Countis m43
Countis m43
COUNTIS M43
MANUAL V1.0
All rights reserved. Without the written permission of Socomec, the contents of any passages and chapters
in this manual shall not be copied or reproduced or disseminated in any form. Otherwise, all
consequences shall be borne by the violator.
Socomec reserve the right to modify the product specifications described in this manual without prior
notice. Before ordering, please contact our company or local agent for the latest specifications of this
product.
2.1 Specifications-----------------------------------------------------------------------------------------------------------------3
2.4 Environment--------------------------------------------------------------------------------------------------------------------4
2.5 Dimendions---------------------------------------------------------------------------------------------------------------------5
3.2 Measurement---------------------------------------------------------------------------------------------------------------6
3.2.4 Energy------------------------------------------------------------------------------------------------------------------------10
3.3.6 Parity--------------------------------------------------------------------------------------------------------------------------15
3.3.8 CT Setting---------------------------------------------------------------------------------------------------------------------17
3.3.9 PT Setting---------------------------------------------------------------------------------------------------------------------18
3.3.16 Clear-------------------------------------------------------------------------------------------------------------------------24
Part 4.
.Modbus register Map------------------------------------------------------------------------------------------------25
COUNTIS M43 measures and displays the characteristics of single phase two wires (1p2w), three phase
three wires(3p3w,) and three phase four wires(3p4w) supplies, including voltage, frequency, current,
power ,active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh.
Maximum demand current can be measured over preset periods of up to 60minutes. In order to measure
energy, the unit requires voltage and current inputs in addition to the supply required to power the
product. The requisite current input(s) are obtained via current transformers(CT).
This meter can be configured to work with a wide range of CTs, giving the unit a wide range of operation.
Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is password protected.
This unit can be powered from a separate auxiliary (AC or DC) supply. Alternatively it can be powered from
the monitored supply, where appropriate.
Measures kWh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD, etc.
RS485 Modbus
1/5A CT connection
Class 0.5S
Line Frequency
-1-
The unit has password-protected set-up screens for:
Changing password
Two pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring
from another display or a computer.
1.3 Application
COUNTIS M43 is a multi-functional three phase energy meter, designed for power system, public facilities,
industrial applications and residential power monitoring needs. It can also be used in AC charging piles,
solar photovoltaic and other occasions. Its complete communication function makes it very suitable for
real-time power monitoring systems.
-2-
Part 2 General Specifications
2.1 Specifications
Voltage::Rated Voltage ( Un) L-N 100 to 276V a.c. (not for 3p3w supplies)
Second Voltage:100-500V
Second Current:1A or 5A
Operational frequency:Rated:50/60Hz
Range:45-65 Hz
2.2 Accuracy
Voltage:0.2%
Current:0.2%
Frequency:0.2%
Power Factor:0.5%
-3-
Active Power:0.5%
Reactive Power:±0.5%
Apparent power:±0.5%
Reactive energy:Class2
Bus Type:RS485
Modbus Address:1-247
Bus load:64pcs
Communication distance:1000m
Parity:EVEN /ODD/NONE
Data bit:8
Stop bit:1
2.4 Environment
-4-
Protection against penetration of dust and water: IP51(indoor)
Altitude: ≤2000m
2.5 Dimensions
35
mm
Height:65 mm
Width:72 mm
Length: 94.5 mm
2.6 Wiring Diagram
-5-
Part 3. Operation Instructions
When the meter is powered on, the meter will initialize and do self-checking
Display as following:
1 Full screen
2 Software version
3 Self-checking finish
3.2 Measurement
Press button :
-6-
1 Phase to neutral voltages(3p4w)
3 Neutral current
-7-
5 Current THD% for each phase
Press button :
-8-
4 Maximum Power Demand
3.2.3 Power
Press :
-9-
4 Total kW, kVAr, kVA
3.2.4 Energy
Press button :
- 10 -
4 Exported active energy in kWh
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing. If an incorrect password is entered, the display will show: Err
- 11 -
To exit setting-up mode, press repeatedly until the measurement screen is restored.
1. After Entering the Setting manu, use the and buttons to select the
required item from the menu. Selection does not roll over between bottom and top of list
4. Having selected an option from the current layer, press to confirm your selection. The
5. Having completed a parameter setting, press to return to a higher menu level. The SET
indicator will be removed and you will be able to use the and buttons for
further menu selection.
- 12 -
6. On completion of all set-up, press repeatedly until the measurement screen is restored.
When setting up the unit, some screens require the entering of a number. In particular, on entry to the
setting up section, a password must be entered. Digits are set individually, from left to right. The
procedure is as follows:
1. The current digit to be set flashes and is set using the and
2. Press to confirm each digit setting. The SET indicator appears after the last digit has
been set.
3. After setting the last digit, press to exit the number setting routine. The SET indicator
will be removed.
1
Use the and
to choose the change password option
2-1
Press the to enter the
change password routine. The new
password screen will appear with the
first digit flashing
- 13 -
2-2
Use and to set
Press to exit the number setting routine and return to the Set-up menu. SET will
be removed
1
From the Set-up menu, use
2-1
Press button to enter the
selection routine. The current setting will
be flashing.
- 14 -
2-2
Use and
buttons to choose Modbus Address(001
to 247)
1
From the Set-up menu, use
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and
buttons to choose Baud rate 2.4k. 4.8k,
9.6k, 19.2k, 38.4k
3.3.6 Parity
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and
buttons to choose Parity (EVEN / ODD /
NONE)
Option:1 or 2.
1
From the Set-up menu, use
- 16 -
2
Press to enter the selection
routine. The current setting will flash.
Use and
buttons to choose Stop Bit (2 or 1)
Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2.
3.3.8 CT Setting
The CT option sets the secondary current (CT2 1A or 5A) of the current transformer (CT) that wires to the
meter.
1
From the Set-up menu, use
2 Secondary CT setting
3
Set CT Ratio value Press to
enter the CT Ratio setting screen. Use
and buttons to
choose the CT ratio. The range is from
0001 to 9999.
- 17 -
Example: If set the ratio to be 100,it means the primary current equals secondary currentx100
3.3.9 PT Setting
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer(PT) that wires to
the meter.
1
From the Set-up menu, use
2 Secondary PT setting
For example, if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100
- 18 -
3.3.10 Pulse Output
This option allows you to configure the pulse output. The output can be set to provide a pulse for a
defined amount of energy active or reactive.
Use this section to set up the pulse output 1—Units: Total kWh, Total kVArh
1
From the Set-up menu, use and
2
Press to enter the selection
routine. The unit symbol will flash.
3.3.11Pulse Constant
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
0.01kWh/0.1kWh/1kWh/10kWh/100/1000kWh.
- 19 -
(It shows 1 impulse = 10kWh/kVArh)
1
From the Set-up menu, use and
2
Press to enter the selection routine.
The energy monitored can be active or reactive and the pulse width can be selected as 200, 100(default)
or 60ms.
- 20 -
(It shows pulse width of 200ms)
1
From the Set-up menu, use and
2
Press to enter the selection routine.
The current setting will flash.
This sets the period in minutes over which the current and power readings are integrated for maximum
demand measurement. The options are: 0, 5, 8, 10, 15, 20, 30, 60 minutes
- 21 -
1
From the set-up menu, use and
2
Press to enter the selection routine.
Press to exit the DIT selection routine and return to the menu.
- 22 -
2
Press to enter the selection routine.
The current time interval will flash
0(always on),5,10,30,60,120minutes
Use this section to set the type of power supply being monitored.
1
From the Set-up menu, use and
2
Press to enter the selection routine.
- 23 -
3.3.16 Clear
The meter provides a function to reset the maximum demand value of current and power.。
1
From the Set-up menu, use
2
Press to enter the selection
routine. The MD will flash.
- 24 -
Part 4.
.Modbus register Map
Function code
3 3 1
Input Register Parameter 寄存器首地址
Ø Ø Ø
Address
Phase 1 current.
30007 4 Float A 00 06 √ √ √
Phase 2 current.
30009 4 Float A 00 08 √ √ X
Phase 3 current.
30011 4 Float A 00 0A √ √ X
Phase 1 power.
30013 4 Float W 00 0C √ X √
Phase 2 power.
30015 4 Float W 00 0E √ X X
Phase 3 power.
30017 4 Float W 00 10 √ X X
- 25 -
Phase 3 volt amps.
30023 4 Float VA 00 16 √ X X
- 26 -
Frequency of supply voltages.
30071 4 Float Hz 00 46 √ √ √
Total VAh
30081 4 Float kVAh 00 50 √ √ √
Ah
30083 4 Float Ah 00 52 √ √ √
30087 4 Float W 00 56 √ √ √
(2).
- 27 -
Average line to line volts.
30207 4 Float V 00 CE √ √ X
- 28 -
Average line to line volts THD.
30341 4 Float % 01 54 √ √ X
Total kwh(3)
30343 4 Float kWh 01 56 √ √ √
Total kvarh(3)
30345 4 Float kVArh 01 58 √ √ √
L1 import kwh
30347 4 Float kWh 01 5A √ √ √
L2 import kwh
30349 4 Float kWh 01 5C √ √ X
L3 import kWh
30351 4 Float kWh 01 5E √ √ X
L1 export kWh
30353 4 Float kWh 01 60 √ √ √
L2 export kwh
30355 4 Float kWh 01 62 √ √ X
L3 export kWh
30357 4 Float kWh 01 64 √ √ X
L1 total kwh(3)
30359 4 Float kWh 01 66 √ √ √
L2 total kWh(3)
30361 4 Float kWh 01 68 √ √ X
L3 total kwh(3)
30363 4 Float kWh 01 6A √ √ X
L1 import kvarh
30365 4 Float kVArh 01 6C √ √ √
L2 import kvarh
30367 4 Float kVArh 01 6E √ √ X
L3 import kvarh
30369 4 Float kVArh 01 70 √ √ X
L1 export kvarh
30371 4 Float kVArh 01 72 √ √ √
L2 export kvarh
30373 4 Float kVArh 01 74 √ √ X
L3 export kvarh
30375 4 Float kVArh 01 76 √ √ X
- 29 -
L1 total kvarh (3)
30377 4 Float kVArh 01 78 √ √ √
Function code
10 to set holding parameter
03 to read holding parameter
Modbus
Protocol
Start Address
Address Parameter Parameter
Hex
Register Number Valid range Mode
High Low
Byte Byte
- 30 -
demand to show the
Length : 4 byte
Length : 4 byte
0 = locked. 1 = unlocked.
40015 8 Password Lock 00 OE r
Reading will also reset the password
timeout back to one minute.
Length : 4 byte
- 31 -
and odd parity.3 = Two stop bits and no
parity. Requires a restart to become
effective.
Length : 4 byte
= 1 to 6
1--0.01kwh/imp
2--0.1kwh/imp
3--1kwh/imp
40023 12 Pulse 1 Divisor 00 16 r/w
4-10kwh/imp
5-100kwh/imp
6-1000kwh/imp
Length : 4 byte
- 32 -
Write the baud rate for MODBUS Protocol,
where:
Length : 4 byte
CT Ratio range:1~2000
Length : 4 byte
40063 32 CT ratio 00 3E r/w
Data Format : Float
(Non MID)
PT Ratio range:1~2000
Length : 4 byte
40065 33 PT ratio 00 40 r/w
Data Format : Float
(Non MID)
Pulse 1
input parameter for pulse
40087 44 00 56 r/w
Energy Type
out 1: 37 = total kwh or 39 = total kVarh,
default 39.
- 33 -
Length : 4 byte
Serial number
Length: 4 byte
464513 32257 Serial number FC 00 ro
- 34 -