Data sheet for SINAMICS G120C
Article No. : 6SL3210-1KE22-6UF1
Client order no. : Item no. : Figure similar
Order no. : Consignment no. :
Offer no. : Project :
Remarks :
Rated data Inputs / outputs
Input Standard digital inputs
Number of phases 3 AC Number 6
Line voltage 380 ... 480 V +10 % -20 % Switching level: 0→1 11 V
Line frequency 47 ... 63 Hz Switching level: 1→0 5V
Rated current (LO) 33.00 A Max. inrush current 15 mA
Rated current (HO) 24.10 A Fail-safe digital inputs
Output Number 1
Number of phases 3 AC Digital outputs
Rated voltage 400V IEC 480V NEC 1) Number as relay changeover contact 1
Rated power (LO) 11.00 kW 15.00 hp Output (resistive load) DC 30 V, 0.5 A
Rated power (HO) 7.50 kW 10.00 hp Number as transistor 1
Rated current (LO) 25.00 A Output (resistive load) DC 30 V, 0.5 A
Rated current (HO) 16.50 A Analog / digital inputs
Rated current (IN) 26.00 A Number 1 (Differential input)
Max. output current 33.00 A Resolution 10 bit
Pulse frequency 4 kHz Switching threshold as digital input
Output frequency for vector control 0 ... 240 Hz 0→1 4V
Output frequency for V/f control 0 ... 550 Hz 1→0 1.6 V
Overload capability Analog outputs
Low Overload (LO) Number 1 (Non-isolated output)
150 % base load current IL for 3 s, followed by 110 % base load current IL for 57 s PTC/ KTY interface
in a 300 s cycle time
1 motor temperature sensor input, sensors that can be connected PTC, KTY and
High Overload (HO) Thermo-Click, accuracy ±5 °C
200 % base load current IH for 3 s, followed by 150 % base load current IH for 57 Closed-loop control techniques
s in a 300 s cycle time
V/f linear / square-law / parameterizable Yes
General tech. specifications V/f with flux current control (FCC) Yes
Power factor λ 0.70 ... 0.85
V/f ECO linear / square-law Yes
Offset factor cos φ 0.95
Sensorless vector control Yes
Efficiency η 0.97
Vector control, with sensor No
Sound pressure level (1m) 66 dB
Encoderless torque control No
Power loss 292.0 W
Torque control, with encoder No
Filter class (integrated) Unfiltered
Communication
Communication PROFINET, EtherNet/IP
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 2 Generated Thu Jun 8 18:55:54 CET 2023
Data sheet for SINAMICS G120C
Article No. : 6SL3210-1KE22-6UF1
Ambient conditions Converter losses to IEC61800-9-2*
Cooling Air cooling using an integrated fan Efficiency class IE2
Cooling air requirement 0.018 m³/s (0.636 ft³/s) Comparison with the reference
32.5 %
converter (90% / 100%)
Installation altitude 1,000 m (3,280.84 ft)
Ambient temperature
Operation -10 ... 40 °C (14 ... 104 °F)
I 227.0 W (1.3 %) 254.0 W (1.5 %) 292.0 W (1.7 %)
100%
Transport -40 ... 70 °C (-40 ... 158 °F)
Storage -40 ... 70 °C (-40 ... 158 °F)
Relative humidity
95 % At 40 °C (104 °F), condensation
Max. operation 152.0 W (0.9 %) 164.0 W (0.9 %) 178.0 W (1.0 %)
and icing not permissible 50%
Connections
126.0 W (0.7 %) 132.0 W (0.8 %)
Signal cable 25%
0.15 ... 1.50 mm²
Conductor cross-section
(AWG 24 ... AWG 16)
Line side
50% 90% f
Version Plug-in screw terminals The percentage values show the losses in relation to the rated apparent power of
the converter.
6.00 ... 16.00 mm²
Conductor cross-section
(AWG 10 ... AWG 6) The diagram shows the losses for the points (as per standard IEC61800-9-2) of
the relative torque generating current (I) over the relative motor stator frequency
Motor end (f). The values are valid for the basic version of the converter without
options/components.
Version Plug-in screw terminals
*converted values
6.00 ... 16.00 mm²
Conductor cross-section
(AWG 10 ... AWG 6)
1)
The output current and HP ratings are valid for the voltage range 440V-480V
DC link (for braking resistor)
Version Plug-in screw terminals
6.00 ... 16.00 mm²
Conductor cross-section
(AWG 10 ... AWG 6)
Line length, max. 15 m (49.21 ft)
PE connection On housing with M4 screw
Max. motor cable length
Shielded 150 m (492.13 ft)
Unshielded 150 m (492.13 ft)
Mechanical data
Degree of protection IP20 / UL open type
Frame size FSC
Net weight 4.40 kg (9.70 lb)
Dimensions
Width 140 mm (5.51 in)
Height 295 mm (11.61 in)
Depth 208 mm (8.19 in)
Standards
Compliance with standards UL, cUL, CE, C-Tick (RCM)
EMC Directive 2004/108/EC, Low-
CE marking
Voltage Directive 2006/95/EC
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 2 of 2 Generated Thu Jun 8 18:55:54 CET 2023