Chloride CP-70Z
AC UPS System
From 2.5 to 500 kVA - 1-ph or 3-ph output
The Chloride CP-70Z industrial Uninterrup- Custom-designed AC UPS systems to secure critical industrial processes
tible Power Supply system (UPS) is the flag-
ship product of Chloride Industrial Power. Associated with an industrial stand-by battery, the Chloride CP-70Z protects
It combines conservative design topology critical industrial AC equipments and processes from the damaging effects of
with proven digital control technology to power interruption and losses. It uses the patented digital Vector Control tech-
offer the best performances in any electrical nology which increases the performances of power components and enables an
and environmental condition. active conditioning of the load. The result is improved reliability for the process
and enhanced safety for the personnel.
The Chloride CP range is designed to meet the
stringent electrical and mechanical require- The CP-70Z is a range of three-phase input / single-phase output or three-phase
ments in industrial environments. Each Chlo- output AC UPS systems available from 2.5kVA to 120kVA. It offers a wide choice
ride CP product is based on interchangeable of DC battery voltages and of output voltages.
sub-assemblies to allow full customization, in The CP-70Z range can be customized to meet higher power needs, up to
compliance with client’s technical specification 250kVA single-phase output or 500kVA three-phase output.
and with project documentation requirements. To further improve load availability and process reliability, the CP-70Z is able to
operate in dual parallel configuration, with single or dual batteries, with
Applications
The Chloride CP-70Z AC UPS System range suits centralized or distributed reserve line, and can include a DC and/or AC bus-tie.
applications such as:
Oil and Gas offshore and onshore
Refining and petrochemical plants
Power generation plants
Transportation (rail, metro, tramway)
Benefits
Tailor made systems to comply with all customer’s
specifications
Ruggedized solutions for demanding
environments: high temperatures, vibrations, dust,
elevation, dripping water and moisture
Efficient maintenance:
Easy front-access to all critical modules
Removable ID Cards to safeguard the UPS
parameters and facilitate control board
replacement
Smart access to UPS data:
Large colour LCD touch-pad for user interface
Embedded event logger (up to 2000 events) and
capability to export recorded events via memory
stick
Key Features
Reliability - Unique design which allows the UPS to
continuously operate for at least 20 years at full load
at 40°C
On-line double conversion - UPS classified VFI SS
111 as per IEC62040-3
Robust mechanical design - the system withstands
vertical and horizontal acceleration stress tests up to
0.5g as standard
Galvanic isolation - input and output transformers
as standard
Remote monitoring capabilities: Modbus, Profibus,
DF1, ethernet, volt-free contact, monitoring
software
Full compatibility with lead-acid and nickel-
cadmium batteries, sealed or vented
Chloride CP-70Z
Chloride CP-70Z 31
ACSystem
AC UPS Uninterruptible Power Supply System
From 2.5 to 500 kVA - 1-ph or 3-ph output
Ratings - Output power(1) (kVA) vs DC intermediate voltage (Vdc) Standards
110-120Vdc 2.5(2) 5 7.5 10 15 20 25 30 40 50 60 - - - Compliance IEC 62040-1, IEC 62040-2, IEC62040-3 / IEC 60950
IEC 61000-6-2, IEC 61000-6-4
220-240Vdc - - - 10 (2)
15 20 25 30 40 50 60 80 100 120 IEC 60529 / IEC 61439 / IEC 60076-11
400Vdc(3) - - - - - - - - 40 50 60 80 100 120 Conformity Low voltage directive: 2006/95/EC
EMC directive: 2004/108/EC
(1)
at power factor 0.8 lagging / (2) 1-ph output only CE Mark
(3)
Up to 250 kVA 1-ph output or up to 500kVA 3-ph output on request
Technical Data Options
Input Rectifier 12-pulse rectifier
AC voltage 3 x 400V (380, 415)(4) Harmonic filter
Ripple filters
Voltage tolerance +/- 10%
Blocking diode
Frequency 50Hz (60Hz) Other input voltage (3x190 to 3x690VAC)
Frequency tolerance +/- 5% Inrush current limitation to 8In
Intermediate DC Circuit Surge and Lightning protections
Nominal DC voltage 110-120 / 220-240 / 400 V Battery Battery circuit protection box
Battery cabinet
Voltage stability +/- 1% in float mode, input within tolerance
Low-voltage disconnect contactor
+/-1.5% for parallel rectifiers
Battery Management System
Voltage ripple 1% RMS, in float, battery connected Battery room temperature sensor
Current limitation I nominal System Dual configurations
Charging characteristic IU according to DIN 41773 Input / intermediate /output isolators
Ouput DC/DC serial regulator
Available ratings see table (at PF 0.8 lagging) isolated DC/DC converter
AC distribution
AC Voltage 1 x 230V (220, 240) ; 1 x 110V (115, 120)(4)
Earth fault monitoring
3 x 400V (380, 415) ; 3 x 220V (200, 208, 230)(4)
Internal lighting
Frequency 50Hz (60Hz) Anti-condensation heater
Frequency stability Temperature monitor
with internal oscillator +/- 0.05% Special cabinet identification
Reserve transformer
with reserve synchronism +/-4% (from 1.2 to 6% adjustable)
Reserve stabilizer
Frequency response <1Hz/s (0.1Hz/s for parallel systems)
Mechanical Up to IP42 external
Voltage stability (for 0-100% load variation) Top cable entry
static +/-1% (+/-2% for parallel systems) Other frame colour
dynamic VFI SS 111 as per IEC/EN 62040-3, class 1 Anti-seismic design
Overload inverter Communication Front-panel analog meters (72x72 class 1.5)
1 minute 150% of nominal power Transducers
Additional Volt-free contacts
10 minutes 125% of nominal power Remote monitoring via Modbus
Short circuit clearance Remote monitoring via other protocol
100 ms 250% (1ph) or 315% (Ph-N; 3ph) of nominal current PPVis monitoring software
5s 175% (1ph) or 220% (Ph-N; 3ph) of nominal current Passive or active mimic panel
Harmonic voltage distortion Non-exhaustive list of options. Consult us for any other requirements.
With 100% linear load < 3%
With 100% non-linear load SS as per IEC/EN 62040-3
Allowable power factor 0.5 lagging to 0.5 leading
Allowable crest factor 3/1
Battery
Type Lead Acid or Nickel Cadmium vented or
recombination
Autonomy From few minutes to several hours, as per
customer’s requirement
Battery current limitation 0.1C (Lead Acid battery)
(typical, float & charge modes) 0.2C (Nickel Cadmium battery)
Battery current limitation 0.05C (Lead acid battery)
(typical, boost mode) 0.1C (Nickel Cadmium battery)
General Data
Operating temperature 0 to 40°C(4)
Storage temperature -20 to +70°C
Relative humidity <95% non condensing
Operating altitude 1000 m max without derating
Cooling Forced ventilation
Efficiency Up to 90% according to rating
External protection IP 20(4) according to IEC 60529