100%(2)100% found this document useful (2 votes) 913 views32 pagesBS EN 1751 2014 Ventilation For Buldings Air Terminal Devices Aerodynamic Testing of Damper and Valves
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
BS EN 1751:2014
EUROPEAN STANDARD EN 1751
NORME EUROPEENNE
EUROPAISCHE NORM January 2014
Ics 91,140.30 Supersedes EN 1751:1998
English Version
Ventilation for buildings - Air terminal devices - Aerodynamic
testing of damper and valves
Ventilation des batiments - Bouches dar Essais LLitung von Gebéudon - Gerite des Lufvertolungssystems
‘aérodynamiquas des regiatres et clapets ‘Aerodynemische Prifungen von Dressel- und
‘Absperrelementen
“This European Standard was approved by CEN on § November 2013,
(CEN members are bound to comply wth the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
‘Standard the status ofa national standard without any alleralion. Up-to-date Iss and bibliographical references conceming such national
standards may bs obtained on application to the CEN-CENELEC Management Cenire or any CEN member.
This European Standard exists in tree official versions (English, French, German). Aversion in any other language made by translation
under the responsiblity of a CEN member into sown language and notfed to the CEN-CENELEC Management Centre has the same
satus as the official versions,
‘CEN members are the natona standards bodies of Aust, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, oeland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netheriands, Norway, Poland, Portugal, Romana, Slovakia, Slovenia, Spain, Sweden, Switzrland, Turkey ard United
Kingaom,
laa!
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITE EUROPEEN DE NORMALISATION
EUROPAISCHES KOMITEE FOR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
©2014 CEN _Allsights of exploitation in any form and by any means reserved Rot, No. EN 1751:2014 E
‘worldwide for CEN national Members.BS EN 1751:2014
EN 1751:2014 (E)
Contents Page
Foreword.
1 Scope
2 Normative references...
3 Terms, definitions, symbols and suffixe
3.1 Terms and definitions
3.2 Symbols...
3.3 Suffixes
4 Instrumentation......
4.1 Air flow rate measurement.
42 Pressure measurement.
43 Temperature measurement..
5 Leakage tests........
5.1 General.
5.2 Damper and valve leakage.
5.3. Casing leakage.......
6 Flow rate and pressure tests.
61 Ducted metho:
62 — Chamber method ..
6.2.1 General.
6.2.2 Size relationshi
62.3 Tests..
63 Test report
‘Annex A (informative) Mechanical testing of dampers and valves...
At — Scope
‘A2 Instrumentation: Torque measuremen
A3 Pressure test to determine limiting value for structural stability.
A4 Torque tests to determine the torque required to operate the damper or valve and the
limiting value to avoid structural damag
Annex B (informative) Thermal transmittance through dampers and valves
B.1__ Introduction
B.2 Scope
B.3.__ Thermal loss test using a substitution method.
Annex C (normative) Classification of a damper or valve leakage...
C4 Scope
€.2 Leakage through closed blade(s).
€.3 Casing leakag
Annex D (informative) Effect of Duct Configuration on Pressure Loss Coefficient
Dl General.
D.2__ Application of correction factor.
Bibliography.BS EN 1751:2014
EN 1751:2014 (E)
Foreword
This document (EN 1751:2014) has been prepared by Technical Committee CEN/TC 156 “Ventilation for
buildings’, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by July 2014, and conflicting national standards shall be withdrawn at the
latest by July 2014,
‘Attention is drawn to the possibilty that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 1751:1998.
According to the CEN-CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.BS EN 1751:2014
EN 1751:2014 (E)
4 Scope
This European Standard specifies methods for the testing and rating of dampers and valves used in air
distribution systems with pressure differences up to 2 000 Pa
‘The tests incorporated in this European Standard are:
a) leakage past a closed damper or valve (for classification see Annex C);
b) casing leakage (for classification see Annex C);
©) flow rate/pressure requirement characteristics;
4) torque: (see Annex A);
€) thermal transmittance: (see Annex B),
The acoustic testing of dampers and valves is not included in this European Standard.
The tests specified above apply to the following:
f)_ measurement of leakage past a closed damper or valve:
9) measurement of casing leakage;
h) determination of flow rate and pressure requirements;
i) measurement of torque characteristics (see Annex A);
j) measurement of thermal transfer characteristics to determine insulation properties (see Annex B).
NOTE Certain aspects of the dynamic performance of dampers or valves are dependent upon the air distribution
system to which they are connected and are, therefore, diffcult to measure in isolation. Such considerations have led to
the omission of these aspects of the dynamic performance measurements from this European Standard, Also, in common
with other air distribution components, the resuits from tests carried out in accordance with this European Standard may
not be directly applicable if the damper or valve is situated in an area of non-uniform flow.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 12792, Ventilation for buildings - Symbols, terminology and graphical symbols
EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-
section conduits running full - Part 1: General principles and requirements (ISO 5167-1)
EN ISO 5167-2, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-
section conduits running full - Part 2: Orifice plates (ISO 5167-2)
EN ISO 5167-3, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-
section conduits running full - Part 3: Nozzles and Venturi nozzles (ISO 5167-3)BS EN 1751:2014
EN 1751:2014 (E)
EN ISO 5167-4, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-
section conduits running full - Part 4: Venturi tubes (ISO 167-4)
3. Terms, definitions, symbols and suffixes
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 12792 apply.
3.2 Symbols
‘The symbols used in this document are given in Table 1.
Table 1 — Symbols
Symbol Quantity Unit
A Internal cross-sectional area of duct im
S Coefficient of discharge :
D. Equivalent hydraulic diameter m
Circular ducts: aA
=
Square/Rectangular ducts: 22?
a+b
P Absolute pressure Pa
pa ‘Atmospheric pressure Pa
Ps Velocity pressure 1/2 p Pa
pi Stagnation or absolute total pressure Pa
Ps Static gauge pressure (p - P,) Pa
4p, | Pressure difference across the damper or Pa
valve under test
4p Flow meter differential pressure Pa
4p | Conventional total pressure difference for Pa
an air density of 1,2 kg-m” at the inlet to
the damper or valve under test
w Volume rate of airflow atthe flow meter ts
oe. Leakage volume rate of air flow ist
Quan Closed blade air leakage factor, volume bs?
rate of airflow per unit duct cross sectional
area
Guca | Case air leakage factor, volume rate of air | bs?
flow per reference casing area (which is
taken as perimeter of damper multiplied by
an equivalent length of 1 m)
v VelocityBS EN 1751:2014
EN 1751:2014 (E)
‘Symbol Quantity Unit
s Position of damper setting %,aorm
T Torque Nm
U Thermal transmittance coefficient wWicm?
q Temperature °c
e Air density kgm®
é Pressure loss coefficient :
3.3 Suffixes
The following suffixes shall be used with the symbols given in Table 1.
1s the inlet of the damper or valve under test;
2 _ isthe outlet of the damper or valve under test;
u__ is the measuring point upstream of the flow meter;
nis the value at a selected point of the flow rate/static pressure
curve.
4 Instrumentation
4.1 Air flow rate measurement
4.1.1 The air flow rate shall be measured using instruments in accordance with EN ISO §167-1,
EN ISO 5167-2, EN ISO 5167-3 and EN ISO 5167-4, or other instruments which have equivalent calibrated
performance.
4.1.2 Airflow meters shall have a minimum calibration accuracy of + 2,5 % over the whole range.
NOTE If necessary, flow meters can be calibrated in situ by means of the Pitot static tube traverse technique
described in ISO 3986.
4.1.3 Flow meters shall be checked at intervals as appropriate but not exceeding 12 months. This check
‘can take the form of one of the following:
a) a dimensional check for all flow meters not requiring calibration;
b) 2 calibration over their full range using the original method employed for the initial calibration of meters.
calibrated in situ;
¢) a check against a flow meter which meets flow meter specifications according to EN ISO 5167-1,
EN ISO 5167-2, EN ISO 5167-3 or EN ISO 5167-4 as appropriate.
4.1.4 Leakage air flow meters shall have a minimum indicated accuracy according to the ranges in Table 2.
Table 2— Accuracy of leakage air flow meters
Range I's" ‘Accuracy of measurement
Up to and including 0,018 £0,000 91s"
More than 0,018 £5%BS EN 1751:2014
EN 1751:2014 (E)
NOTE Alternatively, other devices such as variable area, flow-rate meters or integrating airflow meters ofthe positive
displacement type can be used if calibrated in accordance with 4.1.3 c).
4.2 Pressure measurement
4.2.1 Pressure in the duct shall be measured by means of a liquid filed, calibrated manometer or any other
device conforming to 4.2.2.
4.2.2. The resolution shall not be greater than the characteristics listed for the accompanying range of
manometers, given in Table 3.
Table 3 — Resolution for the ranges of manometers
Range Resolution
Pa Pa
Up to and including 50 Ot
From 50 to 250 1
From 250 to 500 5.0
Above 500 25,0
42.3 The measured value of differential pressure should be greater than 10% of the range of the
measurement device used.
EXAMPLE With a micromanometer with a range from 0 to 1000 Pa the minimum differential pressure to be
measured is 100 Pa.
4.2.4 The uncertainty of calibration standards shall be:
a) for instruments with a measuring range up to 100 Pa, equal or better than + 0,5 Pa;
) for instruments with a measuring range over 100 Pa, equal or better than # 0,5 % of reading,
4.3 Temperature measurement
Measurement of temperature shall be, for example, by means of mercury-in-glass thermometers, resistance
thermometers or thermo-couples. Instruments shall have a resolution better than 0,5 K and be calibrated to an
accuracy of + 0,25 K.
5 Leakage tests
5.1 General
Damper leakage performance could vary depending on whether the damper Is subjected to positive or
negative pressure. The manufacturer shall specify the pressure conditions for test.
5.2 Damper and valve leakage
5.2.1 Measurement of damper andior valve leakage in the shut-off position shall be made under conditions
‘of actual operation with the damper or valve closing against the maximum recommended static pressure
conditions. Since small flow rates exist during the closed damper or valve condition, the method used to
measure these small flow rates will introduce a high pressure loss when the damper or valve is open. This
prectudes a high pressure difference in the inlet duct until the damper or valve approaches the closed position.BS EN 1751:2014
EN 1751:2014 (E)
As the valve is closed and the flow rate decreases, the inlet static pressure difference will increase to
approximately the recommended inlet pressure.
5.2.2 The damper or valve shall be cycled 10 times between the fully open and fully closed positions of the
actuator at the start of each test (before starting the fan of the air supply system) concluding with the damper
or valve in the fully closed position
NOTE In all casos in the closed position, the damper drive is subject to a torque rating recommended by the
manufacturer.
5.2.3 The damper or valve under test shall be connected to a test installation similar to that shown in
Figure 1a) or Figure 1b)). A suitable air supply shall be connected to the duct. In both cases, care shall be
taken to ensure that duct joints are sealed to manufacturer's instructions.
5.2.4 The supply air pressure shall be increased to the maximum recommended inlet pressure difference in
accordance with the appropriate classification from Figure C.1 and Figure C.2. The damper or valve is then
modulated to the open position, without any additional adjustment of the supply air system flow rate, and then
returned to the closed position either manually or by the means provided by the manufacturer. The supply air
pressure shall be adjusted, as the damper or valve nears closure, to maintain the recommended inlet static
‘gauge pressure difference within + 5%. The above process is to ensure that the closed condition is as
representative as possible of typical operation with airflow present.
NOTE The air low measuring device for leakage measurement may have to be disconnected in the above process to
avoid any potential damage to a device for measuring low air rates.
5.2.5 Report the damper or valve al leakage factor as a function of test pressure difference in the closed
position. Also include classification (see Annex C).
5.3 Casing leakage
5.3.1 The test installation shall be similar to that shown in Figure 2 a)) or Figure 2 b)). The damper or valve
casing outlet shall be sealed according to the instructions of the manufacturer. The damper or valve shall be
set to the open position,
5.3.2 The test of the casing shall be carried out by subjecting the casing to its maximum recommended
pressure in accordance with 5.2.4. The pressure shall be maintained for 60s before the measurement of
leakage commences.
5.3.3 Report the test results as casing alr leakage factor as a function of test pressure. Also include
classification (see Annex C).
6 Flow rate and pressure tests
6.1 Ducted method
6.1.1 This method applies for dampers or valves mounted within a duct.
6.1.2 The damper or valve under test shall be mounted in a system comprising a fan, a means of controling
air low rate, a flow rate measuring system and test ducts (see Figure 3)
6.1.3 The test ducts shall have cross-sectional dimensions equal to the nominal size of the unit under test,
or to the manufacturer's instructions. The upstream test duct shall be straight for a minimum length of 5D.
The downstream test duct shall be straight for a minimum length of 5D,2 of 2 m, whichever is the greatestBS EN 1751:2014
EN 1751:2014 (E)
6.1.4 Flow straighteners shall be fitted in the upstream test duct at a position 3D,, from the connection to
the damper or valve under test or, alternatively a straight duct shall be used without a flow straightener.
6.1.5 The velocity profile near the upstream connection to the damper or valve under test shall be uniform
to 10 % of the mean value over the test duct cross section, excluding the area within 15 mm of the duct walls.
Carry out a velocity survey at ten equally spaced intervals along a pair of mutually perpendicular axes to
confirm that the velocity profile is within these limits. Wire mesh screens located no closer than 2,5D4; to the
upstream connection to the damper or valve under test can, if necessary, be incorporated to achieve a
suitably uniform velocity profile.
6.1.6 The upstream duct static gauge pressure (p,:) shall be measured by means of four static pressure
tappings 1,504, from the upstream connection to the damper or valve under test. For a rectangular duct, these
pressure taps shall be al the centre of each side and, for a circular duct, equally spaced around the
circumference. Connect the pressure taps to form a piezomettic ring. Alternatively, use a single Pitot static
probe.
6.1.7 The air temperature shall be measured at the flow meter and at a position 2,5D.; upstream of the
damper or valve under test, and, during the test the temperature variation at the same station shall not be
greater than 3 K.
6.1.8 The damper or valve shall be set in its fully open position and tests shall be carried out as follows:
6.1.8.1 Use a minimum of five air flow rates distributed evenly throughout the total flow range, and
choose the lowest air flow rate so that the test duct static pressure is not less than 10 Pa.
6.1.8.2 Remove the damper or valve from the test installation and connect the upstream test duct directly
to the downstream test duct. Repeat the procedure in 6.1.8 at five air flow rates covering the same flow rate
range used in 6.1.8.
6.1.9 If required, repeat the procedure described in 6.1.8 with the damper or valve other than in the open
position.
6.1.10 Record the data given in Table 4.
Table 4 — Flow rate and pressure test data
‘Symbol | Quantity Unit Uncertainty
Pea Inlet duct static gauge pressure | Pa 3%
with the damper or valve installed
Paes Inlet duct static gauge pressure | Pa 3%
with the damper or valve removed
Pa ‘Atmospheric pressure Pa, 1%
8 Air temperature at inlet to the G 3%
damper or valve under test
ap" Flow meter differential pressure | Pa 3%
Paw Sialic gauge pressure immediately | Pa 3%
upstream of the flow meter
a Air temperature immediately col 3%
upstream of the flow meter
s Position of damper setting %, Gorm 2
™ Or the appropriate parameter which rotates to gwBS EN 1751:2014
EN 1751:2014 (E)
6.2 Chamber method
6.2.1 General
This method applies for dampers and valves with free inlet and discharge.
6.2.2 Size relationship
The size relationship of test setup apparatus for determination of flow rate and static pressure differential of
the device under test shall be limited to the following:
— The chamber cross-sectional area shall be at least 7 times the intemal cross sectional area of duct (A) of
the device being tested.
— Other dimensions shall respect indications of Figure 4.
62.3 Tosts
6.2.3.1 Pressure difference according to test chamber method is a statement of the pressure difference
required to accelerate the air to a given velocity and overcome any entrance (exit) losses due to the blockage
and entrance (exit) conditions.
623.2 Use a minimum of five air flow rates distributed evenly throughout the total flow range, and
choose the lowest air low rate so that the test duct static pressure is not less than 10 Pa.
6.2.3.3 If required, repeat the procedure described in 6.2.3.2 with the damper or valve other than in the
‘open position,
6.2.3.4 Record the data given in Table 5.
Table 5 Flow rate and pressure test data
Symbol | Quantity Unit
ap. Pressure difference across the damper or valve under test Pa
Da Atmospheric pressure Pa
a Air temperature at inlet to the damper or valve under test B
‘Ap? Flow meter differential pressure Pa
Psu Static gauge pressure immediately upstream of the flow meter Pa
8 Air temperature immediately upstream of the flow meter °c
s Position of damper setting %, a.orm
® Or the appropriate parameter which relates to qv
6.3 Test report
6.3.1 The volume air flow rate at the flow meter (q.) shall be determined for each test. If there are significant
differences in the air temperature and static pressure between flow meter and the damper or valve under test
so that the air density ratio is less than 0,98 or greater than 1,02, the following correction shall be applied:
a)
10BS EN 1751:2014
EN 1751:2014 (E)
where
[Pax Po
3,47 @ 10° | —
’ [tr] °
and
Par Po
3.47010" |
ad [é + 273 | ®
Otherwise, g.1 shall be taken as equal to q.
_, Pu
The air density ratio is —~
6.3.2 Having measured values of p.1/.) Nd Pi~) and determined corresponding values of q, in accordance
with 6.3.1, plot the following functions on a linear graph
arias VS (Qui)
Pere 8 (Qui)?
By graphical or caloulation methods determine the best straight line through the plotted points and passing
through zero (see Figure 5a). If isolated points fall outside + 5 % differential pressure band about the best
mean line, repeat the tests at the relevant flow rates to check validity of test data. If, in the case with the
damper fitted, groups of points fall outside the 5 % band indicating the test resulls do not follow a linear
relationship between (q.1)" and pga), draw the best line (curve) through the points and zero (see Figure 5b)). If
the para) Points fall within + 5 % of the line (curve). the curve can be used for calculation in 6.3.3 and 6.3.4. If
the Psi) Points fall outside + 5 % of the curve, only individual test points for ps1) can be used in 6.3.3 and
6.3.4 and the situation shall be made clear in reporting the test results in accordance with 6.3.7.
6.3.3 Having complied with 6.3.2:
a) When pata) vs (qu1)* is a straight line, select a value of flow rate quin within the flow rates investigated. The
static gauge pressure requirement of the unit under test at this condition is:
an = Psa ~ Pain
b) When pei) VS (qu1)" is a curve, select a range of qy;_ at least three values: a low, medium and high value
to determine values of px
6.3.4 Calculate the coefficient Cp as follows using values of p.n from 6.3.3:
___ Actual flow _ 4,
°” Theoretical flow
1) Theoretical flow is defined as the flow with a lass coefficient
"BS EN 1751:2014
EN 1751:2014 (E)
= @
where
1ion* Pe
n= 3,47 01075] Paton * Po ©
0+273
NOTE 1 — Cois normally only ofinteret i the damper blades ar in the fully open poston.
NOTE 2. The relatonship between the coefcient of clscharge Co andthe loss coefficient 6s
g= (6)
6.3.5 Repeat the tests in 6.1 or 6.2 and the reduction of results as required for a number of intermediate
damper blade positions 's.
6.3.6 Calculate all energy and static pressure losses quoted from the test results using the coefficient of
discharge.
6.3.7 Report all the test results as pressure requirements and coefficients of discharge for the flow rates
tested and the related values of damper setting 's’if applicable.
NOTE In the context ofthis European Standard, the damper setting is defined as the angle or positon of the biade(s)
andor the physical displacement of the adjustable component(s) in relation to a datum,
In determining static pressure losses, the damper has ducted inlet and outlet. In using test data for other
configurations, ie. airflow from plenum through damper into a duct, vice versa or plenum/damperiplenum, due
allowance should be made for the additional appropriate contraction and/or expansion losses.
12BS EN 1751:2014
EN 1751:2014 (E)
23D
Key
1 tomanometer
2 sealed joint
a) Valve or damper leakage
1 2 3
C
/ (
Key
1 damper or valve under test
2 pressure measurement
3. volume air flow measurement
b) Arrangement of alternative damper leakage measurement
Figure 1
13BS EN 1751:2014
EN 1751:2014 (E)
Key
1 tomanometer
2 sealed joints
3. blanking plate
a) Casing leakage
1 4 2 3
2X
U
Key
11 damper or valve under test
2 pressure measurement
3. volume air flow measurement
4 blanking plate
b) Arrangement of alternative case leakage measurement
Figure 2
14BS EN 1751:2014
EN 1751:2014 (E)
Key
flow measuring station
fan
flow straightener
wire mesh screen if required at min. 2,5D.1 and temperature measuring point at 2,5De1
4 static taps connected by piezometric ring; alternatively, a probe can be used.
damper or valve under test
direction of flow
connection to flow rate meter, fan and flow rate controller
5 Duo min, or 2 m (whichever is greater)
Figure 3 — Flow rate/pressure requirement - Typical test arrangement
Dimensions in millimetres
Figure 4 — Test Device Setup
Inlet or Discharge Chamber
15BS EN 1751:2014
EN 1751:2014 (E)
Pasaln
Patan
in
b) Flow rate and pressure requirement - Best line (curve) characteristic for Pays) VS Gin
Figure 5
16BS EN 1751:2014
EN 1751:2014 (E)
Annex A
(informative)
Mechanical testing of dampers and valves
A1 Scope
This annex specifies methods for the mechanical testing and rating of dampers and valves described in this
European Standard,
The tests incorporated in this annex are:
a) determination of maximum closed blade duct pressure for mechanical stability of damper;
b) determination of the torque required to open and close a damper or valve;
¢) determination of maximum permitted torque applied to a damper or valve to avoid structural damage
A2 Instrumentation: Torque measurement
A241 The measurement of intial and operating torque can be achieved using either a torque spanner or a
lever arm and balance weight. The length of the lever arm and weight or selection of the torque spanner
should be such that readings of + 0,5 N'm can be achieved.
A2.2 The torque can also be determined by using a strain gauge transducer attached to the lever
mechanism of the actuator. The reading given by the detector should be permanently recorded, e.g. chart
recorder.
A2.3 The equipment of A.2.1 should be calibrated using a lever arm and weight, any bearings used should
be of low friction type. The accuracy of calibration should be #0,2N-m, and the reading interval should
‘correspond to a torque of # 0,5 Nm.
A.3 Pressure test to determine limiting value for structural stability
Use the test configurations as shown in Figure 1 a) or Figure 1 b). With the damper blades closed, increase
the static pressure in the duct in steps. Then, remove the static pressure and measure any permanent
structural deformation at each zero pressure condition.
When permanent deformation progressively increases at zero pressure after each pressure increment or
structural instabilty (ie. vibration) at test pressures occurs, report the test pressure for structural instability or
the pressure at the commencement of the increase of permanent deformation as X Pa.
‘Amaximum acceptable deformation shall not represent more than 1/250th of the span.
7BS EN 1751:2014
EN 1751:2014 (E)
AA Torque tests to determine the torque required to operate the damper or valve
and the limiting value to avoid structural damage
AA.1 Torque required to operate damper
A441 To determine the required torque, connect the damper or valve to ductwork as in Figure A1
‘When the damper is open, adjust the air supply to give duct velocity of 10 m-s"'. When the damper is closed,
adjust the upstream static pressure p,; to
Pat = 0.8 Prax t 20%
where
Prax #8 the limiting duct pressure determined from A.3.
A.41.2 Using the instrumentation of A.2, determine the required torque and pressure difference across
the damper Ap for a total of at least six equally spaced damper settings, including fully open and fully closed.
Conduct the tests from closed to open and open to closed.
4.1.3 Calculate the torque coefficient for each damper setting as follows:
(Aa)
2 Is the torque coefficient, in metres;
T is the measured torque, in newton metres at a given damper setting;
‘Bp: is the pressure drop across damper, in pascals at a given damper setting;
A. ithe duct cross sectional area, in square metres.
AAA. Present the results as a graphical plot of torque coefficient as a function of damper setting
NOTE To obtain more data points additional open damper air velocities can be used (see Figure A2 for typical
results).
A.4.2 Maximum permitted torque
4.2.1 To determine the maximum permissible torque, attach a torque spanner or lever arm and weight
‘system to the damper or valve drive arm or shaft using the same connection as used for the actuator.
4.22 Using the means of load application in A.4.2.1, progressively increase the load on the damper
until permanent deformation of the damper or its linkage, or the manufacturer's limiting torque figure is
reached. Conduct this test with the damper fully open and fully closed.
A423 Report the test results defining the damper status, i.e. open or closed, and detailing the maximum
torque in Nn before permanent deformation or, if lower, the manufacturers limiting value.
18BS EN 1751:2014
EN 1751:2014 (E)
Dimensions in millimetres
3 Der 22,5 De
15 Dy
\
2
Figure A.1 — Test rig for torque measurement
on
Y
0.05
0.02
,0001 1
E m/s
0.002 an
on
0.0001 ow
x8
0,001
0,000, \
0.0002
0.0001
0 2m 406080
x
key
1 open damper velocity
X blade position, «in degrees
Y torque coefficient, a in metres
Figure A.2— Presentation of results
19BS EN 1751:2014
EN 1751:2014 (E)
Annex B
(informative)
Thermal transmittance through dampers and valves
B.1 Introduction
In a ducted system where there is a significant difference in air temperature between two sides of a closed
damper or valve, it is sometimes important to establish thermal loss through the damper due to combination of
air leakage and thermal transmittance of the damper structure.
‘With a tight shut off damper the main contribution to thermal loss is the thermal transmittance of the damper
structure. Thermal loss due to air leakage is related to pressure difference across the closed damper.
B.2 Scope
This annex specifies methods for the thermal testing of dampers and valves in a closed blade condition using
‘a substitution method. The symbols used are shown in Table B.1
B.3 Thermal loss test using a substitution method
B.3.1._ Carry out the tests using the arrangements shown in Figure B.1. Test 1 measures the thermal leakage
of the test chamber with the substitution wall in position; this element is of a similar construction to the test
chamber itself and should be sealed into the aperture of the enclosure. Test 2 measures the thermal leakage
of the test chamber with the damper in place of the wall. The damper should be in the fully closed position,
and the size of the damper should be 1 m x 1m or the nearest largest size.
B.3.2 Connect a fan to the chamber to provide an overpressure to the chamber, with the motor of the fan
‘outside the chamber and not in the airstream. The chamber should contain an electric heat source to heat the
internal air. The dimensions of the test chamber should be as close as practicable to 1.2m x 1,2mx 1.2m
and the walls of well insulated construction (thermal transmittance 0.5 W:m™*:K"')..
B.3.3. Set the fan 10 provide an overpressure of 50 Pa and adjust the heater to give an internal air
temperature at least 30 K higher than the ambient external temperature. When measuring the chamber
temperature, care should be taken to avoid the effects of radiation from the electric resistance.
B34 Test 1
When temperatures inside and outside the enclosure are constant, measure the thermal heat flow leaking
through the walls of the chamber with the substitution wall, Calculate the thermal transmittance (U.) of the test
chamber as follows, and give details of the calculation in the measurement report.
@
Thermal transmittance of the test chamber, Ue =——~——
As* Ave
20BS EN 1751:2014
EN 1751:2014 (E)
Table B.1 —Symbols used for thermal transmittance test
‘Symbol | Quantity Unit
Aut Total wall area of the chamber and substitution wall m
Ae Area of the damper under test m
8, ‘Temperature difference in test 1 K
a Power of the heating resistance in test 1 w
2 Power of the heating resistance in test 2 Ww
Ay ‘Area of the substitution wall m
282 Temperature difference in test 2 kK
2a ‘Thermal leakage of the damper w
uy Thermal transmittance of the damper or valve wank
U, Thermal transmittance of the test chamber Wem K™
Ap. ‘Overpressure in chamber Pa
B35 Test2
Replace the substitution wall with the damper under test and repeat B.3.2 and B.3.3.
B.3.6 When temperatures inside and outside the enclosure are constant, measure the heat flow leaking
through the walls of the chamber and damper (@.). Determine the thermal transmittance of the damper or
valve as follows:
Thermal leakage of the damper De = Dy ~ Us (Ai - As) 482
Thermal transmittance of the damper
B.3.7 Report the test results as thermal transmittance for an over pressure of 50 Pa,
B.3.8 The test report should include an estimation of measurement and calculation error.
aBS EN 1751:2014
EN 1751:2014 (E)
12m
5
12m
Key
1 enclosureichamber
2 substitution wall
3 heating resistance
4 test damper or valve
5 pressurization fan
NOTE Figure B.1 shows two options that are.
— Test t with substitution wall (Key 2) mounted on chamber,
— Test 2 with test damper or valve (Key 4) mounted on chamber.
Figure B.1— Measuring arrangement for thermal transmittance
22BS EN 1751:2014
EN 1751:2014 (E)
Annex C
(normative)
Classification of a damper or valve leakage
C1 Scope
This annex specifies a method of classifying the leakage from a closed damper or valve and the leakage from
a damper or valve casing,
€.2 Leakage through closed blade(s)
‘The range of leakage performance has been divided into classes 0, 1, 2, 3 and 4:
Class 0 No control on leakage applicable, for example, to volume control
dampers which do not have to provide a shut-off capability;
Classes See Figure C.1 for permitted maximum air leakage factor qusn in
1.2.3.4 ks hm “across closed blades as a function of duct static pressure p, in
Pa,
€.3 Casing leakage
The range of case leakage performance is related to the general ductwork leakage classes as follows
‘The reference casing area is taken as the perimeter of the damper multiplied by an equivalent length of 1m.
Figure C.2 gives for classes A, B and C the permitted maximum case air leakage factor quica in |
function of duct static pressure p, in Pa
23BS EN 1751:2014
EN 1751:2014 (E)
2.000
1000
500
200
100
1 3 10 30 ‘0200-300 —«500~=—=«1000~=«2 000
x
Class 0: no control on leakage
Class 1
Class 2
Class 3
Class 4
air leakage factor guna W(S-m°)
duct pressure p, in Pa
Figure C.1 — Class
ication of closed blade leakage
24BS EN 1751:2014
EN 1751:2014 (E)
2.000
1000
500
oa
300
200
100
50
eo
30
2»
0
key
Class A
Class 8
Cass ¢
air leakage factor qu.ca W(s-m’)
duct pressure p. in Pa
Figure C.2 — Classification of case leakage
25BS EN 1751:2014
EN 1751:2014 (E)
Annex D
(informative)
Effect of Duct Configuration on Pressure Loss Coefficient
D.1 General
Depending on the connecting duct configuration (see Figure D.1) the measured pressure drop can vary.
The tests described in 6.1 are based on a fully ducted damper (configuration A)
The tests described in 6.2 using the chamber method can be related to configuration D.
Table D.1 gives very approximate guidance on correction factors to estimate the pressure loss coefficient
depending on the ducting configuration. The fully ducted configuration (A, on Figure D.1) is taken as the
reference
Precise values of these correction factors depend on an actual damper internal construction, blade profile,
blade linkage and blade coupling{opposed or parallel) as these have effects on the local aerodynamics as the
air passes through the damper.
c D
Figure D.1 — Possible duct connections to a damper
26Table D.1 Correction factors to pressure loss coefficient
Te Teo Conection factors F
g ‘ozatin Where blade a =
Duct
Configuration, o | 0’) a | ar} ae | or fer] me | a
8 coed | 6 | 55 | 30 | 20] 15 | 13 | ta] it | 0
paralel 1 | 100} 35) 20.) 15 | 13 | 2] At | 10
¢ opposed 4] 38 | 28] 47 | 14 | 18 | A2] At | 10
wall | 7 | 60 | 22] 16 | 18 | 13 Jia] a | t0
a opposed «| 10 | 80 | 45] 27 | 19 | WT |S) 12 | 10
parale! WY | 60} 50) 24 | 19 | A? | 5) 12 | 10
As pressure drop in eference oniguraon Ais rave sl be accuray of at F canbe vty por,
EN 1751:2014 E)BS EN 1751:2014
EN 1751:2014 (E)
D.2 Application of correction factor
‘As an example, pressure drop was measured in configuration A at a blade angle of 10°,
Require to estimate pressure loss coefficient for configuration C.
Ata=10° =P
Configuration C at a= 10° Ap = 0.5¢F:E spe
28BS EN 1751:2014
EN 1751:2014 (E)
Bibliography
[1] EN 15727, Ventilation for buildings - Ducts and ductwork components, leakage classification and
testing
[2] 1S0 3966, Measurement of fluid flow in closed conduits - Velocity area method using Pitot static tubes
29This page deliberately left blankThis page deliberately left blankINO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW
British Standards Institution (BSI)
BSI is the national body responsible for preparing British Standar
related publicatio
andards
BSI is incorporated by Royal Charter. British Standar
and other
information and services.
and other standardization
products are published by BS! Standards Limited.
About us
We rng tgeter busines, indus, goverment, consumes, nnevates
2 others to shape thelr combned perience an experts into stadt
aed solitons
The knowledge ero our standard hasbeen cretuly ssenbled
2 dependable frat and rein hough ou open consltaten proces.
‘rgenatons of al ses and ais all ectrs chose andar help
sham aie ther goal
Information on standards
We can provide you with he krewlede tet your organization reeds
to succeed Find ut more cut Bris Standard by isting our web at
Istroupcorstondons or conacirg our Custer Srvc team oF
noua Cee
Buying standards
‘os can buy and doonioad PF vesions of 851 pubcatons,irclusng Bits
ard ado European ard itera stand, tov our wet at
tgroup.camop, were hard copes can abo be pues
ured iteration! ad oon stand fom ater Stade Devepment
(roanations, has copies can be ered from Ou Custer Services eam
Subscriptions
(ur range af sbscrpton sevice are designe ta make sng sands
tse for yu. For farher information on or subasption prods go 1
bgioupconubscgtors
“uth Bish Standards Online (8500 youl have sant accesso re 55,000,
Bish ar acootes Euopeon andrea tandars fom your esc.
Iesamolable 247 ands eres daly so you aly be wo 0 dle,
‘ou can keepin touch ith standards devdoprens ar receve ubsanal
Aiszours on the putas pie of Sanda, both in shale copy and substi
‘oxmet, ty becoring 2 BSI Subscribing Member
PLUS san updating service encinie t 851 Subsrbing Members You wil
autora recone he atest hard cap of your standards en theyre
revised or eles.
To find cut more abou becoming 285 Subscribing Member and he berets
of member, please vt bagteup coms
“una Mult User Network Licence (MUN) you ae able fo ost stands
publeasors on your inane Lcenees can cove a few or 5 mary ses 35 ou
wih. Win updates supe’ s00n as hee eal, you canbe sae yur
lcumentaton curent. For further information, eal barslesigoup com,
BSI Group Headquarters:
£389 Chiswick High Road London Ws 4a UK
bsi.
Revisions
(ur ish Standard another puto are updated by amendment reson,
\We comin nprove the qualy of cur products and services to bene yur
twain. Hou re an naceacy or ambiguity wth 2 Bah Standard or the
11 publcabn lease infor he Knowledge Cee.
Copyright
the dts, sft pd documentation tout al sh Str nd
Otte BS patos ae re pope of and copyarte yBS, oa pon
ret that es copie foot sad a hentia
Sanz bode sn has oral Kense h iormaton to Sf
commer pbeatin and ue. Ect permed unde e Copy, Oss
sealants Act 188 na exact ray be tepiomued, ere areal per
or earsnteain any tome by any meaner. pte ana
ox eit wit por wt perms am BS Det and sce cn
be obtaned fom te Copyright & Ucersing Departmen,
Useful Contacts:
Ccusomer Services
Tel 044845 86 9001
mal (orders: rsersabsigyeup com
Email (enquires: serices@bsigyoupcom
Subscriptions
“eb 44845 086 9001
Emaiksorcrpionosigroypcon
Knowledge Centre
Tel +420 996 7008
malt krowedgecerrettsiggoupcom
Copyright a tcensing
“eb 4420 6996 7070
mai copright@bsiroup com
making excellence a habit”