ISBN 978-0-626-24068-4
SANS 10400-J:2010
Edition 3
SOUTH AFRICAN NATIONAL STANDARD
The application of the National Building
Regulations
Part J: Floors
Published by SABS Standards Division
1 Dr Lategan Road Groenkloof [8J Private Bag X191 Pretoria 0001
Tel: +27 12 428 7911 Fax: +27 12 344 1568
www.sabs.co.za
© SABS
SANS 10400-J:2010
Edition 3
Table of changes
Change No. Date Scope
Acknowledgement
The SABS Standards Division wishes to acknowledge the work of the South African Institution of Civil
Engineering in updating this document.
Foreword
This South African standard was approved by National Committee SABS TC 59, Construction
standards, in accordance with procedures of the SABS Standards Division, in compliance with annex 3
of the WTO/TBT agreement.
This document was published in October 2010.
This document supersedes the corresponding parts of SABS 0400:1990 (first revision).
Compliance with the requirements of this document will be deemed to be compliance with the
requirements of part J of the National Building Regulations, issued in terms of the National Building
Regulations and Building Standards Act, 1977 (Act No. 103 of 1977).
SANS 10400 consists of the following parts, under the general title The application of the National
Building Regulations:
Part A: General principles and requirements.
Part B: Structural design.
Part C: Dimensions.
Part D: Public safety.
Part F: Site operations.
Part G: Excavations.
Part H: Foundations.
Part J: Floors.
Part K: Walls.
Part L: Roofs.
Part M: Stairways.
SANS 10400-J:2010
Edition 3
Foreword (concluded)
Part N: Glazing.
Part O: Lighting and ventilation.
Part P: Drainage.
Part Q: Non-water-borne means of sanitary disposal.
Part R: Stormwater disposal.
Part S: Facilities for persons with disabilities.
Part T: Fire protection.
Part V: Space heating.
Part W: Fire installation.
This document should be read in conjunction with SANS 10400-A.
Annex A forms an integral part of this document.
SANS 10400-J:2010
Edition 3
Contents
Page
Acknowledgement
Foreword
1 Scope ..................................................................................................................................... 3
2 Normative references............................................................................................................. 3
3 Definitions .............................................................................................................................. 4
4 Requirements ......................................................................................................................... 6
4.1 General .......................................................................................................................... 6
4.2 Water-resistant floors .................................................................................................... 6
4.3 Suspended timber floors not exposed to the elements ................................................. 6
4.4 Floors supported on ground or filling ............................................................................ 10
Annex A (normative) National Building Regulations – Part J: Floors ....................................... 12
Bibliography............................................................................................................................... 13
SANS 10400-J:2010
Edition 3
The application of the National Building Regulations
Part J:
Floors
1 Scope
This part of SANS 10400 provides deemed-to-satisfy requirements for compliance with part J
(Floors) of the National Building Regulations.
NOTE 1 Part J of the National Building Regulations, issued in terms of the National Building Regulations and
Building Standards Act, 1977 (Act No. 103 of 1977), is reproduced in annex A.
NOTE 2 SANS 10400-B establishes the representative actions and impacts applied to floors, and the
structural response of floors to representative actions and impacts. Compliance with the requirements of this
part of SANS 10400 will result in floors performing in accordance with the structural design performance
parameters established in SANS 10400-B.
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies. Information on currently valid national
and international standards can be obtained from the SABS Standards Division.
SANS 629, Softwood flooring boards.
SANS 929, Plywood and composite board.
SANS 1460, Laminated timber (glulam).
SANS 1783-2, Sawn softwood timber – Part 2: Stress-graded structural timber and timber for frame
wall construction.
SANS 1931, Particle board – Highly moisture-resistant exterior type.
SANS 2001-CC1, Construction works – Part CC1: Concrete works (structural).
SANS 2001-CC2, Construction works – Part CC2: Concrete works (minor works).
SANS 2001-CT1, Construction works – Part CT1: Structural timberwork (flooring).
SANS 10005, The preservative treatment of timber.
SANS 10082, Timber frame buildings.
SANS 10400-J:2010
Edition 3
SANS 10109-1, Concrete floors – Part 1: Bases to concrete floors.
SANS 10177-2, Fire testing of materials, components and elements used in buildings – Part 2: Fire
resistance test for building elements.
SANS 10177-5, Fire testing of materials, components and elements used in buildings – Part 5: Non-
combustibility at 750 °C of building materials.
SANS 10400-A (SABS 0400-A), The application of the National Building Regulations – Part A:
General principles and requirements.
SANS 10400-B (SABS 0400-B), The application of the National Building Regulations – Part B:
Structural design.
SANS 10400-H (SABS 0400-H), The application of the National Building Regulations – Part H:
Foundations.
SANS 10400-T (SABS 0400-T), The application of the National Building Regulations – Part T: Fire
protection.
SANS 10400-V:2010, The application of the National Building Regulations – Part V: Space heating.
SANS 50312/EN 312, Particleboards – Specifications.
3 Definitions
For the purposes of this document, the definitions given in SANS 10400-A (some of which are
repeated for convenience) and the following apply.
3.1
accredited testing laboratory
laboratory that has been accredited by the South African National Accreditation System (SANAS)
3.2
Agrément certificate
certificate that confirms fitness-for-purpose of a non-standardized product, material or component or
the acceptability of the related non-standardized design and the conditions pertaining thereto (or
both) issued by the Board of Agrément South Africa
3.3
Board of Agrément South Africa
body that operates under the delegation of authority of the Minister of Public Works
3.4
competent person (civil engineering)
person who
a) is registered in terms of the Engineering Profession Act, 2000 (Act No. 46 of 2000), as either a
Professional Engineer or a Professional Engineering Technologist,
b) has a tertiary qualification (degree or diploma) in civil engineering, and
c) is generally recognized as having the necessary experience and training to undertake rational
assessments or rational designs in the field of civil engineering
3.5
deemed-to-satisfy requirement
non-mandatory requirement, the compliance with which ensures compliance with a functional
regulation
SANS 10400-J:2010
Edition 3
3.6
floor joist
horizontal beam which is the primary structural member in the construction of a timber floor
3.7
flooring board
board of face side width not less than 50 mm and not more than 140 mm, which may be tongued on
the one edge and grooved on the opposite edge
3.8
foundation
that part of a building which is in direct contact with, and is intended to transmit loads to, the ground
3.9
foundation wall
that portion of a wall between the foundation and the lowest floor above such foundation
3.10
functional regulation
regulation that sets out in qualitative terms what is required of a building or building element or
building component in respect of a particular characteristic, without specifying the method of
construction, dimensions or materials to be used
3.11
load
value of a force corresponding to an action
3.12
occupancy
particular use or the type of use to which a building or portion thereof is normally put or intended to
be put
NOTE Regulation A20 (see SANS 10400-A) classifies and designates occupancies.
3.13
sleeper wall
masonry wall constructed to support a suspended ground floor
3.14
sole plate
strip of timber which is laid on top of walls to level the underside of flooring joists
3.15
span
distance between the centres of supports
3.16
strip flooring
floor that comprises strips of width not less than 35 mm and not more than 90 mm and that are
tongued on the one edge and grooved on the opposite edge
3.17
suitable
capable of fulfilling or having fulfilled the intended function, or fit for its intended purpose
3.18
suspended floor
floor that spans supports
SANS 10400-J:2010
Edition 3
4 Requirements
4.1 General
The functional regulations contained in part J of the National Building Regulations (see annex A)
shall be deemed to be satisfied where
a) floors in any laundry, kitchen, shower room, bathroom or room containing a toilet pan or urinal
comply with the requirements of 4.2;
b) suspended floors are in accordance with the requirements of one of the following:
1) SANS 10400-B and SANS 10400-T;
2) SANS 10082; or
3) 4.3 in the case of occupancies classified as E4, H3, H4 and H5 (see Regulation A20 in
SANS 10400-A) in single-storey and double-storey buildings where floors are not exposed to
the elements;
c) slabs supported on the ground are in accordance with the requirements of
1) SANS 10400-B,
2) SANS 10400-H, or
3) 4.4; and
d) all timber (see Regulation A13(b) used in the erection of a building shall be preservative treated
in accordance with SANS 10005, as relevant.
4.2 Water-resistant floors
A water-resistant floor shall
a) be constructed of concrete in accordance with the requirements of SANS 2001-CC1 or
SANS 2001-CC2; or
b) comprise an impervious material, fit for its intended purpose, laid on top of, or bonded to, the
flooring system, which
1) can hold any surface water in such a manner that it prevents the flooring system from
deteriorating in any way until such time that the water can evaporate, be drained or be
removed, and
2) can accommodate any movement in the flooring system without losing its impermeable
properties.
4.3 Suspended timber floors not exposed to the elements
4.3.1 Floor joists, which are either built into walls with a minimum end bearing of 75 mm or bolted
to walls by means of joist hangers (see figures 1 and 2), shall comply with the requirements of
SANS 1460 or SANS 1783-2, shall be in accordance with the provisions of table 1 or table 2, and
shall comply with the requirements of SANS 2001-CT1.
NOTE 1 Joists under a Iong-term dead load will have a deflection to span ratio of less than 1:300.
NOTE 2 The availability of timber sizes should be confirmed.
SANS 10400-J:2010
Edition 3
a) Detail at sleeper wall b) Detail at external wall
c) Detail at internal wall
DPC = damp-proof course
Figure 1 — Bearing details for suspended timber ground floors
a) Joist built into wall b) Joist bolted to wall with joist hanger
All timber built into masonry shall be coated with carbolineum or a similar preservative.
Figure 2 — Bearing details for suspended timber floors other than ground floors
SANS 10400-J:2010
Edition 3
Table 1 — Maximum span for floor joists of sawn SA pine in H3 or H4 occupancy
classes in single-storey or double-storey buildings
1 2 3 4
Joist spacing
Width Depth 450 mm 600 mm
Maximum span
mm mm m
Grade 5
a
152 3,1 2,7
38 a 4,6 4,0
228
152 3,5 3,1
50 a
5,3 4,6
228
76 228 6,0 5,5
Grade 7
a
152 3,5 3,1
38
228 5,2 4,7
152 3,8 3,4
50
228 5,7 5,2
76 228 6,5 5,9
a
Commonly available sizes.
Table 2 — Maximum span for floor joists of laminated SA pine (grade 5 or higher)
in H3 or H4 occupancy classes in single-storey or double-storey buildings
1 2 3
Maximum span of joists at
Width Depth
600 mm centres
mm mm m
a
32 133 2,1
a
45 133 2,4
a
70 133 3,1
32 166 2,5
45 166 3,0
70 166 3,8
a
45 200 3,7
a
70 200 4,6
45 233 4,3
a
70 233 5,4
a
70 266 6,1
70 300 6,9
a
Commonly available sizes.
SANS 10400-J:2010
Edition 3
4.3.2 Timber flooring shall be in accordance with the provisions of table 3, shall comply with the
requirements of SANS 2001-CT1, and shall be fixed to floor joists at centres that do not exceed
600 mm.
Table 3 — Suspended timber floor specifications in
H3 or H4 occupancy classes in single-storey or double-storey buildings
1 2 3
Minimum thickness
Flooring type Specification
mm
Flooring board Flooring boards shall comply with the requirements of 22
SANS 629, or all of the following:
a) have a face side width of not less than 50 mm and not
more than 140 mm and shall be tongued on one edge
and grooved on the opposite edge with square-sawn
or end-matched ends;
b) be a softwood, derived from trees of the genera Pinus,
Cedrus, Podocarisus or Cypressus; or have a density
of more than 640 kg/m3 at a moisture content of 12 %;
c) be free of loose knots, pith, pitch pockets, in-bark or
pockets of parenchymatous tissue;
d) have individual, sound through-face knots and splay
knots of size that does not exceed one-quarter of the
width of the face side;
e) have tongues and grooves, which produce a tight
sliding fit, and a flush joint on the face side of boards;
and
f) have a length of at least 1,8 m if square-sawn at its
ends, or 0,6 m if matched.
Strip flooring Flooring shall comply with all of the following requirements: 20
a) have a density of more than 640 kg/m3 at a moisture
content of 12 %;
b) have a width between 35 mm and 90 mm and a
nominal length of not less than 460 mm;
c) be free of loose knots and knot holes that have a
diameter that exceeds 6 mm, or sound knots that have
a diameter that exceeds 20 mm; and
d) have tongues and grooves, which produce a tight
sliding fit, and a flush joint on the face side of the
strips.
Particle board Boards shall comply with the requirements of SANS 50312 20
or SANS 1931.
Composite and Boards shall comply with the requirements of SANS 929. 19
plywood board
SANS 10400-J:2010
Edition 3
4.3.3 The clearance between the under-surface of the ground floor joists and the ground beneath
shall be at least 450 mm (see figure 1). Access to the space below shall be provided for inspection
purposes and shall be fitted with covers or doors that prevent entry of rain, termites (in their flying
stage), reptiles and vermin. All debris and the like shall be removed from the void below such floors
upon completion.
4.3.4 Ventilation of the subfloor space in suspended ground floors shall be provided by means of
openings spaced not more than 2,4 m apart with at least one opening within 0,75 m of each corner.
The total area of ventilation openings provided shall be not less than 1 000 mm2 of unobstructed air
passage per square metre of floor area. All ventilation openings shall be fitted with corrosion-
resistant screening of nominal aperture that does not exceed 1,2 mm.
NOTE A 0,220 m × 0,170 m airbrick has an unobstructed area of between 0,006 m2 and 0,009 m2.
Accordingly, one such airbrick is required to serve between 6 m2 and 9 m2 of flooring.
4.3.5 Floor joists in suspended ground floors shall be set on and skew-nailed to sole plates that
have minimum dimensions of 38 mm × 76 mm on top of sleeper walls (see figure 2). Sleeper walls
shall be provided with sufficient openings to ensure good cross ventilation.
NOTE At the junction of solid and suspended floors, e.g. at verandahs, ventilation pipes might have to be
provided underneath solid concrete floors. Where sleeper walls are used, ventilation openings of size at least
115 mm × 75 mm spaced at 1,0 m centres should be provided.
4.3.6 Metal masonry anchors shall be of the expanding type, be corrosion resistant, have a
diameter and length of not less than 10 mm and 45 mm, respectively, and shall be installed in
accordance with the manufacturer’s instructions. Such anchors, when embedded in grade 20
concrete for standard test purposes, shall have a safe working load in shear of not less than 2,5 kN,
certified by the manufacturer. Such certification shall be substantiated by test report certificates
from an accredited testing laboratory.
4.3.7 Metal punched plate hangers shall have a zinc galvanized coating of not less than 275 g/m2
and shall bear a mark which readily identifies the manufacturer or supplier. Hangers shall be tested
by an accredited testing laboratory to demonstrate that, when bolted or nailed through predrilled or
prepunched holes into structural softwood (pine) members, they can transfer a permissible load of
at least 4,0 kN across the joint without slippage occurring.
4.3.8 No timber floor joist or trimmer or any other combustible material shall be built into any
hearth (see 4.4.3 of SANS 10400-V:2010), or within 200 mm of the inside of a chimney (see
4.3.1(c) of SANS 10400-V:2010), or penetrate a fire separation element.
4.4 Floors supported on ground or filling
4.4.1 A floor supported on ground or filling and which does not form an integral part of a foundation
system, does not pass over or is not supported on foundation walls, shall
a) be designed and constructed in accordance with the requirements of SANS 10109-1 under the
direction of a competent person (civil engineering); or
b) in the case of a building not used for storage or industrial purposes, be constructed of
1) impervious floor units, not less than 40 mm thick, consisting of slate, bricks, natural stone or
other suitable material; or
2) a plain grade 10 concrete slab where the slab does not serve as the final wearing surface, or
a plain grade 15 concrete slab where the slab serves as the final wearing surface, of thickness
not less than 75 mm, laid on a polyolefin underfloor membrane and constructed in
SANS 10400-J:2010
Edition 3
accordance with the requirements of SANS 2001-CC1, provided that any panel dimension
does not exceed
• 3,5 m where floors are covered with carpets and flexible floor covering, or
• 2,5 m where floors are covered with semi-flexible or rigid tiles.
NOTE 1 Plain concrete panels that have a panel dimension greater than 2,5 m and 3,5 m, depending
upon the proposed floor covering, fall outside the scope of 4.4.1(b)(2). Such slabs should be designed
by a competent person (civil engineering) or be fabric-reinforced in accordance with the requirements for
slab-on-the-ground foundations contained in SANS 10400-H to mitigate the effects of drying shrinkage.
NOTE 2 Plain concrete floors that comply with the requirements of 4.4.1(b)(2) should perform in
accordance with the relevant requirements of SANS 10400-B. Fabric reinforcement will be required to
improve performance to a lower category of expected damage (see SANS 10400-B). Guidance in this
regard is provided in SANS 10109-1.
NOTE 3 Finishes to concrete floors are described in SANS 10109-2.
4.4.2 A floor supported on ground or filling shall comply with the relevant requirements of
SANS 10400-B or SANS 10400-H should it
a) form an integral part of a foundation system;
b) be constructed of plain concrete and have any panel dimension exceeding 3,5 m; or
c) pass over or be supported on foundation walls.
4.4.3 Floors provided in terms of 4.4.1 and 4.4.2 shall be constructed level or have a slope that
does not exceed 4 mm/m.
4.4.4 Polyolefin underfloor membranes shall have a thickness of not less than 250 μm or be the
subject of an Agrément certificate and be provided where site and ground conditions necessitate
that the floor be underlain with such membranes. Such membranes shall be turned up around the
perimeter of the floors by at least the thickness of the floor and be provided with an overlap of
200 mm at joints. Penetrations by pipes, plumbing fittings or punctures shall be taped with a
pressure-sensitive adhesive tape approved for such use by the manufacturer.
4.4.5 Filling beneath floors constructed in accordance with 4.4.1(b) shall comprise material that
a) contains little or no organic material (material produced by animal or plant activities);
b) excludes stones of average dimensions larger than 75 mm;
c) does not contain more than 10 % rock or hard fragments of material retained on a sieve of
nominal aperture size 50 mm;
d) does not contain large clay lumps that do not break up under the action of compaction, nor be a
predominantly clayey material; and
e) can be placed without significant voids.
4.4.6 Filling shall be moistened before compaction so that a handful squeezed in the hand is firm,
but does not show signs of moisture. Filling shall be placed in uncompacted layers not exceeding
100 mm in respect of hand compaction or 150 mm in respect of compaction by mechanical means.
Each layer shall be well compacted before additional fill material is added.
4.4.7 A competent person (civil engineering) shall design and inspect fills where the maximum
height of fill beneath floors, measured at any point, exceeds 400 mm.
Annex A
(normative)
National Building Regulations
Part J: Floors
Definitions
adequate
adequate
a) in the opinion of any local authority, or
b) in relation to any document issued by the council, in the opinion of the council
fire resistance
shortest period for which a building element or building component will comply with the
requirements for stability, integrity and insulation when tested in accordance with the relevant
provisions of SANS 10177-2
non-combustible
classified as non-combustible when tested in accordance with SANS 10177-5
Regulations
J1 General requirement
(1) Any floor of any building shall –
(a) be designed and constructed to safely support its own weight and any actions which can
reasonably be expected to occur and in such a manner that any local damage (including
cracking), deformation or vibration do not compromise the efficient use of the building or
the functioning of equipment supported by such floor; and
(b) have a fire resistance appropriate to its use and where required, be non-combustible.
(2) The floor of any laundry, kitchen, shower-room, bathroom or room containing a toilet pan or
urinal shall be water-resistant.
(3) Any suspended timber floor in a building shall be provided with adequate under-floor
ventilation.
(4) Where any concrete floor slab is supported on ground or filling, such floor shall be so
constructed that any moisture present in such ground or filling is prevented from penetrating
such concrete floor slab.
(5) The requirements of subregulations (1), (2), (3) and (4) shall be deemed to be satisfied
where the design and construction of any floor complies with SANS 10400-J: Provided that
where the local authority deems it necessary in order to satisfy the requirements of
subregulation (4), such local authority may require that the entire area within the foundation
walls of any building be covered by a suitable damp-proof membrane, and in the case of the
floor of a basement or semi-basement where the highest known level of the extreme
watertable is higher than the floor level of the basement to such an extent that uplift of the floor
might occur, the local authority may require that adequate sub-soil drains under the floor be
provided together with means of removing the water so drained.
12
Bibliography
SANS 10109-2, Concrete floors – Part 2: Finishes to concrete floors.
© SABS
13
This page has been left blank intentionally
SABS – Standards Division
The objective of the SABS Standards Division is to develop, promote and maintain South African
National Standards. This objective is incorporated in the Standards Act, 2008 (Act No. 8 of 2008).
Amendments and Revisions
South African National Standards are updated by amendment or revision. Users of South African
National Standards should ensure that they possess the latest amendments or editions.
The SABS continuously strives to improve the quality of its products and services and would
therefore be grateful if anyone finding an inaccuracy or ambiguity while using this standard would
inform the secretary of the technical committee responsible, the identity of which can be found in
the foreword.
Tel: +27 (0) 12 428 6666 Fax: +27 (0) 12 428 6928
The SABS offers an individual notification service, which ensures that subscribers automatically
receive notification regarding amendments and revisions to South African National Standards.
Tel: +27 (0) 12 428 6883 Fax: +27 (0) 12 428 6928 E-mail: [email protected]
Buying Standards
Contact the Sales Office for South African and international standards, which are available in both
electronic and hardcopy format.
Tel: +27 (0) 12 428 6883 Fax: +27 (0) 12 428 6928 E-mail: [email protected]
South African National Standards are also available online from the SABS website
http://www.sabs.co.za
Information on Standards
The Standards Information Centre provides a wide range of standards-related information on both
national and international standards, and is the official WTO/TBT enquiry point for South Africa. The
Centre also offers an individual updating service called INFOPLUS, which ensures that subscribers
automatically receive notification regarding amendments to, and revisions of, international
standards.
Tel: +27 (0) 12 428 6666 Fax: +27 (0) 12 428 6928 E-mail: [email protected]
Copyright
The copyright in a South African National Standard or any other publication published by the SABS
Standards Division vests in the SABS. Unless exemption has been granted, no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any means without prior
written permission from the SABS Standards Division. This does not preclude the free use, in the
course of implementing the standard, of necessary details such as symbols, and size, type or grade
designations. If these details are to be used for any purpose other than implementation, prior written
permission must be obtained.
Details and advice can be obtained from the Senior Manager.
Tel: +27 (0) 12 428 6666 Fax: +27 (0) 12 428 6928 E-mail:
[email protected]