Mebay
Mebay
Software Version
No. Version Date Note
1 V1.0 2021-08-13 Original release.
2
HMI-07 CONTROLLER USER MANUAL
Symbol Description
Symbol Description
3
HMI-07 CONTROLLER USER MANUAL
Warning
1.The installation of this equipment must be carried out by professionals.
2.When installing and operating the controller, please read the entire instruction
manual first.
3.Any maintenance and commissioning of the equipment must be familiar with all the
equipment.
4.Safety standards and precautions in advance, otherwise it may cause personal
injury or damage to related equipment.
5.After the installation of the controller is completed, please verify that all protection
functions are valid.
4
HMI-07 CONTROLLER USER MANUAL
Catalogue
Summary................................................................................................................................... 6
Main Features........................................................................................................................... 6
Parameters................................................................................................................................8
Fault finding............................................................................................................................ 11
Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form (including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.
5
HMI-07 CONTROLLER USER MANUAL
Summary
HMI-07 is a reliable remote monitoring controller that can monitor multiple or
single generator sets at the same time. It has the functions of data monitoring, alarm
display, generator set start-up and shutdown.
HMI-07 controller adopts 7inch 800*480 large screen high resolution LCD
display. Brand new UI monitoring design, touch screen operation, LCD man-machine
interface display.
HMI-07 controller is designed with 4-core high-frequency processing, and
communicates with DC100D MK2 generator set controller through RS485 interface.
The parameters of the generator set can be directly read out through the
communication interface and displayed on HMI-07 controller.
Main Features
7 inch 800*480 large screen high resolution LCD display, user’s language set if
necessary.
One or up to four DC100D MK2 genset controllers can be monitored remotely.
High-end ARM Cortex architecture microprocessor core, LCD man-machine
interface display, touch screen operation.
Real-time display of generator set parameters and alarm information detected by
the DC100D MK2 controller.
HMI-07 is able to control detailed parameters and keys operation of DC100DMK2
generator set controller.
With 2 USB ports.
A serial compatible interface (COM1_RS232, COM2_RS485, COM3_RS485) .
Standard water-proof rubber gasket. The waterproof can reach IP65.
Module design: All the connections are adapted with European connectors so that
installation, connection, repair and replacement can be more easily.
6
HMI-07 CONTROLLER USER MANUAL
Manual Pressing this key will set the module into manual mode.
Auto Pressing this key will set the module into auto mode.
7
HMI-07 CONTROLLER USER MANUAL
Parameters
Options Parameters
Working voltage DC 24V±20%
Power consumption 6W
DB9 serial port COM1(RS232),COM2(RS485),COM3(RS485)
USB Port 1xUSB Host;; 1xUSB Slave
LAN Port NA
Working condition 0-45℃; 5%-90% non-condensing
Storage condition -10-60℃; 5%-90% non-condensing
IP65: when waterproof rubber gasket is added between
Protection Level
controller and its panel
Overall dimension 203mm*149mm*30mm
Panel cutout 182*138mm
8
HMI-07 CONTROLLER USER MANUAL
+
24V DC COM2 485+
- RS485 3#DC100D MK2
COM2 485- Module address:3
GND
RS485
HMI-07
COM3 485+
RS485 2#DC100D MK2
COM3 485-
Module address:2
GND
Note: Communication line need use shielded line, if the distance is close, not
need to be connected to the shielded layer.
Note: Please unplug HMI-07 power cable before wiring to avoid electric shock
or accident.
Note: HMI-07 communicates with DC100D MK2 via RS485 communication port,
using the matched communication line, one end (DB9) connects with DC100D MK2,
and the other end, which has 6 lines (two communication ports). 1#485+ and 1#485-
are one communication port, which can connect with two DC100D MK2 controllers
(communication address can be set as 1, 3 ); 2#485+ and 2#485- are the other
communication port, which can connect with two DC100D Mk2 controllers
(communication address can be set as 2, 4 ).
9
HMI-07 CONTROLLER USER MANUAL
The controller is fixed by four special fixing members and screws, and the screws
of the metal fasteners cannot be too tight.
Panel Cutout: W192mm*H138mm.
Note: HMI-07 controller is suitable for 24V DC battery voltage. Beyond this
range, the controller may not work properly or damage the controller;
10
HMI-07 CONTROLLER USER MANUAL
Fault finding
Symptoms Possible Solutions
Controller no Please make sure that the DC24V power supply is correctly
response with power connected to HMI-07.
Check the USB connection.
USB communication Check whether the USB port of the computer is normal.
is abnormal Check whether the USB driver is installed.
Check whether the controller is normally powered on.
Check the connection.
RS485 cannot Check if the communication ID number setting is correct.
communicate Check if the A and B lines of RS485 are reversed.
normally Check if the communication port of the PC is damaged.
Add a 100 Ω resistor between the AB of the controller RS485.
Precautions for the Do not push hard or use hard objects to press the HMI-07
display display screen.
11