0% found this document useful (0 votes)
330 views8 pages

Hci434 F

This document provides specifications and technical details for Stamford industrial generators. It includes information on standards, voltage regulators, terminals, shaft/keys, insulation/impregnation, quality assurance, derates, windings, control systems, and other electrical and mechanical specifications. The generators can be self-excited using an AS440 AVR or separately excited using a PMG with either an MX341 or MX321 AVR, providing voltage regulation of ±1% or ±0.5% respectively. They are designed for reliable operation in industrial applications.

Uploaded by

Alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
330 views8 pages

Hci434 F

This document provides specifications and technical details for Stamford industrial generators. It includes information on standards, voltage regulators, terminals, shaft/keys, insulation/impregnation, quality assurance, derates, windings, control systems, and other electrical and mechanical specifications. The generators can be self-excited using an AS440 AVR or separately excited using a PMG with either an MX341 or MX321 AVR, providing voltage regulation of ±1% or ±0.5% respectively. They are designed for reliable operation in industrial applications.

Uploaded by

Alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

HCI434F/444F - Winding 13

APPROVED DOCUMENT
Technical Data Sheet
HCI434F/444F
SPECIFICATIONS & OPTIONS

STANDARDS TERMINALS & TERMINAL BOX

Stamford industrial generators meet the requirements of Standard generators are 3-phase reconnectable with 12
BS EN 60034 and the relevant section of other ends brought out to the terminals, which are mounted on
international standards such as BS5000, VDE 0530, a cover at the non-drive end of the generator. A sheet
NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. steel terminal box contains the AVR and provides ample
Other standards and certifications can be considered on space for the customers' wiring and gland
request. arrangements. It has removable panels for easy
access.
VOLTAGE REGULATORS
SHAFT & KEYS
AS440 AVR - STANDARD
With this self-excited system the main stator provides All generator rotors are dynamically balanced to better
power via the Automatic Voltage Regulator (AVR) to the than BS6861:Part 1 Grade 2.5 for minimum vibration in
exciter stator. The high efficiency semi-conductors of the operation. Two bearing generators are balanced with a
AVR ensure positive build-up from initial low levels of half key.
residual voltage.
The exciter rotor output is fed to the main rotor through a INSULATION/IMPREGNATION
three-phase full-wave bridge rectifier. The rectifier is
protected by a surge suppressor against surges caused, APPROVED DOCUMENT The insulation system is class 'H'.
for example, by short circuit or out-of-phase paralleling. All wound components are impregnated with materials
The AS440 will support a range of electronic accessories, and processes designed specifically to provide the high
including a 'droop' Current Transformer (CT) to permit build required for static windings and the high
parallel operation with other ac generators. mechanical strength required for rotating components.

MX341 AVR QUALITY ASSURANCE


This sophisticated AVR is incorporated into the Stamford
Permanent Magnet Generator (PMG) control system. Generators are manufactured using production
The PMG provides power via the AVR to the main exciter, procedures having a quality assurance level to
giving a source of constant excitation power independent BS EN ISO 9001.
of generator output. The main exciter output is then fed to
the main rotor, through a full wave bridge, protected by a The stated voltage regulation may not be maintained in
surge suppressor. The AVR has in-built protection against the presence of certain radio transmitted signals. Any
sustained over-excitation, caused by internal or external change in performance will fall within the limits of
faults. This de-excites the machine after a minimum of 5 Criteria 'B' of EN 61000-6-2:2001. At no time will the
seconds. steady-state voltage regulation exceed 2%.
An engine relief load acceptance feature can enable full
load to be applied to the generator in a single step. DE RATES
If three-phase sensing is required with the PMG system
the MX321 AVR must be used. All values tabulated on page 6 are subject to the
We recommend three-phase sensing for applications with following reductions
greatly unbalanced or highly non-linear loads.
5% when air inlet filters are fitted.
MX321 AVR 3% for every 500 metres by which the operating altitude
exceeds 1000 metres above mean sea level.
The most sophisticated of all our AVRs combines all the 3% for every 5 C by which the operational ambient
features of the MX341 with, additionally, three-phase rms temperature exceeds 40 C.
sensing, for improved regulation and performance. Note: Requirement for operating in an ambient
Over voltage protection is built-in and short circuit current exceeding 60 C must be referred to the factory.
level adjustments is an optional facility.

WINDINGS & ELECTRICAL PERFORMANCE


NB Continuous development of our products entitles us
All generator stators are wound to 2/3 pitch. This to change specification details without notice, therefore
eliminates triplen (3rd, 9th, 15th …) harmonics on the they must not be regarded as binding.
voltage waveform and is found to be the optimum design
for trouble-free supply of non-linear loads. The 2/3 pitch Front cover drawing typical of product range.
design avoids excessive neutral currents sometimes seen
with higher winding pitches, when in parallel with the
mains. A fully connected damper winding reduces
oscillations during paralleling. This winding, with the 2/3
pitch and carefully selected pole and tooth designs,
ensures very low waveform distortion.

2
HCI434F/444F
WINDING 13
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.

A.V.R. MX341 MX321

VOLTAGE REGULATION ± 1% ± 0.5 % With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 6)

CONTROL SYSTEM SELF EXCITED


A.V.R. AS440
VOLTAGE REGULATION ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT WILL NOT SUSTAIN A SHORT CIRCUIT

INSULATION SYSTEM CLASS H

PROTECTION IP23

RATED POWER FACTOR 0.8

STATOR WINDING DOUBLE LAYER LAP

WINDING PITCH TWO THIRDS

WINDING LEADS 6

MAIN STATOR RESISTANCE


APPROVED DOCUMENT
0.006 Ohms PER PHASE AT 22°C STAR CONNECTED

MAIN ROTOR RESISTANCE 1.37 Ohms at 22°C

EXCITER STATOR RESISTANCE 18 Ohms at 22°C

EXCITER ROTOR RESISTANCE 0.068 Ohms PER PHASE AT 22°C

R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%

MAXIMUM OVERSPEED 2250 Rev/Min

BEARING DRIVE END BALL. 6317 (ISO)

BEARING NON-DRIVE END BALL. 6314 (ISO)

1 BEARING 2 BEARING

WEIGHT COMP. GENERATOR 1160 kg 1160 kg

WEIGHT WOUND STATOR 535 kg 535 kg

WEIGHT WOUND ROTOR 463 kg 440 kg


2
WR² INERTIA 5.4292 kgm 5.2304 kgm2
SHIPPING WEIGHTS in a crate 1230 kg 1230 kg
PACKING CRATE SIZE 155 x 87 x 107(cm) 155 x 87 x 107(cm)

TELEPHONE INTERFERENCE THF<2% TIF<50

COOLING AIR 0.99 m³/sec 2100 cfm

VOLTAGE STAR 380 400 416

VOLTAGE DELTA 220 230 240


kVA BASE RATING FOR
500 500 500
REACTANCE VALUES
Xd DIR. AXIS SYNCHRONOUS 2.86 2.60 2.40

X'd DIR. AXIS TRANSIENT 0.18 0.16 0.15

X''d DIR. AXIS SUBTRANSIENT 0.13 0.11 0.09

Xq QUAD. AXIS REACTANCE 2.53 2.28 2.11

X''q QUAD. AXIS SUBTRANSIENT 0.38 0.34 0.32

XL LEAKAGE REACTANCE 0.06 0.06 0.05

X2 NEGATIVE SEQUENCE 0.25 0.23 0.21

X0 ZERO SEQUENCE 0.08 0.08 0.07

REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.08s
T''d SUB-TRANSTIME CONST. 0.019s
T'do O.C. FIELD TIME CONST. 1.7s
Ta ARMATURE TIME CONST. 0.018s
SHORT CIRCUIT RATIO 1/Xd

3
HCI434F/444F
Winding 13

THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

4
HCI434F/444F
Winding 13
SX Locked Rotor Motor Starting Curves
380V 400V 416V
30

25
.

20
PER CENT TRANSIENT VOLTAGE DIP

15

10
APPROVED DOCUMENT

0
0 200 400 600 800 1000 1200 1400
LOCKED ROTOR kVA

MX

380V 400V 416V


30

25
.

20
PER CENT TRANSIENT VOLTAGE DIP

15

10

0
0 200 400 600 800 1000 1200 1400 1600 1800
LOCKED ROTOR kVA

5
HCI434F
Winding 13

Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed


Based on star (wye) connection.
100000

SYMMETRICAL

ASYMMETRICAL

10000
CURRENT (Amps)

1000

APPROVED DOCUMENT
100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 2400 Amps

Note
N t
The following multiplication factor should be used to convert the values from curve for the
various types of short circuit :

3-phase 2-phase L-L 1-phase L-N


Instantaneous x 1.00 x 0.87 x 1.30
Minimum x 1.00 x 1.80 x 3.20
Sustained x 1.00 x 1.50 x 2.50
Max. sustained duration 10 sec. 5 sec. 2 sec.
All other times are unchanged

6
HC434F/444F
Winding 13 / 0.8 Power Factor

RATINGS

Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Star (V) 380 400 416 380 400 416 380 400 416 380 400 416
60Hz Delta (V) 220 230 240 220 230 240 220 230 240 220 230 240
kVA 465 465 465 500 500 500 535 535 535 550 550 550
kW 372 372 372 400 400 400 428 428 428 440 440 440
Efficiency (%) 93.5 93.7 93.9 93.2 93.5 93.6 92.9 93.2 93.3 92.7 93.0 93.2
kW Input 398 397 396 429 428 427 461 459 459 475 473 472

APPROVED DOCUMENT

DIMENSIONS

7
APPROVED DOCUMENT

Head Office Address:


Barnack Road, Stamford
Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100

www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

HCI4F-13-TD-EN-SG-A