Gunnar Stranne Busbar protection

REB 670

Rio de Janeiro
April 23-25, 2006
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


2
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


3
ABB Power Technologies AB

REB 500 is enabled for use with IEC61850 communication


©

2006-04-20 Gunnar Stranne A


4
Benefits of REB 670 – outstanding features
Very fast, minimum operating time 10 ms
Extremely stable for external faults
Additional sensitive differential protection
Smart open CT detection
One or two protection zones and check zone
Phase segregated
Very low CT requirements
Any CT ratio difference can be accommodated
Settings entered directly in primary amperes
The I/O is flexible and extendable
Easy extension
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


5
Application Areas for REB 670

Differential protection, BFR


& Non-Dir OC Protection
for:

Busbars
Meshed corners,
T-protection
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


6
Pre-configured REB 670 Ready To Use

Three-phase versions
REB 670-A20 for 4 bays 2 zones
REB 670-A31 for 8 bays 2 zones
Single phase and summation
three-phase versions
REB 670-B20 for 12 bays 2
zones
REB670-B21 for 12 bays 2
zones
REB670-B31 for 24 bays 2
zones
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


7
REB 670 Preconfigured Versions

3-Phase Version
Two measuring zone
BFR, OC, EnFP & AR
4 or 8 bays

1-Phase Version
Two measuring zones
BFR, OC, EnFP & AR
12 or 24 bays
ABB Power Technologies AB

One terminal per phase


Summation
©

2006-04-20 Gunnar Stranne A


8
Three-Phase Terminal - 4-8 Bays - Double Zone

Application Areas:
Smaller Buses (up to 8 CTs per zone)
REB 670 – A31
2 Zones (A & B); Single Busbar Stations (with Transfer Bus)
8 Bays
1½ Breaker Stations
Double Busbar Stations (with Transfer Bus)
Zone Interconnection included in the design

No switching of CT secondary circuits


ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


9
REB 670 3-Phase - Basic applications Diff & CBF

M/G

Auto-Transformer Generator/Motor Capacitor Reactor


ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


10
REB 670 3- Phase - BBP, BFP & EnFP for single buses

ZA ZB
ZA

Single Busbar Single Bus with bus tie CB


up to 4/8 feeder bays up to 3/7 feeder bays on each side

ZA

ZA ZB

ZB

H type station with bus-section CB


or sectionalizing disconnector T connections
ABB Power Technologies AB

Alternative CT Location
©

2006-04-20 Gunnar Stranne A


11
REB 670 3- Phase - BBP, BFP, EnFP for 1½ CB stations

ZA

ZB

1½ Breaker Stations
up to 4 diameters

ZA

.. .
ZB

1½ Breaker Stations
ABB Power Technologies AB

up to 8 diameters
©

2006-04-20 Gunnar Stranne A


12
REB 670 3- Phase - BBP, BFP & EnFP for Double CB stations

ZA

.. .

ZB

Double Breaker Station


up to 8 feeders

Alternative CT Location
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


13
REB 670 1- Phase - BBP, BFP & EnFP for double buses
ZA
.. .
ZB

Double Bus with bus-coupler CB


and up to 6/7 feeder bays

ZA
.. .
ZB
.. . Transfer Bay
Transfer Bus
.. . Isolator replica in REB 670*1.0
by configuration
ABB Power Technologies AB

Double Busbars with bus coupler CB and Transfer Bus


up to 6/7 feeder bays

Optional Measuring Point


©

2006-04-20 Gunnar Stranne A


14
Scheme Layout for Double Busbar; 2 Zones/7 feeders
700

EQUIPMENT INCLUDED in the PANEL:


ABB

1 pcs 3 phase, Busbar protection terminal REB 670*1.0


- two differential zones
- check zone
- eight CB failure relays
- eight OC feeder backup protection (EnFP)
- internal disconnector replica logic
- internal individual bay tripping logic
- disconnector status supervision
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


15
Single-Phase Terminal REB670 – B21/B31; 12/24 Bays- Double Zone

Application Areas:
Bigger Buses (up to 12/24 bays per zone)
REB 670; Ph-L1
2 Zones (A & B); Single Busbar Stations (with Transfer Bus)
24 Bays
1½ Breaker Stations
REB 670; Ph-L2 Double Busbar Stations (with Transfer Bus)
2 Zones (A & B);
24 Bays Load Transfer is included into the design
3 Terminals required for complete scheme
REB 670; Ph-L3 LDCM available to share binary IO
2 Zones (A & B);
24 Bays
No switching of CT secondary circuits
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


16
REB 670 1- Ph; BBP, BFP & EnFP for single buses

ZA
.. . ZA
.. . .. .
ZB

Single Bus
Single Bus with bus-section disconnector
up to 12/24 feeder bays
up to 12/24 feeder bays (i.e. 12+12; 16+8 etc.)

ZA ZB ZA ZB
.. . .. . .. . .. .

Single Bus with bus-section CB, up to Single Bus with bus-section CB


ABB Power Technologies AB

11/23 feeder bays (i.e. 12+11; 10+13 etc.) up to 11/23 feeder bays on each side
©

2006-04-20 Gunnar Stranne A


17
REB 670 1- Phase - BBP applications for 1½ CB stations

ZA
ZA

.. . .. .
ZB
ZB
1½ Breaker Stations 1½ Breaker Stations
up to 6 / 12 diameters up to 12 / 24 diameters
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


18
REB 670 1- Phase - BBP, CBF & EnFP for 1½ CB Stations!

ZA

.. .

ZB

Bus Diff, CB Fail & EnFP


1½ Breaker Stations
up to 4/8 diameters
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


19
REB 670 1- Ph; BBP, BFP & EnFP for Double CB stations

ZA ZA

.. . .. .
ZB ZB

Double Breaker Station Double Breaker Station


up to 6 / 12 feeders up to 12 / 24 feeders
Alternative CT Location
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


20
REB 670 1- Ph; BBP, BFP & EnFP for double buses

ZA
.. .
ZB

Double Bus with bus-coupler CB


up to 22/23 feeder bays

Isolator replica in REB 670*1.0


ABB Power Technologies AB

by CAP 531 Configuration


©

2006-04-20
21
Gunnar Stranne A
Optional Measuring Point
REB 670 1- Ph; BBP, BFP & EnFP for double bus & transfer

ZA
.. .
ZB
.. .
Transfer Bus
.. .
Combined Bus-Coupler
& Transfer Bay

ZA
.. . Bus-Coupler Bay
ZB
.. . Transfer Bay
Transfer Bus
.. .
Isolator replica in REB 670*1.0
ABB Power Technologies AB

by CAP 531 Configuration

Double Busbars with Transfer Bus


up to 22/23 feeder bays
©

2006-04-20 Gunnar Stranne A


22
Scheme Layout for Double Busbar; 2 Zones/22 feeders
700

EQUIPMENT INCLUDED in the PANEL:


ABB

3 pcs 1 phase, Busbar protection terminal REB 670*1.0


- two differential zones
- check zone
- 24 CB failure relays
- 24 OC feeder backup protection (EnFP)
- internal disconnector replica logic
- internal individual bay tripping logic
- disconnector status supervision
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


23
REB 670 1-Phase version - for double buses
Main 1 Main 2

.. . .. .
Reserve 1 Reserve 2

Four Zone Double Bus with two bus-coupler CBs and two
bus-section CBs and up to 20/21 feeder bays on each station side.

BBP, BFP & EnFP included


Main 1 Main 2

.. . .. .
Reserve 1 Reserve 2

Four Zone Double Bus with two BC-CBs one BS-CB and one sectionalizing
ABB Power Technologies AB

disconnector with up to 18-20 feeder bays in the whole station


©

Optional
2006-04-20
24 Measuring Point
Gunnar Stranne A
REB 670 1-phase version summation transformers

Buses up to 24 bays per zone


REB 670; 1 Ph Single Busbar
2 Zones (A & B);
24 Bays 1½ Breaker Systems
Double Busbar
Same applications possible as for 1Ph solution
Software Driven Zone Selection
+ N times Cost effective Solution
ABB Power Technologies AB

N≤ 8
©

2006-04-20 Gunnar Stranne A


25
REB 670 Allocation of Software Functionality

Zone Selection Differential Zones


Dynamic Software CT switching High speed tripping for internal
(i.e. no switching in CT secondary faults. Typical operating time 12
circuits neither interposing CTs ms
are required)
Easy adaptation to different Complete stability for through
substation layouts such as: single faults, with heavy CT saturation,
or double bus (with transfer bus), and a maximum remanence in the
one-and-half or double breaker, CT core at auto-reclosing
etc. Low CT requirement, only 2
Simple adaptation to buses with milliseconds to saturation needed
only one set of CTs in the bus- for correct operation
section or bus-coupler bays
Intelligent detection for open or
Selective BBP & BFP tripping for shorted CT secondary circuits and
every bay
settable blocking of differential
Merging of the two differential protection zone
zones when required (i.e. during
load transfer in double busbar Sensitive differential protection
ABB Power Technologies AB

stations) stage for power systems with


limited earth-fault current
Disconnector and/or circuit
breaker status supervision
©

2006-04-20 Gunnar Stranne A


26
REB 670 Software Structure / Function Blocks

Zone Selection Differential Zones


Primary Switchgear Objects Zone A
Status (i.e. disconnector and (Id>, OCT, Sensitive Id>)
breakers) Zone B
Bay (Id>, OCT, Sensitive Id>)
(Interface towards one Check Zone (Id>)
Primary Bay)
Zone Interconnection
(Merging of two zones when
required)

One Basic
Function in AFL,
ABB Power Technologies AB

Hidden
connections exist
©

2006-04-20 Gunnar Stranne A


27
Differential Protection in REB 670

Very fast, minimum operating time 10 ms


Extremely stable for external faults
Completely phase segregated measurement
Differential algorithm not dependent on the number of connected feeders
Very low CT requirements, only 2 ms before CT saturation
Any CT ratio difference can be accommodated
Settings entered directly in primary amperes
Id [Primary Amps]

Operate
I in region
I=
d

Differential protection
ABB Power Technologies AB

operation characteristic
Diff Oper Level
Sensitive Oper Level
s=0.53

Iin [Primary Amps]


©

2006-04-20 Gunnar Stranne A


28
Sensitive Differential Protection in REB 670

Used in low impedance earthed power system or in other


special applications
It has the following characteristics:
Freely settable characteristic with time delay possibility
Automatically blocked for heavy ph-to-ph faults
External release via binary signal (i.e. from open delta
voltage, transformer neutral point current, etc.)
Id [Primary Amps]

Operate
I in region
I=
d

Differential protection
ABB Power Technologies AB

operation characteristic
Diff Oper Level Sensitive
Sensitive Oper Level differential
s=0.53 protection

Iin [Primary Amps]


©

2006-04-20 Gunnar Stranne A


29 en04000260.vsd
Open CT detection for REB 670

Slow and Fast Open CT detection


Settable influence of slow and fast open CT logic:
Off (switched off)
Block (differential protection)
Supervise (Doesn't block, just increase minimum
differential operation level as shown below)
Id [Primary Amps]

Operate
I in
I=
d
region
OCT Logic Supervision Level
Differential protection
operation characteristic
ABB Power Technologies AB

Diff Oper Level Sensitive


Sensitive Oper Level differential
s=0.53 protection

Iin [Primary Amps]


en04000260.vsd
©

2006-04-20 Gunnar Stranne A


30
Check Zone in REB 670

Independent check zone available


Can be switched off (default setting)
Freely settable which CTs shall be connected to check zone
Provide stability in case of problem with disconnector
auxiliary contacts ( stuck contacts or wiring problems)
Id [Primary Amps]

Operate
region

Oper Level
ABB Power Technologies AB

s=0.0-0.90 (settable)

Iout [Primary Amps]


©

2006-04-20 Gunnar Stranne A


31
Zone Supervision in REB 670

Two new types of Diff Zone supervision are available


Id> traditional supervision of differential current level
with settable time delay(i.e. can be used as alarm or for
automatic reset of OCT condition)

Iin> incoming current supervision, without time delay


(i.e. can be used to trigger DR for external faults)
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


32
Disconnector/CB supervision & alarming

For every disconnector/CB status is determined from the


status of aux contacts (i.e. a & b contacts)
Two schemes available depending on philosophy, a or b or both

Position of a disconnector/CB can be forced to OPEN or


CLOSED by a parameter setting
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


33
User Features in REB 670 (3-Ph & 1-Ph)

Easy to set, configure, install & use

Pre-configured for most typical substation layouts

Bay connection matrix built-in (large HMI)

Switchgear Status Matrix (large HMI)


ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


34
Bay-Connections & Switchgear Status Matrices

User Internally Connections


Settable Used Bay to internal
Bay Name FB zones
ABB Power Technologies AB

User Settable Switchgear


Switchgear Object
Names Status
©

2006-04-20 Gunnar Stranne A


35
Breaker Failure Protection

Complete breaker failure protection with:


1ph and/or 3ph starting

Re-trip after a set time delay

Backup trip / bus-strip (i.e. second time delay)

Short reset time of 15ms

Trips CBs via busbar disconnector replica

Integrated station wide trip logic available from Zone Selection


ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


36
Phase Overcurrent function

Four, non-directional phase


overcurrent stages
IF Each stage can be Definite- or
Inverse time delayed.
19 IEC/ANSI curves
Logarithmic inverse
3I> Tailor made curve is available
Each stage can be separately
4 blocked with second harmonic
4th stage can be used for end fault
protection
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


37
End Fault Protection

CB=Clearing Boundary

CT=Measuring Boundary Busbar


Protection
Busbar
Protection

Feeder
Protection
Feeder
Protection

Over-Trip
When feeder CB is Zone
open, stop When feeder CB is
measuring open, extend
boundary at the Under-Trip
measuring
open CB contacts Zone boundary to the
in order to avoid open CB contacts
ABB Power Technologies AB

over-trip and in order to avoid


activate fast OC under-trip
protection to trip
remote endAonly
©

2006-04-20 Gunnar Stranne


38
Autoreclosing Function

Only used in certain markets in order to try to


re-energize the bus after BBP trip
One AR function per Differential Zone is available
ABB Power Technologies AB
©

2006-04-20 Gunnar Stranne A


39
Summary - REB 670 busbar protection
Complete and fast differential protection (10-12ms)
One or two protection zones and check zone
Extremely stable for external faults
Additional sensitivity
Low CT requirements - open CT detection – any CT ratio
Advanced zone selection & integrated zone interconnection
Disconnector and/or CB position supervision & alarming
CB failure and 4-stage backup overcurrent protection
Disturbance and event recording
Preconfigured versions with flexible and extendable I/O
ABB Power Technologies AB

Easy extension
©

2006-04-20 Gunnar Stranne A


40