0% found this document useful (0 votes)
28 views4 pages

Switch Amplifier KCD2-SOT-1.LB: Function

This device provides galvanic isolation between field circuits and control circuits. It transfers digital signals from the field to the control system. It has one input that controls two passive transistor outputs. It has a 24V DC power supply and can be used as a signal splitter or conditioner with reversible operation modes. Key specifications include SIL 2 safety rating, 1-channel input, 2 outputs, and 12.5mm housing width.

Uploaded by

Amir Kalčo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views4 pages

Switch Amplifier KCD2-SOT-1.LB: Function

This device provides galvanic isolation between field circuits and control circuits. It transfers digital signals from the field to the control system. It has one input that controls two passive transistor outputs. It has a 24V DC power supply and can be used as a signal splitter or conditioner with reversible operation modes. Key specifications include SIL 2 safety rating, 1-channel input, 2 outputs, and 12.5mm housing width.

Uploaded by

Amir Kalčo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Switch Amplifier

KCD2-SOT-1.LB
< 1-channel signal conditioner
< 24 V DC supply (Power Rail)
< Dry contact or NAMUR input
< 2 passive transistor outputs
< Usable as signal splitter (1 input and 2 outputs)
< Reversible mode of operation
< Line fault detection (LFD)
< Housing width 12.5 mm
< Up to SIL 2 (SC 3) acc. to IEC/EN 61508

Function
This signal conditioner provides the galvanic isolation between field circuits and control circuits.
The device transfers digital signals (NAMUR sensors or dry contacts) from the field to the control system.
The input controls two passive transistor outputs.
Via switches the mode of operation can be reversed and the line fault detection can be switched off.
Via switch the function of the second output can be defined as a signal output or an error output.
A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.

Connection

KCD2-SOT-1.LB

1+ 5+
10 kΩ I
2- 6-
400 Ω ≤ R ≤ 2 kΩ

7+
II
8-

9+
10-
24 V DC
Release date: 2023-01-03 Date of issue: 2023-01-03 Filename: 214246_eng.pdf

Fault 24 V DC
Power Rail

Technical Data
General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage Ur 19 ... 30 V DC
Ripple ≤ 10 %
Rated current Ir 20 ... 15 mA
Power dissipation ≤ 700 mW including maximum power dissipation in the output

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 1
Switch Amplifier KCD2-SOT-1.LB
Technical Data
Input
Connection side field side
Connection terminals 1+, 2-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio min. 100 µs / min. 100 µs
Output
Connection side control side
Connection output I: terminals 5, 6 ; output II: terminals 7, 8
Rated voltage Ur 30 V DC
Rated current Ir 50 mA
Response time ≤ 200 µs
Signal level 1-signal: (external voltage) - 3 V max. for 50 mA
0-signal: blocked output (off-state current ≤ 10 µA)
Output I signal ; Transistor
Output II signal or fault message ; Transistor
Collective error message Power Rail
Transfer characteristics
Switching frequency ≤ 5 kHz
Galvanic isolation
Input/Output reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Input/power supply reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Output/power supply basic insulation according to EN 50178, rated insulation voltage 50 Veff
Output/Output basic insulation according to EN 50178, rated insulation voltage 50 Veff
Indicators/settings
Display elements LEDs
Control elements DIP switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Protection against electrical shock IEC 61010-1:2010
Release date: 2023-01-03 Date of issue: 2023-01-03 Filename: 214246_eng.pdf

Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
extended ambient temperature range up to 70 °C (158 °F), refer to manual for
necessary mounting conditions
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals
where applicable. For information see www.pepperl-fuchs.com.

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 2
Switch Amplifier KCD2-SOT-1.LB
Assembly

Front view Removable terminal


green

LED green:
1 2
3 4 Power supply

KCD2-SOT-
1.LB LED yellow/red:
PWR
Status output/
Fault signal
OUT/CHK

S1
S2
S3
S4
I II

Switch 1 ... 4
5 6
7 8
9 10

Removable terminals
green

Matching System Components


KFD2-EB2 Power Feed Module

UPR-03 Universal Power Rail with end caps and cover, 3 conductors, length: 2 m

UPR-03-M Universal Power Rail with end caps and cover, 3 conductors, length: 1,6 m

UPR-03-S Universal Power Rail with end caps and cover, 3 conductors, length: 0.8 m

K-DUCT-GY Profile rail, wiring comb field side, gray

K-DUCT-GY-UPR-03 Profile rail with UPR-03-* insert, 3 conductors, wiring comb field side, gray
Release date: 2023-01-03 Date of issue: 2023-01-03 Filename: 214246_eng.pdf

Accessories
KC-ST-5GN Terminal block for KC modules, 2-pin screw terminal, green

KF-CP Red coding pins, packaging unit: 20 x 6

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 3
Switch Amplifier KCD2-SOT-1.LB

Configuration

S1
S1
S2 S2
S3
S4
I II
S3
S4
I II

Switch settings

S Function Position
1 Mode of operation output I (active) with high input current I
with low input current II
2 Assignment output II Switching state like output I I
Fault indication output (passive if fault) II
3 Line fault detection of the input ON I
OFF II
4 no function

Operating states

Control circuit Input signal


Initiator high impedance/contact opened low input current
Initiator low impedance/contact closed high input current
Lead breakage, lead short circuit Line fault

Factory setting: switch 1, 2, 3 and 4 in position I


Release date: 2023-01-03 Date of issue: 2023-01-03 Filename: 214246_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

4
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]