The insulation shall have a factory applied white flame retardant vapor barrier
jacket of minimum 0.05 mm aluminum foil laminated to Kraft paper with flame
retardant type adhesive reinforced with glass fibers. The insulation shall be applied to
the pipe with longitudinal joints staggered. Laps and sealing strips shall be sealed,
applying fire resistance adhesive to circumferential joints.
8. Steam pipe insulation shall conform to above specifications except, have temperature
range up to 316oC. Also vapor barrier will not be required.
9. The thickness of the pipe insulation shall be in accordance with the following table:
10. After installation of pipe insulation it shall be wrapped with approved type cloth and
shall be given a coat of water resistant paint.
11. Pipes shall be properly painted before putting on insulation. The paint shall include
3 layers of red lead paint.
b) Duct Insulation
1. All supply and return air ducts shall be insulated as shown on the drawings.
2. Insulation shall be fiberglass, of the flexible blanket type being 23mm thick.
Insulation shall be provided with a vapor barrier, consisting of 0.05mm aluminum
foil reinforced with Kraft paper and glass fiber or other vapor barrier material.
3. The insulation shall have an average thermal conductivity of not more than 1.23
kcal/m2/oC per hour at a mean temperature of 24oC and density of 1.0 lbs/cu.ft. 16
Kg/m3.
4. All insulation shall have 25mm longitudinal and transverse overlaps, or seam shall be
covered with 50mm wide sealing tape, of similar material to covering material.
5. Insulation shall be applied tightly butted together and secured with non-combustible
adhesive, as recommended by insulation manufacturer. Adhesive to be applied in
150mm wide strips on 300mm centers.
6. In addition to adhesive required in (5) above, it shall be secured by soft annealed steel
wire applied over insulation on 200mm centers. The wire not less than gauge 16
50mm×50mm. Galvanized steel angles 1.5mm thick to be placed along the corner of
duct over the insulation before fixing the wire.
c) Duct Lining:
1. Acoustic duct lining shall be not less than 20mm thick, 48 Kg per cubic meter density
fiberglass.
2. Lining material shall be supplied in rigid or semi rigid board form and shall have a
smooth non-combustible coating on the surface in contact with the air. To prevent
fiberglass from being carried away by air stream.
4. Shall be cut to size before it is applied in a neat smooth manner. It shall be fastened to
the interior surface of the ducts with an approved non-combustible adhesive. If the
duct dimension exceeds 600mm, the lining shall, in addition to adhesive, be secured
with sheet metal screws or fastening hooks.
a) Type – shall be of the double deflection type with adjustable horizontal face bars,
and vertical rear bars, complete with opposed blade damper. The register shall be
constructed of aluminum with a marginal frame of not less than 3.125cm wide
(1.25") by 0.125cm (0.05") thick.
Register shall have a soft, continuous rubber gasket between the periphery of the
register and the building surface to which it is mounted. The register shall have an
effective area of not less than 80%.
b) Construction – the register shall be of aluminum construction unless otherwise
specified.
c) Dampers – the dampers shall be of the opposed blade type and shall be key
operated with a detachable key and one key shall be furnished for each register.
d) Bars – the bars shall be of the roll formed type and shall be rigid heavy gauge
stream-lined aluminum bars on 1.65mm (2/3") centers, reinforced if above 45cm
(18") in length. Bars shall hold deflection setting under all conditions of velocity
and pressure.
2. Fasten extension duct collar and distributing grid assembly to ductwork with
sheet metal screws.
3. After wall is installed, install register with screws on a wood frame as shown in
standard details.
4. Check to see if sponge rubber gasket is drawn up against wall forming an air
tight seal, if not reassemble and recheck.
5. Set face bars and rear bars for best room distribution.
8. Remove damper operator knob from register and turn over to client's
representative.
f) Air distribution grid – provide and install an air distribution grid for each supply
register. The grid shall be installed as recommended by the manufacturer, and
shall be of the same manufacturer as the supply register.
a) Type – shall be of the adjustable horizontal front bars and opposed blade damper
type. The register shall be constructed of aluminum with a marginal frame of not
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 36 Mechanical
Services
less than 1.25" (32mm) wide by 0.05" (1.3mm) thick. The register shall have the
horizontal front bars set at an angle of 35 degrees downward where installed
below 5 ft. (1.5m) from the floor, and 35 degrees upward where installed more
than 5 ft. (1.5m) from the floor. Register shall have a soft, continuous rubber
gasket between the periphery of the register and the building surface to which it is
mounted. The register shall have not less than 70 percent free area.
b) Construction – the register shall be of the opposed blade type and shall be key
operated with a detachable key and one key shall be furnished for each register.
c) Face bar – the face bars shall be 11/16" (17.5mm) wide and shall be set 0.66"
(16.5mm) apart. The face bars shall be constructed of 0.018 aluminum.
3. After ceiling or wall is installed, install register with screws on a wood frame.
4. Check to see if sponge rubber gasket is drawn up against wall or ceiling, forming
an air tight seal. If not, reassemble and check.
8. Remove damper operator jey from register and turn over to client's
representative.
a) Type – the ceiling diffuser shall be of the rectangular type neck, the ceiling
diffuser shall be complete with distributing grid and volume damper and shall be
of the dimension shown on the drawings.
b) Capacity – the capacity of the ceiling diffuser shall be as shown on the drawings.
d) Dampers – each ceiling diffuser shall be equipped with a volume control damper
of the multi blade type.
The damper operator shall be equipped with a spring type lock nut which may be
adjusted to the damper when in the partially open position because of static
pressure.
1. Fasten distributing grid to extension duct collar with sheet metal screws.
2. Fasten extension duct collar and distributing grid assembly to ductwork with
sheet metal screws.
3. Fasten duct ring to extensions duct collar with sheet metal screws.
4. After ceiling is installed, remove inner assembly diffuser cones and fasten
outer cone to duct ring with sheet metal screws.
g) Mounting – the contractor shall coordinate the location of the diffuser, ceiling
lights, and any other ceiling outlets.
a) Type – the return ceiling diffuser shall be of the rectangular type neck, the ceiling
diffuser shall be complete with volume damper and shall be of the dimension
shown on the drawings.
b) Size – the size of the return or exhaust ceiling diffuser shall be as shown on the
drawings.
d) Dampers – each ceiling shall be equipped with a volume damper of the multi
blade type. The damper operator shall be equipped with a spring type lock-nut
which may be adjusted to the required friction to prevent closing of the damper
when in the partially open position because of static pressure.
a) Type – the ceiling diffuser shall be of the round type neck, round outlet type with
adjustable air pattern. The ceiling diffuser shall be complete with distributing grid
and volume damper and shall be of the dimensions shown on the drawings.
b) Capacity – the capacity of the ceiling diffuser shall be as shown on the drawings.
d) Dampers – each ceiling diffuser shall be equipped with a volume control damper
of the multi blade type. The damper operator shall be equipped with a spring type
lock which may be adjusted to the required friction to prevent readjustment by
unauthorized persons and to prevent closing of the damper when in the partially
open position because of static pressure.
1. Fasten distributing grid to extension duct collar with sheet metal screws.
2. Fasten extension duct collar and distributing grid assembly to ductwork with
sheet metal screws.
3. Fasten duct ring to extension duct collar with sheet metal screws.
4. After ceiling is installed, remove inner assembly diffuser cones and fasten
outer cone to duct ring with sheet metal screws.
g) Mounting – the contractor shall coordinate the location of the diffuser with
ceiling lights and any other ceiling outlets.
a) Type – the ceiling diffuser shall be of the round neck, round outlet type with
adjustable air pattern. The ceiling diffuser shall be complete with distributing grid
and volume damper and shall be of the dimensions shown on the drawings.
b) Capacity – the capacity of the ceiling diffuser shall be as shown on the drawings.
d) Dampers – each ceiling diffuser shall be equipped with a volume control damper
of the multi blade type. The damper operator shall be equipped with a spring type
lock which may be adjusted to the required friction to prevent adjustment of
unauthorized persons and to prevent closing of the damper when in the partially
open position because of static pressure.
1. Fasten distributing grid to extension duct collar with sheet metal screws.
2. Fasten extension duct collar and distributing grid assembly to ductwork with
sheet metal screws.
3. Fasten duct ring to extension duct collar with sheet metal screws.
4. After ceiling is installed, remove inner assembly diffuser cones and fasten outer
cone to duct ring with sheet metal screws.
6. Check to see if sponge rubber gasket is drawn up against ceiling forming an air
tight seal. If not, reassemble and recheck.
g) Mounting – the contractor shall coordinate the location of the diffuser with
ceiling lights and any other ceiling outlets.
a) Type – the linear diffuser shall be of the continuous line type, fixed pattern 0o
deflection core. The diffuser shall be complete with volume damper, plenum
boxes and shall of the size shown on drawings.
d) Damper – each section of each diffuser shall be equipped with a volume control
damper. The damper operator shall be constructed with the required friction to
prevent closing of the damper when in the partially open position because of static
pressure.
e) Plenum Boxes – each section of each diffuser shall be equipped with a plenum
box. The plenum box shall be designed to provide even distribution across face of
diffuser. The plenum box shall be constructed of galvanized steel.
a) Type – the linear diffuser shall be of the continuous line type, fixed pattern 0o
deflection core. The diffuser shall be complete with volume damper, plenum
boxes and shall of the size shown on drawings.
d) Damper – each section of each diffuser shall be equipped with a volume control
damper. The damper operator shall be constructed with the required friction to
prevent closing of the damper when in the partially open position because of static
pressure. The integral diffuser shall be fabricated from extruded aluminum with
number of slots and air-flow distribution arrangements as indicated in the
schedule. The terminal unit shall have provision for hangers from four corners.
a) The fresh air intake shall be of the storm-proof design and shall be provided with
aluminum 14 gauge extruded aluminum louvers with minimum of 62% free area
and fitted with an aluminum bird screen with 19mm (0.75") mesh. Bird screen
shall be on the down stream side of the air intake louver. The face velocity
through the louver shall not exceed 2.8 m/s (550 fpm). Blade spacing for louver
shall not be more than 4" (100mm). Louver installed in the mechanical standards
drawing. Exhaust air louvers construction and installation shall be the same as the
fresh air intake louvers.
b) Fresh Air (Roof Intake) – roof fresh air intake shall be through a rectangular type
hood. Hood shall be water tight and provided with a bird screen. Hood
construction and installation shall be as recommended by the latest edition of the
(Sheet Metal and Air Conditioning Contractor's National Association of USA)
handbook and in accordance with the mechanical standard drawings. Exhaust
hood construction and installation shall be the same as the fresh air intake hood.
34 - Door Grille
a) Type – shall be of the fixed inverted vee section, non vision louver type. The
grille shall be constructed of aluminum with a marginal frame of not less than
32mm wide. Grille shall be provided with counter frame for the outer side of the
door.
c) Fixing – the grille shall be fixed at the third of the door at a distance not more
than 25cm from floor level to the lower edge of the frame. Grille shall be secured
by screws to the door.
a) Type – the kitchen hood shall be 6" (152mm) larger than the equipment it covers
and 6'-6" (2000mm) high.
b) Capacity – the air flow capacity of the hood shall be as indicated on the exhaust
fan installed with the hood.
d) Filters (Grease Type) – filters shall be 2" (50mm) thick and of permanent,
cleanable (washable) type as recommended by the manufacturer for the service
required. Filters shall be stainless steel construction. They shall be provided with
complete number of attachments, braces and panels and can be assembled in a
way that a continuous bank of filters of any length can be formed. Filters shall be
installed as detailed on the drawings for kitchen exhaust hood. Filters shall be
extended to the full length of the hood area as nearly as possible.
e) Grease Tray – the hood shall have a removable grease tray installed just under
the filters. The tray shall be removable in sections for ease of cleaning.
f) Duct Connection – the kitchen hood shall house a duct connection from the hood
to the fan as shown on the drawings, and the entire duct from hood to fan shall
have welded or soldered watertight seams to prevent the passage of water or
grease through the duct seams.
g) Firestat Settings – the firestat for the fan serving the kitchen hood shall be set for
175oF (80oC).
a) Type – the air handling unit shall be of the draw through type as shown on the
drawings and as indicated in schedules.
Each air handling uint shall include the following preassembled components:
b) Capacity – the air moving fan and coil capacities shall be as indicated in
schedules.
c) Casing – air handling units shall be double skin constructed from unique panel
elements. That have stiffening sections and rubber seals. Fully integrated into
each panel. Sandwich panels totally enclosed and rot resistant, the insulation core,
tightly enclosed and fully protected against all mechanical and chemical damage.
Double sealing by means of two strips of corrosion resistant and non agoning
hollow body section rubber that is mechanically rolled into each panel. Easy
maintenance given by full height access doors with mechanically bonded rubber
sealing gasket.
Removable panels in fan and coils sections shall provide access to all internal
parts. All unit panels shall be insulated with 25mm (1") glass fiberboard and shall
be chemically cleaned, spray painted, baked and coated with an additional
exterior coat of enamel after final assembly.
d) Motor and Drive – motor shall be v-belt drive with guard and adjustable motor
pulley. Motor name plate horsepower shall exceed brake horsepower by 25% with
airfoil fans. Belts shall be of the oil resistant type. The motor shall be specially
designed for quiet operation (drip-proof motor).
e) Fan – the unit fans shall be double width, double inlet type. Air foil fan wheels
shall be used on all units with greater than 0.93m2 (10 ft2) inlet area. Fan shaft
bearings shall be 200000 hour life lubricated. All rotating parts shall be statically
and dynamically balanced individually after final assembly. Bearings shall be
mounted externally for servicing without dismantling the unit.
f) Heating and Cooling Coil – coil shall be of the continuous aluminum plate fin
and copper tube type assembled in a zinc coated steel frame. The coil shall be
pitched in the unit casing for proper drainage. A drain pan shall be provided as
shown on the drawings. Drain pipe shall be provided as shown on the drawings.
Drain pipe shall be connected to hub outlet on the floor.
The coil shall be tested at 250 psig (17.6 Kg/cm2) air pressure under water for 2
hours. Coils face velocity shall not exceed 4m/s.
h) Filter – filter shall be of the high efficiency type, permanent, cleanable type. It
shall be 50mm (2") thick and of non-ferrous metal wool construction, unless
otherwise indicated.
i) Mixing Box – if it is shown on drawings and/or the schedule, then the units so
shown shall be provided with a combination filter and mixing box.
The mixing box shall be supplied with opposed blade dampers and necessary
linkage. Dampers shall control the fresh air and the re-circulated air.
Damper blades shall be locked to spliced steel rods which shall be rotated in
bronze bushings.
The mixing box shall be manufactured of same gauge galvanized steel as casing
and shall be properly braced and reinforced and shall have the same finish as the
air handling unit.
Mixing box shall be provided with access panel for filter change on either side.
Mixing box casing shall be internally lined with 25mm glass fiberboard. Provide
suitable flanges and openings for duct connections.
37 - Zoning Damper
The zoning damper shall be bolted to the air handling outlet. A longitudinal
division shall separate the hot and cold decks. The transverse section shall be divided into
equal parts. The shaft controlling the dampers in each section shall be jointed by an
external bar to facilitate field groupings. The frame and damper blades shall be
constructed of galvanized steel. The dampers shall be keyed to steel shafts run in bronze
or nylon bushings. Each opening damper shall be operated automatically by an electric
motor under control of a thermostat. The framing shall allow duct connections via flanges
or slip connectors. Units shall be provided with access section with doors for
maintenance and repair of all internal unit parts.
38 - Isolating Valves
Each air handling unit shall be provided with isolating valves and balancing valve
in the water coils as shown on the drawings. In addition, units so specified in the tender
shall also be fitted with automatic motor operated three way electric control valve with a
summer/winter switch and thermostat.
a) Direct Drive Fan Coil Units – the units shall be suitable for chilled and hot water
applications, their ratings, duties and types shall be as tabulated in schedules.
1. Cabinet – the cabinet shall be constructed of best quality heavy gauge steel, reinforced
and braced for maximum rigidity and removable access panel. It shall be water and
corrosion proof, internally insulated and shall have finished factory coat of paint. Each
unit shall be complete with discharge air grille.
2. Coil – the coil shall be constructed of heavy gauge copper tubes and aluminum fins.
Tubes shall be mechanically expanded to the fins. The coil shall be provided with an
automatic air vent of an approved type. An insulated drain pan fitted with a drain
connection shall be provided to receive all condensation and drip from internal fittings.
3. Filters – 2.5cm thick air filters shall be of the heavy duty cleanable type having non-
ferrous metal wool or other well proved material arranged in a solid frame.
Arrangements shall be made for passing all fresh and re-circulated air through the
filters before passing through the coils.
4. Fans – the fan shall be of the multi-blade centrifugal type, with balanced aluminum
wheel directly coupled to an electric motor.
5. Fan Motor – shall be of the shaded pole, three speed drip proof open type. Motors shall
be equipped with sleeve bearings impregnated with oil. Gun nozzles shall be fitted to
permit recharging lubricant without dismantling the motor. Motors shall be fitted with
overload protection. Motor shall have sufficient lubrication storage so that it can
continuously run for one year without attention.
6. Controls – a manual three speed motor control switch with an "OFF" position shall be
provided with each unit. Integral with unit for vertical standing units and wall mounted
for horizontal units. Each unit shall be provided with isolating and balancing valves as
shown on the drawings. Units shall be provided with an automatic motor operated
three way control valves with a summer/winter switch and thermostat.
1. General – these units shall be similar to type (a) above, except as indicated below.
2. Casing – the casing shall be insulated and acoustically lined on the inside with
minimum of 25mm thick fiberglass board.
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 46 Mechanical
Services
3. Fans – the fan wheel shall be manufactured of steel. Wheel shall be double width,
double inlet type mounted on solid steel shafts. Fan wheel shall be statically and
dynamically balanced. Fan bearings shall be self-aligned sleeve type bronze with an
oil cup of ample reserve. The fans shall be belt driven by an electric induction motor
by an adjustable drive. Motor shall be resiliently mounte.
4. Filters – units shall be provided with 5cm thick permanent, cleanable filters.
5. Drain Pan – units shall be provided in addition, to original drain pan, with a secondary
drain pan under valves and piping inside the unit.
6. Unit Mounting – the unit shall be suitable for ceiling suspension and shall be provided
with suitable vibration isolator bases.
7. Unit Control – the manner for unit control shall be as indicated in temperature control
section of these specifications.
40 - Air Filters
Air filters shall be used for outdoor air and re-circulated air and shall be tested in
accordance with ASHRAE test standards 52-76.
The filter media shall be constructed of layers of crimped corrugated wire screen
and expanded galvanized steel to provide large filtering area and shall be held in a
heavy gauge galvanized steel frame capable to withstand shock and abuse.
The filter shall be sized for maximum air velocity of 2.5m/sec. with initial press,
drop of not more than 25 Pa and average arrestance of 75%.
b) Grease Type Washable Filters – shall be permanent, washable heavy duty type.
The filter media shall be constructed of multiple layers of crimped, corrugated
galvanized steel wire and expanded galvanized steel arranged to provide
thousands of small progressive baffles, to ensure uniform air flow and maximum
grease holding capacity. The filter media shall be held in a heavy gauge
galvanized steel frame designed to withstand shock and abuse. These filters shall
be used in commercial kitchens, in hotels, institutions and restaurants, to reduce
fire hazards and prolong the service life of fans, motors and other mechanical
equipments.
c) Disposable Panel Filter with Permanent Frame – disposable panel type filters
with permanent frame shall consist of galvanized steel frame with sealing and
quick release fasteners for filter media changing. Wire grid shall be used as media
support and the effective area shall not be less than 96%. The filter media shall be
made of fiberglass with a nominal thickness of 50mm. capable of operating with
variable face velocity up to 2.54m/sec. without impairing efficiency and rated
initial press. Drop of 50 Pa and a final recommended pressure drop of 125 Pa. The
media shall have an average dust weight arrestance of 75-80 percent on ASHRAE
test standard 52-76. This type of filter may be used as a prefilter to a higher
efficiency filter.
d) Disposable Panel Filters – the filter shall consist of continuous filament glass
fiber of progressive density construction. The air entering side shall have an open
weave fiber pattern with large diameter fibers. The fiber diameter shall become
smaller and the weave shall become progressively tighter from the air entering to
the leaving side of the media. This construction allows dirt to penetrate deep into
the media, utilizing its full depth. Metal retainers shall be placed on both sides of
the media pad to provide support as resistance increases. The medial shall be
contained in a sturdy chipboard frame for dependable operation. The filter
thickness shall be minimum 50mm.
The filter shall be sized for a maximum air velocity of 2.54m/sec. with initial
pressure drop of not more than 50Pa and final pressure drop of 125 Pa. the
average arrestance shall be 75-80 per cent.
e) Disposable Extended Surface Air Filters (Pleated Panel Type) – the filter shall
be of disposable, medium efficiency, pleated panel type. It shall be designed to
provide better performance and larger service life than the conventional panel
filters. It may be used alone or as a prefilter in a high efficiency unit. The filter
shall be of two inches or four inches deep as required in the project documents.
The filter shall consist of a plated media pack enclosed in a strong chipboard
frame.
Metal retainers shall be placed on both sides of the media pack to provide support
as resistance increases. The plated media pack shall be bonded to the inside of the
frame, forming a totally unitized construction.
The media shall be supported by a wire grid to maintain the uniform shape of the
pleats to ensure proper air flow and dust loading at the rated filter velocity.
The medial shall have an average dust spot efficiently of 25 to 30 per cent when
tested in accordance with ASHRAE standards 52-76 and shall have an average
arrestance of not less than 90%, with a rated initial pressure drop of 75 Pa and a
final recommended pressure drop of 200 Pa at a face velocity of 2.54 m/sec. for
50mm. thick filter.
Bag filters are available in different efficiency ranges. The efficiency of the
required filters shall be as given in the project documents.
The following table shows the initial and final pressure drop for different
efficiency ranges:
g) High Efficiency Box Filter – it shall be a high efficiency air filter with a
minimum efficiency if 95% determined by the DOP test method. The filter shall
consist of a frame, in which the media is inserted, in tightly folded form. The
frame shall be of electro-zincated sheet and the media shall be produced from a
waterproof high strength glass fiber paper. The filter shall be held open by a
corrugated separator; the separator shall be of safe edge aluminum. The filter shall
be supplied with gasket of either closed cell neoprene or glass fiber and shall be
provided with sealer between the filter medial and the frame. The sealer shall be
of neoprene rubber, glass fiber, silicon glue, or ceramics according to the
temperature requirements.
The initial pressure drop shall not exceed 250 Pa and final recommended pressure
drop shall not exceed 500Pa at a face velocity of 2.54 m/sec.
h) Automatic Roll Type Filters – automatic roll type filters shall be either of
vertical or horizontal type. It shall consist of filter media roll boxes and drive. The
medial shall be of fiber glass, reinforced by glass filaments and compressed on a
disposable steel core spool with permanent galvanized plates.
Tightly closing filter seat shall be provided to prevent any unfiltered air from
passing around the filter. Roll boxes shall be of galvanized steel and shall
completely enclose both clean and used media and ensure that media can not be
installed backwards. The drive motor shall be factory assembled and pre-wired
and shall be with gear and chain and control consisting of adjustable static
pressure controller or automatic adjustable timer with manual override,
interlocked to fan motor by interlocking relay. Filter medial shall be at least 25m
long and 50mm thick with filter face velocity of maximum 2.54m/sec initial
resistance approximately 50 Pa and average dust weight arrestance shall be 70-80
per cent on ASHRAE test standard 52-76.
i) Activated Carbon Filters – activated carbon filters shall be used for absorbing
gaseous and odorous contaminants from intake air and odorous or harmful
substances from exhaust air. It shall be suitable for duct or wall installation,
cylindrical or panel type as required in project documents. The media shall be
activated carbon and the filter housing shall be made of stainless steel.
j) Sand Filter (Inertial Separator) – the filter shall be factory assembled unit
comprising of V-shaped inertial separator cell or cells, secondary dust manifold
and housing. V-shaped inertial separator cell or cells, secondary dust manifold
and housing shall be of 304 stainless steel. The unit shall have a bleed fan and
dischargeoua. The unit shall be fabricated of one or more cells, individual cells to
be welded to form a multi-bank arrangement of the size required. Each cell shall
consist of V-shaped blades arranged to present circuitous path to the air flow and
to redirect the air towards the clean air outlet. The efficiency of the air cleaner
shall be not less than 90% as per AFI standards on coarse dust and 78% on fine
dust and 10% bleed off. Pressure loss from inlet to clean air outlet shall not
exceed 250 Pa.
Bleed fans shall be of the heavy duty, centrifugal type with straight radial blades,
single inlet single width. Fan shall be direct driven by a totally enclosed fan
cooled motor coupled to the shaft of the impeller. Motors shall be suitable for
ambient temperature up to 50 deg. C.D.B.
a) Type – the fan shall be of the direct drive three or four blade type, mounted on a
steel plate with orifice ring.
b) Mounting Plate – the mounting plate shall be the manufacturer's standard size
and shall be of a size ample to fit the opening provided.
c) Fan Blades – shall be constructed of steel or aluminum. The fan hub shall be of
heavy construction and shall be steel or semi-steel, and blades shall be riveted to
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 50 Mechanical
Services
the hub. Fan blades shall be quiet in operation and shall be statically and
dynamically balanced at the factory.
d) Shaft – shall be of steel, accurately ground and shall be of ample size of the loads
transmitted, and shall not pass through a critical speed through the full range of
speed shown for the fan.
e) Motor – the motor shall be of standard type that is easily replaceable and may be
either sleeve or ball bearing type. Maximum RPM of the motor shall be 1000 rpm.
f) Damper – a gravity exhaust damper shall be provided at the discharge side of the
fan.
g) Control – the fan shall be controlled manually from a wall mounted on-off
switch, or unit mounted pull-cord switch.
a) Type – the unit shall be of the direct, or belt driven centrifugal with aluminum
housing for wall mounting, and shall be completely weatherized, and provided
with bake-draft shutters.
c) Fan – shall be of the centrifugal type that has been statically and dynamically
balanced at the factory. The fan shall be of a backward curved centrifugal wheel.
e) Bird Screen – the entire air outlet of the fan shall be protected by (12mm ×
12mm) aluminum mesh securely installed in place.
a) Type – the unit shall be of the direct or belt driven centrifugal with aluminum
housing for roof mounting, and shall be completely weatherized, and provided
with back-draft shutters.
c) Fan – shall be of the centrifugal type that has been statically and dynamically
balanced at the factory. The fan shall be of low noise level.
g) Bird Screen – the entire air outlet of the fan shall be protected by (12mm ×
12mm) aluminum mesh securely installed in place.
h) Controls – fan shall operate manually by an on/off switch installed on the control
panel in the plant room.
a) Type – the unit shall be of the belt driven centrifugal type and housing shall be
constructed of galvanized steel with the side sheet secured to the scroll by means
of a deep lock seam.
Lock seam construction is required to add rigidity to fan housing and shall insure
an airtight seal between scroll and side sheet.
A stiffener head shall be used for reinforcement around the side and top of the
discharge and shall be completely weatherized.
c) Fan – shall be the backwardly inclined type with centrifugal wheel and has been
statically and dynamically balanced at the factory.
e) Drive – the unit shall be belt driven. The belt shall be oil resistant. And adjustable
sheave in the motor shall be provided to allow changes in the fan speed.
f) Installation – the unit shall be installed on the roof as shown on the drawings.
h) Bird Screen – the entire air inlet of the fan shall be protected by (12mm × 12mm)
aluminum mesh securely installed in place.
i) Vibration Isolation – each fan shall be provided with suitable vibration isolation
as recommended by the manufacturer.
45 - Fans, In-Line
a) Type – the fan shall be of the centrifugal inline type, completely assembled with
fan, motor, belt drive, belt guard, and motor mount. The motor shall be outside of
the air stream.
b) Capacity – the capacity shall be as shown on the drawings and as indicated on the
schedules.
e) Housing – housing shall be constructed of steel sheet and all parts shall be
bonderized and then coated with baked primer-finisher especially formulated to
meet stringent corrosion resistance standards. The fan scroll shall be attached to
the side plates by means of continuous lock seam or welded seam construction.
Intermittent spot welded type construction will not be acceptable. One inch
(25mm) wire mesh inlet screens shall be provided on the inlet.
f) Fan Wheels – the fan wheels shall be of the backward inclined type.
h) Bearings – the bearings shall be of the ball bearing type and shall be especially
constructed for quiet operation. Bearings shall be of the self-aligning, grease pack
pillow block type.
i) Motor and Drive – motor and drive shall be belt driven with adjustable motor
sheave. Motor nameplate horsepower shall exceed brake horsepower by a
minimum of 20%. Belts shall be of the oil resistance type. Motor shall be
especially designed for quiet operation.
j) Rotation Arrow – the rotation of the fan shall be checked on start up and if there
is no rotation arrow supplied by the manufacturer, the subcontractor shall install a
correct rotation arrow.
k) Vibration Isolation – each fan shall be provided with suitable vibration isolation
as recommended by the manufacturer.
a) Type – utility fan shall be of the type that is especially suitable for serviced
indicated in the schedule and shall be of the forward curved wheel, direct drive
unless otherwise indicated in the schedules.
c) Housing – shall be constructed of steel with the side sheet secured to the scroll by
means of a deep lock seam. Lock seam construction required to add rigidity to fan
housing construction and shall insure an air tight seal between scroll and side
sheet.
A stiffener head shall be used for reinforcement around the sides and top of the
discharge.
Motor shall be totally enclosed, drip proof and capable of withstanding high
ambient temperatures 50oC (122oF).
1. Air Movement – air quantity measurements in main and branch ducts shall be
performed by pitot tube traverse of the entire cross sectional area of the duct. Ducts
having velocities of 304m/min (1000ft/min) shall be measured by inclined
manometers (draught gauge) or magnehelic gauges. Air measurements required for
ducts having velocities of less than 304m/min (1000ft/min) shall be performed with
micromanometers, hook gauges, or similar low pressure instruments. Openings in
ducts for pitot tube insertion shall be sealed with snap-in plugs after air balance is
complete. Outlet and inlet air quantities shall be determined by direct reading
velocity meters in accordance with outlet and inlet manufacturer's
recommendations.
Branch duct air quantities shall be adjusted by volume or splitter dampers. Dampers
shall be permanently marked after air balance is complete so that they can be
restored to their correct position if disturbed at any time.
Volume adjusters may be used to balance air quantities at outlets and inlets
providing final adjustments do not produce sound levels in excess of heretofore
specified limits, or objectionable draughts. Air quantity adjustments by outlet
deflectors, grids or air scoops will not be permitted.
c) Reports – the contractor shall conduct air balance test in the presence of the
engineer or his present representative. 3 copies of balance report will be
forwarded to the consultant for evaluation and approval. If requested, the
contractor shall conduct any or all of the above field tests in the presence of the
consultant or his representative.
a) Scope – the contractor under this heading shall furnish all labour, materials,
equipment and services required to provide a compete temperature control
system.
Control diagrams submitted do not limit the number of devices used in the control
system. If more devices were needed to provide a complete control system, the
contractor shall provide them as needed. Control diagrams only indicate the way
the system should operate and do not indicate the number of devices needed.
Wall mounted sensing devices shall be installed at a height of 1.5 meter from
finished floor level.
1. A flow switch in the chilled water circuit established flow through the chiller
piping circuit.
2. A flow switch in the condenser water circuit established flow through the
condenser piping circuit.
1. The chilled water pump, condenser water pump and cooling tower fan shall be
started manually.
2. The flow switches in the chilled water and condenser water circuits shall sense
the flow.
3. The auxiliary contacts (normally open) in the motor starters of the chilled water
pump, condenser water pump and cooling tower fan shall close.
4. If conditions in (1) to (8) of item (b) above are satisfied, the compressor shall
start unloaded.
5. Once the compressor starts it shall be staged in sequence to give the capacity
necessary to maintain chilled water temperature at design value.
7. In case of power interruption, a re-cycling relay shall return the capacity control
system to the start position.
3. A summer/winter change over switch shall adjust the operation of the room
thermostat as direct action for winter season and indirect action for summer
season.
1. Space thermostat, modulating fully proportional type, for each season shall
actuate the electric motor to modulate the face and by-pass dampers of each
individual zone.
3. A summer/winter change over switch shall adjust the operation of the room
thermostat as direct action for winter season and indirect action for summer
season.
1. Control system shall include a manually operated fan switch, (3-speed switch
for direct drive units and single speed for belt drive units) electric thermostat
and a manual summer/winter switch.
Developed in Cooperation with the University of Technology – Baghdad
DRAFT
DRAFT
AFCEE Iraq Interim Construction Standards 57 Mechanical
Services
4. Thermostat and fan switch shall be unit mounted for cabinet vertical units,
floor mounted type and the thermostat shall sense return air temperature.
For horizontal concealed units the thermostat and fan switch shall be wall
mounted in an approved location.
2. The flow switch in the hot water circuit shall sense the flow.
3. The auxiliary contact (normally open) in the motor starter of the hot water
pump shall close.
4. If conditions in (1) to (4) of item (g) above are satisfied the heater shall operate.
5. Once the heater operates it shall be staged in sequence to give the capacity
necessary to maintain hot water temperature at design value.
7. Capacity control system shall provide the required number of control stages as
stated in the schedule or in drawings.
49 - System Tests
a) Scope – subsequent to the final air and water balance tests, the entire heating and
air conditioning systems shall be tested to satisfy performance of all units as a
satisfactory system. Test will run for three weeks.
Contractor shall provide all necessary instruments and measuring devices to carry
out all tests. The quantities measured are shown in the annex.
b) Heating System – the entire heating system shall be tested at completion of the
building and it shall be established that all controls are calibrated accurately and
performing satisfactorily and that all units are heating satisfactorily in the January
after commissioning. The systems shall be checked for vibration and excessive
noise and all such conditions corrected.
c) Air Conditioning System – the entire air conditioning system shall be tested at
the first August summer weather next following the completion of the building
and it shall be established that all controls are calibrated accurately and
performing satisfactorily and that all units are cooling satisfactorily. The systems
shall be checked for vibration and excessive noise and all such conditions
corrected.
e) Final Clean-Up – at the completion of all work, all equipment on the project
shall be checked and thoroughly cleaned, including coils, plenums, under
equipment provided under this section. Any filters used during construction shall
be replaced with new filters during final clean-up.
f) Painting – at the completion of all work all equipment on the project shall be
checked for painting damage, and any factory finished paint that has been
damaged shall be repainted to match the adjacent areas. Any metal or specially
covered areas that have been deformed shall be replaced with new material and
repainted to match the adjacent areas.