Siemens - NXAir - Disjuntor A Vácuo 3AE5 SION
Siemens - NXAir - Disjuntor A Vácuo 3AE5 SION
Vacuum circuit-breaker
7.2 kV – 17.5 kV, 16 kA – 40 kA
24 kV, 16 kA – 25 kA
12 kV – 17.5 kV, 31.5 kA for generator switching applications
OPERATING INSTRUCTIONS
Description                .................................................................................................................................................... 17
    Design ...............................................................................................................................................................     17
    Interlocks ...........................................................................................................................................................     31
    Nameplate .........................................................................................................................................................        34
    Technical data ...................................................................................................................................................         34
    Ambient conditions ............................................................................................................................................            36
    Installation altitudes ..........................................................................................................................................          36
    Operating times .................................................................................................................................................          37
    Circuit diagrams ................................................................................................................................................          37
Installation ...................................................................................................................................................... 39
    Fixing in the panel .............................................................................................................................................          39
    Earthing .............................................................................................................................................................     49
    Connecting low voltage .....................................................................................................................................               50
    Electrical connection of the main conductors ....................................................................................................                          53
    Inserting and racking the SION® withdrawable circuit-breaker .........................................................................                                     64
Operation               ........................................................................................................................................................ 69
    Commissioning .................................................................................................................................................            69
    First closing operation .......................................................................................................................................            70
    Closing ..............................................................................................................................................................     70
    Opening ............................................................................................................................................................       70
Maintenance .................................................................................................................................................. 73
    Maintenance .....................................................................................................................................................          73
    Service life of the vacuum interrupters ..............................................................................................................                     73
    Accessories and spare parts .............................................................................................................................                  74
    Disposal ............................................................................................................................................................      74
Index ................................................................................................................................................................... 77
Central legend                    ............................................................................................................................................. 79
                                DANGER
                            Indicates a hazard with a high degree of risk which, if not avoided, will result in death
                            or serious injury.
                                WARNING
                            Indicates a hazard with a medium degree of risk which, if not avoided, could result
                            in death or serious injury.
                                CAUTION
                            Indicates a hazard with a low degree of risk which, if not avoided, could result in mi-
                            nor or moderate injury.
              High voltage
                                  DANGER
                              Live parts! Touching live parts results in a life-endangering electric shock.
                              Establishing and ensuring a voltage-free state at the work site for the duration of the
                              work.
                              Before starting work, observe the 5 safety rules in the order given in accordance with
                              DIN EN 50110-1:
                              • Disconnect from the power supply
                              • Secure against re-connection
                              • Verify safe isolation from the power supply
                              • Earth and short-circuit
                              • Cover or cordon off neighbouring live parts
                              Checking the vacuum circuit-breaker in the panel with applied high voltage is al-
                              lowed only after full functionality has been determined (see “Commissioning”, on
                              page 69).
                              If work must be carried out on the open operating mechanism housing, all switching
                              operations must be blocked. If the cover has not been refitted for test switching op-
                              erations, a safety distance of at least 1 m must be maintained.
                   Heater
                                 WARNING
                             Risk of burns! Touching hot surfaces can cause burns.
                             Let the heater and its surroundings cool down.
          Switching noise
                                 CAUTION
                             Increased noise levels due to switching noise! Temporary noise levels above
                             85 dB (A) can cause damage to health.
                             Wear suitable ear protection.
   Dangerous substances
                                 CAUTION
                             Eye damage caused by lubricants! Eye contact with Molykote® Longterm causes
                             serious eye damage in category 1 (classification according to Regulation (EC) No.
                             1272/2008)
                             Wear eye protection / face shield.
                                  CAUTION
                             Irritation of the skin caused by grease or lubricant! Contact with grease or lubri-
                             cant causes irritation of the skin.
                             Wear gloves with appropriate protection against penetration of grease or lubricant.
                             Transport
              Lifting gear
                                   WARNING
                             Unsuitable lifting gear! Incorrectly dimensioned fixing gear or incorrectly adjusted
                             lifting gear may cause the transport unit to fall down.
                             • Do not stand below suspended loads.
                             • Select lifting gear, transportation and fixing gear according to the weight of the
                                  transport unit, including any packing, such as transport pallets.
                             • Observe transport symbols.
Transport weight Refer to the delivery documents for the weight of the transport unit.
Transporting with packing    Transport the transport unit to the installation site or storage location:
                             • with a fork-lift truck or
                             • with sling gear suspended from a crane
                                - at a spreading angle of approx. 60° or
                                - with cross-members.
                              Unpacking
         Working materials    Required tools:
                                - Knife/scissors
                                - Lifting gear with lifting harness
                                - Pliers or lever.
                                 CAUTION
                              Risk of injury from sharp edges! Fasteners may break and have sharp edges.
                              Always use a suitable tool to lever out fasteners.
                              Note
                              Damaging the transport belt straps! Belt straps could be severed when cutting
                              open the box on the pallet floor.
                              • The vacuum circuit-breaker is attached to the pallet with belt straps. It is not per-
                                 mitted to transport the vacuum circuit-breaker on the pallet without using belt
                                 straps (see Fig. 3 to Fig. 4).
                              • Keep box for reuse.
                              Note
                              Risk of tipping over due to shift in centre of gravity! Vacuum circuit-breakers
                              with mounted contact arms may tip onto the contact system if not fixed.
                              Before undoing the belt straps, ensure that the vacuum circuit-breaker is positioned
                              safely and hook fixing gear to the points marked with crane hooks (see Fig. 5 to
                              Fig. 7).
Opening the transport unit    •   Place the transport unit on a level, non-slip and pressure-resistant surface.
                              •   Remove lifting gear or means of transportation.
                              •   Remove plastic wrap.
                              •   Lever out the fasteners from the box and lift off the box (see Fig. 2).
                                 Note
                                 Damaged components! In the case of damage, such as breaks, cracks, flaking,
                                 bent metal parts, damaged plug-in contacts, tears or bare cables, voltage break-
                                 downs can occur.
                                 • Do not use the vacuum circuit-breaker.
                                 • Send it back in its original transport unit (see “Reuse of transport unit”, page 13).
Fig. 3      Example – unpacking the fixed mounting ver-      Fig. 4     Example – unpacking version with withdrawa-
            sion                                                        ble part
         Transportation to the   •   Remove all tensioning belts and pieces of fastening wood.
            mounting location    •   Remove the material pack and store it safely in the packing for later installation.
                                 Note
                                 Shifted centre of gravity! If the vacuum circuit-breakers are lifted with contact arms
                                 mounted, the centre of gravity will be towards the contact arms.
                                 The unit is transported in an inclined position.
Fig. 7   Transporting, only for 31.5 kA with distance         Fig. 8     Transporting, only for 24 kV with 2000 A /
         between pole centres 150/160                                    2500 A
                               Note
                               Material damage due to incorrect mounting of sling gear! The holders (49) will
                               be damaged if ropes or similar slings are fastened below the holders (49).
                               Only use the crane eyes to fasten the slinging equipment.
                                 Storage
                                 Store the vacuum circuit-breaker in the following condition:
                                 Note
                                 Risk of corrosion damage if stored improperly!
                                 Failure to observe the storage conditions shortens the storage life and the vacuum
                                 circuit-breaker may be damaged.
                                 •       If the storage conditions listed below are met, the vacuum circuit-breaker can be
                                         stored for up to a year in its transport unit.
                                 •       If the storage conditions are not met, the vacuum circuit-breaker cannot be
                                         stored in the transport unit for longer than 6 months.
                                 •       If storage for more than one year is planned, unpack the vacuum circuit-breaker
                                         from the transport unit. Further storage may necessitate fresh corrosion protec-
                                         tion, and it must be ensured that the vacuum circuit-breaker cannot be dam-
                                         aged.
Blank page
    General information
                              The images shown are examples; not all the variants of the vacuum circuit-breaker
                              are shown here.
                              Areas of application
                              SION® Vacuum circuit-breakers are 3-pole interior circuit-breakers for a rated volt-
                              age range of 7.2 kV to 24 kV.
                              Under normal service conditions, the SION® vacuum circuit-breaker (as per
                              IEC 62271-1:2017 and VDE 0671-1) is maintenance-free for up to 10 000 operating
                              cycles.
                              30 000 operating cycles require maintenance work that must only be performed by
                              personnel trained by Siemens (see also “Maintenance” on p. 73).
               Intended use   SION® Vacuum circuit-breakers are suitable for switching any type of alternating
                              current circuits under normal operating conditions, such as:
                              •   Overhead lines
                              •   Cables
                              •   Transformers
                              •   Capacitors
                              •   Motors
                              •   Generators (SION® generator circuit-breakers)
                              SION® Vacuum circuit-breakers operate in continuous, periodic and short-term op-
                              eration.
                              Standards
                              The basic version and all listed configurations of the vacuum circuit-breakers are
                              type-tested devices as per IEC.
                              The SION® vacuum circuit-breakers comply with the following standards:
•    IEC 62271-1:2017               High-voltage switching devices and switchgear – Part 1: Common specifica-
•    DIN EN 62271-1:2018            tions
•    IEC 62271-100:2017             High-voltage switching devices and switchgear – Part 100: Alternating cur-
•    DIN EN 62271-100:2018          rent circuit-breaker
•    IEC/IEEE 62271-37-013:2015     High-voltage switching devices and switchgear – Part 37-013: AC generator
                                    switch
                              SION® Vacuum circuit-breakers meet the requirements for the classification for cir-
                              cuit-breakers C2, E2, M2 and S1 as per IEC 62271-100:2017.
                              SION® Generator circuit breakers meet the requirements of the classification for cir-
                              cuit breakers G1 or G2 as per IEC/IEEE 62271-37-013:2015.
                              Country-specific and standard-specific deviations from the standards mentioned
                              must be observed.
                      Scope of delivery
                      Delivery includes:
                      • SION® vacuum circuit-breaker
                      • or SION® vacuum circuit-breaker on withdrawable part
                      • Material pack with 10-pole plugs for
                      • 20-pole connector strip or
                      • 30-pole connector strip
                      • Operating instructions and unpacking instructions
                      • Circuit-breaker-specific circuit diagrams
Description
                                        Design
                                        The images shown are examples; not all the variants of the vacuum circuit-breaker
                                        are shown here.
Fig. 9       12 kV, 25 kA, 1250 A, operating mechanism            Fig. 10   12 kV, 25 kA, 1250 A, pole side, without insu-
             side                                                           lating shells for system side
Fig. 11      17.5 kV, 31,5 kA, 1250 A, operating mecha-           Fig. 12   17.5 kV, 31.5 kA, 1250 A, pole side with with-
             nism side with withdrawable part                               drawable part, without insulating shells for
                                                                            system side
Fig. 13    24 kV, 16–25 kA, 2500 A, operating mecha-             Fig. 14    24 kV, 25 kA, 2500 A, pole side with with-
           nism side with withdrawable part                                 drawable part, without insulating shells for
                                                                            system side
                                                     20.1
                                                                                                                            20.2
                                                     57.2                                                                   57.2
                                                     59.3
                                                     56.2                                                                   59.3
                                                                                                                            56.2
                                                     56.1                                                                   56.1
                                                     55.1                                                                   55.1
                                                     56.3                                                                   56.3
 0025-66
0025-05
58 58
Fig. 15    Example of a control board with narrow cover         Fig. 16     Example of a control board with wide metal
           made from insulating material                                    cover
                                There are openings in the covers for the operating and display elements.
                  Functions     The CLOSE pushbutton (56.1) is used to close the vacuum circuit-breaker. After
                                closing, the motor immediately recharges the closing spring. If the supply voltage for
                                the motor fails, the closing spring can be charged with a hand crank. For this pur-
                                pose, the covers contain an opening, behind which you will find the hand crank cou-
                                pling (57.2) of the gear unit.
                                To prevent electrical and manual closing, some designs of the vacuum circuit-break-
                                er can be fitted with a key-operated interlock (59.3).
                  Indicators    The charge state of the springs is indicated by the spring state indicator (55.1). The
                                position indicator device (56.3.) shows the CLOSED or OPEN state. The operating
                                counter (58) indicates the number of performed operating cycles. An operating cycle
                                consists of one closing and one opening.
                                         Fig. 18      Open operating mechanism, example 17.5 kV, 31.5 kA, 2500 A
31     Auxiliary switch (-S1)                                                (optional, not shown)
32     Low-voltage plug connector (-X0) (optional)                    55     Closing spring
33     Plug (Q0-X1.1, Q0-X1.2, Q0-X1.3) only when ordering the        55.1   Spring state indicator
       20-pole or 30-pole connector strip (not shown)                 56.3   Position indicator CLOSED-OPEN
33.2   Plugs (-X01) and (-X02) for withdrawable part (optional)       57.2   Hand crank coupling
34     Anti-pumping device (-K1)                                      58     Operations counter
51.1   1st shunt release (-Y1)                                        59.3   Key-operated interlock (optional)
51.2   2nd release (optional)                                         59.4   Heater (-R01), condensation water protection (optional)
51.3   3rd release (optional)                                         59.5   Electrical closing lock-out (-Y8E) (optional, not shown)
52     Closing solenoid (-Y9)                                         59.6   Resistor (-R1), dependent on voltage 1 or 2 resistors, for
53     Motor (-M1), charging the closing spring                              undervoltage release (-Y7) (optional)
54.1   Position switch (-S12), prevents electrical closing in
       mechanical interlock (not shown)
54.2   Position switch (-S21), motor control
54.3   Position switch (-S3), control for (-K1) anti-pumping device
54.4   Position switch (-S4), signal “Closing spring charged”
54.6   Position switch (-S6), circuit-breaker tripping signal
Additional equipment (not      The SION® vacuum circuit-breaker can also be equipped with the following equip-
            for all designs)   ment:
                               Shunt release 3AX1101-.., 3AY1410-..                                            (-Y2)
                               Transformer-operated release 3AX1102-..                                    (-Y4, -Y5)
                               Transformer-operated release 3AX1104-.. (0.1 Ws)                                (-Y6)
                               Undervoltage release 3AX1103-..                                                 (-Y7)
                                  -   with resistor for undervoltage release (-Y7)                             (-R1)
                               Heater (condensation water protection)                                         (-R01)
                               Electrical closing lock-out 3AX1405-..                                         (-Y8E)
                                  -   with position switch, electrical closing lock-out                        (-S5)
                               Position switch 3AX4206-0A, prevents electrical closing if there is a          (-S12)
                               mechanical interlock
                               Key-operated interlock 3AX1437-.., with position switch                         (-S5)
                               Protective plate 3AX1456-..
                               Circuit-breaker shaft cover 3AX1466-..
                               In addition to the serial shunt release (-Y1), the vacuum circuit-breaker can be
                               equipped with a maximum of two type 3AX11 releases. For the permitted possi-
                               ble combinations of the additional equipment as well as special designs, refer to cat-
                               alogue HG11.02 or contact the relevant Siemens representative.
                                                                       Note
                                                                       The motor protection devices are not included in the de-
                                                                       livery of the vacuum circuit-breaker and must be ordered
                                                                       separately.
                                 *)         The operator’s supply voltage may deviate from the rated supply voltage of the vacuum circuit-
                                            breaker by -15 % to +10 %.
                                 1)         50/60 Hz.
                                 2)         empirically determined values
                                                                               DC       DC      DC     DC    AC1)        DC        AC1)
Rated supply voltage U*)                                                 V      24      48       60    110    110        220       230
Rated current of the protective device I**) A 2 1 1 0.5 0.315 0.315 0.250
                                 *)         The operator’s supply voltage may deviate from the rated supply voltage of the vacuum circuit-
                                            breaker by -15 % to +10 %.
                                 **)        Built-in automatic circuit-breaker with C characteristic
                                 1)         50/60 Hz.
                                  1) Working area for generator circuit breaker as per IEC/ IEEE 62271-37-013
                                                                          DC                             AC
Rated supply voltage U*)
                                                      V       48       110-125     220-250        120          240
Closing                                               V      36-56      90-140     180-280     104-127        208-254
          Power consumption
                                    Rated insulation voltage:                  AC/DC 250 V
                                    Insulation group:                          C as per VDE 0110
                                    Continuous current:                        10 A
                                    Closing capacity:                          50 A
           Breaking capacity
                                           Rated operating voltage                         Rated normal current
                                                  up to U (V)                                     I (A)
                                                                                Resistive load            Inductive load
                                                                                                           (T = 20 ms)
                                                   AC 230                             10                       10
                                                    DC 24                             10                       10
                                                    DC 48                             10                        9
                                                    DC 60                              9                        7
                                                   DC 110                              5                        4
                                                   DC 220                             2.5                       2
Fig. 28   Low-voltage interface (-X0), 64-pole               Fig. 29    Low-voltage interface, cable outlet (60)
          3AX1134-.. (32)
                                 For the connection of the control cable, the standard version of the vacuum circuit-
                                 breakers is equipped with a 64-pole low-voltage interface (-X0).
                                 The 64-pole plug for the external terminal is suitable for crimp termination of control
                                 cables with a nominal cross-section of 1.5 mm2.
Fig. 30 2nd shunt release 3AY1410-.. Fig. 31 2nd shunt release 3AX1101-..
Order via the 9th digit                                      Order via the 9th digit for all other combinations
• for generator circuit-breaker SION®: MLFB = B
•    for all other vacuum circuit-breaker SION®:
     MLFB = B with addition G39
Fig. 32 Transformer operated release (51.3) Fig. 33 Transformer operated release (51.3)
                                The transformer operated releases (-Y4), (-Y5) and (-Y6) consist of an energy store,
                                an unlatching fixture and an electromagnetic system. If the tripping current is ex-
                                ceeded (90 % of the transformer operated release’s rated current), the stored ener-
                                gy mechanism is unlatched, thus initiating opening of the vacuum circuit-breaker.
                                For use of the transformer operated releases, auxiliary transformers are also need-
                                ed for adaptation, in addition to the main current transformers.
                                Transformer-operated releases (-Y4) and (-Y5) are equipped with a rectifier.
                                Power consumption for 0.5 A and 1 A ≤ 6 VA at ≤ 90 % of the transformer operated
                                release’s rated current and with open armature.
          Power consumption     10 W / VA
                                  Note
                                  Damage due to missing or incorrect series resistor! Operation without series re-
                                  sistor (-R1) can cause damage.
                                  The undervoltage release (-Y7) may only be operated with the supplied series resis-
                                  tor (-R1).
                                  The undervoltage release (-Y7) has an electromagnetic system that is always live
                                  when the vacuum circuit-breaker is in the closed state. If the voltage drops below a
                                  certain value, the undervoltage release (-Y7) is unlatched, thus initiating opening of
                                  the vacuum circuit-breaker via the energy storage mechanism.
                                  Random tripping of the undervoltage release (-Y7) is generally performed by an NC
                                  contact in the tripping circuit, but can also be done with the aid of an NO contact by
                                  short-circuiting the solenoid coil. If this release method is used, the solenoid coil’s
                                  short-circuit current is limited by the built-in resistor.
                                  The undervoltage release (-Y7) can also be connected to voltage transformers.
                                  The undervoltage release (-Y7) automatically trips the vacuum circuit-breaker if the
                                  rated supply voltage drops to an inadmissible value.
                                  Undervoltage releases (-Y7) DC  60 V are protected against overvoltage by a var-
                                  istor. Undervoltage releases (-Y7) AC/DC  100 V are equipped with a rectifier.
          Power consumption       20 W / VA
                                                                                               (-R1)   Resistor
                                                                                               (-S1)   Auxiliary switch
                                                                                               (-Y7)   Undervoltage
                                                                                                       release
Fig. 34     Undervoltage release (51.7), with one resistor    Fig. 35    Typical circuit for connection of the undervolt-
            or two resistors depending on the voltage                    age release (-Y7)
                                                               WARNING
                                                           Danger of burns! Touching hot surfaces can cause
                                                           burns.
                                                           Let the heater and its surroundings cool down.
                               Interlocks
                               To lock vacuum circuit-breakers as a function of the switching position, the spring
                               charge mechanisms of the vacuum circuit-breaker can be equipped with an inter-
                               lock. This also applies to vacuum circuit-breakers on switchgear trucks, in with-
                               drawable sections or with disconnectors.
                 Conditions    If the vacuum circuit-breaker is mounted on a carriage or withdrawable part, it may
                               only be switched on in the operating or disconnected position.
                               At the same time, the vacuum circuit-breaker may be moved on the switchgear truck
                               or withdrawable section only when it is open.
                               Positions of the vacuum circuit-breaker in the switchgear
    Disconnected position      The isolating distance between the vacuum circuit-breaker contacts and the fixed
                               contacts in the switchgear is fully attained.
          Operating position   The vacuum circuit-breaker is inserted fully into the switchgear and the contacts
                               overlap completely with the switchgear counter-contacts.
                               Mechanical interlock
                               A sensing and actuation component (b) on the system side detects the operating po-
                               sition (CLOSED/OPEN) of the vacuum circuit-breaker.
  CLOSED switch position       If the vacuum circuit-breaker is closed, actuation of the system’s query and actuation
                               component (b) is prevented. A mechanical system in the switchgear truck or with-
                               drawable section reliably locks movements of the circuit-breaker on the switchgear
                               truck or withdrawable section.
     OPEN switch position      If the vacuum circuit-breaker is open, the query and actuation component (b) on the
                               system side actuates, via the stroke (a), the vacuum circuit-breaker’s mechanical in-
                               terlock and reliably locks closing of the vacuum circuit-breaker.
35 ±0.3 mm
              The installation dimensions (c+d) for the query or actuation component (b) are in-
              cluded in the dimensional drawing supplied.
                                                           Note
                                                          In the as-delivered condition, the vacuum circuit-breaker
                                                          is locked with the key-operated interlock and must be un-
                                                          locked for test switching operations and commissioning.
                                                           Note
                                                          For mechanical or electrical circuits, the electrical clos-
                                                          ing lock-out 3AX1415-.. must be connected to the control
                                                          voltage, otherwise closing is not possible.
                                Nameplate
                                                                                        1)       Manufacturer
                                                                                        2)       Type designation
                                                                                        3)       Factory number
     1)                                                                                 4)       Rated voltage Ur
                                                                                        5)       Rated frequency fr
     2) Type: 3AE5656-6                                                                 6)       Rated short-circuit breaking current Isc
     3) No.: S 3AE5/90000508               Year of manufacture 2021             9)      7        Rated power frequency withstand voltage Ud
 4), 5) Ur      17.5 kV 50/60 Hz           Ir                    2500 A       10)       8)       Rated lightning impulse withstand
                                                                                                 voltage Up
     6) Isc      40 kA                     tk                          3s     11)
                                                                                        9)       Year of manufacture
 7), 8) Ud/Up    42 kV/   95 kV            m                      140 kg      12)
                                                                                        10)      Rated normal current Ir
                                                                                        11)      Rated short-circuit duration tk
          Rated operating sequence: O–0.3 s–CO–15 s–CO                        13)       12)      Mass m
              Class as per IEC 62271-100: E2, C2 and M2                       14)       13)      Rated operating sequence
                           Made in Germany                                              14)      Classification E2, C2 and M2 for circuit-
                                                                                                 breakers according to the standard
                                Technical data
                                Vacuum circuit-breaker SION®
                                  a)       On request
                                  b)       From 2000 A upwards only with 310 mm space between the lower and the upper terminal
                                           and a pole-centre distance of 210/275 mm
                                  c)       only with additional active cooling (fc)
                                 a)        On request
                                 c         only with additional active cooling (fc)
                                 d)        Rated insulation level as per IEC 62271-100:2017
                                 Ambient conditions
                                 Occasional condensation may occur under these ambient conditions.
                                 SION® Vacuum circuit-breakers are suitable for use in the following climate classes
                                 according to IEC 60721-3-3:2019:
                                +55 °C                                                                                Class
                                                             •    Climatic ambient conditions:                        3K41)
                                131 °F
                                                             •    Biological ambient conditions:                      3B1
                                                             •    Mechanical ambient conditions:                      3M2
     -5 °C 1)                                                •    Chemically active substances:                       3C22)
     23 °F 1)                                                                                                         3C33)
                                                             •    Mechanically active substances:                     3S24)
                                           5)
                                95 %
                                90 % 6)                      1)      Minimum temperature limit: -5 °C / 23 °F (with addition A40 to
                                                                     -25 °C / -13 °F)
                                                             2)      Without occurrence of salt fog and simultaneous condensation
                                                             3)      Class 3C3 (H2S < 20 ppm in dry air < 50 % with order suffix
                                                                     D20)
                                                             4)      Restriction: Clean insulation parts
  5%                                                         5)      Average value, measured over 24 hours
                                                             6)      Average value, measured over 1 month
                                 Installation altitudes
          Dielectric strength    The dielectric strength of air insulation decreases with increasing altitude due to low-
                                 er air density. As per IEC 62271-1, the rated lightning impulse withstand voltage val-
                                 ues and rated short-duration power frequency withstand voltage given in Fig. 42 are
                                 valid up to an installation altitude of 1 000 m above sea level.
                                 Above an altitude of 1000 m, the insulation level must be corrected as shown in
                                 Fig. 44:
                                                             U  U0 x K a
Ka = em x (H - 1000)/8150
                                                             Example
                                                             For a required rated withstand voltage of 75 kV at an al-
                                                             titude of 2 500 m, an insulation level of at least 90 kV un-
                                                             der standard reference atmosphere conditions is
                                                             required:
                                                             90 kV  75 kV x e1 x (2500 - 1000)/8150
                                                                   75 kV x 1.2
Fig. 44    Altitude correction factor Ka
                                 Operating times
Closing time                                                                                                  ≤ 60 ms
Opening time
1st shunt release                                                    (-Y1)                                    ≤ 30 ms
2nd/3rd release                                                      (-Y2 to -Y7)                             ≤ 45 ms
Arcing time                                                                                                   < 15 ms
Break time
1st shunt release                                                    (-Y1)                                    ≤ 45 ms
2nd/3rd release                                                      (-Y2 to -Y7)                             ≤ 60 ms
Dead time                                                                                                      300 ms
Closed/open contact time
1st shunt release                                                    (-Y1)                                    ≤ 45 ms
2nd/3rd release                                                      (-Y2 to -Y7)                             ≤ 60 ms
Minimum command duration
Closing solenoid                                                     (-Y9)                                      45 ms
1st shunt release                                                    (-Y1)                                      40 ms
2nd/3rd release                                                      (-Y2 to -Y7)                               20 ms
Shortest pulse time for circuit-breaker tripping signal (-S6)
1st shunt release                                                    (-Y1)                                    > 10 ms
2nd/3rd release                                                      (-Y2 to -Y7)                               > 6 ms
Charging time if actuated electrically                               (-M1)                                      < 15 s
Synchronous error between the poles                                                                             ≤ 2 ms
                                 Fig. 45   Operating times
                                 Closing time = period between starting (command) of the closing movement and
                                 the moment of contact with all poles.
                                 Opening time = interval of time between the initiation (command) of the opening op-
                                 eration and extinction of the arc in last-pole-to-clear.
                                 Arcing time = interval of time from the start of the first arc until the arc is extin-
                                 guished in all poles.
                                 Break time = period between starting (command) of the opening movement and ex-
                                 tinction of the arc in the pole extinct last (= opening time + arcing time).
                                 Closed-open contact time = in a make-break operating cycle - between the instant
                                 when the contacts touch in the first pole in the closing process, and the instant when
                                 the contacts separate in all poles in the subsequent opening process.
                                 Dead time = period from the end of the current flow in all poles up to the start of the
                                 current flow in the first pole.
                                 Circuit diagrams
                                 The circuit diagrams for the vacuum circuit-breaker are compiled based on your or-
                                 der.
                                 The corresponding circuit diagram book can also be downloaded from the following
                                 URL on the internet: https://support.industry.siemens.com
Blank page
 Installation
         Preliminary work     For preliminary work, the vacuum circuit-breaker must be
                              • placed on a suitable surface and secured against falling over,
                              • or prepared for installation while suspended from a crane
                              Note
                              Property damage due to incorrect operation when the mechanical interlock is
                              activated!
                              If the SION® vacuum circuit-breaker is tripped manually with the cover removed and
                              the mechanical interlock actuated, the operating mechanism of the vacuum circuit-
                              breaker will be irreversibly damaged.
                              Any warranty claims are lost in the event of such incorrect operation.
                              Use suitable means to prevent the SION® vacuum circuit-breaker from closing if the
                              cover has been removed and the mechanical interlock has been actuated.
Fig. 47   Removing cover made from insulating materi-     Fig. 48   Mounting cover made from insulating material
          al
                 Removing      •   Pull off both the engaging hooks of the cover (20.1) simultaneously.
                               •   Swing cover (20.1) forward and then remove forwards and upwards.
                Installation   •   Insert the cover (20.1) into the guide from the top, do not jam, and swing it
                                   down.
                               •   Let both engaging hooks of the cover (20.1) fully engage.
12 Nm
Fig. 49 Removing metal cover – example Fig. 50 Mounting metal cover – example
                Removing      •   Loosen both upper M6 hexagonal bolts but do not unscrew them.
                              •   Unscrew the bottom four M6 hexagonal bolts with the contact washers.
                              •   Lift the cover (20.2) slightly upwards and remove.
               Installation   •   Position the openings of the cover (20.2) over the upper hexagonal bolts and
                                  the contact washers and hook in the cover.
                              •   Put contact washers on the hexagonal bolts with the serrated side facing the
                                  cover (20.2) and screw M6 hexagonal bolts in with a tightening torque of 12 Nm.
                               3.
                                                          0025-47
46
  47
                                                        0102-14
                                                                                                                         0102-18
Fig. 52     Up to 17.5 kV, mounting insulating shells             Fig. 53    Up to 17.5 kV, engaging insulating shells
                                 •   Slide insulating shells (47) onto previously mounted threaded rods of main con-
                                     ductors (for connecting the main conductors, see “Mounting conductor bars”
                                     page 54).
                                 •   Place insulating shell (47) onto the pole shell (46) and engage into the guide.
                                 •   Engage the hooks by hand if necessary.
                                                                   0025-61
                                                    46
  0025-60
48
Fig. 54 24 kV, mounting insulating shells Fig. 55 24 kV, engaging insulating shells
                                 •   Press upper and lower insulating shell (48) horizontally against the pole shell
                                     (46) until they engage audibly.
Fig. 56 Mounting the insulating shells Fig. 57 Engaging the insulating shells
                                •   Place insulating shell (47) onto the rib (arrow a) from the top at a slight angle.
                                •   Push the bottom part of the insulating shell (47) against the pole shell (46) until
                                    it engages audibly.
                                •   Check whether the engaging hooks of the insulating shell (47) have fully
                                    engaged behind the insulation ribs. Engage the hooks by hand if necessary.
                                Installation of a fixed-mounted circuit-breaker on a horizontal plane
48 ±4 Nm 48 ±4 Nm
Fig. 58 Installation for fixed mounting from below Fig. 59 Installation for fixed mounting from below
                                There are 4 mounting holes on the base plate for the various installation types.
                                Use M10 screws – strength class 8.8 – for fastening. The binding dimension draw-
                                ings are decisive.
     Fixing on the mounting     Use 4 bolts M10 and washers to fasten the fixed-mounted circuit-breaker to the
                    surface     mounting surface from below. Tightening torque 48 ±4 Nm (greased threads only).
Fixing on the withdrawable      For fixing to the withdrawable part, remove the cover prior to installation (see “Re-
                      part      moving and mounting covers”, page 40) and fix the cable harness inside the oper-
                                          M8
                                          24 Nm
                                                                    M8
                                                                    24 Nm
Fig. 61 Mounting the fixing straps Fig. 62 Mounting the fixing straps
                                •   Remove the fixing straps from the material pack and mount them as shown in
                                    the installation drawing. Tightening torque 24 Nm
                                •   Installation of the vacuum circuit-breaker on a vertical plane.
 M8
 24 Nm
                                                                 M8
                                                                 24 Nm
Fig. 63   Mount a continuous protective plate between        Fig. 64     Mounting divided protective plates on both
          the pole and operating mechanism housing                       sides (optional, only for 31.5 kA and distance
          (optional)                                                     between pole centres 150/160 mm)
                                                                                       64       65
  65                                               64
  M6 (polyam-
  ide)
  1 Nm                                             20
0025-62 20
                                                                                                                   0025-63
Fig. 66   Mounting the transparent insulating plate (op-      Fig. 67   Position the fully equipped insulating plate
          tional)                                                       (optional)
                                 Earthing
                                  Note
                                 If the SION® vacuum circuit-breaker is installed in an earthed metal framework and
                                 is connected permanently and electrically conductive, no separate earthing is re-
                                 quired.
                                 Place serrated washers under the screw heads when fixing the vacuum circuit-
                                 breaker in this case.
          Connecting to earth    Connect the vacuum circuit-breaker on the earthing terminal (70) to the high-voltage
                                 protective earth as specified by the standard (DIN EN 50341).
                                 • Select the cross-section of the earthing conductor so that a current of 30 A, with
                                    a maximum voltage drop of 3 V, can be conducted to the provided earthing point
                                    (see IEC 62271-200).
                                 • Remove hexagonal bolt M12 with washers from the material pack or, if already
                                    mounted, completely unscrew from the earthing terminal.
                                 • Note the order of installation of the fixing elements: Place the washer, ring lug of
                                    earthing conductor and contact washer (SN 70093) with the serrated side facing
                                    the operating mechanism housing under the bolt head.
                                 • Fix M12 hexagon head bolt with the fixing elements to the earthing terminal (70)
                                    with 105 Nm.
70 70
                                           M12
                                           105 Nm                                              M12
                                                     0025-75
                                                                                                                  0025-22
                                                                                               105 Nm
Fig. 69     Connecting the earthing conductor to the side      Fig. 70   Connecting the earthing conductor to the side
            of the operating mechanism housing – exam-                   of the operating mechanism housing – exam-
            ple with a plastic cover                                     ple with a metal cover
Fig. 73 Laying the cable harness Fig. 74 Laying the cable harness
 Laying the cable harness      •   Feed the cable harness of the withdrawable part with the plugs (-Q0) along the
              (see Fig. 73)        side wall through the vacuum circuit-breaker.
                               •   Fix the cable harness to the existing cable harness using cable straps and
                                   ensure there is sufficient distance from the spring state indicator.
 Laying the cable harness      •   Feed the cable harness of the withdrawable part with the plugs (-Q0) through
              (see Fig. 74)        the vacuum circuit-breaker.
                               •   Fix the cable harness to the right side wall with cable straps.
Fig. 75 Mounting the plug for the withdrawable part Fig. 76 Mounting the plug for the withdrawable part
          Mounting the plug    •   Insert the plug bottom (-Q0) into the frame as far as it will go and let it engage.
                               •   Wire the plug (-Q1) and insert it (see “Wiring of connectors Q0-X1.1, Q0-X1.2,
                                   Q0-X1.3” page 50).
Fig. 77   As-delivered condition – retaining screw in po-    Fig. 78   Remove the transport block
          sition A
Fig. 79   Cleaning the connecting surfaces               Fig. 80    Cleaning the connecting surfaces of the con-
                                                                    ductor bars
                              Use a steel brush to brush contact surfaces of the conductor bars (cross-wise) until
                              they are bright and wipe off any residue using a clean cloth.
                              After cleaning, very lightly grease the bright contact areas with acid-free Vaseline
                              (e. g. Shell Vaseline 8420) and screw together immediately.
                                Adjust the conductor bars in such a way that, before fastening, they lie flat easily and
                                fit the holes on the contact surfaces of the upper and lower terminal.
                                                                                                         M12: 40 ±4 Nm
                                                                                                         M16: 100 ±10 Nm
Fig. 82   Screw-in depths in the upper and lower termi-           Fig. 83         Mounting the conductor bars (flat). Example
          nals                                                                    for 1 250 A with hole for dowel pin
                                Depending on the rated current strength, use M12 or M16 screws and nuts –
                                strength class 8.8 – and the appropriate spring elements and plain washers for the
                                connection of the conductor bars.
                                When tightening the screws, hold the nuts against the tightening torque with a suit-
                                able screwdriver or socket spanner.
                                    Tightening torques apply to greased threads only:
                                    - M12: 40 ±4 Nm
                                    - M16: 100 ±10 Nm
     Securing with a spiral     The conductor bars can be secured against twisting with a spiral spring pin accord-
                spring pin      ing to ISO 8748 or a dowel pin according to ISO 8752 — 4 × X*) mm — N — C.
A 1.
                              2.                                                                         4.
                                                                                         3.
                                                                                                       22
                          B                                                                       22.1
                                                  22.1
                                                                 0025-69
 0025-68
Fig. 84    Cleaning and mounting threaded rods (22.1)           Fig. 85      Cleaning and mounting contact arms (22)
           for contact arms (22)
                               •   Grease the screw-in section of the threaded rods (22.1) with Vaseline (see 1.).
                               •   Screw in the threaded rod (22.1) and observe the screw-in depths A+B (see 2.)
                                   (see Table “Screw-in depths for screws or threaded rods from the contact sur-
                                   face in the upper and lower connection”, page 54).
                               •   Tighten the threaded rods (22.1) on the contact surfaces of the upper and lower
                                   connections (see 3.)
                               •   Tightening torques for greased threads:
                                   - M12: 40 ±4 Nm
                                   - M16: 100 ±10 Nm
                               •   Contact surfaces,                                               Copper,          silver plated
                                   - roughen                                                         x                    –
                                   - clean,                                                          x                    x
                                   - grease with Vaseline (see 4.)                                   x                    x
                                                                           1.                                  2.
                                                                                                                         23
                                                                                                                         23.1
                                                  22.1                                                                   22.2
                                                  22
4.
0025-70
                                                                     0025-71          3.
Fig. 86    Attaching contact arms – example with                 Fig. 87        Inserting contact arm adapter on the back –
           Ø 40 mm                                                              example for contact arms with Ø 40 mm
                        6.
                                                   7.
 0025-72
Fig. 88 Fix contact system with contact arm adapter to contact arm with Ø 40 mm
                                                                                                     1.
                                               22.1
22
2.
4.
                                                               0025-73
                                                    0025-74
                                                                                3.
Fig. 89   Attaching contact arms – example with               Fig. 90    Example with contact arms Ø 60 mm – attach-
          Ø 60 mm                                                        ing the contact system without the contact arm
                                                                         adapter
                              Contact systems without a contact arm adapter are only mountable on contact arms
                              with Ø 60 mm. These contact arms already have an integrated contact arm adapter
                              (see Fig. 89).
                              •   Place the contact arms (22) on the threaded rod (22.1) (see Fig. 89).
                              •   Grease contact systems without contact arm adapter for contact arms with
                                  Ø 60 mm on the rear side on the contact fingers with Molykote Longterm 2 (see
                                  1.).
                              •   Attach the contact system to the threaded rod up to the contact arm. Note the
                                  position of the contact system (round outer edge toward the contact arm) (see
                                  2.)
                              •   Tighten the contact system with the washer and hexagon nut (see 3.)
                                  Tightening torques for greased threads:
                                  - M12: 40 ±4 Nm
                                  - M16: 100 ±10 Nm
                              •   After installing the contact system, grease the contact fingers with Molykote
                                  Longterm 2 (see 4.)
1.
                        2.                                                                          M12: 40 ±4 Nm
                                                                                                    M16: 100 ±10 Nm
                                                   0102-17
0102-15
Fig. 92   Clean thread and mount for 1 250 A contact         Fig. 93   Mounted contact arms 1 250 A.
          arms
                                  If insulating shells are used on the system side, the main current conductors may
                                  only have a maximum diameter or cross-section of 60 mm.
46
  47
                                                       0102-14
                                                                                                                       0102-18
Fig. 94   Installation of the insulating shell                    Fig. 95   Mounted insulating shell
                                  •   Position the insulating shell in front of the pole shell and snap it into the guides.
                                  •   If necessary, snap the hooks into place by hand.
                                                                                                               3.
                                                 1.
                                                                                                               4.
                                                 2.
                                                        0102-19
0102-20
Fig. 96   Installation of the 1250 A contact system with          Fig. 97   Installation of the 1250 A contact system with
          installation aid                                                  installation aid
                                  •   Observe the alignment of the contact system. The contact fingers must point to
                                      the system side.
                                  •   Grease the inside of the contact system with Molykote Longterm 2.
                                  •   For the installation of the 1250 A contact system on the contact arm, a
                                                  M12: 40 ±4 Nm
                                                  M16: 100 ±10 Nm
Fig. 99   Fixing of the additional insulating plate to the   Fig. 100 Additional insulating plate mounted
          insulating shell
                                 •   Position additional insulating plate and mount it on the underside of the insulat-
                                     ing shell.
                                 •   The additional insulating plate must audibly click into place.
Fig. 101 Mounting the insulating shell Fig. 102 Insulating shell engaged
                             When installing the 2000 A contact arm, make sure that the end of the contact arm
                             on the interrupter side does not tilt with the nut and that the front side is fully on the
                             pole contact plate.
Fig. 104 Completion of the 2000 A contact system          Fig. 105 Installation of the 2000 A contact system
         (sectional view)
                                                          M12: 40 ±4 Nm
                                                          M16: 100 ±10 Nm
            Function test   After completing all work on the vacuum circuit-breaker, perform a function test in
                            accordance with “Commissioning”, p. 69.
                                 For SION® vacuum circuit-breakers, two versions of withdrawable part are available,
                                 each designed for different types of switchgear. The two versions differ in part with
                                 regard to their design, installation, commissioning and operation. In the following, a
                                 distinction is made between the two variants where technically relevant.
                                 The withdrawable part must be safely locked in the switchgear. The dimensions of
                                 the slots for receiving the lock on both sides of the system-side guide rails must be
                                 observed. For dimensions, see Fig. 107.
Fig. 107 Example of insertion in guide rails with the di-     Fig. 108 Example – inserting and locking
         mensions of the slots
                                 •    Insert the withdrawable circuit-breaker into the switchgear-side guide rails (see
                                      1.).
                                 •    Push the withdrawable circuit-breaker into the guide rails until they hit the side
                                      stops (large arrow), moving locking handles towards the middle of the with-
                                      drawable part (small arrows, see 2.).
                                 •    After reaching the side end stops, let go of the locking handles (small arrows,
                                      see 3.) and check that it is securely locked.
Disconnected position / test position Intermediate position Retracted position / service position
 Buttons –S1.5; –S1.6; –S1.7; –S1.8       No signal                   Buttons –S1.0; –S1.1; –S1.2; –S1.3 send
 send a signal or message                                             a signal or message
Withdrawable part in entry    •   Insert hand crank into the coupling of the withdrawable part
                 position     •   Turn inserted hand crank of withdrawable part clockwise in order to move the
                                  vacuum circuit-breaker to a perceivable end stop
                              •   Remove the hand crank withdrawable part from the coupling of the withdrawa-
                                  ble part
      Withdrawable part in    •   Insert hand crank into the coupling of the withdrawable part
          service position    •   Turn inserted hand crank counter-clockwise for racking the vacuum circuit-
                                  breaker into the service position to a perceivable stop
                              •   Remove hand crank from the coupling of the withdrawable part
                               The motor-driven withdrawable part is not suitable for continuous operation. A max-
                               imum of 3 retraction and extension operations are allowed without a break. A break
                               of 3 minutes must be observed before further retraction and extension operations.
                               The maximum permissible torque on the drive spindle of the motor-driven with-
                               drawable part is 25 Nm.
                               Clearance must be guaranteed under the motor-driven withdrawable part, down to
                               the level of the running surfaces of the wheels.
                               The motor-driven withdrawable part is inserted in the guide rails on the system side
                               as described in chapter “Inserting and racking the SION® withdrawable circuit-
                               breaker”, p. 64.
                             For this purpose, the following signals of the vacuum circuit-breaker must be used
                             and processed accordingly in the electronic circuit by the customer:
                                                                          Connections according to the supplied
                                                                          circuit diagram
                             Vacuum circuit-breaker in switch position
                                                                       -Q0-S1
                             OPEN:
                                                                          -Q01-X01:1 and -Q01-X01:2
                                                                          -Q01-X01:3 and -Q01-X01:4
                             Position button S8
                                                                          -Q01-X01:5 and -Q01-X01:6
                                                                          -Q01-X01:7 and -Q01-X01:8
                                                                          -Q01-X02:1 and -Q01-X02:2
                                                                          -Q01-X02:3 and -Q01-X02:4
                             Position button S9
                                                                          -Q01-X02:5 and -Q01-X02:6
                                                                          -Q01-X02:7 and -Q01-X02:8
                             Motor:
                                                                          L+ to -Q0-X02:9 and
                             Moving towards the “service position”
                                                                          L- to -Q0-X02:10
                                                                          L+ to -Q0-X02:10 and
                             Moving towards the “operating position”
                                                                          L- to -Q0-X02:9
                             See also “Connecting the low voltage for the withdrawable part” on p. 51.
                             Manual movement of the motor-driven withdrawable part using the hand
                             crank 3AX1430-8A
 Notes on using the hand     As long as secondary voltage is applied, the motor-driven withdrawable part must
    crank for the motor-     not be moved manually with the hand crank.
 driven withdrawable part
                                WARNING
                             Risk of injury due to inserted hand crank on the withdrawable part
                             As long as secondary voltage is applied, the motor of the withdrawable part can be
                             started at any time.
                             If the hand crank is inserted into the coupling of the withdrawable part, the sudden
                             turning or detachment of the hand crank can lead to considerable personal injury or
                             damage to property.
                             •   Do not insert the hand crank into the coupling of the withdrawable part as long
                                 as secondary voltage is applied.
                             •   After manual operation without secondary voltage, immediately remove the
                                 hand crank from the withdrawable part
                             If the secondary voltage fails or during maintenance work, the motor-driven with-
                             drawable part can be moved manually with the hand crank 3AX1430-8A under the
Operation
                                 Commissioning
                                 Before commissioning, check the following points to ensure that the vacuum circuit-
                                 breaker is functioning correctly at operating temperature:
Checklist  Notes
 Does the information on the nameplate (see page 34) match the order
 data?
 Check whether that the plug-in connection of the connector strip is seated
 firmly.
 Electrically check auxiliary switch S1 and position switch in both end posi-
 tions – operate the vacuum circuit-breaker to do so.
                                     WARNING
                                 Faulty or damaged vacuum circuit-breaker
                                 There is a risk of injury if the vacuum circuit-breaker is damaged or malfunctions!
                                 •   Immediately take the vacuum circuit-breaker out of operation.
                                 •   Do not put vacuum circuit-breaker back into operation.
                                 •   If the malfunctions or the damage cannot be remedied, contact a sales repre-
                                     sentative or Siemens Service and, if necessary, send back the vacuum circuit-
                          Position indicator and spring state indicator when charging the closing
                          spring, closing and opening
            CLOSE pushbut-
 Closing    ton                                                                                                   *
            Remote operation
 Opening
            OPEN pushbutton
            Remote operation
                                                                                            
                          * Spring only charged if motor voltage is applied
                          Fig. 111     Control element indicators
                          Closing
                          Provided there is no lock-out due to a mechanical interlock, send the closing com-
                          mand via the CLOSE pushbutton or the corresponding control unit until the vacuum
                          circuit-breaker is closed, and shows and signals the CLOSED switch position.
                          Change to the position indicator:
                                                                              
                                                      OPEN                         CLOSE
                          After closing and, if necessary, releasing the CLOSE pushbutton, the closing spring
                          is immediately automatically charged by the motor and the symbol for “Closing
                          spring charged” becomes visible in the spring state indicator.
                          Change to the spring state indicator:
                                                                                      
                                     Charged                          Discharged                Charged
                          Opening
                          The opening spring is charged during the closing operation.
                          To open, send the opening command via the OPEN pushbutton or the correspond-
                          ing control unit until the vacuum circuit-breaker is open, and shows and signals the
                          OPEN switch position.
                                                           
                                         CLOSE                      OPEN
                   The spring state indicator does not change.
                   Discharging the closing spring
                   To discharge the closing spring:
                   •   Deactivate the supply voltage
                   •   On the vacuum circuit-breaker, actuate the OPEN, CLOSE and OPEN pushbut-
                       tons manually one after the other.
                   This ensures that the vacuum circuit-breaker is open and the closing spring is dis-
                   charged.
                                  WARNING
                             Suddenly rotating hand crank when motor starts up! Risk of injury if hand cranks
                             other than the original hand crank are used.
                             If the hand crank does not have a slip coupling, the inserted hand crank will also ro-
                             tate when the motor starts up.
                             The vacuum circuit-breaker must only be charged with the original hand crank.
                             •   To do this, fit the hand crank onto the hand crank coupling through the opening
                                 with the adapter pushed forward and
                             •   turn clockwise until the spring state indicator changes over:
                                                                     
                                                    Discharged                Charged
                             The adapter of the hand crank is designed in such a way that the hand crank be-
                             comes uncoupled when the motor supply voltage returns.
Maintenance
                             Maintenance
                             The SION® vacuum circuit-breaker is maintenance-free under normal service con-
                             ditions (up to rated current). We do, however, recommend you carry out regular
                             visual checks. The highest permissible mechanical operating cycle number is:
                             • 10 000 Operating cycles: Maintenance-free
                             • 30 000 operating cycles: When maintenance is performed by Siemens author-
                                 ised personnel.
                             Maintenance after 10 000 operating cycles
         Preliminary work    • Prior to starting work on the vacuum circuit-breaker, observe the local safety
                               regulations for high-voltage devices and the "5 safety rules" as per EN 50110-1.
                             • Switch off the supply voltage and secure against reclosing.
                             • On the vacuum circuit-breaker, actuate the OPEN, CLOSE and OPEN pushbut-
                               tons manually one after the other. This ensures that the vacuum circuit-breaker
                               is open and the closing spring is discharged.
                             Special operating conditions
                             If the vacuum circuit-breaker is operated under unfavourable conditions indoors
                             (heavy and frequent condensation, dusty air, etc.), we recommend cleaning the in-
                             sulating parts and possibly the outer parts of the circuit-breaker more regularly.
                             Cleaning
          Insulating parts   The insulating parts must be clean to ensure their dielectric strength is not reduced.
                             Rub insulating parts with a moist cloth.
                             As a cleaning agent, use only warm water with a mild, liquid household cleaner add-
                             ed and leave to dry.
 Joints and bearing points
                             For joints and bearing points that cannot be disassembled, only wipe off with a dry,
                             lint-free cloth.
                             Under no circumstances may these joints and bearing points be cleaned with clean-
                             ing agents or water!
                                 Always specify the vacuum circuit-breaker’s type and serial no. (see “Nameplate”,
                                 on page 34) when ordering spare parts.
                                 Disposal
                                 The materials of the vacuum circuit-breaker should be recycled. Vacuum circuit-
                                 breakers can be disposed of in an ecological manner on the basis of existing nation-
                                 al legal regulations.
                         Metal   The switching device’s metal components can be recycled as mixed scrap, although
                                 it is more environmentally sustainable to dismantle the unit as thoroughly as possi-
                                 ble into sorted scrap and residual mixed scrap.
               Electronics       Electronic scrap must be disposed of in accordance with applicable regulations.
                  Materials      The vacuum circuit-breaker consists of the following materials:
                                 • Metals
                                   - Steel (partly phosphatised, galvanised and yellow chromated or thick layer
                                       passivated)
                                   - Copper (partly silver-plated)
                                   - Aluminium (partly silver-plated)
                                   - Brass (partly containing lead)
                                   - Chrome
                                 • Insulating material (partly glass fibre reinforced)
                                   - Epoxy resin, polyester resin, polyamide, polycarbonate, ABS-PC mixture
                                   - Silicone
                                   - Rubber
                                 • Ceramics
                                 • Lubricant
      Further information    Contact your Siemens Service Centre if you require further information. See also
                             “Service”on p. 2.
Blank page
Index
A                                                                                I
Accessories available for order .............................               74   Installation altitudes ...............................................       36
Altitude correction factor .......................................          36   Installation position ................................................       39
Ambient conditions ................................................         36   Insulated operating rod ..........................................           19
Anti-pumping device (-K1) .................... 21– 22,                      24   Insulating shell .............................................. 17–          18
Areas of application ..............................................         15       mounting ................................................ 43–            44
Auxiliary switch (-S1) ............................ 20– 22,                 26   Insulator ........................................................ 17–       18
                                                                                 Interlock, mechanical .................................... 22,               31
B                                                                                Interlocks ...............................................................   31
Basic equipment ................................................... 22           Intermediate position .............................................          65
Bushing ................................................................. 58
                                                                                 K
C                                                                                Key-operated interlock .......................... 19– 22, 33
Cable harness .......................................................       51
Cable outlet ...........................................................    42   L
Charging ...............................................................    70   Low-voltage
Circuit-breaker shaft cover ............................ 22,                48      interface (-X0) ........................................ 22, 50
Circuit-breaker tripping signal (-S6) ...... 20– 22,                        27      plug connector (-X0) ............... 17– 18, 20– 21
CLOSE pushbutton ....................................... 19,                70
Closing lock-out (-Y8E), electrical ......... 21– 22,                       33   M
Closing solenoid (-Y9) ........................... 20– 22,                  24   Manual closing, mechanical ..................................                22
Closing spring ............................... 20– 21, 71–                  72   Manual opening, mechanical .................................                 22
Conductor bar .......................................................       54   Mating contact .......................................................       58
Connection bar ......................................................       54   Motor (-M1) ................................................... 20–          23
Connection thread .................................................         54   Motor short-circuit protection .................................             23
Connector strip
    (Q0-X1.1, Q0-X1.2, Q0-X1.3) .........................                   22   N
    20-pole ............................................................    50   Nameplate ............................................ 17– 18, 34
    30-pole ............................................................    50   O
Contact arm .......................................... 55– 56,              62   OPEN pushbutton ......................................... 19,                70
Contact arm adapter .............................................           56   Opening spring ......................................................        70
Contact surface, pole ............................................          54   Operating mechanism ...........................................              19
Contact system ..................................... 18, 56–                57   Operating position .................................................         31
Contacts                                                                         Operations counter ....................................... 19–               22
    1250 A, third-party provider ............................               58
Cover ............................................ 17– 19, 40,              70   P
    Insulating material ..........................................          19   Plug
    Metal ...............................................................   19       (-Q0) ................................................................   51
    mounting .........................................................      40       (Q0-X1) .................................................. 20–           21
    removing .........................................................      40       (-Q1) ................................................................   51
                                                                                     (-X01) and (-X02) ................................... 20–                21
D
                                                                                     withdrawable part ............................................           51
Dielectric strength ................................................. 36
                                                                                 Pole contact plate ......................................... 17–             18
Disconnected position ................................... 31, 65
                                                                                 Pole head ..................................................... 17–          18
Dowel pin .............................................................. 54
                                                                                 Pole shell .............................................. 17– 18,            43
E                                                                                Pole-centre distance ..................................... 34–               35
Earthing terminal ................................................... 49         Position indicator ...................................................       70
                                                                                 Position indicator CLOSED-OPEN ............... 19–                           21
H                                                                                Position queries .....................................................       65
Hand crank ............................................................     72   Position switch .......................................................      25
    for manual charging of the closing spring .......                       19       (-S12) ..................................................... 20–         22
    Siemens withdrawable part ............................                  65       (-S21) ............................................. 20– 22,             25
    third-party withdrawable part ..........................                67       (-S3) ............................................... 20– 22,            25
Hand crank coupling ..................................... 19–               21       (-S4) ............................................... 20– 22,            25
Heater (-R01) ........................................ 20– 22,              31       (-S5) ................................................................   22
High-voltage protective earth ................................              49       (-S6) ............................................... 20– 21,            27
                                                                                 Pressure plate .......................................................       22
                                                                                 Protective plate ......................................................      46
R
Rated frequency ....................................................          34
Rated lightning impulse withstand voltage .... 34–                            35
Rated normal current ............................ 34– 35,                     54
Rated operating sequence ............................ 34–                     35
Rated power frequency withstand voltage .... 34–                              35
Rated short-circuit breaking current ...... 34– 35,                           54
Rated short-circuit duration ...................................              34
Rated voltage ........................................ 34– 35,                54
Resistor (-R1) ........................................ 20– 21,               30
Retracted position .................................................          65
S
Separating shell ............................................ 17,             43
Service position .....................................................        65
Shunt release
    (-Y1), 1st release ............................ 20– 22,                   25
    (-Y2), 2nd release ........................... 20– 22,                    28
Spiral spring pin ....................................................        54
Spring state indicator ............................ 19– 21,                   70
Standards ..............................................................      15
Switching times .....................................................         37
T
Test position ..........................................................      65
Threaded rod .........................................................        55
Transformer operated release
    (-Y4) ........................................................ 22,        29
    (-Y5) ........................................................ 22,        29
    (-Y6) ........................................................ 22,        29
Travel ....................................................................   65
Travel distances ....................................................         64
U
Undervoltage release (-Y7) ................... 22, 30, 52
V
Vacuum interrupter ........................................ 17–               18
   contact stroke .................................................           18
   contact system ................................................            18
   service life .......................................................       73
W
Withdrawable part ......................................... 18, 44
Withdrawable part, motor-driven ........................... 67
Central legend