OMICRON PTL ALSTOM MiCOM P642 PTT User Manual

OMICRON PTL

ALSTOM MiCOM P642 PTT

User Manual

V1.000

© OMICRON electronics GmbH 1/6


OMICRON PTL ALSTOM MiCOM P642 PTT User Manual

Content
1. General ...................................................................................................................................................3
2. Software and Hardware Requirements ...............................................................................................3
3. Hardware ................................................................................................................................................4
4. Functional Range...................................................................................................................................5
5. XRIO Converter ......................................................................................................................................5
5.1 Additional Information ...........................................................................................................................6

© OMICRON electronics GmbH 2/6


OMICRON PTL ALSTOM MiCOM P642 PTT User Manual

1. General
This user manual describes details of testing MiCOM P642 relay with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.

The template has been tested with the following relay:


Manufacturer: ALSTOM
Model: MiCOM P642
Software Version: 06

2. Software and Hardware Requirements


To use this template, you must have a valid test license for the OMICRON Test Universe 3.00 software or
higher versions and the following test modules:

 Control Center
 Diff Configuration
 Diff Trip Time Characteristic
 Diff Operating Characteristic
 Diff Harmonic Restraint
 Overcurrent
 Ramping
 State Sequencer

A CMC test set with six current outputs is required. A CMA 156 current amplifier may be additionally
required for testing with higher currents e.g. relays with 5A current measuring inputs.

© OMICRON electronics GmbH 3/6


OMICRON PTL ALSTOM MiCOM P642 PTT User Manual

3. Hardware
There are multiple possibilities of wiring a MiCOM P642 relay to a CMC test set. The advised connections
are shown in Figure 1. These connections are the default settings in the Hardware Configuration of the
PTT.

Figure 1: Connection diagram for testing MiCOM P642

Hardware Configuration for Earth Fault Protection, EF Input is set to “Measured”


For testing a Earth Fault protection with a residual current measured by a separate current transformer
(TN1, TN2), please change the connections according to the advised connections in Figure 2 for Earth
Fault protection side 1 and Figure 3 for Earth Fault protection side 2.

Figure 2: Connection diagram for testing Earth Fault protection side 1 (EF Input “Measured”, TN1)

© OMICRON electronics GmbH 4/6


OMICRON PTL ALSTOM MiCOM P642 PTT User Manual

Figure 3: Connection diagram for testing Earth Fault protection side 2 (EF Input “Measured”, TN2)

4. Functional Range
Supported functions:
 Differential Protection (87)
 Phase Overcurrent Protection (50, 51)
 Earth Fault Overcurrent Protection (50N, 51N)

Not supported functions:


 Directional Time Overcurrent Protection
 REF Protection
 Negative Sequence Overcurrent Protection
 Thermal Overload Protection
 Through Fault Protection
 Overfluxing Protection
 Volt Protection
 Frequency Protection
 RTD Protection
 CB Fail Protection
 VT/CT Supervision
 CLIO Protection

5. XRIO Converter
The Test Object already contains the ALSTOM MiCOM P642 XRIO Converter, which includes setting
parameters of the modelled protection relay. The setting parameters are built as an image of the MiCOM
S1 Agile V1.1.1 software.

The XRIO Import Filter can be used for importing settings into the Relay Parameter Section.

Note: The MiCOM P642 PTT works with settings in secondary values. Please ensure that the parameter
Setting Values (09.2E) is set to Secondary before exporting to XRIO from the MiCOM S1 Agile SW.

© OMICRON electronics GmbH 5/6


OMICRON PTL ALSTOM MiCOM P642 PTT User Manual

5.1 Additional Information


The Additional Information block contains additional data for testing the ALSTOM MiCOM P642 relay
functionality. The block is divided into the sections General Information, Relay Information, Circuit
Breaker Information, Test Tolerance.

Note: Please check and adjust the parameters in the Additional Information block before testing!

The General block includes detailed information needed for the test report like manufacturer, device type,
substation name etc. This section includes parameters which have to be changed by the user according
to the customer relay type and substation.

The Relay Information block contains relay specific parameters. It includes all tolerances which can be
found in the ALSTOM MiCOM P642 relay manual. Typically, the parameters in the specific blocks don't
have to be changed, as the parameters are already set to the values given in the user manual of the relay.

The Circuit Breaker Information blocks have been added for circuit breaker information. This section
includes parameters which have to be changed by the user according to the customer’s circuit breaker
data.

The Test Tolerance block includes the information of the global test tolerance.

© OMICRON electronics GmbH 6/6