Masterlogic-200 Spectech
Masterlogic-200 Spectech
Release 202
Version 9.0
Contents
1. INTRODUCTION .................................................................................................................. 4
1.1 OVERVIEW......................................................................................................................... 4
1.2 MASTERLOGIC-200 PLC SYSTEM ARCHITECTURE ............................................................. 5
1.3 GENERAL SPECIFICATIONS ................................................................................................ 7
1.4 CPU SUMMARY SPECIFICATIONS ...................................................................................... 9
1.5 POWERFUL & VERSATILE CPU ....................................................................................... 14
1.6 POWER SUPPLY MODULES (2MLI-CPUU, CPUH, CPUS) .............................................. 34
1.7 POWER SUPPLY MODULES (2MLR-CPUH/#).................................................................. 36
1.8 BASE OPTIONS (2MLI-CPUU, CPUH, CPUS)................................................................. 37
1.9 BASE OPTIONS (2MLR-CPUH/#, 2MLI-CPUS/P) .......................................................... 40
1.10 I/O INTERFACE MODULES (2MLR-DB##)....................................................................... 43
2. OPEN NETWORKS ............................................................................................................. 44
2.1 NETWORK SUMMARY SPECIFICATIONS............................................................................ 44
2.2 FAST ETHERNET (FENET) ................................................................................................ 46
2.3 SERIAL COMMUNICATION (SNET) .................................................................................... 52
2.4 PROFIBUS-DP (PNET) ...................................................................................................... 56
2.5 DEVICENET (DNET) ......................................................................................................... 59
3. SOFTMASTER ..................................................................................................................... 62
4. MODEL NUMBERS ............................................................................................................ 67
4.1 CPU MODULES ................................................................................................................ 67
4.2 I/O BASE & POWER & CABLES (2MLI-CPUU, CPUH, CPUS) ................................................. 68
4.3 I/O BASE & EXPANSION DRIVE & POWER & CABLES (2MLR-CPUH/#) ............................................... 69
4.4 BASE & POWER (2MLI-CPUS/P) .................................................................................... 70
4.5 DIGITAL I/O MODULES .................................................................................................... 71
4.6 ANALOG I/O, HIGH SPEED COUNTER & EVENT INPUT MODULES .................................... 72
4.7 COMMUNICATION MODULES ........................................................................................... 73
4.8 PROGRAMMING CABLES .................................................................................................. 73
4.9 OTHERS ........................................................................................................................... 73
Version 9.0
Revision History
9.0 Dec. 2013 A – 8 channel RTD, HART analog input and output, 8
slot rack, CPU for redundant power
M – Revised with latest IEC standards
Version 9.0
1. Introduction
1.1 Overview
MasterLogic-200, Honeywell’s next
generation Programmable Logic
Controllers (PLC), adds power and
robustness to logic-interlock-sequence
batch control capabilities of Experion
network.
It is state of the art, compact yet
powerful & versatile, cost-effective
solution ideal for fast logic, sequential,
and batch control applications
T
The highlights of MasterLogic-200 PLC system are:
• Powerful & Versatile CPU (high speed / memory, IEC programming etc)
• Compact footprint (Rack room, cabinet space saver, shipping costs
saver)
• Modular options (power supply, range of I/O modules to suit your
configuration)
• Flexibility in module assignment – any module can be installed in any
slot of any base without any restrictions.
• Open networks (Fast Ethernet, UTP/Fiber-Optic, serial RS232C
/422/485)
• Open protocols (Profibus-DP, MODBUS ASCII/RTU/TCP, DeviceNet)
• Peer-to-Peer networks (Dedicated Fast Ethernet on UTP/Fiber-optic)
• Simulation Environment to test control strategies without hardware or
process connections.
• Engineer-friendly software (Connection options, easy configuration &
trouble-shooting)
• Diagnostics (System/Error Logs, system monitoring, network monitoring,
ping test, frame monitor)
• Experion HS/LS Integration (PLC alarm/events, clock synch, etc)
• Redundancy (CPU, Power, I/O network redundancy)
Version 9.0
Redundancy options
MasterLogic-200 provides the control system designer with various redundancy
architecture options that fits the requirement.
Non-redundant system
For cost-effective applications, CPU Model: 2MLI-CPU# provides a fully non-
redundant system:
• Non-redundant CPU
• Non-redundant Power
• Non-redundant I/O cable
Version 9.0
Version 9.0
Related
No. Item Specifications
Standards
Ambient
1 0 ~ 55°C
Temp.
Storage
2 −25 ~ +70°C
Temp.
Ambient
3 5 ~ 95%RH (Non-condensing)
humidity
Storage
4 5 ~ 95%RH (Non-condensing)
humidity
Occasional vibration -
Pulse Sweep
Frequency Acceleration
width Count
10 ≤ f <57Hz − 0.075mm
2
57 ≤ f ≤ 150Hz 9.8m/s (1G) −
5 Vibration 10 times
Continuous vibration each IEC61131-2
Pulse direction
Frequency Acceleration (X, Y and
width
Z)
10 ≤ f < 57Hz − 0.035mm
2
57 ≤ f ≤ 150Hz 4.9m/s (0.5G) −
• Peak acceleration: 147m/s (15G)
2
• Duration: 11ms
6 Shocks IEC61131-2
• Pulse wave type: Half-sine (3 times in each of X, Y and X
directions)
Square wave
±1,500V
impulse noise
IEC61131-2
Electrostatic
Voltage: 4kV (Contact discharge) IEC61000-
Noise discharge
7 4-2
immunity
IEC61131-
Radiated 2,
electromagnetic 27 ~ 500MHz, 10V/m
field noise IEC61000-
4-3
Version 9.0
Digital/Analog
Power Input/Output, IEC61131-2
Fast transient Classification
supply Communication IEC61000-
/Burst noise Interface 4-4
Voltage 2kV 1kV
8 Atmosphere Free from corrosive gases and excessive dust
9 Altitude Less than 2,000m
Pollution
10 Less than 2
degree
Cooling
11 Air-cooling
method
Note:
IEC (International Electrotechnical Commission) – An international civil community that
promotes international cooperation for standardization of electric/ electro technology, publishes
international standard and operates suitability assessment system related to the above.
Pollution Degree – An index to indicate the pollution degree of used environment that
determines the isolation performance of the device. For example, pollution degree 2 means the
state to occur the pollution of non-electric conductivity generally, but the state to occur
temporary electric conduction according to the formation of dew.
Compliance to European Union Directives. This product has the CE mark and is approved for
installation within the European Union and EEA regions. It has been designed and tested to
meet the following directives:
EMC Directive. This apparatus is tested to meet Council Directive 2004/108/EC
Electromagnetic Compatibility (EMC) using a technical construction file and the following
standards, in whole or in part:
• EN61000-6-4 EMC – Generic Emission Standard, Part 2 – Industrial Environment
• EN61000-6-2 EMC – Generic Immunity Standard, Part 2 – Industrial Environment
The product described in this document is intended for use in an industrial environment.
Low Voltage Directive. This product is also designed to meet Council Directive 2006/95/EC
Low Voltage, by applying the safety requirements of EN61131-2 Programmable Controllers,
Part 2 – Equipment Requirements and Tests.
Version 9.0
Specifications
Related
No. Item 2MLR-CPUH/# Standards
Redundant CPU
Cyclic scan, Time-driven interrupts, Internal
1 Program Execution methods
Memory interrupts
Scan synchronous batch processing I/O (refresh
2 I/O control method
method), Direct I/O method by program instruction
Ladder Diagram, Sequential Function Chart,
3 Program language
Structured Text, Instruction List (view only)
Operator 18
Basic functions 130 + real number operation function
Number of Basic function
4 41
instructions block
Dedicated Special function blocks, Process function blocks
function block Dedicated communication function blocks (P2P)
LD 0.042µs/Step
Processing MOV 0.112µs/Step
speed S: Single real
5 ±: 0.602µs (S), 1.078µs (D)
(Basic Real number number
instruction) ÷: 1.106µs (S), 2.394µs (D)
operation D: Double real
x: 1.134µs (S), 2.660µs (D)
number
Including Upload
6 Program memory 7MB & System
Version 9.0
12 Flash Memory 16 MB
Symbolic
Variable Area 512 KB (Maximum, 256 KB retain settable)
(A)
Occupying 20
No point limit bytes of
Timer Time Range: 0.001 ~ 4,294,967.295 seconds symbolic
(1,193hours) variable area
per point
Occupying 8
No point limit bytes of
Counter symbolic
Coefficient Range : -32,768 ~ +32,767 variable area
per point
Fixed Area
M 512 KB
Variable
64 KB * 2 File Register
R (uses flash
Data (%RW0~%RW32767)
memory)
13 Memory
Capacity 16 KB Input Image
Direct Variable I
(%IW0.0.0~%IW127.15.3) Area
16 KB Output Image
Q
(%QW0.0.0~%QW127.15.3) Area
F 4 KB System Flag
K 18 KB (PID 256 loops) PID Flag
High Speed
L 22 KB
Flag Variables Link Flag
N 42 KB P2P Flag
Analog Refresh
U 32 KB Flag as
VAR_GLOBAL
Program INIT task 1 max
14 Type Timer Interrupt
Allocation 32 max
tasks
Version 9.0
Internal Device
32 max
Interrupt tasks
Scan program Balance: 256 minus sum of above
Total 256 max
15 CPU operation mode RUN, STOP, DEBUG
16 CPU restart mode Cold or warm restart
Watchdog timer, memory error, I/O error, battery
17 Self-diagnosis
error, power error, communication error etc.
RS-232C(1CH) Modbus slave
supported via
18 Built-in Program port USB (1CH) @ 12MBPS RS-232C port
Note: Additional program connections via Ethernet
& serial communication module (locate or remote)
Data storage method at power
19 Retain area configuration via Basic parameters
off
1173 (2MLR-CPUH/T)
20 Current consumption (mA)
1360 (2MLR-CPUH/F)
0.257 (2MLR-CPUH/T)
21 Weight (kg)
0.276 (2MLR-CPUH/F)
Redundancy Feature
Version 9.0
Specifications
Item Remarks
2MLI-CPUU 2MLI-CPUH 2MLI-CPUS(/P)
Operator 18
Version 9.0
Version 9.0
High Speed
Facilitated by a powerful state of the art processor (NGP1000), MasterLogic-200
CPU provides high speed execution of program instructions and backplane/
communication data transfers. In addition, dedicated intelligent communication
modules (Ethernet, Serial, Profibus etc) offer co-processing assistance to the
main controller CPU.
High Memory
High memory of MasterLogic-200 CPU combined with high speed & huge I/O
capacity feature provides a robust platform for efficient performance in large
applications.
Summary specification for CPU Models:
Memory Specification Memory size Remarks
Program Memory (Incl. 7 MB 4MB 3.5MB 640KB For program execution, upload,
System Memory) system parameters, history logs
Version 9.0
Without any restriction, any of the above modules (except for Ethernet module)
can also be installed in remote I/O bases located far away (by using FO network
of 2MLR-CPUH/#).
Version 9.0
Version 9.0
Ladder (LD)
MasterLogic-200 provides a friendly ladder (LD) programming editor, best suited
for relay logic / interlocks with timers and counters. The same editor serves as
online monitoring display for trouble-shooting situations.
Online Monitoring
Contact On
Version 9.0
Version 9.0
Version 9.0
Mode
Cold Restart Warm Restart
Parameter
Version 9.0
Bit BOOL
Byte BYTE
Version 9.0
Three-dimensional arrays
Array variables are extremely useful to a programmer to store a series of related
data items. For example, an array variable Tank_Level[0..9] can be used to store
level values of a max of 10 similar tanks typically using “for loop” command.
Version 9.0
+
Coils Coil/Negated coils, Set/Reset coils (latch), ±Transition
sensing coils
Data type Bool_to_*, Byte_to_*, Word_to_*, Int*_to_*, UInt*_to*,
conversions Real*_to_*, Time_to_*, Date_to_*, String_to_*, BCD_to_*,
*_to_BCD
Bit functions AND, OR, NOT, XOR, XNR, SHL, SHR, ROL, ROR etc.
Date & Time Multiply, Subtract, Divide, Add functions on date and time
functions variables
Mathematical Exponential, Degree/Radian, ADD/MUL/DIV/SUB, ABS,
functions MOD, Trignometric (SIN, COS, TAN…), SQRT, LOG…,
Version 9.0
The control engineers can simply building named variables circumventing the
hassles of manual memory allocation and derive the convenience of letting the
CPU automatically allocate memory according to the data types. This eliminates
human lapses involved in duplicate assignment, unused memory etc.
Retention Memory
Portions of data memory area provide (non-volatile) memory retention function.
• %R (File Register) memory area comprising 2 blocks of 64KB each
serving always as non-volatile memory for the engineers. Data stored
here will be retained even upon power failure to CPU and during cold or
warm restart options. The data in this area can be cleared only by
operating the CPU switch D.CLR for > 3 sec or upon battery failure
Version 9.0
Refer to the following table for the maintenance or reset (clear) of the retain area
data according to the PLC operation.
Symbolic
Item M area retain R area
Variables
Maintaining the
Over all reset Initializing as ‘0’ Initializing as ‘0’
previous value
Maintaining the
DCLR Initializing as ‘0’ Initializing as ‘0’
previous value
Version 9.0
Cold:
Initializing as ‘0’
* Cold Restart Mode if the program is downloaded
Please refer to Cold or Warm Restart Options section to know more about
memory retention functions.
Hot-swapping
Any faulty I/O module can be swapped online with a new one without having to
stop a running CPU. There are two methods:
o By operating a switch M.XCHG in CPU module (Available for 2MLI-
CPUU only)
o By running a software wizard in SoftMaster
Online Editing
Any part of the PLC program can be
edited online when CPU is running & the
new program can be downloaded to the
CPU without having to stop the CPU.
SoftMaster allows an intermediate step of
downloading the modified program to
CPU and monitor the outcome. The
programmer can continue to make
changes if required without quitting the
session.
Version 9.0
Fault Mask
Fault Mask enables program to continue uninterrupted even if a module error
occurs. Fault Mask can be set for any base/slot module either by
• SoftMaster software tool
• Program instruction setting fault mask flag
Only the faulty module stops operating while the overall system continues to
operate due to Fault Mask settings. If there is no error in the module, CPU works
normally with this setting.
Skip I/O
Skip I/O setting for any base/slot module
instructs the CPU to skip processing of
specified I/O module(s). The input image
(%I) area would not be refreshed for
those modules and output image area will
not be transferred to the actual module.
Force I/O
This function enables the control engineer
to force either ON or OFF values to digital
input or output locations in I/O bit image
areas.
Version 9.0
Data Tracing
This is one of unique features of MasterLogic PLC. Data tracing works at CPU
level, quite different from the trend monitoring feature usually available at
software level in many PLCs. Configure the trace parameters (trigger condition,
trace variables, sampling size) and trouble-shoot the variables in trend graphic or
tabular format.
Function Specification
Version 9.0
Version 9.0
Version 9.0
Function Specification
Version 9.0
Debug Modes
Buffer Size
Event type Description
in CPU
Any error occurring in system – error 2048
Error Log
code, timestamp, error details events
Version 9.0
The event buffer in CPU is limited and FIFO cyclic. But all the above 4 types of
PLC alarms & events can be archived in Experion and consolidated with
Experion system alarms & events display. Please refer to MasterLogic-Experion
Integration specification for further details.
Version 9.0
There are four power supply modules with different specifications to choose from,
according to the site requirements e.g. flexible voltage input range, DC input
power, output voltages and current rating.
Version 9.0
Battery Specifications
Item Specifications
Version 9.0
Rated input voltage 110 VAC 220 VAC I10 VAC 220 VAC 24 VDC
Input voltage range 85V~132VAC 176V~264VAC 85V~132VAC 176V~264VAC 19.2 ~ 28.8 VDC
Version 9.0
Battery Specifications
Item Specifications
Model
2MLB-M12A 2MLB-M08A 2MLB-M06A 2MLB-M04A
Item
No of Modules 12 modules 8 modules 6 modules 4 modules
Version 9.0
Version 9.0
Version 9.0
The above diagram demonstrates co-existence of both local I/O base and remote
I/O base (i.e. UTP and fiber-optic cables) in a dual link I/O network.
Please note that only FEnet module can reside on CPU Base.
FEnet module can not be installed on the Expansion base.
In redundant system employing CPU model: 2MLR-CPUH/#, Local I/O bases can
communicate with the CPU via Industrial Ethernet using UTP CAT5 cable
traveling up to a max 100m distance.
Remote I/O bases as far as 2km can communicate with the CPU on fiber-optic
networks available in both CPU as well I/O base communication slave modules.
Version 9.0
Model
2MLR-M02P 2MLR-M06P
Item
No. of Modules 2 modules 6 modules
Version 9.0
Version 9.0
Specification
Item Remarks
2MLR-DBSF/DBDF 2MLR-DBST/DBDT 2MLR-DBSH/DBDH
Media Optical Electrical Mixed
Loader
Expansion drive USB
connection
Version 9.0
2. Open networks
2.1 Network Summary Specifications
A wide range of open networking capability makes adds versatility to
MasterLogic-200 PLC’s scalable architecture. System engineers have an array of
choices and features to design & construct a system architecture that is not just
meeting the application but also renders high performance and bandwidth for
future expansions.
Configuration
SoftMaster-NM SoftMaster-NM & Sycon
Software
No of communication Max 24 communication modules per CPU
modules per CPU (Max 12 HSL services & 8 P2P services per CPU)
Network Diagnostics Auto-scan, Ping Test, Frame Monitor, Link Monitor, Loop back (as applicable)
Version 9.0
HSL Service
High Speed Link can be defined as a communication service that performs bi-
directional data transfers between:
o Two or more MasterLogic-200 PLCs (Peer-to-Peer)
o MasterLogic-200 and Profibus-DP devices (Pnet)
o MasterLogic-200 and DeviceNet devices (Dnet)
Version 9.0
Overview
Open standard (IEEE802.3U) high speed Ethernet (FEnet) modules facilitate
inter-connecting MasterLogic PLCs with either higher level computers or other
peer PLCs on industrial Ethernet network. Network control uses industry
standard Carrier Sense Multiple Access with Collision Detection (CSMA/CD)
protocol. Two types of modules are available to choose depending on the
distance and cabling philosophy.
o Twisted pair (UTP/STP-CAT5) media with RJ45 connector (100m)
o Fiber-optic (x62.5/125um, Multi-mode) media with SC connector (2km)
Concurrent services
The above services are based on TCP-IP & UDP-IP protocols and thus many of
the above processes can be concurrent, i.e. running at the same time in a single
FEnet module. For example, a single FEnet module can be used for a) peer-to-
peer integration with other PLCs, b) Experion integration c) MODBUS TCP-IP
Version 9.0
master protocol d) SoftMaster I/F all at the same time. However, performance
could be limited depending on the load.
Specifications
Fast Ethernet
Modules 2MLL-EFMT 2MLL-EFMF
Ethernet Standard IEEE802.3U
Protocol TCP-IP, UDP-IP
Network Control Protocol
CSMA/CD
(Access Method)
Software Firewall IP address settings in SoftMaster-NM
Public Network Access DNS server and Gateway IP address setting
Dynamic IP address for ADSL DHCP protocol
Highway Topology
Baseband
(Transmission Method)
Transmission Speed 10/100 Mbps 100 Mbps
Physical Layer 100baseTx (T.P) 100baseFx (Fiber-Optic)
UTP/STP, CAT5 (RJ45 x62.5/125um, Multi-mode, SC
Media
connector) connector
100m (Switch/Node , 2Km (Switch/Node , Fiber
Transmission Distance
UTP/STP) Optic)
Max # of nodes 64
√
HSL
(Peer-to-Peer High Speed Link with other MasterLogic PLCs)
HSL Send/Receive blocks 200 words / block, (Max. 128 blocks)
√
MLDP
(Experion Interface – MasterLogic Dedicated Protocol)
Service /
Protocol √
Modbus TCP slave
(MODBUS TCP slave protocol)
√
P2P
(MODBUS TCP master, User defined Protocol master)
SoftMaster I/F √
Configuration Software SoftMaster-NM
LEDs RUN, I/F, HS, P2P, PADT, PC, ERR, TX, RX, 10/100
Network Diagnostics Auto-scan, Ping Test, Frame Monitor, Link Monitor
Current Consumption (mA) 410 630
Weight (g) 105 120
Version 9.0
High Speed Link (HSL) services in Fast Ethernet module (FEnet) ensures
efficient and reliable peer-to-peer networking of MasterLogic-200 PLCs.
In the above example, there are five PLCs (Station#1 ~ 5) configured for peer-to-
peer network. Station#1 is configured with 2 “send” blocks which are
broadcasted to rest of all the stations in the network. Only the station with
“receive” blocks decides to accept or reject the broadcast packet based on
parameters.
Read and Write parameters define the memory areas & size of data transfer for
each block. Thus the engineer can configure and get peer-to-peer function
working within a few minutes by few clicks and keys.
A max of 128 blocks can be configured in each HSL service and each block can
handle of max of 200 words data size. Out of 128, a max of 64 blocks can be
configured as “send” and the rest as “receive” blocks. A max of 64 MasterLogic
Version 9.0
Function Modbus
Description Remarks Response size*
Code Address
Output Contact Status Read 0XXXX
01 Bit read 2000 coils
(Read Coil Status) (bit-output)
Input Contact Status Read 1XXXX
02 Bit read 2000 coils
(Read Input Status) (bit-input)
Output Register Read 4XXXX
03 Word Read 125 registers
(Read Holding Registers) (word-output)
Input Registers Read 3XXXX
04 Word Read 125 registers
(Read Input Registers). (word-input)
Version 9.0
Version 9.0
Version 9.0
Overview
Like Ethernet, Serial Communication (Snet) modules add versatility and
openness to MasterLogic architecture. Open standard RS232C/ RS422 / RS485
modules facilitate communication of MasterLogic PLCs with a wide range of
serial devices i.e. RTU, panels, weigh bridges, barcode readers, high level
computers or even other PLCs.
Three types of modules are available to choose depending on the distance and
the partner device.
o Two ports of RS232C
o Two ports of RS422/485
o One RS232C port and one RS422/485 port
Version 9.0
Specifications
Serial Interface (Snet)
Modules 2MLL-C22A 2MLL-C42A 2MLL-CH2A
1ch – RS232C
Interface Standard RS232C – 2ch RS422/485 – 2ch
1ch – RS422/485
Modem connection with remote √ (only on RS232C
√ -
devices port)
Start Bit 1
#Data Bits 7 or 8
Communication
Settings Stop Bits 1 or 2
(SoftMaster-
Parity Odd/Even/None
NM)
Options: 300 / 600 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 / 57600
Baud rate
/ 115200 bps
Synchronization Asynchronous
RS232C - 15m
15m (extendable by (extendable by modem)
Transmission Distance 500m max
modem / phone line)
RS422 - 500m max
RS232C - 1:1
Network Configuration 1:1 1:1, 1:N, N:M
RS422 - 1:1, 1:N, N:M
Station No Setting Setting range : 0-31 (Max. station No. available : 32 stations)
Modbus RTU /
√
ASCII slave
Service / √
Protocol P2P
(MODBUS RTU/ASCII master, User defined Protocol master)
SoftMaster I/F √
Configuration Software SoftMaster-NM
LEDs RUN, I/F, TX, RX, ERR
Network Diagnostics Auto-scan, Frame Monitor, Link Monitor, Loop back
Current Consumption (mA) 310 300 310
Weight (g) 121 116 119
Version 9.0
The Snet module can be configured to serve open standard MODBUS RTU or
ASCII slave protocol for allowing any third-party controllers / HMI / SCADA to
communicate with MasterLogic PLCs.
Version 9.0
Version 9.0
Overview
Pnet I/F module is one of the communication modules of MasterLogic-200 PLC
system. It uses token ring topology to control the communication and configure
the network. Pnet I/F module uses a shielded Twisted Pair Copper Cable to
control the fieldbus.
Specifications
Profibus-DP (Pnet) Master
Standard EN50170/DIN19245
Version 9.0
200 1.5M
100 3M/6M/12M
Specifications
Profibus-DP (Pnet) Remote & Slave
Standard EN50170/DIN19245
Version 9.0
1,200 9.6K/19.2K/93.7K/187.5K
Max. Distance &
400 500K
Transmission Speed
200 1.5M
100 3M/6M/12M
2MLL-PSRA : 600
Current Consumption (mA)
2MLL-PSEA : 410
2MLL-PSRA : 114
Weight (g)
2MLL-PSEA : 103
Version 9.0
Overview
DeviceNet is an application layer which is used as a communication link to
interconnect control devices for data exchange. It uses Controller Area Network
as the backbone technology and defines an application later to cover a rage of
device profiles. Typical applications that use Dnet are industrial devices of limit
switch, photo-electronic sensor, motor controller, inverter, bar code reader, and
apnel display to the network.
Version 9.0
Specifications
Item Performance Specifications
Trunk/drop line
Network Structure Power/Signal cable inside the identical
network cable
Version 9.0
Version 9.0
3. SoftMaster
Overview
SoftMaster is a software tool designed to program and debug MasterLogic-200. It
provides integrated PLC programming environment.
Project Management
• Program multiple PLCs through a single window
• One project file (.xgp) as central storage for complete PLC info
• Compare project files to detect minor differences
• Import / Export entire PLC or selectively individual component
• Flexible documentation – entire PLC data or selectively
62 MasterLogic-200 Specifications and Technical Data
Release R202 Dec. 2013
Version 9.0
Version 9.0
logic & strategies in these function blocks using configurable input and output
parameters & data types. These user defined function blocks can be password
protected for security and copyright purposes
Monitoring
When SoftMaster is in connected mode, it allows monitoring of the below
functions:
1. Program Monitoring
2. Variable Monitoring
3. System Monitoring
4. Address Monitoring
5. Special Module Monitoring
6. Trend Monitoring
7. Data Traces
Debugging
SoftMaster allows program debugging with advanced features like Step Over,
Step Into, Step Out and Conditional Breakpoints.
Online
SoftMaster provides the following features when it is connected with PLC:
1. Online Editing
2. Write programs to PLC
3. Read programs from PLC
4. Change Operation Mode (RUN/STOP/DEBUG)
5. Reset / Clear PLC
6. View PLC information / history / errors and warnings
7. Specify Flash Memory Setting
Version 9.0
Simulation
Simulation allows an engineer to programs without PLC, or debug program by
using input condition setting or module simulation function.
The following features are supported by the simulation environment:
1. Program simulation
The program written in LD/SFC/ST can be simulated. Online editing and
debugging is supported by the simulation environment.
3. Module simulation
Digital I/O module, A/D conversion module, D/A conversion module, High
counter, Temperature control module can be simulated.
System Requirements
Version 9.0
Version 9.0
4. Model Numbers
4.1 CPU modules
Version 9.0
4.2 I/O base & Power & Cables (2MLI-CPUU, CPUH, CPUS)
Version 9.0
4.3 I/O base & Expansion Drive & Power & Cables (2MLR-CPUH/#)
Version 9.0
Version 9.0
Version 9.0
Version 9.0
4.9 Others
Version 9.0
Experion, PlantScape, TotalPlant are U.S. registered trademarks of Honeywell International Inc. All other
products and brand names shown are trademarks of their respective owners.
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the
implied warranties of merchantability and fitness for a particular purpose and makes no express warranties
except as may be stated in its written agreement with and for its customer. In no event is Honeywell liable
to anyone for any indirect, special or consequential damages. The information and specifications in this
document are subject to change without notice