3BUS095593 LR B en Symphony Plus Alarm Management For Power Generation
3BUS095593 LR B en Symphony Plus Alarm Management For Power Generation
Definition of the term “alarm” The definition means that an alarm must indicate a problem, not a
The concept of alarms (French for “a l’arme” which means normal process condition. The main target audience of an alarm
“spring to arms”) is very old and originates from the military should be operators, not engineers, maintenance technicians, or
concept where a guard warns his fellows in case of an attack. In managers.
process control, alarms have a very long tradition (eg, a whistle
indicating that water is boiling). Older plants were using panels Today’s reality in many plants is different: most of the occurring
with bulbs and bells to alarm the operators. alarms have little or no value for the operators. The supervision of a
process is usually supported by an alarm system.
Unfortunately in many of today’s power plants, an alarm means
something very different: some value has exceeded a threshold, Human capacity is limited
resulting in a cacophony of alarms with most of them having no Theoretically, every alarm shown to the operators should be
value at all for the operator. meaningful and require operator action (see EEMUA 191). EEMUA
191 has emphasized the fact that the human capacity to absorb
Alarm configuration seems to be an easy task alarms is limited. If this limit is exceeded for longer periods of time,
The configuration of alarms historically has been expensive, it is likely that important alarms will be overlooked, and in extreme
because each alarm required extra hardware and wiring. Therefore cases the whole alarm system might be more or less ignored.
the designers of a plant put considerable thought in the decision of
whether an alarm was meaningful or not. This form of implicit alarm The guideline EEMUA 191 published first in 1999 and the standard
management often resulted in good quality operator interfaces. In ISA 18.2 published in 2009 have profoundly changed the way
the current generation of control systems, the cost associated with alarms are engineered in modern control systems.
alarm configuration has been significantly reduced. Therefore, it is
easy to configure several alarms on each and every tag. EEMUA 191 focuses on the properties of the operator’s information
processing capabilities. It emphasizes the usability of an alarm
Project engineers tend to hesitate before removing an alarm when system from the operator’s perspective. If the operator is
unsure if the alarm is relevant. Modern field devices are able to overloaded with alarms, the whole alarm system becomes useless.
generate a multitude of diagnostic messages, many of them issued The document specifies several measurable performance
as alarms. This typically results in huge amounts of configured indicators that can be used to benchmark a plant’s alarm system
alarms. As a consequence, during plant operation, operators performance, for example:
receive huge amounts of alarms, even during normal operation. -- Long term average alarm rate in steady operation: less than
Today it is very common to receive more than 2000 alarms a day 1 alarm in 10 minutes
per operator. Most of those alarms are nuisance alarms that -- Number of alarms during first 10 minutes after a major plant
provide no value for the operators. upset: under 10
-- Alarm priority distribution: high (5%) - medium (15%) - low (80%)
Permanent high alarm rates indicate bad alarm quality -- Average fewer than 10 standing alarms.
More and more companies understand that these high alarm rates
are not acceptable and have an adverse effect on operator Priority distribution report
overloaded
100
reactive
10
robust stable
predictive
10 100 1000
Maximum alarm rate (on 10 minute time base)
Settings
From: 01.09.2008 00:00:00 To: 01.10.2008 00:00:00
First: 01.09.2008 02:03:01 Last: 30.09.2008 23:45:56
Operation
Monitoring &
Assessment
Maintenance
ize De
The alarm philosophy document defines the KPIs describing
it m the required alarm system quality. In the initial plant setup
Op
these KPIs may (or may not) reach the desired quality. But a
fin
re
u
as crucial for maintenance and optimization of the system. Alarm
Me management is often implemented as part of the continuous
Define – Measure – Analyze – Improve – Control (DMAIC) cycle
in Six Sigma programs.
Alarm management system Systematic alarm management usually reveals weak spots in
Careful planning and conception is as important for the alarm the plant and can therefore help to directly improve plant
system as it is for the whole plant. The same applies for performance.
documentation - it is equally important for the whole plant as
for the alarm management system.
The operator guidance given by a high quality alarm system will Alarm simulation
further improve the plants performance. Alarm measurement and alarm analysis are essential for
permanent alarm management optimization. But advanced
If the alarm system quality has degraded, the reasons for this alarm management does not end there. S+ Operations‘
degradation need to be analyzed, and actions to fix these modern alarm management system in combination with the
problems need to be performed. For example if new operating information management system supports advanced
procedures are driving the process more to its borders, the old techniques like alarm simulation.
alarm thresholds might be too tight and might need to be
adapted to the new operating procedures. If a broken While analyzing the plants alarm system, this technique allows
measurement instrument permanently generates alarms, this the simulation of changes in alarm limits, thresholds and other
instrument needs to be repaired or exchanged. alarm values to get information with which alarm system
configuration values the optimum results are to be achieved.
With S+ Operations, the measurement of alarms and events is Alarm simulation allows the simulation of value changes for
very easy: its patented integrated information management single alarms as well as the simulation of alarm grouping,
system simply logs every system event within a milliseconds state-based alarm hiding and other simulations.
resolution and makes data easily available for further
processing. Alarm analysis and alarm simulation pave the way for the
optimization and rationalization of the existing alarms.
Standard alarm reports (EEMUA 191 and ISA SP 18.2
compliant) are already integrated and preconfigured eg, Alarm optimization
- - Most-frequent alarms During alarm optimization the results of alarm measurement,
- - Longest-standing alarms analysis and simulation are transferred to the plant.
- - Average time to acknowledge alarms over time (trend)
- - Alarm priority distribution Alarm management lifecycle
- - Number of disabled alarms, inhibited alarms, shelved alarms Since the plants constantly change, the alarm management
and hidden alarms over time (trend) system has to be checked regularly and modified if necessary.
Direct navigation from alarm list to actual values and related information Alarm hiding is set up during the engineering phase. Its main
purpose is to suppress alarms that are either expected or not
relevant in a particular situation, or that are based on a known
process state eg, low temperatures or flow during a controlled
shutdown. As the name suggests, ‘hidden’ alarms are never visible
to operators. They only see alarms that require action on their part.
Alarm shelving
Shelving lets operators decide whether or not to put an alarm
‘on the shelf’ for a defined period of time or a certain
occurrence. This temporarily removes it from the main alarm
list to a special list, but the alarm itself is not affected. It will
later require attention from the operator. In the meantime, the
operator can concentrate on tasks judged to require their
immediate focus. Simple navigation makes alarm shelving a
valuable and much-appreciated tool that helps operators work
with maximum efficiency.
The visible part of S+ Operations alarm lists always gives direct
access to the actual values of the parameters that have S+ Operations alarm grouping
triggered the alarm. For example, when operators are alerted
that the amount of liquid in a tank has fallen below a specified
level, they can see exactly what the current level is. Their
response can thus be based on whether it is just below or way
below.
Germany
Email: [email protected]