0% found this document useful (0 votes)
491 views2 pages

EM341 5D - Rev00 Low Voltage - EN

The document summarizes the specifications and features of the SmartG-02 EM341-5D three phase electricity meter. The meter is designed for residential, commercial, and industrial low voltage applications. It can measure active and reactive energy consumption in 220 VAC, 50 Hz, 3-phase 4-wire networks of 5-100 amperes. The meter complies with various IEC and EN standards and has configurable communication interfaces, energy profiling capabilities, and tamper detection features.

Uploaded by

Amr Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
491 views2 pages

EM341 5D - Rev00 Low Voltage - EN

The document summarizes the specifications and features of the SmartG-02 EM341-5D three phase electricity meter. The meter is designed for residential, commercial, and industrial low voltage applications. It can measure active and reactive energy consumption in 220 VAC, 50 Hz, 3-phase 4-wire networks of 5-100 amperes. The meter complies with various IEC and EN standards and has configurable communication interfaces, energy profiling capabilities, and tamper detection features.

Uploaded by

Amr Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SMARTG-02 DIRECT

THREE PHASE METER


EM341-5D
Residential, Commercial, and Industrial
Applications (Low Voltage)

INTRODUCTION
The SmartG-02 electricity meter series are modern, electronic, fully programmable
devices, designed for application in AMI systems for monitoring and control of
electricity consumption.
The SmartG-02 electricity meter series meet remote data transmission
requirements and enable readouts of various measurands. The meters are
compliant with IEC and DLMS/COSEM standards and have been designed to
serve billing purposes.
EM341-5D, is a four wire, Prepaid/Postpaid compact electronic meter (direct
connection meter), with accuracy class 0.5, capable of measuring Active & Reactive
Energy and is type approved according to IEC & EN standards. This makes it
perfectly suitable for Residential, Commercial, and Industrial Applications (Low
Voltage).
The direct connection meter is used to measure energy consumption in 220
VAC, 50 Hz, and 5-100 Ampere, three-phase four wire power net. It contains an
independent measuring element allowing consumed energy to be measured.
There is a LED mounted on the front panel of the meter, pulsing at a rate of 1000
pulses per KWh or KVAr for energy registration.
The modular nature of the meter means that its communications interface
supports a broad range of field-upgradable communications options including
GPRS, PLC, and RF among others.

STANDARDS
• IEC 62052-11 • IEC 62056-42
• IEC 62053-23:2003 • IEC 62056-46
• EN 50470 • IEC 62056-53
• IEC 695-2-1 • IEC 62056-61
• IEC62055 (for contactor) • IEC 60068

www.elsewedyemg.com
[email protected]
METER SPECIFICATIONS METER FEATURES
Electrical Characteristics Feature Description
Nominal Voltage 3X220/380 V Display • Fully electronic (LCD) with backlight

Voltage Variation (Min) -40% Vn • The meter is capable of storing two profiles. One
for energy and one for other parameters
Voltage Variation (Max) 30% Vn
Load Profile • Each profile has an integration period of 1 to 60
Nominal Current (Ibase) 5A minutes

Maximum Current (Imax) 100 A • The profiling period extends for at least 45 days

Nominal Frequency 50 Hz • The EM341-5-SmartG-02 records a considerable


amount of data for extended periods of time
Frequency Variations ±5%
Events • In addition, the EM341-5-SmartG-02 stores up to
0.5 Active 400 events
Accuracy Class
2 Reactive • Events are logged with a date/time stamp
Starting Current 0.4 % Ib
• The EM341-5-SmartG-02 has the ability to detect
Wiring 3 PH, 4 wires Network the following types of tamper attempts:

Number of elements 4 3  Meter Cover Open


3  Meter Cover Open
Power Consumption ≤ 2W 3  Terminal Cover Open
3  Module Cover Open
KWh Tamper Proofing 3  Reverse Connection
Measurements
MD(A)(KW) 3  Earth or Current Bypass Connection
3  Overload
Back-up Battery Type Lithium Battery 3  Over Voltage
3  Under Voltage
Back-up Battery Lifetime 10 Years 3  Phase Sequence
3  Missing Potential
Memory
Type Flash memory • The meter supports two alarm methods
3  LED Indicator
Retention Period More than 20 Years
3  Audible Alarm
Alarms
3  Messages on LCD
Environmental Conditions
• The meter can be configured to give any
IP Rating IP54 combination of alarms as required

Temperature Range -5°C to +70°C


• The relay control modes include:
Storage Temperature -25°C to +80°C 3  Remote Disconnect
3  Local Disconnect
Humidity Range <90%
• The relay is configurable to be triggered in the
Altitude 0-3600M event of:

Service Life 20 Years 3  Meter cover open


3  Meter Terminal Cover Open
Relay Operation
Communication 3  Module Cover Open
3  Energy Reverses
Standard Optical Port (IEC 3  Earth or Current Bypass Connection
62056-21) 3  Meter Current Overload
Optical Interface
Complies with DLMS/COSEM 3  Meter Over Voltage and Under Voltage
HDLC mode-E protocol 3  At Low Battery
RS-485 3  Phase Sequence
Serial Communication Port Complies with DLMS/COSEM 3  Missing Potential
direct HDLC protocol 3  Low Credit

Supported through the use


• With each power-up or firmware update, the
AMI/AMM Module of a GSM/GPRS Modem, PLC
meter shall diagnose:
Modem or RF Modem
Auto-diagnostics 3  Meter and memory integrity
Optical Port: 9600 bit/s
Data Transmission Rate RS-485: 9600 bit/s GPRS: 3  Display, alarms & battery status
56–114 Kbit/s 3  External communication module status

D
MECHANICAL SPECIFICATIONS
4 Dimensions: (L x W x D) =
W
277.3 mm x 177.4 mm x 88.5 mm L
4 Weight: Approximately 1.8Kg
4 Meter Housing: Flame Retardant Polycarbonate

You might also like