Additive Wire Maintenance
Additive Wire Maintenance
It is the requirements and precautions that OCs workers need to comply when carrying out
additive wire.
PW
additive wire parallel line
03
overhead
lightning wire 02 04
positive feeder
additive
power line
01 wire of OCS 05
reinforcement
line
08 06
overhead return line
ground wire 07
protection line
tools and materials
Before climbing the pole, the workers working at height should check the signs and marks of
the poles and towers.
Before climbing the prop, check the status of the prop, observe whether there are other
equipment on the prop, select the climbing direction and conditions, and keep the handle
firmly and the foot firmly when climbing
Before climbing the equipment, the workers working at height should carefully check the
condition of the equipment body and connecting, and take the method of external force
impact inspection;
prevention and control measures
When working at height, workers must fasten the safety belt at a safe and reliable place.
Before moving, the ladder car and operation vehicle shall follow the command of the
personnel on the workbench, and the personnel and machines and tools can be moved only
when they are in a safe position.
Small tools and materials used in high-altitude operation shall be placed in tool and material
bags, and special tools shall be used to transfer tools, parts and materials during operation;
There is no rust, damage, crack and deformation in the appearance of the stressed tools, no
twist, broken strand and loose strand in the wire rope, the transmission part of the hand hoist
and the lifting chain are well lubricated, and the idling condition is normal.
preparation before maintenance
Check whether
Check the clues Check whether it
the material and
for loose strand, meets the
cross-sectional Check whether Check whether
broken strand, requirements
area meet the the tension and the joint and
burn and damage, when crossing or
maximum sag meet the damage meet
and whether the approaching
current and requirements the requirements
installation is railway, highway
strength safety
firm and power line
factor
inspection and
measurement
Standard value:
security risks
inspection and adjustment methods:
In any case, the distance between the additive wire and the ground, the
distance between each wire shall not be less than the values in the table below.
Power line,
Protection line,
Num Relevant information positive feeder
return line(mm)
(mm)
Residential area and station
7000 6000
platform
Height of conductor from ground at Non residential area 6000 5000
1
maximum sag Hillsides, cliffs and rocks
inaccessible to vehicles and 5000 4000
agricultural machinery
When there is no wind 1000 500
The distance between conductor and cliff,
2 Calculation of maximum wind 300 75
retaining wall
deviation time
Crossing non electrified track
7500 7500
(opposite track surface)
3 When the conductor crosses the railway
Crossing electrified tracks of
3000 2000
different circuits
Distance between suspension points of
4 two conductors in different phases or Two line horizontal arrangement 2400 ——
different power supply sections
Minimum vertical distance at
5 Minimum distance from building 4000 2500
maximum sag
Check and adjust the insulation distance of each part of the additive
wire
Maintenance standard
security risk
3. Improper use of stressed tools causes personal If the insulation distance of each part of the additive wire does not meet the
requirements, the fixed points shall be increased or adjusted, the insulation
injury. protection shall be added or the shoulder frame shall be replaced
Inspection and adjustment of additive wire joint and damage
When crossing railways, first-class and second-class highways, and important navigable rivers,
it is required that additive wires shall not have joints.
There shall be no more than one joint of a conductor in a span. The total number of joints,
broken strands and reinforced sections of additive wires in a strain section shall not exceed the
following provisions, and the distance between joints and suspension points shall be greater than
500mm:
(1) When the length of strain section (2)When the length of strain
is 800m or less section exceeds 800 meters
standard value :0 standard value :0
standard state :0 standard state :0
warning value :2 warning value :4
limit value:4 limit value:8
Inspection and adjustment of additive wire joint and damage
When the aluminum wire of aluminum strand or steel cored aluminum strand is broken or damaged to 3
strands or less, it can be bound and reinforced with pre twisted wire connecting strip or aluminum binding wire.
When the broken strand and damage are more than 3 strands and less than 7 strands, the same material
conductor shall be used for reinforcement;
When the broken strand or damage is more than 7 strands, the joint should be made again or replaced.
When the steel core of ACSR is broken or damaged, the joint shall be made again or replaced.
Inspection and adjustment of additive wire joint and damage
security risks
1. Induced electric injury caused by improper equipping measures for workers working at
height;
2. High altitude personnel accidentally touch live equipment due to insufficient electrical
distance, causing electric shock injury;
3. Personal injury caused by improper use of stressed tools;
4. The high-altitude workers violate the safety regulations when using the working vehicle,
causing high falling injury; High falling injury caused by improper use of safety belt.
Inspection and adjustment of additive wire joint and damage
1. The broken strand of aluminum strand or steel cored ①Select the connecting pipe and die according to the
aluminum strand is 7% or less of the total number of strands: wire specification, and wipe the inside of the connecting
pipe and gasket clean
grind the broken strand, bind it with binding wire of the same ②Cut the wire
material, and the binding length exceeds the defect part by 30-
50mm ③Put the connected wire into the connecting pipe to
make the wire end expose 20-30mm outside the pipe
④Crimping
2. When the broken strand of aluminum wire of aluminum
strand or steel cored aluminum strand is 7% - 25% of the total
strand number: the steel core of steel cored aluminum strand is broken,
cut and reconnected
parallel groove clamp and auxiliary wire of the same material
shall be used for reinforcement the additive wire has back buckle and other permanent
deformation, cut and reconnected
Inspection and adjustment of additive wire shoulder
security risks
Maintenance standard inspection:
Methods of investigation:
security risks