0% found this document useful (0 votes)
81 views16 pages

A1 1c Innova Ups 1000va

This document discusses a new full range double conversion UPS system with capabilities from 1-20kVA. The UPS features true online power protection for IT and OT applications. It comes with future-proof connectivity that allows safe and secure connection to the cloud for remote monitoring of the UPS through internet connected devices. The connectivity complies with cybersecurity standards to protect user information.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
81 views16 pages

A1 1c Innova Ups 1000va

This document discusses a new full range double conversion UPS system with capabilities from 1-20kVA. The UPS features true online power protection for IT and OT applications. It comes with future-proof connectivity that allows safe and secure connection to the cloud for remote monitoring of the UPS through internet connected devices. The connectivity complies with cybersecurity standards to protect user information.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Online UPS

INNOVA Unity IOT RT


1-20KVA

• Programmable outlet group will extend back up time for most critical
equipment (6-20K need PDU model)
• Automatic detect additional EBM quantity will simplify EBM
installation for IT users
• Compact size requiring small installation space
• Hot swappable battery will save customer service cost (For 1-3K
standard UPS model)
• Low audible noise at typical load
• Dot matrix LCD support up to 10 languages for easy installation and
service. 10-20K 3-3 model support colorful touchable LCD display
with gravity sensor
• Embedded Ethernet port solution provide safe network connection to
Cloud which will meet the increasing IoT trend
9 min
• WLAN module for IoT connection
• Mobile APP for monitoring, configuration. Support Android/iOS
• USB HID enable monitoring on UPS without software installation
Key features
• Dry contactor for industrial condition
• True double-conversion design with high adaptability to harsh • Upgraded network card compliance with IEC standard cybersecurity
mains conditions
• Real PF 1 can provide more power in same space Typical application
• High efficiency results in energy saving
• Adjustable charging current and flexible battery configuration
• Optimized changing method to expand battery life time.
• 10-20K 3-3 model can be configure as 3-1 or 1-1 model to
meet utility and load wiring
• 10-20K 3-3 model can be configure as single source input or AC mains/
Generator
dual source input for utility and bypass
• Built-in OVCD protection, fan lock detection, over temperature
detection, overload warning to enhance the product reliability

Financial Work station Network Health care Telecom


equipment
New full range double conversion UPS
High density, true double conversion on-line power protection
for IT (Information technology) and OT (operation technology)
applications. Capable of supporting loads from 1 to 20kVA in a
rack/tower convertible form with a 2U/3U space.

These latest range of UPS comes with future-proof connectivity


design having the capability to connect to cloud seamlessly
to allow the monitoring of the UPS online through any internet
connected device. To ensure users information is safe and
protected, these connectivity is compliant with IEC standard
cybersecurity and GDPR regulation.

Network connected and data to cloud


• Easy to setup the Safe connection to Cloud
• Connect to Cloud through MQTT protocol (the most widely
used IoT protocol)
• Real time health monitoring on the equipment to enable
business continuity and failure prevention
• Remote monitoring, scheduled maintenance and UPS
firmware upgrade *
• Improve the data visibility to the service people and end user
• Reduce the responsive time on product failure as Cloud push
the exact information to end user and service people at the
same time
• Create value added service opportunities based on
digitalization transformation

* Will be launched soon

End to End Cybersecurity


End to End Cybersecurity

APP On Cloud monitoring

Ethernet port Optional Optional

Cloud port WLAN dongle NMC card

2
Product rear panel

1K-1.5K rear panel 2k rear panel 3k rear panel

1k-1.5K EBM rear panel 2K-3k EBM rear panel 6-10k rear panel

6-10k EBM rear panel 6-10k MBP rear panel 10K 3-1 rear panel

10K 3-1 MBP rear panel 10K 3-3 rear panel 10K 3-3 EBM rear panel

10-20K 3-3 MBP rear panel

15-20K 3-3 rear panel 15-20K 3-3 EBM rear panel 10-20K 3-3 MBP parallel 1+1
version rear panel

3
Product specification
Model name RT 1K RT 1KS RT 1.5K RT 1.5KS
Power rating VA/Watt 1000VA/1000W 1000VA/1000W 1500VA/1500W 1500VA/1500W
Double coversion mode 89% 89% 89% 89%
Efficiency
ECO mode 96% 96% 97% 97%

160-300V 100% load, 110- 160-300V 100% load, 110- 160-300V 100% load, 110- 160-300V 100% load, 110-
Voltage range 160V derating to 50% load 160V derating to 50% load 160V derating to 50% load 160V derating to 50% load
linearly linearly linearly linearly

Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz

Input performance 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz


Frequency range
54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%)

PF >0.99 >0.99 >0.99 >0.99

THDI <5% <5% <5% <5%

Input connection IEC C14 IEC C14 IEC C14 IEC C14

200/208/220/230/240 200/208/220/230/240 200/208/220/230/240 200/208/220/230/240


Rated voltage VAC(derating 10% at 208V, VAC(derating 10% at 208V, VAC(derating 10% at 208V, VAC(derating 10% at 208V,
derating 20% at 200V) derating 20% at 200V) derating 20% at 200V) derating 20% at 200V)
Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz
Maximum PF 1 1 1 1
Voltage accuracy ±1% ±1% ±1% ±1%
<1% linear load <1% linear load <1% linear load <1% linear load
THDv
<5% non linear load <5% non linear load <5% non linear load <5% non linear load
Output performance 0ms(4ms @ line <-> 0ms(4ms @ line <-> 0ms(4ms @ line <-> 0ms(4ms @ line <->
Transfer time bypass;10ms @ ECO bypass;10ms @ ECO bypass;10ms @ ECO bypass;10ms @ ECO
<->Inverter) <->Inverter) <->Inverter) <->Inverter)
Crest Ratio max 3:1 max 3:1 max 3:1 max 3:1
100%<load≤105% continu- 100%<load≤105% continu- 100%<load≤105% continu- 100%<load≤105% continu-
ous. ous. ous. ous.
105%< load ≤125% for 3 105%< load ≤125% for 3 105%< load ≤125% for 3 105%< load ≤125% for 3
Overload(line mode) minutes minutes minutes minutes
125<load≤150% for 30 125<load≤150% for 30 125<load≤150% for 30 125<load≤150% for 30
seconds. seconds. seconds. seconds.
>150% for 500ms. >150% for 500ms. >150% for 500ms. >150% for 500ms.

1 main outlet group (with 4 1 main outlet group (with 4 1 main outlet group (with 4 1 main outlet group (with 4
x IEC C13) and 1 program- x IEC C13) and 1 program- x IEC C13) and 1 program- x IEC C13) and 1 program-
Wiring/socket
Output connection mable outlet group (with 4 mable outlet group (with 4 mable outlet group (with 4 mable outlet group (with 4
x IEC C13) x IEC C13) x IEC C13) x IEC C13)

Load segment control Yes Yes Yes Yes


Voltage 36V/24VDC 36VDC 36VDC 36VDC

Capacity(AH) 3 x 12V/7Ah NA 3 x 12V/9Ah NA


Battery
Backup time Typical value
"3.0min 100% load "2.4min 100% load
by default battery capacity, NA NA
12.2min 50% load" 8.7min 50% load"
PF=1
Maximum connect external
4 4 4 4
battery module quantity
Charging current 1.5A 8A 1.5A 8A
Charger
Recharging time 3h to 90% NA 3h to 90% NA

4
Product specification
Model name RT 1K RT 1KS RT 1.5K RT 1.5KS

CVCF Yes (derating to 60% load) Yes (derating to 60% load) Yes (derating to 60% load) Yes (derating to 60% load)
Other working mode

Parallel no no no no
Dot matrix LCD, rotatable Dot matrix LCD, rotatable Dot matrix LCD, rotatable Dot matrix LCD, rotatable
Display manually(optional segment manually(optional segment manually(optional segment manually(optional segment
LCD) LCD) LCD) LCD)
Language 10 Languages 10 Languages 10 Languages 10 Languages
USB USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID
RS232 Yes(DB9) Yes(DB9) Yes(DB9) Yes(DB9)
1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1
Dry in/out
programble dry out programble dry out programble dry out programble dry out
HMI(human-machine EPO yes yes yes yes
interface) Intelignet slot yes(for long card) yes(for long card) yes(for long card) yes(for long card)
Network card Optional, NMC long card Optional, NMC long card Optional, NMC long card Optional, NMC long card
Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus
Modbus card
Long Card Long Card Long Card Long Card
Optional,AS400 Optional,AS400 Optional,AS400 Optional,AS400
Dry contactor card
Long Card Long Card Long Card Long Card
WLAN module Optional,HDMI type Optional,HDMI type Optional,HDMI type Optional,HDMI type
Ethernet port for IOT RJ45 RJ45 RJ45 RJ45
Monitor software Winpower Winpower Winpower Winpower

Dimension(W*D*H)MM 438*445*86.5(2U) 438*445*86.5(2U) 438*445*86.5(2U) 438*445*86.5(2U)


Physical performance

IP protection level IP20 IP20 IP20 IP20

Operating temperature 0-40⁰C 0-40⁰C 0-40⁰C 0-40⁰C

Relative Humidity 0-95% 0-95% 0-95% 0-95%


Environment 0~3000m(the load derat- 0~3000m(the load derat- 0~3000m(the load derat- 0~3000m(the load derat-
Operating Altitude ing 1 % every up 100m ing 1 % every up 100m ing 1 % every up 100m ing 1 % every up 100m
@1000~3000m) @1000~3000m) @1000~3000m) @1000~3000m)
<45dB @ typical load with <45dB @ typical load with <45dB @ typical load with <45dB @ typical load with
Acoustic Noise
battery fully charged battery fully charged battery fully charged battery fully charged
Certification CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040
EMI Conduction/Radiation C2 C2 C2 C2
ESD IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2
RS IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3
EMS
EFT IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4
Surge IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5

Maintenance bypass switch NA NA NA NA

Input power cable yes yes yes yes


Accessory Output power cable yes,1*10A yes,1*10A yes,1*10A yes,1*10A
EBM cable yes(in EBM) yes(in EBM) yes(in EBM) yes(in EBM)
USB cable yes yes yes yes
RS232 cable Optional Optional Optional Optional
Rail kit Optional Optional Optional Optional
Tower Feet yes yes yes yes
Rack ear yes yes yes yes
Manual yes yes yes yes
5
Product specification
Model name RT 2K RT 2KS RT 3K RT 3KS
Power rating VA/Watt 2000VA/2000W 2000VA/2000W 3000VA/3000W 3000VA/3000W
Double coversion mode 93% 93% 93% 93%
Efficiency
ECO mode 97% 97% 97% 97%

160-300V 100% load, 110- 160-300V 100% load, 110- 160-300V 100% load, 110- 160-300V 100% load, 110-
Voltage range 160V derating to 50% load 160V derating to 50% load 160V derating to 50% load 160V derating to 50% load
linearly linearly linearly linearly

Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz

Input performance 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz


Frequency range
54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%)

PF >0.99 >0.99 >0.99 >0.99

THDI <5% <5% <5% <5%

Input connection IEC C20 IEC C20 IEC C20 IEC C20

200/208/220/230/240 200/208/220/230/240 200/208/220/230/240 200/208/220/230/240


Rated voltage VAC(derating 10% at 208V, VAC(derating 10% at 208V, VAC(derating 10% at 208V, VAC(derating 10% at 208V,
derating 20% at 200V) derating 20% at 200V) derating 20% at 200V) derating 20% at 200V)
Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz
Maximum PF 1 1 1 1
Voltage accuracy ±1% ±1% ±1% ±1%
<1% linear load <1% linear load <1% linear load <1% linear load
THDv
<5% non linear load <5% non linear load <5% non linear load <5% non linear load
Output performance 0ms(4ms @ line <-> 0ms(4ms @ line <-> 0ms(4ms @ line <-> 0ms(4ms @ line <->
Transfer time bypass;10ms @ ECO bypass;10ms @ ECO bypass;10ms @ ECO bypass;10ms @ ECO
<->Inverter) <->Inverter) <->Inverter) <->Inverter)
Crest Ratio max 3:1 max 3:1 max 3:1 max 3:1
100%<load≤105% continu- 100%<load≤105% continu- 100%<load≤105% continu- 100%<load≤105% continu-
ous. ous. ous. ous.
105%< load ≤125% for 3 105%< load ≤125% for 3 105%< load ≤125% for 3 105%< load ≤125% for 3
Overload(line mode) minutes minutes minutes minutes
125<load≤150% for 30 125<load≤150% for 30 125<load≤150% for 30 125<load≤150% for 30
seconds. seconds. seconds. seconds.
>150% for 500ms. >150% for 500ms. >150% for 500ms. >150% for 500ms.

1 main outlet group (with 4 1 main outlet group (with 4 1 main outlet group (with 1 main outlet group (with
x IEC C13) and 1 program- x IEC C13) and 1 program- 1 x IEC C19 + 4 x IEC C13) 1 x IEC C19 + 4 x IEC C13)
Wiring/socket
Output connection mable outlet group (with 4 mable outlet group (with 4 and 1 programmable outlet and 1 programmable outlet
x IEC C13) x IEC C13) group (with 4 x IEC C13) group (with 4 x IEC C13)

Load segment control Yes Yes Yes Yes


Voltage 72V/48VDC 72VDC 72VDC 72VDC

Capacity(AH) 6 x 12V/7Ah NA 6 x 12V/9Ah NA


Battery
Backup time Typical value
"3.3min 100% load "2.5min 100% load
by default battery capacity, NA NA
12.9min 50% load" 9.3min 50% load"
PF=1
Maximum connect external
4 4 4 4
battery module quantity
Charging current 1.5A 8A 1.5A 8A
Charger
Recharging time 3h to 90% NA 3h to 90% NA

6
Product specification
Model name RT 2K RT 2KS RT 3K RT 3KS

CVCF Yes (derating to 60% load) Yes (derating to 60% load) Yes (derating to 60% load) Yes (derating to 60% load)
Other working mode

Parallel no no no no
Dot matrix LCD, rotatable Dot matrix LCD, rotatable Dot matrix LCD, rotatable Dot matrix LCD, rotatable
Display manually(optional segment manually(optional segment manually(optional segment manually(optional segment
LCD) LCD) LCD) LCD)
Language 10 Languages 10 Languages 10 Languages 10 Languages
USB USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID
RS232 Yes(DB9) Yes(DB9) Yes(DB9) Yes(DB9)
1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1
Dry in/out
programble dry out programble dry out programble dry out programble dry out
HMI(human-machine EPO yes yes yes yes
interface) Intelignet slot yes(for long card) yes(for long card) yes(for long card) yes(for long card)
Network card Optional, NMC long card Optional, NMC long card Optional, NMC long card Optional, NMC long card
Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus
Modbus card
Long Card Long Card Long Card Long Card
Optional,AS400 Optional,AS400 Optional,AS400 Optional,AS400
Dry contactor card
Long Card Long Card Long Card Long Card
WLAN module Optional,HDMI type Optional,HDMI type Optional,HDMI type Optional,HDMI type
Ethernet port for IOT RJ45 RJ45 RJ45 RJ45
Monitor software Winpower Winpower Winpower Winpower

Dimension(W*D*H)MM 438*600*86.5(2U) 438*600*86.5(2U) 438*600*86.5(2U) 438*600*86.5(2U)


Physical performance

IP protection level IP20 IP20 IP20 IP20

Operating temperature 0-40⁰C 0-40⁰C 0-40⁰C 0-40⁰C

Relative Humidity 0-95% 0-95% 0-95% 0-95%


Environment 0~3000m (the load derat- 0~3000m (the load derat- 0~3000m (the load derat- 0~3000m (the load derat-
Operating Altitude ing 1 % every up 100m ing 1 % every up 100m ing 1 % every up 100m ing 1 % every up 100m
@1000~3000m) @1000~3000m) @1000~3000m) @1000~3000m)
<50dB @ typical load with <50dB @ typical load with <50dB @ typical load with <50dB @ typical load with
Acoustic Noise
battery fully charged battery fully charged battery fully charged battery fully charged
Certification CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040
EMI Conduction/Radiation C2 C2 C2 C2
ESD IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2
RS IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3
EMS
EFT IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4
Surge IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5

Maintenance bypass switch NA NA NA NA

Input power cable yes yes yes yes


Accessory Output power cable yes,1*10A yes,1*10A yes,1*10A yes,1*10A
EBM cable yes(in EBM) yes(in EBM) yes(in EBM) yes(in EBM)
USB cable yes yes yes yes
RS232 cable Optional Optional Optional Optional
Rail kit Optional Optional Optional Optional
Tower Feet yes yes yes yes
Rack ear yes yes yes yes
Manual yes yes yes yes
7
Product specification
Model name RT 6K RT 6KS RT 10K RT 10KS
Power rating VA/Watt 6000VA/6000W 6000VA/6000W 10000VA/10000W 10000VA/10000W
Double coversion mode 95% 95% 95% 95%
Efficiency
ECO mode 98% 98% 98% 98%

160-275V 100% load, 110- 160-275V 100% load, 110- 160-275V 100% load, 110- 160-275V 100% load, 110-
Voltage range 160V derating to 50% load 160V derating to 50% load 160V derating to 50% load 160V derating to 50% load
linearly linearly linearly linearly

Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz

Input performance 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz


Frequency range
54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%) 54Hz-66Hz @ load>60%)

PF >0.995 >0.995 >0.995 >0.995

<3% linear load <3% linear load <3% linear load <3% linear load
THDI
<5% non linear load <5% non linear load <5% non linear load <5% non linear load

L/N/PE hardware terminnal L/N/PE hardware terminnal L/N/PE hardware terminnal L/N/PE hardware terminnal
Input connection  
connection connection connection connection

Rated voltage 220/230/240V 220/230/240V 220/230/240V 220/230/240V

Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz


Maximum PF 1 1 1 1
Voltage accuracy ±1% ±1% ±1% ±1%
<1% linear load <1% linear load <1% linear load <1% linear load
THDv
<5% non linear load <5% non linear load <5% non linear load <5% non linear load
Output performance
Transfer time 0ms(10ms @ ECO->Inverter) 0ms(10ms @ ECO->Inverter) 0ms(10ms @ ECO->Inverter) 0ms(10ms @ ECO->Inverter)

Crest Ratio max 3:1 max 3:1 max 3:1 max 3:1
100%<load≤105% continu- 100%<load≤105% continu- 100%<load≤105% continu- 100%<load≤105% continu-
ous. ous. ous. ous.
105%< load ≤125% for 10 105%< load ≤125% for 10 105%< load ≤125% for 10 105%< load ≤125% for 10
Overload(line mode) minutes minutes minutes minutes
125<load≤150% for 30 125<load≤150% for 30 125<load≤150% for 30 125<load≤150% for 30
seconds. seconds. seconds. seconds.
>150% for 500ms. >150% for 500ms. >150% for 500ms. >150% for 500ms.

L/N/PE hardware terminnal L/N/PE hardware terminnal L/N/PE hardware terminnal L/N/PE hardware terminnal
Wiring/socket
Output connection connection connection connection connection

Load segment control Optional (need MBP model) Optional (need MBP model) Optional (need MBP model) Optional (need MBP model)
192VDC(192~240VDC 192VDC(192~240VDC 192VDC(192~240VDC 192VDC(192~240VDC
Voltage
adjustable) adjustable) adjustable) adjustable)
16*12V/7Ah, 16~20pcs 16*12V/9Ah, 16~20pcs
Capacity(AH) NA NA
Battery adjustable adjustable
Backup time Typical value
"3.6min 100% load "2.1min 100% load
by default battery capacity, NA NA
9.6min 50% load" 8min 50% load"
PF=1
Maximum connect external
  6 6 6 6
battery module quantity
Charging current 1.4A(0-4A adjustalbe) 4A(0-12A adjustable) 2A(0-4A adjustable) 4A(0-12A adjustable)
Charger
Recharging time 3h to 90% NA 3h to 90% NA

8
Product specification
Model name RT 6K RT 6KS RT 10K RT 10KS

CVCF Yes (derating to 60% load) Yes (derating to 60% load) Yes (derating to 60% load) Yes (derating to 60% load)
Other working mode

Parallel Optional (up to 3) Optional (up to 3) Optional (up to 3) Optional (up to 3)

Dot matrix LCD, rotatable Dot matrix LCD, rotatable Dot matrix LCD, rotatable Dot matrix LCD, rotatable
Display
manually manually manually manually

Language 10 Languages 10 Languages 10 Languages 10 Languages


USB USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID
RS232 Yes(DB9) Yes(DB9) Yes(DB9) Yes(DB9)
1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1
Dry in/out
programble dry out programble dry out programble dry out programble dry out
HMI(human-machine EPO yes yes yes yes
interface) Intelignet slot yes(for long card) yes(for long card) yes(for long card) yes(for long card)
Network card Optional, NMC long card Optional, NMC long card Optional, NMC long card Optional, NMC long card
Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus
Modbus card
Long Card Long Card Long Card Long Card
Optional,AS400 Optional,AS400 Optional,AS400 Optional,AS400
Dry contactor card
Long Card Long Card Long Card Long Card
WLAN module Optional,HDMI type Optional,HDMI type Optional,HDMI type Optional,HDMI type
Ethernet port for IOT RJ45 RJ45 RJ45 RJ45
Monitor software Winpower Winpower Winpower Winpower
5U height including 5U height including
438*573*86.2 (power 438*573*86.2 (power 438*573*86.2 (power 438*573*86.2 (power
Dimension(W*D*H)MM
Physical performance module, 2U) module, 2U) module, 2U) module, 2U)
438*593*129 (Battery, 3U) 438*593*129 (Battery, 3U)
IP protection level IP20 IP20 IP20 IP20
0-50⁰C(power derating to 0-50⁰C(power derating to 0-50⁰C(power derating to 0-50⁰C(power derating to
Operating temperature
50% @40-50⁰C ) 50% @40-50⁰C ) 50% @40-50⁰C ) 50% @40-50⁰C )
Relative Humidity 0-95% 0-95% 0-95% 0-95%
Environment 0~3000m(the load 0~3000m(the load 0~3000m(the load 0~3000m(the load
Operating Altitude derating 1 % every up 100m derating 1 % every up 100m derating 1 % every up 100m derating 1 % every up 100m
@1000~3000m) @1000~3000m) @1000~3000m) @1000~3000m)
<50dB @ typical load with <50dB @ typical load with <55dB @ typical load with <55dB @ typical load with
Acoustic Noise
battery fully charged battery fully charged battery fully charged battery fully charged
Certification   CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040
EMI Conduction/Radiation C3 C3 C3 C3
ESD IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2
RS IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3
EMS
EFT IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4
Surge IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5

Optional (build in 1 main Optional (build in 1 main Optional (build in 1 main Optional (build in 1 main
outlet group with 1 x IEC outlet group with 1 x IEC outlet group with 1 x IEC outlet group with 1 x IEC
C19 + 2 x IEC C13 and 1 C19 + 2 x IEC C13 and 1 C19 + 2 x IEC C13 and 1 C19 + 2 x IEC C13 and 1
Maintenance bypass switch
programmable outlet group programmable outlet group programmable outlet group programmable outlet group
with 1 x IEC C19 + 2 x IEC with 1 x IEC C19 + 2 x IEC with 1 x IEC C19 + 2 x IEC with 1 x IEC C19 + 2 x IEC
C13) C13) C13) C13)

Input power cable NA NA NA NA


Accessory Output power cable NA NA NA NA
EBM cable yes(in EBM) yes(in EBM) yes(in EBM) yes(in EBM)
USB cable Yes Yes Yes Yes
RS232 cable Optional Optional Optional Optional
Rail kit Optional Optional Optional Optional
Tower Feet Yes Yes Yes Yes
Rack ear Yes Yes Yes Yes
Manual Yes Yes Yes Yes
9
Product specification
Model name RT 10K 3-1 RT 10KS 3-1 RT 10K 3-3 RT 10KS 3-3
Power rating VA/Watt 10000VA/10000W 10000VA/10000W 10000VA/10000W 10000VA/10000W
Double coversion mode 95% 95% 95% 95%
Efficiency
ECO mode 98% 98% 98% 98%
160-300V (273-520) 100% 160-300V (273-520) 100%
160-275V 100% load, 110- 160-275V 100% load, 110-
load, 100-160V(173-273 load, 100-160V(173-273
Voltage range 160V derating to 50% load 160V derating to 50% load
) derating to 50% load ) derating to 50% load
linearly linearly
linearly linearly
Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz

40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz


Input performance
Frequency range 54Hz-66Hz @ load>60% 54Hz-66Hz @ load>60% 54Hz-66Hz @ load>60% 54Hz-66Hz @ load>60%
and 1 phase in 1 phase out) and 1 phase in 1 phase out) and 1 phase in 1 phase out) and 1 phase in 1 phase out)

>0.95 at 3 phase input >0.95 at 3 phase input


PF >0.995 >0.995
>0.99 at 1 phase input >0.99 at 1 phase input
<30% at 3 phase input <30% at 3 phase input <3% linear load <3% linear load
THDI
<5% at 1 phase inut <5% at 1 phase inut <5% non linear load <5% non linear load
L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/
L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/ PE hardware terminnal PE hardware terminnal
Input connection   PE hardware terminnal PE hardware terminnal connection connection
connection connection Dual input for line and Dual input for line and
bypass bypass

220/230/240V or 220/230/240V or
Rated voltage 220/230/240V 220/230/240V
380/400/415V 380/400/415V

Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz


Maximum PF 1 1 1 1
Voltage accuracy ±1% ±1% ±1% ±1%
<1% linear load <1% linear load <1% linear load <1% linear load
THDv
<5% non linear load <5% non linear load <5% non linear load <5% non linear load
Output performance 0ms(10ms @ ECO- 0ms(10ms @ ECO- 0ms(2ms @ ECO+ ->In- 0ms(2ms @ ECO+ ->In-
Transfer time
>Inverter) >Inverter) verter) verter)
Crest Ratio max 3:1 max 3:1 max 3:1 max 3:1
100%<load≤105% 100%<load≤105% 100%<load≤105% 100%<load≤105%
continuous. continuous. continuous. continuous.
105%< load ≤125% for 10 105%< load ≤125% for 10 105%< load ≤125% for 10 105%< load ≤125% for 10
Overload(line mode) minutes minutes minutes minutes
125<load≤150% for 30 125<load≤150% for 30 125<load≤150% for 1 125<load≤150% for 1
seconds. seconds. minutes minutes
>150% for 500ms. >150% for 500ms. >150% for 500ms. >150% for 500ms.

L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/


L/N/PE hardware terminnal L/N/PE hardware terminnal
Wiring/socket PE hardware terminnal PE hardware terminnal
Output connection connection connection
connection connection

Load segment control No No Optional (need MBP model) Optional (need MBP model)
192VDC(192~240VDC 192VDC(192~240VDC 192VDC(192~240VDC 192VDC(192~240VDC
Voltage
adjustable) adjustable) adjustable) adjustable)
16*12V/9Ah, 16~20pcs 2*8*12V/9Ah, 16~20pcs
Capacity(AH) NA NA
Battery adjustable adjustable
Backup time Typical value
"2.1min 100% load "1.8min 100% load
by default battery capacity, NA NA
8min 50% load" 4.5min 50% load"
PF=1
Maximum connect external
  6 6 6 6
battery module quantity
Charging current 2A(0-12A adjustalbe) 4A(0-12A adjustalbe) 2A(0-13A adjustalbe) 2A(0-13A adjustalbe)
Charger
Recharging time 3h to 90% NA 3h to 90% NA

10
Product specification
Model name RT 10K 3-1 RT 10KS 3-1 RT 10K 3-3 RT 10KS 3-3
Yes (derating to 60% load Yes (derating to 60% load Yes (derating to 60% load Yes (derating to 60% load
CVCF @ 1 phase in and 1 phase @ 1 phase in and 1 phase @ 1 phase in and 1 phase @ 1 phase in and 1 phase
Other working mode out mode) out mode) out mode) out mode)
Parallel Optional (up to 3) Optional (up to 3) Optional (up to 3) Optional (up to 3)

Dot matrix LCD, rotatable Dot matrix LCD, rotatable colour touch LCD (optio- colour touch LCD (optio-
Display
manually manually nal Dot matrix LCD) nal Dot matrix LCD)

Language 10 Languages 10 Languages 10 Languages 10 Languages


USB USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID
RS232 Yes(DB9) Yes(DB9) Yes(DB9) Yes(DB9)
1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1
Dry in/out
programble dry out programble dry out programble dry out programble dry out
HMI(human-machine EPO yes yes yes yes
interface) Intelignet slot yes(for long card) yes(for long card) yes(for long card) yes(for long card)
Network card Optional, NMC long card Optional, NMC long card Optional, NMC long card Optional, NMC long card
Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus
Modbus card
Long Card Long Card Long Card Long Card
Optional,AS400 Optional,AS400 Optional,AS400 Optional,AS400
Dry contactor card
Long Card Long Card Long Card Long Card
WLAN module Optional,HDMI type Optional,HDMI type Optional,HDMI type Optional,HDMI type
Ethernet port for IOT RJ45 RJ45 RJ45 RJ45
Monitor software Winpower Winpower Winpower Winpower
5U height including 6U height including
438*573*86.2 (power 438*573*86.2 (power 438*589*129(power 438*589*129(power
Dimension(W*D*H)MM
Physical performance module, 2U) module, 2U) module, 3U) module, 3U)
438*593*129 (Battery, 3U) 438*593*129 (Battery, 3U)
IP protection level IP20 IP20 IP20 IP20
0-50⁰C(power derating to 0-50⁰C(power derating to 0-50⁰C(power derating to 0-50⁰C(power derating to
Operating temperature
50% @40-50⁰C ) 50% @40-50⁰C ) 50% @40-50⁰C ) 50% @40-50⁰C )
Relative Humidity 0-95% 0-95% 0-95% 0-95%
Environment 0~3000m(the load derat- 0~3000m(the load derat- 0~4000m(the load derat- 0~4000m(the load derat-
Operating Altitude ing 1 % every up 100m ing 1 % every up 100m ing 1 % every up 100m ing 1 % every up 100m
@1000~3000m) @1000~3000m) @1000~4000m) @1000~4000m)
<55dB @ typical load with <55dB @ typical load with <55dB @ typical load with <55dB @ typical load with
Acoustic Noise
battery fully charged battery fully charged battery fully charged battery fully charged
Certification   CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040
EMI Conduction/Radiation C3 C3 C3 C3
ESD IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2
RS IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3
EMS
EFT IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4
Surge IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5

Maintenance bypass switch Optional (need MBP model) Optional (need MBP model) Optional (need MBP model) Optional (need MBP model)

Input power cable NA NA NA NA


Accessory Output power cable NA NA NA NA
EBM cable yes(in EBM) yes(in EBM) yes(in EBM) yes(in EBM)
USB cable Yes Yes Yes Yes
RS232 cable Optional Optional Optional Optional
Rail kit Optional Optional Optional Optional
Tower Feet Yes Yes Yes Yes
Rack ear Yes Yes Yes Yes
Manual Yes Yes Yes Yes
11
Product specification
Model name RT 15K 3-3 RT 15KS 3-3 RT 20K 3-3 RT 20KS 3-3
Power rating VA/Watt 15000VA/15000W 15000VA/15000W 20000VA/20000W 20000VA/20000W
Double coversion mode 96% 96% 96% 96%
Efficiency
ECO mode 98.8% 98.8% 98.8% 98.8%
160-300V (273-520) 100% 160-300V (273-520) 100% 160-300V (273-520) 100% 160-300V (273-520) 100%
load, 100-160V(173-273 load, 100-160V(173-273 load, 100-160V(173-273 load, 100-160V(173-273
Voltage range
) derating to 50% load ) derating to 50% load ) derating to 50% load ) derating to 50% load
linearly linearly linearly linearly
Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz

40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz 40Hz-70Hz(45Hz-55Hz


Input performance
Frequency range 54Hz-66Hz @ load>60% 54Hz-66Hz @ load>60% 54Hz-66Hz @ load>60% 54Hz-66Hz @ load>60%
and 1 phase in 1 phase out) and 1 phase in 1 phase out) and 1 phase in 1 phase out) and 1 phase in 1 phase out)

PF >0.995 >0.995 >0.995 >0.995

<3% linear load <3% linear load <3% linear load <3% linear load
THDI
<5% non linear load <5% non linear load <5% non linear load <5% non linear load
L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/
PE hardware terminnal PE hardware terminnal PE hardware terminnal PE hardware terminnal
Input connection   connection connection connection connection
Dual input for line and Dual input for line and Dual input for line and Dual input for line and
bypass bypass bypass bypass

220/230/240V or 220/230/240V or 220/230/240V or 220/230/240V or


Rated voltage
380/400/415V 380/400/415V 380/400/415V 380/400/415V

Rated frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz


Maximum PF 1 1 1 1
Voltage accuracy ±1% ±1% ±1% ±1%
<1% linear load <1% linear load <1% linear load <1% linear load
THDv
<5% non linear load <5% non linear load <5% non linear load <5% non linear load
Output performance 0ms(2ms @ ECO+ ->In- 0ms(2ms @ ECO+ ->In- 0ms(2ms @ ECO+ ->In- 0ms(2ms @ ECO+ ->In-
Transfer time
verter) verter) verter) verter)
Crest Ratio max 3:1 max 3:1 max 3:1 max 3:1
100%<load≤105% 100%<load≤105% 100%<load≤105% 100%<load≤105%
continuous. continuous. continuous. continuous.
105%< load ≤125% for 10 105%< load ≤125% for 10 105%< load ≤125% for 10 105%< load ≤125% for 10
Overload(line mode) minutes minutes minutes minutes
125<load≤150% for 1 125<load≤150% for 1 125<load≤150% for 1 125<load≤150% for 1
minutes minutes minutes minutes
>150% for 500ms. >150% for 500ms. >150% for 500ms. >150% for 500ms.

L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/ L1/L2/L3/N/PE or L/N/


Wiring/socket PE hardware terminnal PE hardware terminnal PE hardware terminnal PE hardware terminnal
Output connection connection connection connection connection

Load segment control Optional (need MBP model) Optional (need MBP model) Optional (need MBP model) Optional (need MBP model)
384VDC(384~480VDC 384VDC(384~480VDC 384VDC(384~480VDC 384VDC(384~480VDC
Voltage
adjustable) adjustable) adjustable) adjustable)
2*16*12V/7Ah, 32~40pcs 2*16*12V/9Ah, 32~40pcs
Capacity(AH) NA NA
Battery adjustable adjustable
Backup time Typical value
"2.0min 100% load "1.8min 100% load
by default battery capacity, NA NA
5.2min 50% load" 4.7min 50% load"
PF=1
Maximum connect external
  6 6 6 6
battery module quantity
Charging current 1.4A(0-13A adjustalbe) 1.4A(0-13A adjustalbe) 2A(0-13A adjustalbe) 2A(0-13A adjustalbe)
Charger
Recharging time 3h to 90% NA 3h to 90% NA

12
Product specification
Model name RT 15K 3-3 RT 15KS 3-3 RT 20K 3-3 RT 20KS 3-3
Yes (derating to 60% load Yes (derating to 60% load Yes (derating to 60% load Yes (derating to 60% load
CVCF @ 1 phase in and 1 phase @ 1 phase in and 1 phase @ 1 phase in and 1 phase @ 1 phase in and 1 phase
Other working mode out mode) out mode) out mode) out mode)
Parallel Optional (up to 3) Optional (up to 3) Optional (up to 3) Optional (up to 3)

colour touch LCD (optio- colour touch LCD (optio- colour touch LCD (optio- colour touch LCD (optio-
Display
nal Dot matrix LCD) nal Dot matrix LCD) nal Dot matrix LCD) nal Dot matrix LCD)

Language 10 Languages 10 Languages 10 Languages 10 Languages


USB USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID USB 2.0 with HID
RS232 Yes(DB9) Yes(DB9) Yes(DB9) Yes(DB9)
1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1 1 programble dry in; 1
Dry in/out
programble dry out programble dry out programble dry out programble dry out
HMI(human-machine EPO yes yes yes yes
interface) Intelignet slot yes(for long card) yes(for long card) yes(for long card) yes(for long card)
Network card Optional, NMC long card Optional, NMC long card Optional, NMC long card Optional, NMC long card
Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus Optional,CMC/Modbus
Modbus card
Long Card Long Card Long Card Long Card
Optional,AS400 Optional,AS400 Optional,AS400 Optional,AS400
Dry contactor card
Long Card Long Card Long Card Long Card
WLAN module Optional,HDMI type Optional,HDMI type Optional,HDMI type Optional,HDMI type
Ethernet port for IOT RJ45 RJ45 RJ45 RJ45
Monitor software Winpower Winpower Winpower Winpower
9U height including 9U height including
438*589*129(power 438*589*129(power
438*589*129(power 438*589*129(power
Dimension(W*D*H)MM module, 3U) module, 3U)
Physical performance module, 3U) module, 3U)
(438*593*129)*2 (Battery, (438*593*129)*2 (Battery,
6U) 6U)
IP protection level IP20 IP20 IP20 IP20
0-50⁰C(power derating to 0-50⁰C(power derating to 0-50⁰C(power derating to 0-50⁰C(power derating to
Operating temperature
50% @40-50⁰C ) 50% @40-50⁰C ) 50% @40-50⁰C ) 50% @40-50⁰C )
Relative Humidity 0-95% 0-95% 0-95% 0-95%
Environment 0~4000m(the load derat- 0~4000m(the load derat- 0~4000m(the load derat- 0~4000m(the load derat-
Operating Altitude ing 1 % every up 100m ing 1 % every up 100m ing 1 % every up 100m ing 1 % every up 100m
@1000~4000m) @1000~4000m) @1000~4000m) @1000~4000m)
<55dB @ typical load with <55dB @ typical load with <55dB @ typical load with <55dB @ typical load with
Acoustic Noise
battery fully charged battery fully charged battery fully charged battery fully charged
Certification   CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040 CE,IEC/EN 62040
EMI Conduction/Radiation C3 C3 C3 C3
ESD IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2 IEC/EN 61000-4-2
RS IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3 IEC/EN 61000-4-3
EMS
EFT IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4 IEC/EN 61000-4-4
Surge IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5 IEC/EN 61000-4-5
Maintenance bypass switch Optional (need MBP model) Optional (need MBP model) Optional (need MBP model) Optional (need MBP model)
Input power cable NA NA NA NA
Output power cable NA NA NA NA
EBM cable yes(in EBM) yes(in EBM) yes(in EBM) yes(in EBM)
USB cable Yes Yes Yes Yes
Accessory
RS232 cable Optional Optional Optional Optional
Rail kit Optional Optional Optional Optional
Tower Feet Yes Yes Yes Yes
Rack ear Yes Yes Yes Yes
Manual Yes Yes Yes Yes

13
Note

14
Note

15
PHOENIXTEC
ADDRESS: No. 114, Sec. 2, Xiwan Rd.,
Xizhi District, New Taipei City 22179, Taiwan
TEL: +886 2 6614 2000
FAX: +886 2 6614 2099

You might also like