RelaySimTest-AppNote-Line Distance Protection With Power Swing Blocking-2022-ENU V2.2 (Not Official)
RelaySimTest-AppNote-Line Distance Protection With Power Swing Blocking-2022-ENU V2.2 (Not Official)
Author
Jens Baumeister | [email protected]
Tomasz Bednarczyk | [email protected]
Date
December 2022
Application Area
Power Swing Detection, Distance protection
Keywords
RelaySimTest, Power Swing, System-based Testing,
Version
v2.2
Document ID
ANS_17009_ENU
Abstract
This application note describes the Power Swing Test Template of the RelaySimTest Software.
General information
OMICRON electronics GmbH including all international branch offices is henceforth referred to as
OMICRON.
The product information, specifications, and technical data embodied in this application note
represent the technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate
and entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which
may be present.
OMICRON translates this application note from the source language English into a number of other
languages. Any translation of this document is done for local requirements, and in the event of a
dispute between the English and a non-English version, the English version of this note shall govern.
All rights including translation reserved. Reproduction of any kind, for example, photocopying,
microfilming, optical character recognition and/or storage in electronic data processing systems,
requires the explicit consent of OMICRON. Reprinting, wholly or partly, is not permitted.
© OMICRON 2018. All rights reserved. This application note is a publication of OMICRON.
NOTICE
Equipment damage or loss of data possible
Carefully read and understand the content of this Application Note as well as the manuals
of the systems involved before taking them into operation.
Please contact OMICRON support if you have any questions or doubts regarding the
safety or operating instructions.
Follow each instruction listed in the manuals, especially the safety instructions, since this
is the only way to avoid the danger that can occur when working on high voltage or high
current systems.
Only use the equipment involved according to its intended purpose to guarantee safe
operation.
Existing national safety standards for accident prevention and environmental protection
may supplement the equipment’s manual.
Before starting a test always check that the test signals are suitable for your system under
test.
DANGER
Death or severe injury caused by high voltage or current.
Before wiring up or rewiring the equipment always turn off each system
involved to the test process.
Only experienced and competent professionals that are trained for working in high voltage or high
current environments may implement this Application Note. Additionally, the following qualifications
are required:
• Authorized to work in environments of energy generation, transmission or distribution, and
familiar with the approved operating practices in such environments.
• Familiar with the five safety rules.
• Familiar with protection testing
• Good knowledge in working with the OMICRON CMC test sets and RelaySimTest
Before you get started with this application note, read the “Getting Started” manual [1] of
RelaySimTest. Please make sure that you also have a good knowledge about the CMC test system.
The application note does not describe wiring checks and parameter tests. To test the protection
thoroughly such tests are also recommended.
2.3 Definitions
Power Swing: a variation in three phase power flow which occurs when the generator rotor
angles are advancing or retarding relative to each other in response to changes in load
magnitude and direction, line switching, loss of generation, faults, and other system
disturbances.
Pole Slip: a condition whereby a generator, or group of generators, terminal voltage angles
(or phases) go past 180 degrees with respect to the rest of the connected power system.
Stable Power Swing: a power swing is considered stable if the generators do not slip poles
and the system reaches a new state of equilibrium, i.e. an acceptable operating condition.
Unstable Power Swing: a power swing that will result in a generator or group of generators
experiencing pole slipping for which some corrective action must be taken.
Out-of-Step Condition: Same as an unstable power swing.
In a power grid static load flow is generated by a stationary voltage difference. In a mostly inductive
grid, the difference is mainly given by an angle deviation between the ends in order to transport
active power while a difference in magnitude would mainly produce reactive power. Figure 1 shows
a grid with two infeed’s, while Figure 2 illustrates the corresponding node voltages and the grid
current.
V ZQ1 V L
V ZQ2
V Q1 V Q2
V AE
V ZQ2
V Q2
B
V L
V AE ϑ E
A I
V ZQ1
V Q1
D
Figure 2 Voltages and Current
According to Figure 2 the source voltage VQ1 is leading compared to VQ2. That means there is an
active power transmission from infeed 1 to infeed 2. The amount of power depends on the
impedances, on the magnitudes of VQ1 and VQ2 and finally on the angle between them. Error!
Reference source not found. describes the amount of transmitted active power, if the reactances
of ZQ1, ZL and ZQ2 are neglected and only X as the sum of their reactances is considered:
V sin ϑ (1)
P= V ∙
X
X C
Z Q2
ZL
Z Load ϑ E
A
Z Q1 R
Figure 1 assumes node A as location of a distance protection relay. During a power swing the load
impedance ZLoad measured by the distance relay changes depending on the voltage angle changes
of VQ1 and VQ2. If both source voltages have the same magnitude, the impedance Z Load would move
on a line, while the angle ϑ changes. Figure 4 illustrates this. The figure shows also a tripping zone
of the distance protection function. It is possible that the impedance measured by the relay moves
X C
distance protection tripping zone
Z Q2
ZL
E
E
Z Load
Z Load ϑ E
A I
Z Q1 R
D
Figure 4 ZLoad calculated by relay A changes during a power swing
But how does the relay distinguish between a stable power swing, an unstable one and a fault?
During a power swing the impedance change is rather slow. In contrast to that, the impedance vector
jumps directly into the tripping zone when a fault occurs. At a stable power swing the measured
impedance enters the distance protection zones from one side, then turns around and leaves at the
same side. During an unstable power swing the impedance crosses the X axis completely and leaves
the zones on the other side. Therefore, the angle ϑ increases continuously. Figure 5 illustrates an
unstable power swing. The moment when ZLoad crosses the dashed red line, angle ϑ is 180° - this is
the theoretical limit for a stable power swing.
X C
Z Q2
ZL
E
E
Z Load ϑ E
A I
Z Q1 R
D
Figure 5 Load Impedance during an Instable Power Swing
X C
distance protection tripping zone
Z Q2
ZL
E
E
Z Load ϑ E
A I
Z Q1 R
D
Figure 6 Power Swing Detection Zone
There are two different power swing functions in modern numerical relays:
1. Power Swing Blocking: The whole distance protection or only assigned zones are blocked
when a power swing occurs.
2. Power Swing Tripping: The relay trips after detecting an unstable power swing.
Whether any one of these functions (or if even both of them) are used depends on the requirements
at the corresponding grid connections where the distance protection relay is installed. As example
for this Application Note it is assumed that the distance protection relay uses only the first function
(Power Swing Blocking).
For more information about power swing see [2] and [3].
The following figure (Fig.7) shows the power system that is used as example in the RelaySimTest
template. The line is protected by a distance protection relay with power swing blocking.
t
Z1 = 0,85·ZLine
Z/Ω
600 / 1 A
110 / 0,1 kV
Figure 7 Example – Line protected by Distance Protection Relay using Power Swing Blocking
Figure 7 shows that the distance relay protects the line with Zone 1 (Z1) and 2 (Z2). The first zone
has no time delay, which means the nominal trip time is 0 s. In the second zone the nominal trip time
is 400 ms. Figure 8 shows distance protection zones of the example in the complex impedance
plane using secondary values.
A double click on the protection relay opens the corresponding configuration menu (Fig.10). It
contains details like general settings and device connections as well as the description of signal in-
and outputs. The distance protection relay is connected to VT A and CT A as well as to CB A (trip
signal).
The test template uses the following binary relay signals by default:
Please remember to adapt your binary input settings for WET or DRY signals.
At the beginning of each test case for a time period of 800 ms there are no events active. During
this time – depending on the test scenario - either no load current or a constant load flow between
both infeeds is simulated. After that time a phase slip event for Infeed B begins.
This moment starts the simulation of the power swing. To change its parameters you can set:
The number of swings,
The duration of each swing (which corresponds to the power swing frequency),
The slip angle (which corresponds to the minimum impedance that can be reached during
the power swing).
The following chapters describe how to set the power swing parameters to get the outcome you
need.
∙ ∙
t = = = 1000 ms (1)
,
Table 1 shows the calculated slip time periods (1) depending on different power swing frequencies
for both mentioned power system frequencies (50 or 60 Hz).
The number of swings (Nswing) is defined by the duration of the phase slip infeed event. The duration
of a state tstate can be set via the time at which the following state starts. As an example, the settings
for one and two swings will be calculated. The slip time of 1000 ms is set to be constant, therefore
in order to simulate one swing the active time is equal to:
To define the simulation correctly the third state (after the power swing) needs to start after the power
swing duration tstate has passed. The states can be selected by clicking on them in the time signal
view. The duration of the whole simulation can be set at the bottom right corner of the time signal
view (next to the time line). This also defines the duration of the last state.
State during the power swing State after the power swing
To simulate two swings with the same power swing frequency (1 Hz) the duration of the power swing
state must be doubled:
t =t ∙N = 1000 ∙ 2 = 2000 ms
State during the power swing State after the power swing
An observation of the impedance trajectory (Fig.12) shows that a greater phase slip angle causes
the impedance to go deeper into the distance protection zones (respectively closer to the line angle).
Therefore, per default RelaySimTest templates are preset with a phase slip angle close to 180°
(e.g. 179,90°). This should allow for testing the distance protection function with power swing
blocking as the vector of the impedance can move deep into the distance zones.
5.0
-180°
2.5
3,81 Ω -120°
10,16 Ω
0.0
-60°
-2.5
27,71 Ω
X/Ohm(secondary)
-5.0
-7.5
-10.0
-12.5
-15.0
-5 0 5 10 15 20 25 30 35
R/Ohm(secondary)
Figure 12 Different slip angle values of infeed B (ratio of: Voltage UInfeedB / UInfeedA = 1.0; Impedance SInfeedB / SInfeedA = 1.0)
10.0
7.5
+180°
5.0
-180°
2.5 3,81 Ω
X/Ohm(secondary)
0.0
-2.5
-5.0
-7.5
-10.0
-20 -15 -10 -5 0 5 10 15 20
R/Ohm(secondary)
Figure 13 Different slip angle sign of infeed B (ratio of: Voltage UInfeedB / UInfeedA = 1.0; Impedance SInfeedB / SInfeedA = 1.0)
The voltage ratio between Infeed B and Infeed A also has an influence on the impedance during a
power swing. The higher the voltage of Infeed B is (Infeed A remains at constant voltage), the closer
the peak of the impedance trajectory will come to 0 Ohms (Fig.14).
5.0
0.0
-2.5
X/Ohm(secondary)
-5.0
-7.5
-10.0
-12.5
-15.0
-5 0 5 10 15 20 25 30 35 40
R/Ohm(secondary)
Figure 14 Different source voltage ratio (Slip angle B = -180°; Impedance ratio SInfeedB / SInfeedA = 1.0)
Similarly, a difference in the infeed impedance ratio between Infeed B and Infeed A has an impact
on the impedance change during a power swing. A lower impedance of Infeed B (which corresponds
7.5
5.0
-2.5
-5.0
-7.5
-10.0
-12.5
-15.0
-10 0 10 20 30 40 50
R/Ohm(secondary)
Figure 15 Different source impedance ratio (Slip angle = -180°; Voltage ratio UInfeedB / UInfeedA = 1.0)
a) b)
→ During both test cases the impedance trajectory moves into the distance protection tripping
zones. Hence the distance protection may pick up, if the pickup criteria are fulfilled. The relay
should detect the stable power swing. Therefore, it should not trip.
> For test case 3 a slip angle of -159,9° is used. That means the maximum phase angle difference
between the infeeds is -179,90° (-20° phase angle and -159,9° slip angle).
> For test case 4 the phase angle of infeed B is +20°, while the phase angle of infeed A stays at
0°. Furthermore, a slip angle of +159,9° is used.
→ In the beginning of both test cases the impedance ZLoad has a finite value due to the phase angle
difference of the infeeds. During the power swing this impedance changes and moves into the
distance protection tripping zones. Hence the distance protection may pick up, if the pickup
criteria are fulfilled. The relay should detect the stable power swing and, therefore, it should not
trip.
> The moment when the fault occurs defines the impedance jump, from the “power swing” to the
“fault” impedance. Figure 19 illustrates this. It is useful to create different test cases with different
times for the fault occurrence. To keep the test template simple, it uses only one where the fault
occurs 0.25 s after the beginning of the power swing (slip time period is 1 s).
→ At the start of the power swing the impedance ZLoad moves relatively slowly. The relay should
detect the power swing. The moment the fault occurs ZLoad jumps into the distance protection
tripping zones. The distance protection must trip using the corresponding tripping zone.
NO Infeed B event Add frequency Ramp event for Infeed B Add 2nd frequency Ramp event for Infeed B
The table below shows different settings which can adjust a frequency ramp event for an infeed.
1 ∙ 10 1 ∙ 10 (3)
t = ∙N = ∙ 1 = 1000 ms
f 1.0
Note: In this example at 800 ms the frequency of Infeed B begins to gradually decrease to 49 Hz.
This frequency ramp continues for 100 ms as set by the ramp duration. After this (so at 900 ms) the
frequency of Infeed B remains constant at 49 Hz. The next infeed event starts exactly 1000 ms after
the frequency started to decrease (so at 1800 ms). There the frequency of Infeed B begins to
increase again back to 50 Hz for 100 ms (ramp duration). When the frequency reaches 50 Hz (so at
1900 ms) it stays stable and therefore the power swing has ended.
To simulate two swings with the same frequency (-1 Hz), the power swing duration must be doubled:
1 ∙ 10 1 ∙ 10
t = ∙N = ∙ 2 = 2000 ms
f 1.0
12.5
10.0
7.5
5.0
2.5
X/Ohm(secondary)
0.0
-2.5
-5.0
-7.5
-2 Hz
-10.0
-1 Hz
+1 Hz
-12.5
-15.0 +2 Hz
-30 -20 -10 0 10 20 30
R/Ohm(secondary)
Figure 21 Different frequency changes (ratio of: Voltage UInfeedB / UInfeedA = 1.0; Impedance SInfeedB / SInfeedA = 1.0)
The voltage ratio between Infeed B and Infeed A also has an influence on the impedance during a
power swing. The higher the voltage of Infeed B is (Infeed A remains at constant voltage), the closer
the the impedance trajectory will come to 0 Ohms (Fig.22).
15
10
5
X/Ohm(secondary)
-5
-10
0,8 UInfeed_A
0,9 UInfeed_A
1,0 UInfeed_A
-15
1,1 UInfeed_A
1,2 UInfeed_A
-20
R/Ohm(secondary)
Figure 22 Different source voltage ratios (Frequency of Infeed B = 49 Hz; Impedance ratio SInfeedB / SInfeedA = 1.0)
Similar to the stable power swing test cases, a difference in the infeed impedance ratio between
Infeed B and Infeed A has an impact on the impedance change during a power swing. A lower
impedance of Infeed B (which corresponds to a higher power) compared to a constant impedance
of Infeed A shifts the impedance trajectory closer to 0 Ohms (Fig.23).
20
15
10
5
X/Ohm(secondary)
-5
-10
-15
0,5 SInfeed_A
1,0 SInfeed_A
2,0 SInfeed_A
-20
-40 -30 -20 -10 0 10 20 30 40
R/Ohm(secondary)
Figure 23 Different source impedance ratios (Frequency of Infeed B = 49 Hz; Voltage ratio UInfeedB / UInfeedA = 1.0)
a) b)
→ The absolute value of the phase angle difference between the infeeds increases in both test
cases from 0° to 360°. That means both test cases show an unstable power swing. In test case 7
the impedance ZLoad moves from the right to the left side of the impedance plane, in test case 8
the situation is reversed. In both cases the impedance crosses the distance protection tripping
zones. The relay must detect the unstable power swing and the power swing blocking function
has to prevent the distance protection from tripping.
→ Due to the unstable power swing, the impedance ZLoad crosses the distance protection tripping
zones in the impedance plane. The relay must detect the unstable power swing and the power
swing blocking function has to prevent the distance protection from tripping.
Power swings can be simulated with or without load. The load current magnitude can be set by
changing the phase angle of Infeed B as shown in Figure 25. The phase angle of Infeed A stays
at 0°. That means by adapting the phase angle of Infeed B the magnitude and the direction of the
power exchange between both infeeds can be changed.
phase angle
0°
10°
While testing the power swing blocking function it is important to check if the distance protection is
blocked during a power swing but it is also crucial to verify if the distance protection will trip when a
short circuit appears during a power swing event. Therefore, the RelaySimTest template also
consists of test cases for fault scenarios during stable and unstable power swings. To keep the
template simple, the test cases with faults only use the following Fault types: L1-N, L2-L3 and L1-
L2-L3.
Depending on the relay under test, its parameters and on the grid in which the protection system
is used, it can be necessary to add more fault types. All test cases should have an adequate
simulation time to cover the whole test scenario and to ensure that the relay has enough time to
show its reaction on the test.
In order to change the fault parameters e.g., when fault should occur simply select the fault icon
(Fig. 26) and adapt the settings accordingly.
Figure 27 shows for this example how the impedance trajectory changes from a stable power swing
to a three phase fault.
Figure 27 Example of 3-ph fault event during stable power swing event
The OMICRON TransView software is useful to analyze the test results. Here it is possible to display
the impedance and power trajectories resulting from the test voltages and currents. The feature
Synchronize to TransView in RelaySimTest offers a direct export of the signals that is automatically
updated, when the test parameters change.
It is also possible to display the distance zones in the TransView Circle Diagrams, if they are
available as RIO file (for example in the Menu Test Object of the OMICRON Test Universe).
The RIO file can be exported from the Test Universe Test Object as follows (Fig.29):
(1) Select File in the Test Object main menu.
(2) Select Export … in the submenu.
(3) Select RIO file type and enter %TEMP%\SIMULATIONTEST.RIO as file name.
The RIO file will be saved in the same location where the RelaySimTest signal export is
saved (C:\Users\UserName\AppData\Local\Temp).
(4) Save the file.
Figure 29 RIO export from the menu Test Object of the OMICRON Test Universe
© OMICRON
www.omicronenergy.com Subject to change without notice.