Waterfall Pumps Quality Management Policy

The document provides an index of vendor documents for a fire pump system including pump data sheets, drawings, certificates and more. It lists diesel and electric driven fire pumps as well as a jockey pump and associated accessories. The index identifies document titles, references and remarks for each item to help locate specific information.

Uploaded by

Mostafa Sharaf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
237 views152 pages

Waterfall Pumps Quality Management Policy

The document provides an index of vendor documents for a fire pump system including pump data sheets, drawings, certificates and more. It lists diesel and electric driven fire pumps as well as a jockey pump and associated accessories. The index identifies document titles, references and remarks for each item to help locate specific information.

Uploaded by

Mostafa Sharaf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 152

10/01/2023

QUALITY POLICY

As part of its ongoing commitment to excellence Waterfall Pumps Manufacturing is committed to supply its

products that meet or exceed the requirements of our customers. By consistently providing product/services that
meet or exceed consumer expectation and international standards to strong business performance.

A key way to achieve this is by operating a Quality Management System (QMS) in accordance with the
requirements of ISO 9001: 2015.

Top management is committed to:

Satisfying applicable requirements by ensuring that All Interested Parties Requirements and All
applicable statutory and regulatory requirements are determined, understood and consistently met.
Continual improvement of the QMS by ensuring the risks and opportunities that can affect conformity of
products and services and the ability to enhance customer satisfaction are determined and addressed
and the focus on enhancing customer satisfaction is maintained.

Top management shall:

Take accountability for the effectiveness of the QMS.


Ensure the quality policy and quality objectives are established for the QMS and are compatible with the
context and strategic direction of the Company. Quality objectives have been set and are maintained as
part of the QMS internal auditing, monitoring and management review processes, in order to enhance
customer satisfaction.
Promote the use of a process approach and risk-based thinking.
Ensure that the resources needed for the QMS are available; including training, support and
encouragement.
Communicate the importance of effective quality management and of conforming to the QMS
requirements.
Ensuring that the QMS achieves its intended results.
Engage, direct and support persons to contribute to the effectiveness of the QMS.
Promote improvement.
Support other relevant management roles to demonstrate their leadership as it applies to their areas of
responsibility.
Establish partnerships with suppliers and interested parties to provide an improved service.

This policy will be communicated to all employees and organizations working for or on our behalf. Employees and
other organizations are expected to co-operate and assist in the implementation of this policy, whilst ensuring that
their own work, so far as is reasonably practicable, is carried out without risk to themselves, others, or the
environment. This policy will be reviewed annually by top management and where deemed necessary will be
amended and re-issued.

This policy is available to relevant interested parties, upon reasonable request.

Waterfall Management

Rev. Date: September 23, 2018 Rev. 01


10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

GENERAL DOCUMENTS

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Project: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA Ref.No:WFVT618
Consultant: Rev. No:
Contractor:

S/N Vendor Document Title Remarks


GENERAL DOCUMENTS
1 Vendor Document Index
2 Equipment Description
3 Sub Vendors List
DIESEL DRIVEN PUMP
4 Pump Data Sheet & Curve
5 G & A Drawing
6 Cross-Sectional Drawing
VENDOR DOCUMENT INDEX

7 Diesel Engine Data


8 Diesel Controller Data
ELECTRIC DRIVEN PUMP
9 Pump Data Sheet & Curve
10 G & A Drawing
11 Cross-Sectional Drawing
12 Electric Motor Data
13 Electric Controller Data
JOCKEY PUMP
14 Pump Data
15 Jockey Controller Data
16 ACCESSORIES

Air Release Valve


Casing Relief Valve
Pressure Gauges
Flow Meter
Fuel Tank Drawing

17 CERTIFICATES
UL/FM Certificates
ISO Certificate

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
DIESEL DRIVEN FIRE PUMP
FLOW RATE: 1000 GPM Ref. No: WFVT618
PRESSURE: 10 Rev. No:
PUMP:
Type : Vertical Turbine
Model : WF-12F2 VT
Speed : 3000 RPM
: 2
Listing : UL Listed
Construction : Ductile Iron Casing, Stainless Steel Impeller, Stainless Steel Shaft
Accessories : Pressure Gauges,
Diesel Fuel Tank (180 G), Batteries and Cables,
Air Release Valve, Pressure Relief Valve

DRIVER:
Type : Diesel Engine
Manufacturer : Kirloskar
Model : KFP4R-UF16R1
Speed : 3000 RPM
Rating : 152 HP
Listing : UL Listed & FM Approved

Type :
Manufacturer : SMI
Model : H125
ati : 1:1
:

CONTROLLER:
Type :
Manufacturer :
Supply : 12V-220
Listing : UL Listed & FM Approved
Enclosure :
10/01/2023
ELECTRIC DRIVEN FIRE PUMP
FLOW RATE: 1000 GPM Ref. No: WFVT618
PRESSURE: 10 Rev. No:

PUMP:
TYPE : Vertical Turbine
Model : WF-12S4 VT
Speed : 1780 RPM
: 5
Listing : UL Listed
Construction : Ductile Iron Casing, Stainless Steel Impeller, Stainless Steel Shaft
Accessories : Pressure Gauges, Casing Relief Valve
Flow Meter, Air Release Valve

DRIVER:
Type : Vertical Hollow Shaft Electric Motor
Brand : Marathon
Speed : 1780 RPM
Frame Size : 405TP
Rating : 125 HP
Listing : UL Listed
Supply : 380-415V/3PH/60Hz
Enclosure : ODP

CONTROLLER:
Type : GPY-Controller
Manufacturer : Tornatech
Rating : 125 HP
Listing : UL Listed & FM Approved
Supply : 380-415V/3PH/60Hz
Enclosure : NEMA-2

10/01/2023
ELECTRIC DRIVEN JOCKEY PUMP
FLOW RATE: 100 GPM Ref. No: WFVT618
PRESSURE: 11 Rev. No:

PUMP:
Type :
Model : RV15-9

Speed : 3500 RPM

Construction :

Accessories :

DRIVER:
Type :

Speed : 3500 RPM

Rating : 20 HP

Supply : 380-415V/3PH/60Hz

Enclosure :

CONTROLLER:
Type : JP3 Controller

Manufacturer :
Listing : UL Listed

Supply : 380-415V/3PH/60Hz

Enclosure : NEMA-2

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
SUB VENDORS LIST

: Pumps (Waterfall, U.A.E)

: Diesel Engine (<ŝƌůŽƐŬĂƌ, /ŶĚŝĂ)

͗ůĞĐƚƌŝĐDŽƚŽƌ;DĂƌĂƚŚŽŶ͕h͘^͘Ϳ

: Controller (Tornatech, h͘͘)

: 'ĞĂƌƌŝǀĞ (ŵĂƌŝůůŽ, h͘^͘)

͗ŝƌZĞůĞĂƐĞsĂůǀĞ;ůĂͲsĂů͕^ǁŝƚnjĞƌůĂŶĚͿ

10/01/2023
SUB VENDORS LIST

: Casing Relief Valve (Aquatrol,U.S.A)

: Gauges (Wika, U.S.A)

: Flow Meter (Gerand, U.S.A)

: Pressure Relief Valve (Cla-Val, Switzerland)

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA Ref. No: WFVT618
Model: WF-12F2 VT Rev. No:
PUMP DATA
Service Diesel Driven Pump
Series Vertical Turbine
Size 12 Inch Bowl x 8 Discharge Head
Rated Flow 1000 GPM
Rated Pressure 145 PSI
Speed 3000 RPM
Rotation Clockwise
Liquid Type Water
Discharge Size 8
8
Impeller Diameter 221 mm
Base Type Steel
Weight N/A
Efficiency 66%
HP Maximum 147 HP

MATERIALS OF CONSTRUCTION
Casing Ductile Iron
Impeller Stainless steel
Shaft Stainless steel
Shaft sleeve Stainless steel
Wear ring Bronze
DRIVER DATA
Manufacturer Kirloskar
HP Rating 152 HP
Speed 3000 RPM
Weight 690 KG
Starting Two(2)12V-DC
Model KFP4R-UF16R1

10/01/2023
Max. 140% at
Shut-off

Rated

150% Rated

Min. 65% at
150% Rated

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
A B C D E F G H
ENGINE GEAR DRIVE NO. OF STAGES A B C D E F G H
80A/100A/125A 2 1004 1000 760 908.1 444.5 292.1 2258.5 1855.1
80A/100A/125A 3 1248 1000 760 908.1 444.5 292.1 2258.5 1855.1
8 KFP4R-UF16R1/R2 150A 3 1248 1000 760 908.1 444.5 292.1 2309.3 1855.1 8
H110/H125 2 1004 1000 760 904.9 444.5 288.9 2277.5 1851.9
2 1004 1100 760 908.1 435 292.1 2515.8 1957.1
125A
3 1248 1100 760 908.1 435 292.1 2515.8 1957.1
2 1004 1100 760 908.1 435 292.1 2566.6 1957.1
KFP6R-UF26R1/R2 150A
3 1248 1100 760 908.1 435 292.1 2566.6 1957.1
7 3 1248 1100 760 965.3 435 349.3 2617.4 2014.3 7
200A
4 1492 1100 760 965.3 435 349.3 2617.4 2014.3
SIDE VIEW FRONT VIEW
G+10
-10

475
-A-

6 6

TOP VIEW
H+15

-A-
-15

4-Ø24

F
Ø200MM DISCHARGE
E+2.5
-2.5
Ø340MM O.D. FLANGE 70
5 12-Ø22 BOLTS
5
PN 16 STANDARD 100
70
D+5
-5

575+2.5
-2.5

Slab Thickness
SOLE PLATE

750+2.5
-2.5
500
C+5
(16mm THICK)

-5
190.5

GROUTING
F.F.L

330
(25mm THICK)

4 4
500
Ø400 750+2.5
Ø400 -2.5

B+5
-5

X
3 Notes: 3
1. Column pipe(s) length, X vary as per the tank depth and
slab thickness.

Tank Depth
2. Minimum Submergence requirement of the pump model
is 810mm above the strainer.
3. All dimensions are in mm unless otherwise specified.

A+10
-10 WATERFALL
2 2
PUMPS
270

MANUFACTURING
DRAWING TITLE:
Ø246
G&A WF-12F2 VT PUMP WITH
305

B.O.T DIESEL ENGINE KIRLOSKAR


PUMP MODEL: WF-12F2 VT SCALE:

1 For Preliminary Use. DRAWING No: M12F2VTGA-D-KRL NTS 1


Not For Construction Unless Engineering Drawings R3 01/06/2021 SOLE PLATE ADDED AND MODIFICATION DRN BY: CHKD BY: APPD BY: DRN DATE: PAGE SIZE:
10/01/2023A4 REVISION No:

Represent General Construction. REV No DATE REVISIONS DESCRIPTION


A.D L.S L.R 01/06/2021 PAGE: R3
1 of 1
A B C D E F G H
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
----

A B C D E F G H

01 NO PART NAME MATERIAL / SPECIFICATION

01 LINE SHAFT STAINLESS STEEL ( AISI 416 / AISI 420 )


02
8 02 DISCHARGE HEAD CAST IRON / DUCTILE IRON ( HT 250/QT 450 ) 8

03 03 GLAND COVER SS / BRONZE ( AISI 304 / - )

04 STUFFING BOX DUCTILE IRON ( QT 450 )


04
05 STUFFING BOX BEARING PTFE / NBR

06 INTERCONNECTING PIPE CARBON STEEL / SS ( ASTM A53 Grade B / AISI 304 )


7 05 7
07 SPIDER CAST IRON ( HT 250 )

06 08 SPIDER BEARING PTFE / NBR

09 COUPLING STAINLESS STEEL ( AISI 416 / AISI 420 )


07
10 COLUMN PIPE CARBON STEEL / SS ( ASTM A53 Grade B / AISI 304 )

6 11 CASING BOWL DUCTILE IRON ( QT 450 ) 6

08 12 IMPELLER BRONZE / SS ( C90700 / AISI 304 / AISI 316 )

13 BOWL WEAR RING BRONZE


09
14 CASING BOWL BEARING PTFE / NBR

15 IMPELLER COLLET SLEEVE BRONZE / SS ( C90700 / AISI 304 / AISI 316 )


5 10 5
16 IMPELLER SHAFT STAINLESS STEEL ( AISI 416 / AISI 420 )
11 17 SUCTION BELL BEARING PTFE / NBR

18 SUCTION BELL DUCTILE IRON ( QT 450 )


12
19 SUCTION STRAINER STAINLESS STEEL ( AISI 304 / AISI 316 )

4 4
13

14

15
3 3
16

17

WATERFALL
2 18 2
PUMPS
19
MANUFACTURING
DRAWING TITLE:

SECTION VIEW FOR WF-12F2 VT


PUMP MODEL: WF-12F2 VT SCALE:

1 DRN No: M12F2VT-CS NTS 1


R0 01/27/2020 FOR INITIAL SUBMISSION DRN BY: CHKD BY: APPD BY: DRN10/01/2023
DATE: PAGE SIZE: REVISION No:
A4
A.A M.I M.C 01/27/2020 PAGE: R0
REV No DATE REVISIONS DESCRIPTION
1 of 1
A B C D E F G H
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Project: ‫ﻣدارس اﻻﯾواء‬
Customer: ADVANCED PUMPS CO
-
Engineer:
WATERFALL PUMPS MANUFACTURING
Pump Manufacturer:

Technical Data
Submittal Document
Model GPD
Diesel Engine Driven Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are


for controllers covered under our standard
RႇHULQJ $FWXDO $6 %8,/7 GUDZLQJV PD\
GLႇHUIURPZKDWLVVKRZQLQWKLVSDFNDJH
10/01/2023
June 2022
Technical Data
Model GPD Diesel Fire Pump Controller

Built to NFPA 20 (latest edition)


Underwriters Laboratory (UL) UL218 - Fire Pump Controllers
Standard,
/LVWLQJV FM Global Class 1321/1323
$SSURYDOVDQG New York City Accepted for use in the City of New York by the Department of Buildings
&HUWL¿FDWLRQV Optional
CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
Ƒ
✔ Standard: NEMA 2

Optional
Ƒ NEMA 12 Ƒ NEMA 4X-304 sst painted Ƒ IP54
Ƒ NEMA 3 Ƒ 1(0$;VVWEUXVKHG¿QLVK Ƒ IP55
Enclosure
Ƒ NEMA 3R Ƒ NEMA 4X-316 sst painted Ƒ IP65
Ƒ NEMA 4 Ƒ 1(0$;VVWEUXVKHG¿QLVK Ƒ IP66
$FFHVVRULHV 3DLQW6SHFL¿FDWLRQV
• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle ‡ *ORVV\WH[WXUHG¿QLVK

Standard
$PELHQW
Temperature
Ƒ 4°C to 40°C / 39°F to 104°F
Optional
Rating Ƒ✔ 4°C to 55°C / 39°F to 131°F
Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.

AC Ƒ 120V / 1ph / 60hz


Ƒ 208V to 240V / 1ph / 50-60hz

DC Ƒ 12VDC

General Ƒ 24VDC
Grounding system • Negative
• Two independent fully automatic
Battery chargers • 10A continuous charge
• 500mA trickle charge
• Battery 1 & Battery 2 voltage
Electrical Reading • Battery 1 & Battery 2 charging amperage
• Charging mode
• Continuous system pressure display
Pressure Reading
• Cut-in and cut-out pressure setting
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event Recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPD Diesel Fire Pump Controller

• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing connection 1/2” Female NPT
Pressure sensing • Drain connection 3/8”
• Rated and calibrated for 0-500psi working pressure
• Externally mounted with protective cover
$XGLEOH$ODUP 6” alarm bell - 85 dB at 10ft. (3m)
• Engine run • Periodic test
• Main switch AUTO • Cranking Cycle
9LVXDO,QGLFDWLRQV • AC Power available
• Main switch in OFF
• Main switch in HAND • Pump room temperature (ºF or ºC)

Visual only
• Pump room trouble • Loss of continuity 1 & 2 ‡6HUYLFHUHTXLUHG
• Pump on demand • High fuel level • ECM warning
• AC Failure • Fuel tank leak • Weekly test cut-in not reached
• Charger 1 & 2 Failure • PLD low suction pressure • Check weekly test solenoid
• Weak battery 1 & 2 • High raw water temperature • Pressure transducer fault
• Battery 1 & 2 overvoltage • Low pump room temperature • Invalid Cut-In
9LVXDO $XGLEOH
$ODUPV
Visual and Audible
• Engine trouble • Battery 1 & 2 Failure
• Controller trouble • Engine fail to start
• Engine low oil pressure • Low fuel level
• Engine high temperature • ECM fault
• Engine low temperature • ECM SS in Alternate Position
• Engine overspeed • Fuel injection malfunction
• DC Failure

DPDT-8A-250V.AC
• Engine run
• Common controller trouble
• Charger #1 & Charger #2 failure • Pressure transducer fault
• Common engine trouble
• High engine temperature • Battery #1 & battery #2 failure • Overspeed
• Fail to start • DC failure • Fail when running
5HPRWH$ODUP
• Fuel injection malfunction** • Loss of continuity (starter) #1 and/or #2 • Low oil pressure
Contacts
• ECM selector switch in alternate position*** • PLD low suction pressure
‡&RPPRQSXPSURRPWURXEOH ¿HOGUHDVVLJQDEOH
• Low fuel level • Low pump room temperature • AC Failure
• High fuel level • High pump room temperature
• Fuel tank leak
• H-O-A selector switch in OFF or HAND
‡)UHH ¿HOGSURJUDPPDEOH

([FHSWLIRSWLRQ&LVRUGHUHG7RUQDWHFKUHVHUYHVWKHULJKWWRXVHDQ\RIWKHVHIRXUDODUPSRLQWVIRUVSHFLDOVSHFL¿FDSSOLFDWLRQUHTXLUHPHQWV
**Applicable to electronic engines only.
*** Applicable to electronic engines only. Alarms when ECM selector switch on the engine is in alternate mode.

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model GPD Diesel Fire Pump Controller

• Low fuel level


Terminals for
• Remote AUTOMATIC start
Field Connections
• Water reservoir low (re-assignable)
for External
• Fuel tank leak (re-assignable)
Devices
• High fuel level (re-assignable)
• Embedded microcomputer with software PLC logic
ViZiTouch V2 • 7.0” color touch screen (HMI technology)
2SHUDWRU,QWHUIDFH • Upgradable software
• Multi-language
‡+DQG2ႇ$XWR
Selector Switch
• Behind lockable and breakable cover
• Start on pressure drop
$XWRPDWLF6WDUW
• Remote start signal from automatic device
• Crank 1 and Crank 2 start pushbuttons
Manual Start • Run test pushbutton
• 6 consecutive cycle attempts
&UDQN&\FOH • 3 X 15s crank from battery 1 or 2 alternatively
• 15s rest in between each crank attempt
Operation
• Manual with Stop pushbutton
Stopping
• Automatic after expiration of minimum run timer ****
‡0LQLPXPUXQWLPHU RႇGHOD\
)LHOG$GMXVWDEOH 
Timers ‡6HTXHQWLDOVWDUWWLPHU RQGHOD\
Visual Countdown
• Periodic test timer
• Pressure
$FWXDWLRQ
• Non-pressure
9LVXDO,QGLFDWLRQ
• Automatic
Mode
• Non-automatic
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
&DSDELOLW\
• Addresses: See bulletin MOD-GPD

Automatic Start Manual or Remote Start Run Test or Periodic Test


$ODUPDQG High Coolant Alarm only Alarm only Shutdown
shutdown
schedule Low Oil Pressure Alarm only Alarm only Shutdown
Overspeed Shutdown Shutdown Shutdown

Wall Mount Floor Mount


Approx. shipping Approx. shipping
Approx. Shipping Approx. Shipping
Starting Voltage dimensions in inches dimensions in inches
Weight in Lbs (kg) Weight in Lbs (kg)
(mm) (mm)

12V.DC
32" l x 29" w x 16" h 32” l x 29” w x 26” h
85 (39) 115 (52)
(813 x 737 x 407 ) (813 x 737 x 661)
24V.DC

**** Automatic shutdown shall be approved by the AHJ.

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPD Diesel Fire Pump Controller

9L=L7RXFK92SHUDWRU,QWHUIDFH

Home

2 3

9
5 6 7 8

1 - Color touch screen 3 - Screen protector


2 - Onscreen menu 4 - Power LED (3 colors)
• HOME page 5 - CRANK 1 button
• ALARM page 6 - CRANK 2 button
• CONFIGURATION page 7 - STOP button
• HISTORY page 8 - RUN TEST button
• SERVICE page 9 - USB port
• MANUAL page
• LANGUAGES page

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 Manufacturer reserves the right to modify this information without notice 7
Diesel Engine Fire Pump Controller Model:GPD
12Vdc or 24Vdc Negative Ground
Dimensions Built to the latest edition of the NFPA 20 standard

27" [684] 9 5/8" [245]


26" [661] 8 5/8" [220]
23 5/8" [600] Ø3/8" [Ø10] X4 1/2" [12]
7 7/8" [200] 22 1/8" [562]

See Notes
28 7/8" [732] 27 1/2" [700]
29 7/8" [757]
20 1/4" [514]

SV1 PT1

2 7/8" [73]

6 7/8" [174]

- Controller standard without mounting stand.


- Order option D25 if mounting stand required.

20 1/2" [520] 13 1/8" [333]

23 5/8" [600]
Sensing Line Connection - 1/2 " F.NPT
Drain - 3/8 " M.TUBE
23 3/8" [594]

9 1/6" [233] 4 1/2" [115] 7 1/8" [182]

3 1/3" [84] 10 7/8" [275]


Notes: 1 1/4" [31]
13 1/8" [333]
- Standard: NEMA 2
- Standard paint : textured red RAL 3002.
- All dimensions are in inches [millimeters].
- Center of ViZiTouch screen: 20-1/4" [514] from bottom (no feet).
- Bottom conduit entrance through removable gland plate recommended.
- Use watertight conduit and connector only.
- Protect equipment against drilling chips.
- Door swing equal to door width.

Drawing for information only. Projection


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC 2. Removed Seismic logo (optional) 18/05/22
Dpt of Building
Approved
1. Revised logo 18/06/18 GPD-DI700 /E
0. First issue 18/11/16 10/01/2023
CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Wiring schematic Built to the latest edition of the NFPA 20 standard
2
1
NO Black
AB1
NO - +
Controller Trouble C J36 J50 Red
C
(Fail Safe) TB1 AB
NC NC
2
1

NO NO
SV1
VMB1
J37 Brown
C SV
Engine Run / Louver Activation Circuit C J24
TB2 Blue
NC NC
2
1

NO NO
C J38
Main Switch in HAND or OFF C
TB3 +
NC
NC J16 AI5
2
1 -
NO NO I/O
C J39
Engine Trouble C +
TB4
NC
NC J14 AI4
2
1 -
NO

COM
NO

DI5

DI4
Pump Room Alarm C J40
C +
TB5
NC
NC J15 AI3
2 30 32 31
1 -
NO NO
C J42
(Field Programmable) C
TB6 +
NC
NC J17 AI2
-
SS1 H
OFF
A
+ Red
PT1
Low Fuel Level IN1 J18 AI1 White

- Black AUTO
Remote Auto Start J1* IN2

HAND
Water Reservoir Low IN3 J25 53
J44 VIN
54
Fuel Tank Leak IN4

High Fuel Level IN5 J20 UP

J8 DOWN
MP+
J35
MP-

ECM Selector Switch in Alternate Position 301 301


J4 24V in
Fuel Injection Malfunction 302 302 24V out

Electronic Control Module Warning 303 303


B1+
15 B1 BC1

BOOST
16
Electronic Control Module Fault 304 304 B1- B2
J103 J106 17
CF1 Com
PLD Low Suction Pressure 305 305 18
ALARM
NO
High Raw Water Temperature 310 310 NC

Low Raw Water Flow 311 311 BATT. SUPPLY

+ - L N
Low Engine Temperature 312 312 B2+
19 B1 BC2
BOOST

B2-
20 B2
J107 63 11 13 54
Energize to Start Solenoid 1 1 CF2
21 Com
22
ALARM

NO
Engine Run 2 2
NC
Overspeed 3 3
BATT. SUPPLY
Low Oil Pressure 4 4 + - L N

High Engine Temperature 5 5 62


62
Battery 1 6 6 J104 6
6 CB3 83 11 14 54

Battery 2 8 8 63
63
Start Contactor 1 9 9 11
J105 11
Start Contactor 2 10 10

11 83
Ground 11 83
Ground 11 8
11 8
82 CB4
Energize to Stop Solenoid 12 12 DB1 82

Legend
53 54 AB Alarm Bell
BC Battery Charger
CB Circuit Breaker

IS1 CB2 DB Diesel I/O Board

53 F Filter
14
1L L' IS Isolating Switch
L
CB1 J Jumper
120-240 VAC
50-60Hz F1 13
PT
SS
Pressure Transducer
Selector Switch
1N
N 54 SV Solenoid Valve
E N' VMB ViZiTouch Main Board

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
* Remove jumper to use this feature Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
4 Removed Seismic logo (optional) 18/05/22
Approved 3 Water Reservoir Modified 04/04/19 GPD-WS700 /E
2 Revised logo 18/06/18 10/01/2023
CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Layout Built to the latest edition of the NFPA 20 standard

Designation Description
BC1-BC2 Battery Charger #1 and #2
CB1-2 Magnetic Breaker 1 Pole 10 A
CB3-4 Magnetic Breaker 1 Pole 16 A
DB1 I/O Diesel Board
F1 Filter
IS1 Isolating Switch

SS1 Lockable 3 Position Selector Switch


VMB1 ViZiTouch Main Board

BC1

VMB1

BC2
CB3
CB4
CB1
CB2

F1
54

0 - OFF 0 - OFF 0 - OFF 0 - OFF

SS1

IS1
DOWN
UP

CF1

CF2
-

VIN

B1-

B2-
AB

SV

+
AI5

AI4

AI3

AI2

AI1

24V in
24V out

B1+

B2+

62

63

83

82
6

DB1
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC
C

C
2

MP+
IN1

IN2

IN3

IN4

IN5

MP-

10

11

11

12
301

302

303

304

305

310

311

312
NO

NO

NO

NO

NO

NO

9
NC

NC

NC

NC

NC

NC
C

C
1

Front Door Layout Internal Layout

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
2 Removed Seismic logo (optional) 18/05/22
Approved
1 Revised logo 18/06/18 GPD-LY700 /E
0 First issue 21/11/16 10/01/2023
CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Terminal Diagram Built to the latest edition of the NFPA 20 standard
Power Supply Remote Alarm Terminals (DB1)
Terminals Wire Size: Terminals Wire Size:
14 - 6 AWG 250VAC / 8A Max.
3.9 Nm 24 - 12 AWG
0.5 Nm

120-240 VAC L
50-60Hz IS1 Normally closed
2

N Opens to alarm
NO

Normally open C

Closes to alarm
G Controller Trouble NC
J36
(Fail Safe) 1
Normally open NO
TB1
Normally closed Closes to alarm C
Opens to alarm
Engine Connections (DB1) NC

2
Normally open NO
Energize to Start Solenoid Closes to alarm
1 1 Engine Run Normally closed C

Engine Run Opens to alarm NC


J37
2 2 1
Normally open NO
TB2
Overspeed Louver Activation Circuit Normally closed Closes to alarm
3 3 C
Opens to alarm NC
Low Oil Pressure
4 4
2
High Engine Temperature Normally open
5 5 NO
Normally closed Closes to alarm
C
Battery 1 Opens to alarm
6 6 J104 NC
J38
Main Switch in HAND or OFF 1
Battery 2 Normally open NO
TB3
8 8 Closes to alarm
Normally closed C
Start Contactor 1 Opens to alarm
9 9 NC
Engine Terminal Strip

Start Contactor 2
10 10 Normally open
2

NO
Ground Normally closed Closes to alarm C
11 11
Opens to alarm NC
Engine Trouble ** J39
Ground 1
11 11 Normally open NO
TB4
Normally closed Closes to alarm
Energize to Stop Solenoid C
12 12 Opens to alarm NC

2
ECM Selector Switch in Alternate Position Normally open
301 301 NO
Normally closed Closes to alarm
C
Fuel Injection Malfunction Opens to alarm
302 302 NC
J40
Pump Room Alarm ** 1

Electronic Control Module Warning Normally open NO


TB5
303 303
Normally closed Closes to alarm C
Electronic Control Module Fault Opens to alarm NC
304 304

PLD Low Suction Pressure J103 2


305 305 Normally open NO
Normally closed Closes to alarm
High Raw Water Temperature C
310 310 Opens to alarm NC
(Field Programmable) J42
1

311
Low Raw Water Flow
311
Normally open NO
TB6
Normally closed Closes to alarm C
Low Engine Temperature
312 312 Opens to alarm NC

Field Connections (DB1)


Terminals Wire Size:
24 - 12 AWG All wiring between the controller and diesel engine shall be stranded
0.5 Nm (NFPA20)

Low Fuel Level IN1 Wiring between controller and engine (terminals 301, 302, 303, 304, 305,
310, 311, 312, 2 ,3 ,4 ,5) must be #14AWG as minimum.
Remote Auto Start J1* IN2

Water Reservoir Low IN3


J25
Wiring between controller and engine (terminals 12 [rated at 10A or 22A for
Fuel Tank Leak ** IN4
20 seconds] 1, 9, 10 [rated at 10A]) must be stranded #10AWG as minimum.

High Fuel Level ** IN5


Wiring between controller and engine (terminals 6, 8, 11 [rated at 30A]) must
be stranded and sized according to distance.
Network Connection (VMB1) 0-5' (0-1.5m) - 12 AWG (4 mm2)
Shielded Female Connector RJ45 6-10' (1.8-3m) - 10 AWG (6 mm2)
11-15' (3.3-4.5m) - 8 AWG (10 mm2)
16-20' (4.8-6m) - 2x10 AWG (2x6 mm2)
Modbus TCP/IP I/O 21-32' (6.4-9.75m) - 2x8 AWG (2x10 mm2)
Drawing for information only.
* Remove jumper to use this feature Manufacturer reserves the right to modify this drawing without notice.
** Re-assignable Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
4 Removed Seismic logo (optional) 18/05/22
Approved
3 Revised text 22/07/21 GPD-TD700 /E
2 Revised IN3 22/05/19 10/01/2023
CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Louver Connection Built to the latest edition of the NFPA 20 standard

Located in Controller
Engine Run Alarm Contacts

C-NO C-NC

Normally open Normally closed


Closes to alarm Opens to alarm

NO
NO
J37
C
TB2
C
NC
NC

M
Louvers Motor

Power Supply from a Reliable


External Power Source
(See NFPA20-2016 11.3.2 & A 11.3.2)

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
2 Removed Seismic logo (optional) 18/05/22
Approved
1 Revised logo 18/06/18 GPD-TD701 /E
0 First issue 10/11/16 10/01/2023
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA Ref. No: WFVT618
Model: WF-12S4 VT Rev. No:
PUMP DATA
Service Electric Driven Pump
Series Vertical Turbine
Size 12 Inch Bowl x 6 Discharge Head
Rated Flow 1000 GPM
Rated Pressure 145 PSI
Speed 1780 RPM
Rotation Clockwise
Liquid Type Water
Discharge Size 6
8
Impeller Diameter 225 mm
Base Type Steel
Weight N/A
Efficiency 68%
HP Maximum 138 HP

MATERIALS OF CONSTRUCTION
Casing Ductile Iron
Impeller Stainless steel
Shaft Stainless steel
Shaft sleeve Stainless steel
Wear ring Bronze
DRIVER DATA
Marathon
HP Rating 125 HP
Speed 1780 RPM
Weight N/A
Starting Method WYE-Delta
Enclosure Type ODP
Service Factor 1.15
Frame Size 405TP
Temperature 50 °C

10/01/2023
Performance Curve WF-12S4 VT

100 160 1000


WF-12S4 VT
1000 GPM
Max. 140% at 145 psi (102 m)
90 1780 RPM (5-Stage) 900
Shut-off
140

80 800
120
Rated
70 700
TOTAL HEAD (meters of head)

100
60 600

150% Rated

BHP
50 80 500

40 400
60 Min. 65% at
150% Rated

30 300
40
20 200

20
10 100

0 0 0
0 200 400 600 800 1000 1200 1400 1600 1800
FLOW (GPM)

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
A B C D E F G H
MOTOR NO. OF STAGES A B C
365TP 5 1736 908 1404
5 1736 1079.5 1575.5
404TP / 405TP
8 6 1980 1079.5 1575.5 8
6 1980 1220 1716
7 2224 1220 1716
444TP / 445TP
8 2468 1220 1716
10 2956 1220 1716
SIDE VIEW FRONT VIEW
7 7

B+5
-5
TOP VIEW
6 6

C+10
-10
Ø150MM DISCHARGE 70 4-Ø24
Ø285MM O.D. FLANGE
8-Ø22 BOLTS
PN 16 STANDARD
70

455+2.5
SOLE PLATE

-2.5
171.5+2.5 (16mm THICK)

750+2.5
-2.5
500
-2.5
5 GROUTING
5
F.F.L
(25mm THICK) 41

305
Ø400 Ø400

Slab Thickness 500


750+2.5
-2.5

X
4 4

3 Notes: 3

Tank Depth
1. Column pipe(s) length, X vary as per the tank depth and
slab thickness.
2. Minimum submergence requirement of the pump model

A+10
-10
is 1610 mm above the strainer.
3. All dimensions are in mm unless otherwise specified.

WATERFALL
2 2
PUMPS
270

MANUFACTURING
Ø246 DRAWING TITLE:
G&A WF-12S4 VT PUMP WITH
305

B.O.T MARATHON VERTICAL MOTOR


PUMP MODEL: WF-12F4 VT, WF-12S4 VT SCALE:

1 For Preliminary Use. DRAWING No: M12S4VTGA-E-MAR NTS 1


Not For Construction Unless Engineering Drawings DRN BY: CHKD BY: APPD BY: DRN10/01/2023
DATE: PAGE SIZE: REVISION No:
A4
Represent General Construction. M.F M.I M.C 05/27/2022 PAGE: R3
1 of 1
A B C D E F G H
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
----

A B C D E F G H
NO PART NAME MATERIAL / SPECIFICATION
01
01 LINE SHAFT STAINLESS STEEL (AISI 420 )

8
02 CAST IRON / DUCTILE IRON ( HT 250/QT 450 ) 8
02 DISCHARGE HEAD

03 GLAND COVER SS / BRONZE ( AISI 304 / - )


03
04 STUFFING BOX DUCTILE IRON ( QT 450 )
04
05 STUFFING BOX BEARING PTFE / NBR

06 STUFFING BOX SHAFT SLEEVE BRONZE/SS (C90700/AISI304)


7 7
05
07 INTERCONNECTING PIPE CARBON STEEL / SS ( ASTM A53 Grade B / AISI 304 )

08 SPIDER CAST IRON ( HT 250 )


06
09 SPIDER BEARING PTFE / NBR
07
10 SPIDER SHAFT SLEEVE BRONZE/SS (C90700/AISI304)

6 08 6
11 COUPLING STAINLESS STEEL ( AISI 416 / AISI 420 )

12 COLUMN PIPE CARBON STEEL / SS ( ASTM A53 Grade B / AISI 304 )


09
13 CASING BOWL DUCTILE IRON ( QT 450 )
10 BRONZE / SS ( C90700 / AISI 304 / AISI 316 )
14 IMPELLER

5
11 15 BOWL WEAR RING BRONZE
5
16 CASING BOWL BEARING PTFE / NBR
12
17 IMPELLER COLLET SLEEVE BRONZE / SS ( C90700 / AISI 304 / AISI 316 )

18 IMPELLER SHAFT STAINLESS STEEL ( AISI 416 / AISI 420 )


13
19 SUCTION BELL BEARING PTFE / NBR
4 4
14 20 SUCTION BELL DUCTILE IRON ( QT 450 )

21 SUCTION STRAINER STAINLESS STEEL ( AISI 304 / AISI 316 )


15

16
3 3
17

18

19
WATERFALL
2 2
20 PUMPS
MANUFACTURING
DRAWING TITLE:
21
SECTION VIEW FOR WF-12S4 VT
PUMP MODEL: WF-12S4 VT, WF-12F4 VT SCALE:

1 DRN No: M12S4VT-CS NTS 1


R0 02/24/2020 FOR INITIAL SUBMISSION DRN BY: CHKD BY: APPD BY: DRN10/01/2023
DATE: PAGE SIZE: REVISION No:
A4
A.A M.I M.C 02/24/2020 PAGE: R0
REV No DATE REVISIONS DESCRIPTION
1 of 1
A B C D E F G H
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
MODEL PHASE FRAME TYPE RATINGS
4WP1HS125HEFP 3 405TP AC HIGH EFFICIENCY
HP: (93.2kW) 125
POLES: 4
VOLTS: 400
HTZ: 60
SERVICE FACTOR: 1.15
EFFICIENCY (%):
FULL 94.3
3/4 94.9
1/2 94.7
POWER FACTOR (%):
FULL 0.89
3/4 0.88
1/2 0.87
AMPS:
FULL 152.8
LOCKED ROTOR 811
NEMA CODE LETTER G
NEMA DESIGN LETTER B
FULL LOAD RPM 1780
AMBIENT ('C) 50
ALTITUDE (FASL) 3300
TORQUES:
BREAKDOWN %F. L. 242%
LOCKED ROTOR %F.L. 175%
FULL LOAD LB-FT 352
NEMA Nominal and Minimum Efficiencies are up to 3300 feet above sea level and 25 'C ambient
The Above Data is Typical Sinewave Power Unless Noted Otherwise

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Project: ‫ﻣدارس اﻻﯾواء‬
Customer: ADVANCED PUMPS CO.
Engineer: -
WATERFALL PUMPS MANUFACTURING
Pump Manufacturer:

Technical Data
Submittal Document
GPx Series
Full Service
Electric Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers


FRYHUHG XQGHU RXU VWDQGDUG RႇHULQJ$FWXDO$6 %8,/7
GUDZLQJVPD\GLႇHUIURPZKDWLVVKRZQLQWKLVSDFNDJH
10/01/2023
June 2022
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Select starting method

0RGHO*3$ Model GPP


$FURVVWKHOLQH Partwinding
1M 1M
3L3 T3
3L3 T3

*
3L2 T2

M
3L2 T2 T1

*
3L1

3L1 T1 CR4
1M 2M T9
M
CR4 CR5 T8
2M
1M T7
3L1

3L1 3L2 3L2

Model GPS Model GPR


Soft Start Soft Stop $XWRWUDQVIRUPHU
1M 1M
3L3 3L3 T3
T3

* M
3L2 T2
3L2

* 3L1
T2

T1
M CR4 CR5 2S
3L1 T1

1S 100%
1M
0% ATR
CR5 1M CR5
1M 2S

3L1 65%
1S
2S
3L1

3L2 Soft Starter 3L2

Model GPY Model GPW


Wye-Delta Open Wye-Delta Closed
1M 3L3
1M
3L3 T3 T3

*
3L2 3L2 T2

*
T2

3L1 T1
3L1 T1

M
CR4

M
CR4 1M 2M
1M 2M T5 CR5 1S
T5

T4
CR5 1S T4
2M

2M(LB) CR3A T6
2M
T6 3L1 2S
CR5 2M 2S(LB) 2M(LB) CR3A
3L1
1S
1S 1S

1S

3L2

3L2
2S
RES
RES
RES

*From normal incoming power through Disconnecting Means (IS/CB)

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 2
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

%XLOWWR1)3$ ODWHVWHGLWLRQ
8QGHUZULWHUV/DERUDWRU\
UL218 - Fire Pump Controllers
8/
Standard, )0*OREDO Class 1321/1323
/LVWLQJV
$SSURYDOVDQG New York City Accepted for use in the City of New York by the Department of Buildings
&HUWL¿FDWLRQV CE Mark Various EN, IEC & CEE directives and standards
Built in Canada or U.A.E Built in Europe
CE Mark Option Supplied as Standard
Protection Rating

Built in Canada or U.A.E Built in Europe

Standard: NEMA 2 Standard: IP55


Optional

NEMA 12 NEMA 4X-304 sst painted IP54

Enclosure NEMA 3 1(0$;VVWEUXVKHG¿QLVK IP55

NEMA 3R NEMA 4X-316 sst painted IP65

NEMA 4 1(0$;VVWEUXVKHG¿QLVK IP66

$FFHVVRULHV 3DLQW6SHFL¿FDWLRQV
• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle ‡*ORVV\WH[WXUHG¿QLVK

Shortcircuit 200V to 208V 220V to 240V 380V to 415V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating
HP (kw)

6WDQGDUGN$
5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
2SWLRQDON$

6WDQGDUGN$ 200 (149) 250 (186) 350 - 450 (261 - 335) 450 - 500 (335 - 373)
5 - 500 (3.7- 373)
2SWLRQDON$ N/A N/A 350 - 500 (261 - 373) 450 - 500 (335 - 373)

2SWLRQDON$ 5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A

*Please see Disconnecting Means details on page 4

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 3
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

$PELHQW Standard: Optional:


Temperature 4°C to 40°C / 39°F to 104°F 4°C to 55°C / 39°F to 131°F
Rating
Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.
Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
‡&RPPRQÀDQJHPRXQWHGRSHUDWLQJKDQGOH
Service Entrance
Suitable as service entrance equipment
Rating

Emergency Start • Flange mounted • Integrated limit switch


Handle • Pull and latch activation • Across the line start (direct on line)

/RFNHG5RWRU • Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current

Electrical • Voltage phase to phase (normal power)


Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Drain connection 3/8”
• Rated for 0-500PSI working pressure (standard display at 0-300PSI)
• Externally mounted with protective cover

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 4
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

$XGLEOH$ODUP 6” alarm bell - 85 dB at 10ft. (3m)


• Power available • Deluge valve start • Pump on demand/Automatic start
• Motor run • Remote automatic start • Pump room temperature (ºF or ºC)
9LVXDO,QGLFDWLRQV
• Periodic test • Remote manual start • Lockout
• Manual start • Emergency start
Visual
• Control voltage not healthy • Overcurrent • Pump on demand
• Invalid cut-in • Overvoltage • Pump room alarm
• Lock rotor current • Phase loss L1 • Service required
• Loss of power • Phase loss L2 • Undercurrent
9LVXDO $XGLEOH • Phase loss L3 • Undervoltage
• Low ambient temperature
$ODUPV • Phase unbalanced • Check weekly test solenoid
• Low water level
• Motor trouble • Pressure transducer fault detected • Weekly test cut-in reached
• Phase reversal (normal power)
Visual and audible
• Fail to start

DPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
‡&RPPRQSXPSURRPDODUP ¿HOGUHDVVLJQDEOH
• Overvoltage
• Undervoltage
5HPRWH$ODUP • Phase unbalance
Contacts • Low pump room temperature
• High Pump room temperature
‡&RPPRQPRWRUWURXEOH ¿HOGUHDVVLJQDEOH
• Overcurrent
• Fail to start
• Undercurrent
• Ground fault
‡)UHH ¿HOGSURJUDPPDEOH **

7RUQDWHFKUHVHUYHVWKHULJKWWRXVHDQ\RIWKHVHWKUHHDODUPSRLQWVIRUVSHFLDOVSHFL¿FDSSOLFDWLRQUHTXLUHPHQWV

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 5
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

• Embedded microcomputer with software PLC logic


ViZiTouch V2 • 7.0” color touch screen (HMI technology)
2SHUDWRU,QWHUIDFH • Upgradable software
• Multi-language
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
Capability
• Addresses: See bulletin MOD-GPx
• Start on pressure drop
$XWRPDWLF6WDUW • Remote start signal from automatic device
• Deluge valve start
• Start pushbutton
Manual Start • Run test pushbutton
• Remote start from manual device
• Manual with Stop pushbutton
Stopping
Operation • Automatic after expiration of minimum run timer ***
‡0LQLPXPUXQWLPHU RႇGHOD\
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
$FWXDWLRQ
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic

***Can only be used if approved by the AHJ

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 6
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

9L=L7RXFK92SHUDWRU,QWHUIDFH

Home

2 3

8
5 6 7

1 - Color touch screen 3 - Screen protector


2 - Onscreen menu 4 - Power LED (3 colors)
• HOME page 5 - START button
• ALARM page 6 - STOP button
• CONFIGURATION page 7 - RUN TEST button
• HISTORY page 8 - USB port
• SERVICE page
• MANUAL page
• LANGUAGES page

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 9
Manufacturer reserves the right to modify this information without notice
Electric Fire Pump Controller Model:GPA/GPP/GPY
Dimensions Built to the latest edition of the NFPA 20 standard

27 1/4" [694]
26 3/8" [671]
1/2" [12] 17 3/4" [452] 24" [610]

14" [356] 22 1/2" [572]


Ø7/8" [Ø23] X2
Ø3/8" [Ø10] X4

See Notes

48" [1220]
55 1/8" [1400]

54" [1372]
51 7/8" [1318]

27" [685]
21 1/4" [541] 21 5/8" [549]

1" [25] Adjustable Feet

Sensing Line Connection - 1/2 " F.NPT


28" [711]
26" [660]
Drain - 3/8 " M.TUBE Ø1/2" [Ø13] X4 7" [178] 1" [25]

Voltage / Power Table


9 1/8" [233] Normal
7" [178] Power and
12" [305]
Motor Leads
Voltage Min HP Max HP Entrance

208 40 60 Notes: 1 1/4" [31] 3 1/2" [89] 4" [102]


1" [25]
220 - 240 40 75
- Standard NEMA: NEMA 2
- Standard paint : textured red RAL 3002.
380 - 400 - 415 75 125
- All dimensions are in inches [millimeters].
- Center of ViZiTouch screen: 47-5/8" [1208] from Bottom.
440 - 480 75 150 - Bottom conduit entrance through removable gland plate recommended.
- Use watertight conduit and connector only.
600 100 200 - Protect equipment against drilling chips.
- Door swing equal to door width.
Drawing for information only. Projection
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
4. Removed Seismic logo (optional) 18/05/22
Approved
3. HP Table Modified 22/12/20 GPX-DI261 /E
2. New Logo 10/05/18 10/01/2023
CDL
Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller
Reduced Voltage / Wye-Delta (Open Transition)
Model: GPY
Wiring schematic Built to the latest edition of the NFPA 20 standard
IS1 CB1
1L3 3L3 CT3 1M**
1L2 3L2 CT2
1L1 3L1 CT1
CR4

White

White

White
Black

Black

Black
17
ST1 1M 3L3 64 66 68 2M**
SA1 CR5
18
1S
20
3L2
3L1
65 67 69

2M
4 2 3L1 CR5 2M
19 21
1S To J2-J3-J4 To J76
1S
2
1
3L2
NO NO +
C J40 J14 AI4
Motor Run C
TB1
NC NC -
2
1

NO NO +
C J42 J15 AI3
Power Available C
TB2
NC NC -
2
1

NO NO +
C J37 J16 AI2
Phase Reversal C
TB3
NC NC -
2
1

NO NO
J39
+
Red
White
PT1
Pump Room Alarm C C J17 AI1
TB4 Black
NC NC -

1
2

NO
LS1 **
NO LS1-1
C J41 LS1
Motor Trouble C
TB5 J54 LS1-2
NC NC
2
1
NO J20 UP
NO
C J55
(Field Programmable) C
TB6
NC NC J8 DOWN

VMB1
Black
AB1
- +
J46 Red
AB
Remote Manual Start IN1

SV
SV1-1 Brown SV1
Lockout IN2 J43 SV1-2 Blue

I/O
Remote Automatic Start J1* IN3

4
Deluge Valve J45
J2* IN4 ST 2
J25
Water Reservoir Low IN5
J44 24V in XTR1
IN6 24V out 3L2
X1 H2
1 24VAC
IN7 J47 24VAC 3 X2 H1
3L1
IN8
NC
J36 CR4-1
CR4
C
CR4-2
CR4
NO

NC
J38 CR5-1
CR5
C
CR5-2
CR5
NO

GF

69
L3 68
J76 67
L2 66 To CT1-CT2-CT3 Legend

65 1M-2M Contactors
1S Contactor
L1 64
AB Alarm Bell
CB Circuit Breaker
CR Control Relay

J53 CT Current Transformer


EB Electric I/O Board
IS Isolating Switch
J Jumper
J4 L3 3L3 LS Limit Switch
PT Pressure Transducer
SA Surge Arrester

J3 ST Shunt Trip
L2 3L2 To 3L1-3L2-3L3
SV Solenoid Valve
VMB ViZiTouch Main Board

EB1 J2 L1 3L1
XTR Transformer

Drawing for information only.


* Remove jumper to use this feature Manufacturer reserves the right to modify this drawing without notice.
** Contact closes when emergency start is in "ON" position Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
3 Removed Seismic logo (optional) 18/05/22
Approved
2 Update Logo 23/04/18 GPY-WS600 /E
1 Removed (fail safe) text from Power Available relay 20/02/17 10/01/2023
CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing for Isolating Switch Built to the latest edition of the NFPA 20 standard
Power Terminals
3 Phases Notes:
Bonding Incoming Power 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
Ground 2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
L1 L2 L3
IS1

COPPER CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
Space 5 " (127 mm) 8 " (203 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
12 " (305 mm) 16 " (406 mm)
Space

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 2x (1/0 to 500) 2x (2/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 3x (4/0 to 500) -------- -------- -------- -------- -------- --------

220 to 240 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 3x (250 to 500) -------- -------- -------- -------- --------

380 to 416 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (400 to 500) 3x (250 to 500) 3x (300 to 500) --------

440 to 480 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 3x (250 to 500)

600 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

ALUMINUM CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
Space 5 " (127 mm) 8 " (203 mm) 10 " (254 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 2x (2/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 3x (300 to 500) -------- -------- -------- -------- -------- --------
1x (350) **
220 to 240 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (500) 3x (400 to 500) -------- -------- -------- -------- --------
N/A
1x (350) ** 3x (300 to 500)**
380 to 416 1x (3/0) 1x (250 to 350) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (500) 3x (350 to 500) 3x (400 to 500) --------
N/A 2x (500) 90°C *
1x (300 to 350)**
440 to 480 1x (1/0 to 3/0) 1x (3/0) 1x (250) 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (500) 90°C * 3x (350 to 500)
1x (250) 90°C *
600 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500)

Bending
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
Space

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
** Consult Factory Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1 Removed Seismic logo (optional) 18/05/22 GPX-TD612 1/2 /E
0 First issue 22/12/20 10/01/2023
CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing For GPP,GPY & GPW Built to the latest edition of the NFPA 20 standard

Notes:
Motor Terminals 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
2M 1M 2M 1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
T7 T8 T9 T1 T2 T3 T6 T4 T5 T1 T2 T3

M M
Model : GPP Models : GPW & GPY

COPPER CONDUCTORS for Motor Connection (1M-2M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4) 1x (6 to 4) 1x (6 to 4) 1x (4 to 2/0) 1x (2 to 2/0) 1x (1 to 2/0)

220 to 240 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4) 1x (6 to 4) 1x (6 to 4) 1x (4) 1x (3 to 2/0) 1x (2 to 2/0)

380 to 416 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4) 1x (6 to 4) 1x (4)

440 to 480 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4) 1x (6 to 4)

600 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (2/0 to 3/0) 1x (3/0 to 300) 1x (250 to 300) 2x (1/0 to 300) 2x (3/0 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (1/0 to 2/0) 1x (3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (4/0 to 350) -------- -------- -------- -------- --------

380 to 416 1x (4 to 2/0) 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 350) 2x (4/0 to 350) --------

440 to 480 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300) 2x (3/0 to 350) 2x (4/0 to 350)

600 1x (6 to 4) 1x (4) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (250 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300)

ALUMINUM CONDUCTORS for Contactor (1M-2M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (2/0)

220 to 240 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) 1x (1/0 to 2/0)

380 to 416 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (3 to 2/0) **

440 to 480 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) **

600 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) **

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (3/0) Consult Factory 1x (300) 90°C * 2x (3/0 to 300) 2x (250 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (2/0) 90°C * Consult Factory 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (300 to 350) -------- -------- -------- -------- --------

380 to 416 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (1/0 to 2/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (250 to 300) 2x (300 to 350) 2x (300 to 350) --------

440 to 480 1x (3 to 2/0) ** 1x (2 to 2/0) 1x (2/0) 90°C * 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 350) 2x (300 to 350)

600 1x (4 to 2/0) ** 1x (3 to 2/0) ** 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * Consult Factory 2x (3/0 to 300) 2x (4/0 to 300)

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
** Option V659 required. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1 Removed Seismic logo (optional) 18/05/22 GPX-TD612 2/2 /E
0 First issue 22/12/20 10/01/2023
CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing Built to the latest edition of the NFPA 20 standard

Control Terminals (EB1) Remote Alarm Terminals (EB1)


Terminals Wire Size: Terminals Wire Size:
24 - 12 AWG 24 - 12 AWG
0.5 Nm 0.5 Nm

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Remote Manual Start Close to start pump IN1 J25 Motor Run J40
1
Normally open NO
TB1
Normally closed Closes to alarm C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Lockout Close to block start IN2 J25 Power Available J42
1
Normally open NO
TB2
Normally closed Closes to alarm
C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm
C
Opens to alarm NC
Remote Automatic Start Open to start pump J1* IN3 J25 J37
Phase Reversal Normally open
1
TB3
NO
Normally closed Closes to alarm C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Deluge Valve Open to start pump J2* IN4 J25 Pump Room Alarm ** J39
1
Normally open NO
TB4
Normally closed Closes to alarm
C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm
C

Alarm Inputs (EB1) Motor Trouble **


Opens to alarm
1
NC
J41
Normally open NO
TB5
Terminals Wire Size:
24 - 12 AWG Normally closed Closes to alarm C
0.5 Nm Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Water Reservoir Low Close to signal alarm IN5 J25 (Field Programmable ***) J55
1
Normally open NO
TB6
Normally closed Closes to alarm C
Opens to alarm NC

Network Connection (VMB1)


Shielded Female Connector RJ45

Modbus TCP/IP I/O

* Remove jumper to use this feature Drawing for information only.


** Re-assignable Manufacturer reserves the right to modify this drawing without notice.
*** Not available on GPS models Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
3 Removed Seismic logo (optional) 18/05/22
Approved
2 Revised logo 18/06/18 GPX-TD603 /E
1 General Revision (added AL coverage) 10/07/17 10/01/2023
CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Performance Curve RV15-60Hz

0 10 20 30 40 50 60 70 80 90 100 110 Q[US.GPM]

0 10 20 30 40 50 60 70 80 90 Q[IMP.GPM]
P H
[kPa] [m] H
-12 RV15
240 [ft]
60Hz

220
700
2000 -10
200

-9 600
180

1600 -8

60Hz
160
500
-7
140
-6
1200 120 400
-5
100
-4 300
800 80
-3
60 200

-2
400 40
100
-1
20

0 0 0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 3
Q[m /h]

0 1 2 3 4 5 6 7 Q[I/s]
P2 Eta
[kW] [%]
1.6 Eta 80
1.2 60
P2
0.8 40
0.4 20
0.0 0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 3
Q[m /h]
H NPSH
[m] [m]
20 QH-3500rpm 8
15 6
10 4
5 2
NPSH
0 0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 Q[m 3/h]

42 10/01/2023
Technical Data RV15-60Hz

Performance Table
Power Q
Model P 2(kW) (m 3/h) 10 12 14 15 16 18 20 22 24 26

RV15-1 1.5 18.3 18 17.5 17 16.5 16 15 14 12.5 10.5


RV15-2 3.0 36.5 36 35 34 33 32 30 27 25 21
RV15-3 4.0 55 54 52 51.5 50 48 45 41 37 32
RV15-4 5.5 73 72 70 69 66 64 60 55 49 42
RV15-5 7.5 92 89 87 86 83 80 74 69 62 53
RV15-6 11 110 107 105 103 100 96 89 83 74 64
RV15-7 11 128 125 122 120 117 112 104 97 86 74
H
RV15-8 11 (m) 146 143 140 138 133 128 119 110 98 85
RV15-9 15 165 161 157 155 150 144 134 124 111 96
RV15-10 15 183 179 175 172 167 160 149 138 123 106
RV15-12 18.5 220 215 210 207 200 192 179 166 148 128

Installation sketches Dimensions and weights


Dimensions(mm) Weight
Model
D (kg)

RV15-1 356 241/293 597 - 154 111 47


RV15-2 406 293 681 - 177 116 54
RV15-3 476 305 781 - 197 148 65
RV15-4 542 390 932 300 275 210 84
RV15-5 587 390 977 300 275 210 91

FGJ(DIN-ANSI-JIS) RV15-6 662 505 1167 350 330 255 123


PN16-25-40(DN50)
RV15-7 706 505 1211 350 330 255 125
RV15-8 752 505 1257 350 330 255 126
RV15-9 797 505 1302 350 330 255 143
RV15-10 842 505 1347 350 330 255 144
RV15-12 932 560 1492 350 330 330 157

10/01/2023 43
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
Project: ‫ﻣدارس اﻻﯾواء‬
Customer: ADVANCED PUMPS CO.
-
Engineer:
WATERFALL PUMPS MANUFACTURING
Pump Manufacturer:

Technical Data
Submittal Document
Model JP3
Across the Line Start
Jockey Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers


FRYHUHG XQGHU RXU VWDQGDUG RႇHULQJ $FWXDO $6 %8,/7
GUDZLQJVPD\GLႇHUIURPZKDWLVVKRZQLQWKLVSDFNDJH
10/01/2023
June 2022
Technical Data
Model JP3 Jockey Pump Controller

Underwriters Laboratory (UL) UL508A - Industrial Pump Controllers


New York City Accepted for use in the City of New York by the Department of Buildings
/LVWLQJ
Optional
CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
✔ Standard: NEMA 2
Optional
NEMA 12 NEMA 4X-304 sst painted
NEMA 3 1(0$;VVWEUXVKHG¿QLVK
Enclosure
NEMA 3R NEMA 4X-316 sst painted
NEMA 4 1(0$;VVWEUXVKHG¿QLVK
$FFHVVRULHV 3DLQW6SHFL¿FDWLRQV
• Wall mounting lugs ( x4) • Red RAL3002
• Powder coating
‡ *ORVV\WH[WXUHG¿QLVK

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model JP3 Jockey Pump Controller

• Main disconnect – padlockable – rotary type handle – door interlocked


Fuseless Motor
• Thermo-magnetic motor protector
Starter
• Contactor
Control Circuit • 24V.AC
• Solid state controls
iPD+ Operator
• All adjustments on door front
,QWHUIDFH
• Navigation pushbuttons
• Pressure transducer for fresh water application 316 stainless steel construction
Pressure Sensing • Rated for 0-600psi working pressure
• Pressure sensing line connection 1/2” brass Male NPT
• Manual motor start/run LED
• Automatic motor start/run LED
• Motor overload
• Pressure reading
• Start pressure
• Stop pressure
9LVXDO,QGLFDWLRQV • System pressure
• System pressure diagnostic LED’s
• Green: system pressure at or above stop pressure
• Yellow: system pressure between start and stop pressure
• Red: system pressure at or below start pressure
• AUTO mode
• OFF mode
‡0LQLPXPUXQWLPHU RႇGHOD\
Timers • Delay start timer (on delay)
• Visual countdown
• Pump start counter
Counters
• Elapsed timer meter (hours / non-resettable)
• OFF-AUTO pushbutton
Operators
• Start and Stop pushbutton
Automatic Start Start on pressure drop

Manual Start Start pushbutton


Operation
Stopping Stop pushbutton
Field adjustable & ‡0LQLPXPUXQWLPHU RႇGHOD\
Timers
visual countdown • Delay start timer (on delay)

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model JP3 Jockey Pump Controller

iPD+2SHUDWRU,QWHUIDFH

3 2

4 7

HAND AUTO

5
8

1 - Power on LED 6 - STOP pushbutton


2 - System status LED 7 - Auto start LED
3 - Digital display 8 - Navigation keypad
4 - Hand start LED 9 - ON - OFF pushbutton
5 - START pushbutton

This is a Marketing document. Please consult factory for more information. 10/01/2023
June 2022 Manufacturer reserves the right to modify this information without notice 5
0 1 2 3 4 5 6 7 8

Jockey Pump Controller


PER QUOTE DRAWING No. NYC
Dpt of Building
Approved

Across the Line / 3 Phase


Model:JP3
REV. DESCRIPTION DD/MM/YY
A 8 Sensing line connection changed 25/03/20 Drawing No. A
Dimensions 9
10
UL logo updated CSA logo removed
Removed Seismic logo (optional)
14/07/20
18/05/22
JP3-DI500/E

FU1 DS
B B
D

IPD+

XTR1
F C

C C
Main Disconnect
G

Y
ON
R

C1 OL1

OFF
HAND G G AUTO

G DS

D B E D

PT1
Underwriters
Laboratories Inc.

DANGER
R R

LISTED
ENCLOSED INDUSTRIAL CONTROL PANEL
No. AC-XXX

Rating
E Label E
Standard Internal Layout
Ø3 8 "[9] x4

Sensing Line Connection 1/2 " M.NPT


F F

Dimensions*
Maximum Motor Horsepower Enclosure Dimensions Door Dimensions Anchor Dimensions

G 4-½" [115] 200-208V


10HP
220-240V
10HP
380-416V
15HP
440-480V
20HP
575-600V
25HP
AXBXC
10"X12"X6-½"
DXE
10-⅝"X12-⅝"
FXG
8"X12-¾"
G
20HP 30HP 40HP 60HP 60HP 16"X16"X7-½" 16-½"X16-½" 14"X16-¾"

2-¼" [58]
A
H H

Notes: Drawing for information only.


- Standard NEMA: NEMA 2
Manufacturer reserves the right to modify this drawing without notice.
- Standard Paint: Textured Red RAL 3002.
I - All Dimensions are in Inches [Millimeters] Contact manufacturer for "As Built" drawing. I
- Use Watertight Conduit and Connector Only. *Dimensions may change depending on option required. Consult Factory for exact Projection

- Protect Equipment Against Drilling Chips. dimensions.


- Door Swing Equal to Door Width
0 1 2 3 4 5 6 7 10/01/2023
8
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8

Jockey Pump Controller


PER QUOTE DRAWING No. NYC
Dpt of Building
Approved

Across the Line / 3 Phase


Model:JP3
REV. DESCRIPTION DD/MM/YY
A 7 Revised logo 18/06/18 Drawing No. A
Wiring schematic 8
9
UL logo updated CSA logo removed
Removed Seismic logo (optional)
14/07/20
18/05/22
JP3-WS500/E

Pressure Sensor
L1 L2 L3
PT1 Type 0.5 - 4.5V
B B
G
DS G

White

Black
Y

Red
R

B W G R 5 S

RESET J5
HAND G G AUTO

PsOut-
PsIn-

PsOut+
PsIn+
OL1
C 34 33 7 C
9 IN1 J9
J21
G
IN2
OUTPUT ON J8

J19
"IPD+"
D D
F5

FU1 J2 J3 J1
XTR1
24Vac 24Vac
H2 X1 3 A2 A1
3 1 22 8
H1 X2
1
E E

A1 A2
C1

F F

G G

H H
OL1

C1

I
- Drawing for information only. I
G Manufacturer reserves the right to modify this drawing without notice.
T1 T2 T3
Contact manufacturer for "As Built" drawing.
P1
0 1 2 3 4 5 6 7 10/01/2023
8
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8

Jockey Pump Controller


PER QUOTE DRAWING No. NYC
Dpt of Building
Approved

Across the Line / 3 Phase


Model:JP3
REV. DESCRIPTION DD/MM/YY
A 7 Revised logo 18/06/18 Drawing No. A
Line and Motor Terminal Size 8
9
UL logo updated CSA logo removed
Removed Seismic logo (optional)
14/07/20
18/05/22
JP3-TD500/E

B B

Power Connections and Motor Connections

3 Phase
Incoming Power
Bonding Ground

C C

L1 L2 L3
DS

C1

D T1 T2 T3 D

E E

Line Terminals (L1,L2,L3,GND)


Maximum Motor Horsepower
Wire Size Copper Only Torque Wire Size Ground Copper Only
200-208V 220-240V 380-416V 440-480V 575-600V
10HP 10HP 20HP 20HP 25HP #14 AWG - #6 AWG 2 Nm #14 AWG - #2 AWG
F 20HP 30HP 40HP 60HP 60HP #12 AWG - #1 AWG 6 Nm #6 AWG - #2 AWG F

G G

Motor Terminals (T1,T2,T3,GND)


Maximum Motor Horsepower
Wire Size Copper Only Torque Wire Size Ground Copper Only
200-208V 220-240V 380-416V 440-480V 575-600V
5HP 7.5HP 10HP 15HP 20HP #14 AWG - #10 AWG 1.8 Nm #14 AWG - #2 AWG
H 10HP 10HP 15HP 20HP 25HP #14 AWG - #6 AWG 2.5 Nm #12 AWG - #2 AWG H
15HP 20HP 30HP 50HP 50HP #10 AWG - #3 AWG 5 Nm #12 AWG - #2 AWG
20HP 30HP 40HP 60HP 60HP #10 AWG - #2 AWG 11.3 Nm #12 AWG - #2 AWG

I I

0 1 2 3 4 5 6 7 10/01/2023
8
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
MODEL
50B-4KG1 Globe
2050B-4KG1 Angle
Listed/Approved Fire Protection Pressure Relief Valve

• U.L. Listed / U.L.C. Listed


• Factory Mutual Approved
• Fast Opening to Maintain Steady Line Pressure

LAB
LLED B
Y
• Accommodates Wide Range of Flow Rates
• Closes Gradually for Surge-Free Operation
ULC
U N D E R W RIT

CANADA

• Adjustable Pressure Settings, Not Affected by


OF

R
E

S E
LAB RI
O R AT O
Pressure At Valve Discharge

The Cla-Val Model 50B-4KG1 Globe / 2050B-4KG1 Angle


Pressure Relief Valve is designed specifically to automati-
cally relieve excess pressure in fire protection pumping sys-
tems. Pilot controlled, it maintains constant system pres-
2050B-4KG1 (Angle)
sure at the pump discharge within very close limits as
DESIGN
demands change. The 50B-4KG1 and 2050B-4KG1 can be
U.L. Listed...............Sizes 3" thru 8" supplied with optional internal and external epoxy coating of
ASSE
SSED
F.M. Approved.........Sizes 3" thru 8" the main valve wetted surfaces.
U.L.C. Listed............Sizes 2” thru 10”
Type Approved

Typical Application KOModel 2050B-4KG1 Operation Sequence


Pressure Relief Valve
(Angle Pattern) At pump start, Cla-Val Relief Valve modulates to relieve
excess pump capacity, maintaining positive system pres-
sure at the pump discharge.

When fire demand slows or ceases, Cla-Val Model


50B-4KG1 opens, diverting entire pump output to dis-
charge, allowing fire pump to be stopped without causing
Fire Pump surging in the lines.

(Please note that if the Model 50B-4KG1 is to be used on


a continuous duty basis to maintain fire-system pressure,
suitable back pressure must be provided on the valve to
prevent cavitation damage. Consult the factory for details.)
Check Valve

Optional UL Listed Materials for Seawater and Severe


Service Applications:
• Nickel Aluminum Bronze (NAB) - ASTM B148 Alloy C95800
To Fire • Monel - QQ-N-288 Comp B - ASTM A494 Grade M30H
Protection System • Cast Steel - ASTM A216 Grade WCB
• 316 Stainless Steel - ASTM A743 Grades CF3M and CFM8
• Super Austenitic Stainless Steel - ASTM A351 Grade
CK3MCuN (SMO 254)
• Super Duplex Stainless Steel - ASTM A890 Grade 5A
"Fluid Control at It's Best" (CE3MN)
10/01/2023
Specifications Dimensions
B
Sizes Globe: 2" - 10” flanged = U.L., F.M. and
Angle: 2" - 10" flanged ULC sizes
End Details 150 and 300 ANSI B16.42
Pressure Ratings Class 150 - 250 psi Max. G
= ULC sizes only
Class 300 - 400 psi Max
Water, to 180°F Max.
Model 50B-4KG1 Globe Model 2050B-4KG1 Angle
Standard Materials Main Valve Body & Cover
A H E
Ductile Iron ASTM A536 Grade 65-45-12
Standard Main Valve Trim:
Bronze Seat, Teflon Coated
Stainless Steel Stem, Dura-Kleen Stem
C
Standard Pilot Control System: C
Cast Bronze with
Stainless Steel trim
Available in the following relief
pressure ranges: D F
Adjustment Range 20-200 psi (150 Class)
100-300 psi (300 Class) We recommend providing adequate space around valve for maintenance work.
Protective epoxy resin coating
of wetted surfaces of main Valve Size (inches) 2” 2-1/2” 3” 4” 6” 8” 10”
Optional valve cast iron components Threaded Ends 9.38 11.00 12.50 --- --- --- ---
(UL listed HNFX EX2855) A 150 Flanged 9.38 11.00 12.00 15.00 20.00 25.38 29.75
300 Flanged 10.00 11.62 13.25 15.62 21.00 26.38 31.12
300 X 150 12.88 15.31 20.56 25.88 30.44
Purchase Specifications B 3.31 4.00 4.56 5.75 7.88 10.00 11.81
The Fire Pump Pressure Relief Valve shall modulate to relieve excess C 12.00 12.25 12.50 13.00 14.31 16.31 18.00
pressure in a fire protection system. It shall maintain constant pressure D 1.50 1.69 2.66 3.19 4.31 5.31 9.25
in the system regardless of demand changes. It shall be pilot controlled Threaded Ends 4.75 5.50 6.25 --- --- --- ---
and back pressure shall not affect its set point. It shall be actuated by
E 150 Flanged 4.75 5.50 6.00 7.50 10.00 12.75 14.88
line pressure through a pilot control system and open fast in order to
300 Flanged 5.00 5.88 6.38 7.88 10.50 13.25 15.56
maintain steady system pressure as system demand decreases. It shall
close gradually to control surges and shall re-seat drip-tight within 5% of Threaded Ends 3.25 4.00 4.50 --- --- --- ---
its pressure setting. The main valve shall be of the hydraulically-operat- F 150 Flanged 3.25 4.00 4.00 5.00 6.00 8.00 8.62
ed, pilot-controlled, diaphragm-type, globe or angle valve. It shall have 300 Flanged 3.50 4.31 4.38 5.31 6.50 8.50 9.31
a single, removable, teflon-coated seat, a grooved stem guided at both G & H 6.00 6.69 7.75 7.88 8.50 9.75 13.25
ends, and a resilient disc with a rectangular cross section, being con-
tained on 3 1/2 sides. No external packing glands shall be permitted and Valve Size (mm) 50 65 80 100 150 200 250
the diaphragm shall not be used as a seating surface. The pilot control Threaded Ends 238 279 318 --- --- --- ---
shall be a direct-acting, adjustable, spring-loaded, diaphragm-type valve
A 150 Flanged 234 279 305 381 508 645 756
designed for modulating service to permit flow when controlling pressure
300 Flanged 254 295 337 397 533 670 790
exceeds spring setting. This valve shall be UL Listed and Factory Mutual
approved. It shall be the Model 50B-4KG1 (globe) or Model 2050B- 300 X 150 --- --- 327 389 522 657 773
4KG1 (angle) Pressure Relief Valve as manufactured by Cla-Val Newport B 84 102 116 146 200 254 300
Beach, California. C 305 311 1318 330 363 414 457
*Special Note: D 38 43 65 81 109 135 235
The Model 50B-4KG1 Pressure Relief Valve is available with 300# ANSI Threaded Ends 121 140 159 --- --- --- ---
inlet flange and 150# ANSI outlet flange. This valve is used on higher
E 150 Flanged 121 140 152 191 254 324 378
pressure systems where 300# flange connections are required, and
300 Flanged 127 149 162 200 267 337 395
allows for adapting of a discharge cone (generally supplied with 150#
flange) to accommodate "atmospheric break" at relief valve discharge. Threaded Ends 83 102 114 --- --- --- ---
This relief valve, with 300# / 150# flanges is available on special order, F 150 Flanged 83 102 102 127 152 203 219
and is UNDERWRITERS LABORATORIES LISTED AND FACTORY 300 Flanged 89 109 111 135 165 216 236
MUTUAL APPROVED. G & H 152 170 197 200 216 248 337

Specifications: Seawater Service Option Valve Capacity


Sizes Globe: 2" - 8" flanged
Angle: 2" - 8" flanged Valve Sizes in Inches: 2" 2 1/2" 3" 4" 6" 8" 10"
Consult factory for flange ratings. NFPA 20 Maximum
See page 1 for seawater service materials options. Recommended GPM 208 300 500 1000 2500 5000 11000

CLA-VAL Represented By:


1701 Placentia Avenue • Costa Mesa CA 92627 Phone: 949-722-4800
Fax: 949-548-5441 Web Site: cla-val.com E-mail: [email protected]
CLA-VAL CANADA CLA-VAL EUROPE CLA-VAL UK
4687 Christie Drive Chemin des Mésanges 1 Dainton House, Goods Station Road
Beamsville, Ontario CH-1032 Romanel/ GB - Tunbridge Wells
Canada L0R 1B4 Lausanne, Switzerland Kent TN1 2 DH England
Phone: 905-563-4963 Phone: 41-21-643-15-55 Phone: 44-1892-514-400
Fax: 905-563-4040 Fax: 41-21-643-15-50 Fax: 44-1892-543-423
E-Mail: [email protected] E-Mail: [email protected] E-Mail: [email protected]
E-50B-4KG1/2050B-4KGL1  (R-04/2015)
© Copyright CLA-VAL 2015 Printed in USA Specifications subject to change without notice.
10/01/2023
Series 34
Fire Protection System
Air Release Valve
• Ductile Iron Body
• Stainless Steel Trim and Float
• Easily serviced without removal from pipeline
• Available Pressure Ratings: 175 and 300
• Engineered for drip tight seal at low pressures

Cla-Val Series 34 Fire Protection System Air Release Valves are


designed to vent entrained air that collects at high points in a pipeline.
This valve continuously eliminates air from a system by releasing small
quantities of air before large air pockets can occur. In many installations,
Figure A
continuing accumulations of air in the pipeline (lacking air release
valves); cause flow capacity to slowly decrease; power consumption
slowly increases; un-noticeable at first, until flow drops dramatically,
Installation even stopping due to air blocks in the piping.
Series 34 Fire Protection System Air Release Valves are
typically installed at high-points in pipelines and at regular Another problem resulting from excessive air accumulation is
intervals, of approximate 1/2 mile, along uniform grade line unexplained pipeline rupture. These ruptures are passed off as the result
pipe. of ground settling or defective pipe, Where as in reality its large air
pockets that greatly increase pressure surges (normally occurring) when
Mount the unit in the vertical position on top of the pipeline flow stops and starts causing the rupture. During normal pipeline
with an isolation valve installed below each valve in the event operation, air accumulation at the high point will displace the liquid within
servicing is required. A vault with adequate air venting and the air valve and lower the water level in relation to the float. As level of
drainage is recommended. the liquid lowers, where the float is no longer buoyant, the float drops and
opens the valve orifice seat and permitting accumulated air to be
Note: exhausted to atmosphere. After air is released, the liquid level in the air
Vacuum check valves can be supplied on the discharge of all valve rises and closes the valve orifice seat. This cycle automatically
size air release valves to prevent air re-entering the system; during repeats as air accumulates inside the air release valve, thereby preventing
negative pressure conditions the formation of air pockets.

Purchase Specifications Product Specifications


The fire protection system air release valve shall be of the
Sizes Materials
float operated, simple lever or compound lever design, and
1/2", 3/4", 1" Body and Cover:
capable of automatically releasing accumulated air from a
fluid system while the system is pressurized and operating. Ductile Iron ASTM 536 65-45-12
Pressure Ratings (see note)
An adjustable designed orifice button shall be used to seal 175 UL/FM Float:
the valve discharge port with drip-tight shut-off. The orifice 300 UL/FM Stainless Steel
diameter must be sized for use within a given operating
pressure range to insure maximum air venting capacity. Temperature Range Internal Parts:
Water to 180°F Stainless Steel
The float shall be of all stainless steel construction and
guaranteed to withstand the designed system surge pressure Note: Specify when operating Seal:
without failure. The body and the cover shall be ductile iron pressure below 10 PSI Viton or Buna-N® (Standard)
TM

and valve internal parts shall be stainless steel and Viton or


Buna-N® (standard)for water tight shut-off.
TM

The air release valve shall be manufactured per ANSI/AWWA


C512-04 Series 34 from Cla-Val in Newport Beach, CA, USA. visit www.cla-val.com to see our
complete line of air and check valves.

10/01/2023
Series 34
Fire Protection System
Air Release Valve
Air Release Valve Sizing
Air release valve sizing requires determining the volume of air that must be released from pipeline high points during normal
operation and the diameter of the pipeline. Series 34 Fire Protection System Air Release Valves are primarily used to
continuously release pockets of air (as they develop) from high point, hence it is not critical to determine exact volume of air
to be released.

See chart on page 3 for sizing based on venting capacity.

Air Release Valve Sizing Chart For Water Pipelines

Figure A Model No. Inlet Size Outlet Size Orifice Size GPM MWP Height Width Wt. (lbs.)

UL Listed • FM
Approved
200 -
3450-AR332 1/2", 3/4", 1" 1/2" 3/32" 175 5-7/8" 3-3/4" 6
2200
3475-AR332
3410-AR332

UL Listed
FM Approved
200 -
3450-AR116.3 1/2", 3/4", 1" 1/2" 1/16" 300 5-7/8" 3-3/4" 6
2200
3475-AR116.3
3410-AR116.3

Figure A

10/01/2023
Series 34
Fire Protection System
Air Release Valve
Venting Capacity Graph for Air Release Valves
Pressure Differential Across Valve is PSI

Venting Capacity in Cubic Feet of Free Air Per Minute

Valve Selection Based on Venting Capacity


Follow these steps to select and size an air release valves when a specific venting capacity is required:

A) Enter graph with required system pressure and venting capacity

B) Read off nearest orifice diameter to intersection of pressure and capacity lines on graph

C) Enter table above with orifice diameter and select valve that can use this orifice diameter with the
corresponding pressure

Figure A
10/01/2023
Series 34 Fire Protection System Air Release Valve Technical Data

Combination Air Valve
at peaks and sharp change in gradient due to
possibility of column separation and vacuum
OR
Hydraulically Controlled Air/Vacuum Valve
Hydraulically Controlled Air/Vacuum Valve
where secondary surges due to rejoining of
where secondary surges due to rejoining of
previously separated water could occur
previously separated water could occur
OR
Combination Air Valve
at peaks and sharp change in gradient due to
Air Release Valve possibility of column separation and vacuum
on long, ascending stretches
at 1/4 to 1/2 mile intervals

Air/Vacuum Valve
Air Release Valve at peaks and sharp change in gradient due to
on long, ascending stretches possibility of column separation and vacuum
at 1/4 to 1/2 mile intervals

Air/Vacuum Valve

Air Release Valve

Combination Air Valve

Hydraulically Controlled Air/Vacuum Valve


Figure A

Installation Tips
1. The effectiveness of Series 34 Fire Protection System Air Release Valve is dependent upon it being located at appropriate high
points in a pipeline and at uniform intervals of approximately 2500 feet on horizontal pipelines.

2. There are four variables that can cause an air pocket to form slightly downstream of the true high point in a piping system:
1. Severity of the slope adjacent to the high point or change of gradient
2. Velocity of the liquid
3. Texture of the inside surface of the pipe being used
4. Viscosity of the fluid

It is recommended where an air pocket can form slightly downstream of the high point, to install additional Series 34 Fire Protection
System Air Release Valves at this point.

3. Cla-Val has available, upon request, a Slide Rule Air Valve Calculator. It will greatly reduce the amount of time to size valves for
pipeline service.

Other typical applications include: When Ordering, Please Specify:


1. Centrifugal pumps 1. Model Number
2. Hydropneumatic tanks 2. Inlet Size (NPT)
3. Enclosed systems 3. Inlet Pressure Rating
4. Sewage lines 4. Orifice Size

CLA-VAL ©
1701 Placentia Avenue • Costa Mesa CA 92627 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: [email protected] • Website cla-val.com
Copyright Cla-Val 2019 Printed in USA Specifications subject to change without notice. E-34 Series Fire Protection System (R-10/2019)
10/01/2023
10/01/2023
R

10/01/2023
03/10/2018
R

10/01/2023
03/10/2018
10/01/2023
03/10/2018
10/01/2023
03/10/2018
10/01/2023
03/10/2018
VENTURI: ZINC PLATED STEEL

VALVES: ONE PIECE BRASS BODY


ZINC DIECAST STEEL HANDLE

ID TAG: Chain: brass


Tag: Aluminum

HOSES: GOODYEAR 3/6" FREON CHARGE


HOSES WITH NYTRILE CORE,
POLYESTER BRAID AND NYTRILE
COVER WITH PVC FOR ABRASION
RESISTANCE

10/01/2023
10/01/2023
10/01/2023
A B C D E F G H
NOZZLE SCHEDULE ITEM QTY. DESCRIPTION
ITEM QTY. DESCRIPTION 1 1 FILL CAP
19 1 2" NPT FILLER NECK 2 1 REMOVABLE STRAINER
20 1 2" NPT CONN. FOR FLASH ARRESTER (OPTIONAL) 3 1 FUEL LEVEL INDICATOR GAUGE
8 21 1 OPENING FOR EMERGENCY VENT- 'G' (Size in Inches) 4 1 FLASH ARRESTER (OPTIONAL) 8
4 22 1 1" NPT PIPE PLUG FOR DRAIN 5 1 2" STD PIPE,LENGTH TO SUIT INSTALLATION
23 1 2" NPT CONN. FOR FUEL SWITCH(OPTIONAL) 6 1 2"x2"x21" FEMALE PIPE TEE
1
5
24 1 2" NPT CONN. FOR FUEL LEVEL INDICATOR 7 2 2" STD PIPE x 1 21" LG

3028mm-MIN
1 1
25 1 2" NPT PIPE CONN. FOR FUEL RETURN LINE 8 1 2" NPT UNION
15 6 1
8
26 1 2"NPT CONN. (34" NPT FOR 550 GALLON TANK) FOR 9 STD PIPE,LENGTH TO SUIT INSTALLATION
9 FUEL SUPPLY LINE 10 1 1 1 1
2"x2"x2" FEMALE TEE PIPE
7 3 1 2
1
11 1 2" STD PIPE
7 19 12 1 2" STD PIPE 7

305
21 13 1 LONG NIPPLE
10 14 1 LOCK-OPEN VALVE
25 15 1 CHECK VALVE
EXPANSION AREA 5% OF TOTAL VOLUME

24 23
16 1 FLEXIBLE METAL HOSE
20
MODE SELECTOR

SEE NOTE # 3
17 1 PIPE COUPLING
MANUAL RUN

13

(MAX. HEAD)
FIRE PUMP ENGINE-MANUAL OPERATING INSTRUCTIONS
TO START ENGINE
1. Position MODE SELECTOR switch to MANUAL RUN.
2. Lift and hold MANUAL CRANK #1 until engine starts, or release after 15 seconds. If unit fails to start, wait 15 seconds, use MANUAL
CRANK #2 and repeat step. AUTOMATIC
3. If COOLING WATER is not flowing or engine TEMPERATURE is too HIGH, open cooling system manual by-pass valve. OR
MANUAL STOP
TO STOP ENGINE
1. Return MODE SELECTOR switch to AUTOMATIC and MAUAL STOP position, engine will stop.
2. Close cooling system manual by-pass valve.
IMPORTANT
leave the MODE SELECTOR switch in the MANUAL RUN position during AUTOMATIC operation. (The controller will be unable
DO to
NOT WARNING
MODE SELECTOR NOT
stop the engine and DAMAGE MAY RESULT). IN AUTOMATIC
ENGINE WILL NOT STOP
OVERSPEED RESET
1. After problem has been corrected, reset the speed sensing device by lifting the OVERSPEED RESET and hold for 2 seconds.

12 14
OVERSPEED
67% VERIFY
MANUAL CRANK
#2
MANUAL CRANK
#1
OVERSPEED
RESET
OVERSPEED
SHUTDOWN

18 1 FITTINGS TO SUIT VARIOUS ENGINES


B

C126738

6 11 6
C

SUMP AREA 5% OF TOTAL VOLUME


FUEL PUMP ℄

26

TABLE 1
22
D

H
(DRAIN
OUTER
TANK)
E

ENGINE CRANKSHAFT ℄

A
5 5
F
Notes:
1. All dimensions are in mm unless otherwise specified.
2. Fuel piping shall not be galvanized steel or copper.
16 17 18
3. The engine manufacturer's fuel pump static head pressure
FUEL SUPPLY limits shall not be exceeded when the level of fuel in the tank
FUEL RETURN is at a maximum.
4. The fuel supply tank and fuel shall be reserved exclusively for
4 the fire pump diesel engine. 4
5. Illustration shown for component identification only. Installation
shall conform to NFPA 20, NFPA 31 or any other applicable
standards.
6. Additional fittings and accessories according to project
requirements and mutually agreed scope.
7. Fuel supply tank(s) shall be sized for a minimum of 12 hours
of engine run time based on the fuel supply rate requirements
3 of the engine, plus 5 percent volume expansion and 5 percent 3
volume for sump.
TABLE 1 TABLE 2 8. The fuel return line shall be installed according to the engine
ENGINE MODEL H ENGINE MODEL
FUEL SUPPLY
HOSE SIZE
FUEL RETURN
HOSE SIZE
manufacturer's recommendation. In zones where freezing
temperature [320F(00C)] could be encountered, the fuel tank
KA4H 174 KA4H 3/8" 1/4"
shall be located in the pump room.
JU4H 364 JU4H 1/2" 3/8"
JU6H 364 JU6H 1/2" 3/8"
UF05 283 UF05 M16x1.5 M14x1.5 WATERFALL
2 2
S. NO. CAPACITY US.GAL A B C D E F G
UF08 333 UF08 M16x1.5 M14x1.5 PUMPS
UF16R1/R2 300 UF16R1/R2 M16x1.5 M14x1.5
1 40 1000 450 1320 48 618 247 3" UF26R1/R2 300 UF26R1/R2 M16x1.5 M14x1.5 MANUFACTURING
380HE 80 DRAWING TITLE:
2 70 1143 565 1435 48 618 318 3"
FUEL SYSTEM FOR DIESEL
3 120 1322 685 1543 65 623 318 3" 480HE 80
490HE 136.5
DRIVEN FIRE PUMP
4 180 1322 838 1683 79 623 318 3" DRAWING No: SCALE:
5 280 1270 1067 1873 112 623 318 3" FS-DSL-01 NTS
1 1
6 360 1575 1067 1878 112 623 318 3"
DRN BY: CHKD BY: APPD BY: DRN10/01/2023
DATE: PAGE SIZE: REVISION No:
7 440 1575 1219 2068 114 663 368 4" A4
M.J M.F M.I 11/25/2022 PAGE: R4
8 550 1880 1219 2068 110 663 368 4" 1 of 1
A B C D E F G H
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
Thrust Capacity

VERTICAL STANDARD HEAVY Two way STANDARD HEAVY Two way


VERTICAL
BEARING Downthrust Downthrust
ARRANGEMENTS SHAFT DOWNTHRUST ONLY (lbs) SHAFT DOWNTHRUST ONLY (lbs)
or Upthrust or Upthrust
MODEL R.P.M. H.P. MIN. MAX. MIN. MAX. Max. MODEL R.P.M. H.P. MIN. MAX. MIN. MAX. Max.

1160 15 1400 750 2300 1400 720 100 3600 12000 3400 16200 6750
860 116 3300 11000 3200 15300 6300
1460 17 1300 750 2200 1300
STANDARD H20 H200 1160 144 3050 10200 3000 14300 5700
(OT) 1760 20 1200 750 2000 1200
1460 172 2850 9500 2850 13500 5300
3460 30 1000 750 1600 1000 1760 200 2700 9000 2700 13000 5100
720 150 3750 13700 3750 18800 8200
1160 30 900 4400 2600
860 174 3550 13000 3600 17900 7800
H40 1460 35 850 4200 2500 H300 1160 216 3350 12200 3350 16700 7300
1460 258 3150 11500 3150 15700 6900
TWO-WAY 1760 40 800 4000 2400
1760 300 3000 11000 3000 15000 6600

Bl
(OF)
860 34 1450 6000 3600 720 175 4250 16300 4200 20000 9800
860 203 4050 15500 4000 19000 9300
1160 43 1300 5500 3300
H60 H350 1160 252 3750 14400 3750 17800 8600
1460 52 1250 5200 3100
1460 301 3550 13600 3500 16700 8200
1760 60 1200 5000 3000 1760 350 3400 13000 3400 16000 7800

860 46 2050 7400 1500 9700 4400 720 213 4650 18700 4750 25000 11200
STANDARD 860 246 4450 17900 4550 24000 10700

D.
HEAVY 1160 58 1950 6900 1500 9100 4100
HBO H425 1160 306 4150 16600 4200 22000 10000
(DTIDT) 1460 69 1800 6400 1500 8300 3800

••
1460 366 3900 15700 4000 21000 9400
1760 80 1700 6000 1500 8000 3000 1760 425 3800 15000 3800 20000 9000

660 63 2350 7400 1800 9700 4400 720 250 5250 18700 5250 25000 11200
860 290 5000 17900 5050 24000 10700
1160 80 2200 6900 1800 9100 4100
H110 HSOO 1160 360 4650 16600 4600 22000 10000
1460 95 2050 6400 1800 8500 3800
1460 430 4400 15700 4400 21000 9400
1760 110 1900 6000 1800 8000 3000 1760 500 4200 15000 4200 20000 9000
TWO-WAY

nr
720 63 2900 8500 2800 12200 5100 720 300 5500 20000 5450 26000 12000
HEAVY
(OF/OT) 860 72 2700 8000 2650 11600 4800 860 348 5200 19000 5250 25000 11400
H125 1160 90 2550 7500 2500 10800 4500 H600 1160 432 4900 17800 4850 23000 10700
1460 108 2400 7000 2300 10100 4200 1460 516 4600 16700 4600 22000 10000

H.
1760 125 2200 6500 2200 9500 3900 1760 600 4400 16000 4400 21000 9600

720 75 3050 9800 3150 15000 5900 720


660 87 2950 9400 3000 14300 5600 860
H150 1160 108 2750 8800 2800 13300 5300 H750 1160
1460 129 2600 8300 2600 12500 5000 1460 CONSULTFACTORY
1760 150 2500 8000 2500 12000 4800 1760 750 - - 10000 30000 10600

• Unless otherwise specified, Saudi Johnson Gear units are equipped with a thrust bearing arrangement necessitating a minimum downthrust to prevent
bearing separation. Ratings are shown in the Standard column apply, see above.
• When the downthrust exceeds the values of the STANDARD column, select a suitable size from the HEAVY THRUST column.
• When there are conditions of sustained upthrust, or minimum downthrust is not available in the installation, other bearing arrangement can be provided.

Power Ratings
The Johnson Gear Drive model number indicates the normal horsepower at 1760 RPM of the vertical
pump shaft. Horsepower and thrust capacities are based on vertical shaft speed and apply
regardless of gear ratios.

SERVICE FACTOR: Ratings in the catalog tables incorporate an adequate service factor for continuous duty
when driving a centrifugal or turbine type deep well pump. To select the correct size gear drive, use the
tabulated values directly to match the horsepower required by the pump. On other applications consult the
factory.
The AGMA service factor for the spiral bevel gears is 1.5 or greater. Specific values for given applications are
available on request.

10/01/2023
Dimensions

BX

��I 0
I >(
....J
><
DRIVE COUPLING

KEYSEAT"X"

1/2 PIPE TAP-COOLING WATER


FOR MODEL H60 AND UP

CD and H dimensions for all heavy thrust drives and U-XA-N and XD dimensions for all speed decreasing ratios in models Hl 50 and up are subject to change.

BX
MODEL CD D u XA N AG H BE BD AJ AK BB BF KEYSEATX
MAX STD.
XD

H20 14-1/2 6-3/8 1.1/8 13 2-3/4 18 3 5/8 10 9-1/8 8-1/4 3/1 5 7/16 1/4X 1/8 X2-1/4 1 + 1-1/4

H40(12) 20-1/4 9 1-1/2 16 3-1/2 24-3/4 4 3/4 12 9-118 8-1/4 3/16 7/16 3/8 X 3/16 X 2-3/4 1-1/2 + 1-3/4

H40 20-1/4 9 1-112 16 3-112 24-3/4 4 3/4 16-1/2 14-3/4 13-112 3/16 11/16 3/8 X 3/16 X 2-3/4 1-1/2 1 1-3/4

H60 20-1/4 9 1-1/2 16 3-1/2 24-3/4 4 3/4 16-1/2 14-3/4 13-1/2 3/16 11/15 3/8X3/16 X2-3/4 1-1/2 1 1-3/4

H80 20-1/4 9 1-7/8 16-1/2 3-1/2 24-3/4 4 3/4 16-1/2 14-3/4 13-112 3/16 11/15 112 X1/4X2-3/4 1-1/2 1-1/4 1-3/4

H110 25 11-3/8 2 17-1/2 3.1/2 29-1/2 4 1 16-1/2 14-3/4 13-1/2 3/16 11/16 1/2 X 1/4X2-¾ 1-1/2 1-1/4 2-1/8

H125 25 11-3/8 2 17-1/2 3-1/2 29-1/2 4 1 16-1/2 14-3/4 13-1/2 3/16 11/15 1/2 X 1/4X2-3/4 1-1/2 1-1/4 2-1/8

H150 30 13-1/4 2-7/16 20-1/2 4-3/4 34-1/2 4 1 20 14-3/4 13-1/2 3/16 11/16 5/8X5/16 X3-3/4 1-15/16 1-1/2 2-3/8

H200 30 13-1/4 2-7/16 20-1/2 4-3/4 34-1/2 4 1 20 14-3/4 13-1/2 3/16 11/15 5/8X5/16 X 3-3/4 1-15/16 1-1/2 2-3/8

H300 34-1/4 15 2-3/4 24 5-1/2 40 5-1/4 1-1/8 20 14-3/4 13-1/2 3/15 11/15 5/8X5/16 X 3-3/4 2 1-11/16 2-5/8

H350 38-1/2 16-1/2 2-3/4 29 5-1/2 46 7 1-1/4 24-1/4 22· 13-1/2 3/16 15/16 5/8 X 5/16 X 3-3/4 2-3/16 1-11'16 3

H425 39-1'2 16-1/2 3 30 5-3/4 46 6-1/4 1-1/4 24-1/4 22· 13-1/2 3/8 15/16 3/4 X 3/8 X4-¾ 2-7/16 1-15/16 3-3/8

HSOO 39-1/2 16-1/2 3.1/2 31 6-3/4 46 6-1/4 1-1/4 24-1/4 22· 13-1/2 3/8 15/15 7/8X7'1 s X 5-112 2-7'16 1-15/ 16 3-3/8

H600 42-1/2 16-1/2 3-3/4 33 7-1/2 51 8 1-1/4 24-1/4 22· 13-1/2 3/8 15'16 7/8X7f1 s X5-1/2 2-11/16 1-15/ 16 4

H750 45 20-112 3-3/4 33 7-1/2 56 11 1-5/16 24-1/4 22· 13-1/2 3/8 15/1 5 7/8 X 7/15 X 5-1/2 2-11'16 2-3/16 4

Tolerances: Shaft extensions+ 0.000-0.00 I


BX BZ BY XL
Base Rabbet AK+ 0.002, + 0.005
BORE BOLT CIRCLE TAP DEPTH KEYSEAT
Coupling Bore BX+ 0.0005+0.0015
*Also5/8-11 Tap on 14-3/4BoltCirc/e /"Deep 3/4 1-3/8 10-32 5/16 3/16 X 3/3 2

1 1-3/8 10-32 7/16 1/4X 1/8


+=Consult factory
1-3/16 1-3/4 1/4-20 7'16 1/4X 1/8
Dimensions in Inches
1-1/4 1-3/4 1/4-20 9/16 1/4X1/8

1-7/s 2-1/8 1/4-20 9/16 3/8 X 3/ 16

1-1/2 2-1/8 1/4-20 9/16 3/8 X 3/16

1-11/16 2-1/2 1/4-20 9/16 3/8 X 3' 16

1-15/16 2-1/2 1/4-20 11/15 112 X 1/4

2-3/16 3-1/4 3/8-16 11/1 6 112 X 1/4

2-7/s 3-1/4 3/8-16 11/16 5/8 X 5/15

2-11/16 3-3/4 3/8-16 11/16 5/8X5/16

10/01/2023
10/01/2023
Service & Warranty
Saudi Mechanical Industries provides a separate and fully
equipped centre for service and spare parts of Johnson
Gears. The centre caters for all requirements of service
maintenance, reproduction and itemized part sales. A
test station is the final step of service which guarantees
proper performance under actual field conditions.

The Johnson Right Angle Gear Drive is warranted to be


free from defects in materials and workmanship under
normal use and service for a period of one year from the
date of factory shipment. Warranty is only when operated
within the rated capacity for which it was supplied and in
accordance with recognized usage and practice.

Packing & Weights


Approximate Shipping Weights and Dimensions
Net Weight Gross Weight - Lbs. Box Dimensions - Inches Volume
Model
Lbs. Domestic Container Plywood Width Depth Height Cu.Ft.
H20 120 145 160 175 25 19 37 10
H40 240 265 280 295 25 19 37 10
H60 250 275 290 305 25 19 37 10
HBO 280 305 320 335 25 19 37 10
H110 385 410 425 440 25 19 37 10
H125 395 420 435 450 25 19 37 10
H150 640 680 700 720 33 23 44 19
H200 640 680 700 720 33 23 44 19
H300 900 1000 1000 1050 40 30 51 35
H350 1390 1500 1500 1550 46 30 52 42
H425 1590 1700 1700 1750 46 30 52 42
H500 1610 1720 1720 1770 46 30 52 42
H600 2050 2230 - 2230 50 31 59 53
Weights are for standard hollowshaft drives only. Refer to factory for other types.

©�
.
ISO 9002
"
(IQ )

10/01/2023
Ref. No:WFVT618 Rev. No:

Doc. No: FR-WFPM-SLS-03 Seq. No: 00

Consultant: Contractor:

Project Name: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
WFVT618 Rev. No:

FR-WFPM-SLS-03 00

: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
10/3/22, 9:30 AM WF-12F2 VT - Centrifugal Fire Pumps, Vertical Turbine | UL Product iQ

WF-12F2 VT - Centrifugal Fire Pumps, Vertical Turbine

Centrifugal Fire Pumps, Vertical Turbine


File Number: EX28268

COMPANY

WATERFALL PUMPS MANUFACTURING


Al T’tay, Warehouse no. 1-5,Plot No.2840764
Warehouse no.1-3, Plot No. 2840474
Dubai, 446054 United Arab Emirates

MODEL INFO

WF-12F2 VT
Centrifugal Fire Pumps, Vertical Turbine

RATING DETAILS

Rated Capacity, GPM (L/Min) Minimum Net Pressure Range, psig (kPa) Maximum Net Pressure Range, psig (kPa) Approx Speed, RPM Stages

750 (2,839) 77 (530) 257 (1,771) 2600 2-4

750 (2,839) 92 (634) 305 (2,102) 2800 2-4

750 (2,839) 100 (689) 330 (2,275) 2900 2-4

750 (2,839) 104 (717) 343 (2,364) 2950 2-4

750 (2,839) 108 (744) 355 (2,447) 3000 2-4

1,000 (3,785) 91 (627) 314 (2,164) 2950 2-4

1,000 (3,785) 95 (655) 326 (2,247) 3000 2-4

400 (1,514) 87 (599) 295 (2,033) 2600 2-4

400 (1,514) 102 (703) 347 (2,392) 2800 2-4

400 (1,514) 110 (758) 374 (2,578) 2900 2-4

400 (1,514) 115 (792) 388 (2,675) 2950 2-4

400 (1,514) 119 (820) 402 (2,771) 3000 2-4

450 (1,703) 88 (606) 286 (1,971) 2600 2-4

450 (1,703) 101 (696) 339 (2,337) 2800 2-4

450 (1,703) 108 (744) 367 (2,530) 2900 2-4

450 (1,703) 112 (772) 381 (2,626) 2950 2-4

450 (1,703) 116 (799) 396 (2,730) 3000 2-4

500 (1,892) 84 (579) 282 (1,944) 2600 2-4

500 (1,892) 100 (689) 331 (2,282) 2800 2-4

500 (1,892) 109 (751) 357 (2,461) 2900 2-4

500 (1,892) 113 (779) 370 (2,551) 2950 2-4

500 (1,892) 117 (806) 385 (2,654) 3000 2-4

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL Solutions' Follow - Up Service. Only those
products bearing the UL Mark should be considered to be Certified and covered under UL Solutions' Follow - Up Service. Always look for the Mark on the product.

UL Solutions permits the reproduction of the material contained in Product iQ subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or
Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from Product iQ with
permission from UL Solutions" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "©2022 UL LLC."

10/01/2023

https://iq.ulprospector.com/en/profile?e=4907864 1/1
10/3/22, 9:30 AM WF-12S4 VT - Centrifugal Fire Pumps, Vertical Turbine | UL Product iQ

WF-12S4 VT - Centrifugal Fire Pumps, Vertical Turbine

Centrifugal Fire Pumps, Vertical Turbine


File Number: EX28268

COMPANY

WATERFALL PUMPS MANUFACTURING


Al T’tay, Warehouse no. 1-5,Plot No.2840764
Warehouse no.1-3, Plot No. 2840474
Dubai, 446054 United Arab Emirates

MODEL INFO

WF-12S4 VT
Centrifugal Fire Pumps, Vertical Turbine

RATING DETAILS

Rated Capacity, GPM (L/Min) Minimum Net Pressure Range, psig (kPa) Maximum Net Pressure Range, psig (kPa) Approx Speed, RPM Stages

500 (1,892) 145 (999) 339 (2,337) 1780 5 - 10

750 (2,839) 129 (889) 154 (1,061) 1750 5

750 (2,839) 165 (1,137) 307 (2,116) 1750 6 - 10

750 (2,839) 136 (937) 159 (1,096) 1780 5

750 (2,839) 171 (1,179) 318 (2,192) 1780 6 - 10

1,000 (3,785) 120 (827) 292 (2,013) 1750 5 - 10

1,000 (3,785) 124 (854) 304 (2,096) 1780 5 - 10

300 (1,136) 145 (999) 348 (2,399) 1750 5 - 10

300 (1,136) 148 (1,020) 360 (2,482) 1780 5 - 10

400 (1,514) 137 (944) 334 (2,302) 1750 5 - 10

400 (1,514) 145 (999) 346 (2,385) 1780 5 - 10

450 (1,703) 137 (944) 332 (2,289) 1750 5 - 10

450 (1,703) 145 (999) 344 (2,371) 1780 5 - 10

500 (1,892) 137 (944) 327 (2,254) 1750 5 - 10

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL Solutions' Follow - Up Service. Only those
products bearing the UL Mark should be considered to be Certified and covered under UL Solutions' Follow - Up Service. Always look for the Mark on the product.

UL Solutions permits the reproduction of the material contained in Product iQ subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or
Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from Product iQ with
permission from UL Solutions" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "©2022 UL LLC."

10/01/2023

https://iq.ulprospector.com/en/profile?e=4915287 1/1
WFVT618 Rev. No:

FR-WFPM-SLS-03 00

: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
WFVT618 Rev. No:

FR-WFPM-SLS-03 00

: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
10/01/2023
10/01/2023
WFVT618

FR-WFPM-SLS-03 00

: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
CERTIFICATE OF COMPLIANCE
Certificate Number EX3971
Report Reference EX3971-20030507
Issue Date 2022-MARCH-07

Issued to: TORNATECH INC


Listee Company: 4100 Desserte Sud, (A-440 Ouest)
Laval
QC H7T 0H3 CANADA

Manufaturer Company: TORNATECH FZE


WAREHOUSE NO RA08CC04
JEBEL ALI FREE ZONE
DUBAI UNITED ARAB EMIRATES

This is to certify that PUMP CONTROLLERS, FIRE


representative samples of Model GPD Series controller for engine-driven centrifugal
fire pumps.

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 218 / CSA C22.2 No. 263-15, Fire Pump Controllers
UL 508, Industrial Control Equipment
NFPA 20, Installation of Stationary Pumps for Fire
Protection
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 1
10/01/2023
CERTIFICATE OF COMPLIANCE
Certificate Number EX3971
Report Reference EX3971-20061111
Issue Date 2022-AUGUST-18

Issued to: TORNATECH INC


Listee Company: 4100 Desserte Sud, (A-440 Ouest)
Laval QC H7T 0H3 CA

Manufaturer Company: Tornatech FZE


Warehouse No RA08CC04
Jebel Ali Free Zone
Dubai
AE

This is to certify that PUMP CONTROLLERS, FIRE


representative samples of See Addendum Page for Product Designation(s).

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 218 / CSA C22.2 No. 263-15, Fire Pump Controllers, UL 508,
Industrial Control Equipment, and NFPA 20, Installation of
Stationary Pumps for Fire Protection

Additional Information: See the UL Online Certifications Directory at


https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 2
10/01/2023
CERTIFICATE OF COMPLIANCE
Certificate Number EX3971
Report Reference EX3971-20061111
Issue Date 2022-AUGUST-18

This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.

Addendum:

Horsepower rated, Models GPA, GPP, GPR, GPS, GPV, GPY, or GPW; may be followed by a number
110 through 575 with - or /; followed by a number 200 through 600 with /; followed by a number 1
through 500 with /; followed by 1 or 3 with /; followed by 50 or 60 or 50/60.

Kilowatt rated, Models GPA, GPP, GPR, GPS, GPV, GPY, or GPW; followed by -400/; followed by a
number 0.75 through 560 with kW/; followed by 3 with /; followed by 50 or 60 or 50/60

Transfer Switches, horsepower rated, Models GPU; may be followed by a number 110 through 575
with - or /; followed by a number 200 through 600 with /; followed by a number 1 through 500 with /;
followed by 1 or 3 with /; followed by 50 or 60 or 50/60.

Transfer Switches, kilowatt rated, Models GPU; followed by -400/; followed by a number 0.75 through
560 with kW/; followed by 3 with /; followed by 50 or 60 or 50/60

Limited Service Fire Pump Controllers, horsepower rated, Models GPL; may be followed by a number
110 through 575 with - or /; followed by a number 200 through 600 with /; followed by a number 1
through 30 with /; followed by 1 or 3 with /; followed by 50 or 60 or 50/60.

Limited Service Fire Pump Controllers, kilowatt rated, Models GPL; followed by -400/; followed by a
number 0.75 through 22 with kW/; followed by 1 or 3 with /; followed by 50 or 60 or 50/60

Limited Service Transfer Switches, for connection to a second utility, horsepower rated, Models GLU;
may be followed by a number 110 through 575 with - or /; followed by a number 200 through 600 with /;
followed by a number 1 through 30 with /; followed by 1 or 3 with /; followed by 50 or 60 or 50/60.

Limited Service Transfer Switches, for connection to a second utility, kilowatt rated, Models GLU;
followed by -400/; followed by a number 0.75 through 22 with kW/; followed by 1 or 3 with /; followed by
50 or 60 or 50/60

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 2
10/01/2023
CERTIFICATE OF COMPLIANCE
Certificate Number E158750
Report Reference E158750-19940223
Issue Date 2022-MARCH-11

Issued to: TORNATECH INC


Listee Company: 4100 Desserte Sud, (A-440 Ouest)
Laval
QC H7T 0H3 CANADA

Manufaturer Company: TORNATECH FZE


WAREHOUSE NO RA08CC04
JEBEL ALI FREE ZONE
DUBAI UNITED ARAB EMIRATES

This is to certify that INDUSTRIAL CONTROL PANELS


representative samples of Industrial Control Panels.
Includes Jockey Pump Controller Models JP1, JP2, JP3,
JPY, JPD, DJP, and DJD; Remote Alarm Panel Models
APE, APEE, APD, APDD, and APED; Low Level Lockout
Panel Model LPL; and Low Suction Pressure Shutdown
Panel Model LPS. These models are not exhaustive.

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 508A, Industrial Control Panels


CSA C22.2 No. 14-13, Industrial Control Equipment
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 1
10/01/2023
Certificate of Compliance
This certificate is issued for the following:

Controllers for Electric Motor Driven and


Diesel Engine Driven Fire Pumps

Model GPx Series electric motor driven and


Model GPD diesel engine driven fire pump controllers
manufactured at Tornatech FZE in Dubai, UAE

Prepared for: Manufactured at:

TornaTech Inc. TornaTech FZE


7075 Pl Robert-Joncas, #132 Warehouse CC-4 near R/A 08
St Laurent, QC H4M 2Z2 P.O. Box 18435, Jebel Ali
Canada Dubai, United Arab Emirates

FM Approvals Class: 1321/1323

Approval Identification: 0003052698 Approval Granted: June 24, 2014

To verify the availability of the Approved product, please refer to www.approvalguide.com

Said Approval is subject to satisfactory field performance, continuing Surveillance Audits, and strict conformity to the
constructions as shown in the Approval Guide, an online resource of FM Approvals.

Richard B. Dunne
Manager, Fire Protection
FM Approvals
1151 Boston-Providence Turnpike
Norwood, MA 02062

10/01/2023
WFVT618

FR-WFPM-SLS-03 00

: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
1/19/2021 QWBS.EX27022 - Air-release Valves for Fire Pumps | UL Product iQ

QWBS.EX27022 - Air-release Valves for Fire Pumps

Air-release Valves for Fire Pumps


See General Information for Air-release Valves for Fire Pumps

GRISWOLD INDUSTRIES, DBA CLA-VAL CO EX27022


1701 PLACENTIA AVE
COSTA MESA, CA 92627-4416 USA
Air-release valves for use with split-case fire pumps.

Inlet Size Orifice Outlet Size Rated Pressure


Model NPT In. Size In. NPT In. psig

3410-AR332 1/2, 3/4 and 1 3/32 1/2 175

3410-AR116.3 1 1/16 1/2 300

3410-AR332KX 1/2, 3/4 and 1 3/32 1/2 175

Last Updated on 2019-04-29

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2021 UL LLC"

10/01/2023
https://iq.ulprospector.com/en/profile?e=142765 1/1
Air Release Valves
Air release valves permit trapped air to be released from sprinkler piping without losing water pressure. They are used on wet pipe
sprinkler systems and on casings of horizontal split case pumps. Unless otherwise noted in the listing, these valves have 175 psi
(1205 kPa) rated working pressure.

Models 3450AR-116 ,3475AR-116, 3410AR-116, 3450AR-116.3, 3475AR-116.3, 3410AR-116.3...

Product Specification

Size Orifice Diameter Rated Working Pressure


Model No Remarks
in (mm) in (mm) psi (kPa)
3450AR116.3 1/2 (13) 1/16 (2) 300 (2070) a
3475AR116.3 3/4 (19) 1/16 (2) 300 (2070) a
3410AR116.3 1 (25) 1/16 (2) 300 (2070) a
3450AR-116 1/2 (13) 1/16 (2) 300 (2070)
3475AR-116 3/4 (19) 1/16 (1.6) 300 (2070)
3410AR-116 1 (25) 1/16 (1.6) 300 (2070)
3450AR-332 1/2 (13) 3/32 (2.4) 175 (1205)
3475AR-332 3/4 (19) 3/32 (2.4) 175 (1205)
3410AR-332 1 (25) 3/32 (2.4) 175 (1205)
3450AR-116.3 1/2 (13) 1/16 (1.6) 300 (2070)
3475AR-116.3 3/4 (19) 1/16 (1.6) 300 (2070)
3410AR-116.3 1 (25) 1/16 (1.6) 300 (2070)

Remarks:
a. Valve supplied with a female NPT inlet end connection and a 1/2 inch female NPT outlet connection.

Company Name: Cla-Val Co.


Company Address: 1701 Placentia, Costa Mesa, California 92627, USA
Company Website: http://cla-val.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved
Class of Work: 1344-Air Release Valves

10/01/2023

© 2007-2021 FM Approvals. All rights reserved. Page 1 of 1


10/01/2023
10/01/2023
10/01/2023
10/01/2023
10/01/2023
3/8/22, 2:33 PM QXZQ.EX2855 - Fire Pump Relief Valves | UL Product iQ

QXZQ.EX2855 - Fire Pump Relief Valves


Fire Pump Relief Valves
GRISWOLD INDUSTRIES, DBA CLA-VAL CO EX2855
1701 PLACENTIA AVE
COSTA MESA, CA 92627-4416 United States

Nom Pipe

Max Relief

Body
Size,
End
(Set)

Model Type NPS Configuration* Pressure, psig

Fire pump relief valve

50B-4KG1 Globe 3,4,6,8 Class 150-F by F 250

50B-4KG1 Globe 3,4,6,8 Class 300 - F by F, G by G 300

50B-4KG1KOL Globe 3,4,6,8 Class 150-F by F 250

50B-4KG1KOL Globe 3,4,6 Class 300 - F by F, G by G 300

50B-4KG1KOL Globe 8 Class 300 - F by F 300

2050B-4KG1 Angle 3,4,6,8 Class 150-F by F 250

2050B-4KG1 Angle 3,4,6 Class 300 - F by F, G by G 300

2050B-4KG1 Angle 8 Class 300 - F by F 300

2050B-4KG1KOL Angle 3,4,6,8 Class 150-F by F 250

2050B-4KG1KOL Angle 3,4,6 Class 300 - F by F, G by G 300

2050B-4KG1KOL Angle 8 Class 300 - F by F 300

750B-4KG1 Wafer 3,4 Wafer 200

750B-4KG1 Globe 6,8,10 Class 150-F by F 200

750B-4KG1 Wafer 3,4 Wafer 300

750B-4KG1 Globe 6,8,10 Class 300 F by F 300

F - Flanged

T - Threaded

G- Grooved

KOL- indicates anti-cavitation seat.

* End configurations are intended to be installed on systems not exceeding end configurations' working capabilities.

Last Updated on 2021-10-21

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing
the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or
Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications
Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format:
"© 2022 UL LLC"

10/01/2023
https://iq.ulprospector.com/en/profile?e=143000 1/1
10/01/2023
10/01/2023
10/01/2023
WFVT618

FR-WFPM-SLS-03 00

: ‫ @ ﻣﺪارس اﻻﻳﻮاء‬KSA

10/01/2023
10/01/2023
10/01/2023
10/01/2023