0% found this document useful (0 votes)
48 views2 pages

CTV SLB031 en - 05192020

Uploaded by

Nguyen Thuong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views2 pages

CTV SLB031 en - 05192020

Uploaded by

Nguyen Thuong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Adaptive Frequency™ Drive

Remote-Mounted Drive
CenTraVac™ chiller models CVHE/CVHF
460/480V and 575/600V 60 Hz applications

Adaptive Frequency™ Drives


While chiller efficiencies have improved dramatically
over the past twenty years, for most commercial
buildings the single largest energy user is still the
chilled water system. A Trane® Adaptive Frequency
Drive (AFD) can improve chilled water system
efficiency without sacrificing comfort. Adaptive
Frequency is a trademarked term for a Trane variable
speed drive which is made to Trane specifications and
uses proprietary control logic.

A variable speed drive maximizes chiller efficiency


and reduces power consumption by adapting the
compressor motor speed and inlet guide vanes to the
chiller operating temperatures.

Features and benefits


Energy reduction
Conventional chillers use inlet guide vanes to provide
stable operation at part load conditions. Capacity Patented Adaptive Control™ chiller controller
is reduced by closing the vanes while maintaining a The combination of speed control and inlet guide vane
constant motor speed. position is optimized mathematically and controlled
simultaneously to meet the dual requirements of water
While AFDs can increase the off-design efficiency of temperature control and efficiency.
chillers, adding them for every application may not be
appropriate. Intelligent control of the condenser and Tracer AdaptiView™ AFD control reaches the optimum
chilled water temperatures is crucial for AFD savings in speed faster, responds to changes more quickly, and
chiller system applications. provides improved water temperature stability. The
chiller controller reduces speed to the surge boundary
As with any chiller plant design strategy, it’s important based on the current differential operating pressure,
to look at various alternatives and use tools such making instantaneous corrections to speed and guide
as Trane System Analyzer™ or TRACE™ 700 HVAC vane settings as conditions change, to optimize chiller
system analysis software programs to determine the efficiency.
best overall design strategy.

The myPLV™ Chiller Performance Evaluation Tool


provides a simple tool for quick and reliable chiller
economic comparisons considering both full and part
load ratings. To learn more or to download a free copy
of the myPLV tool, please visit www.trane.com/myPLV.
Remote (free-standing) AFD A Air Exhaust
The compact design of this AFD offers a flexible option
B Circuit Breaker
for installation in mechanical rooms in which space is
limited and a unit-mounted drive may not fit. The AFD C AFD Display Interface
is designed for front access only and ships completely
factory-tested and wired. D Lockable Enclosure

The drive has a DC link choke that minimizes harmonic E Low Voltage Access Door
distortion and results in a Total Demand Distortion
F Air Intake (filter on inside)
(TDD) of approximately 30%.
G Top Line Power Entry
Design information
H AFD Rectifier and Inverter
Tonnage range: CenTraVac chillers, 120-1600 tons. (with top cover removed)
Voltage: 460/480V and 575/600V 60 Hz input power,
±10%. I Control Power Transformer
Efficiency: Minimum efficiency of 97% at rated load.
G
Power factor: Displacement power factor of 0.96 at all A
loads.
B B
Enclosure: NEMA 1 ventilated enclosure1 with tested C
short circuit current rating (SCCR) of 65,000 amps. H
D
Includes padlockable door-mounted circuit breaker/ G
E
shunt trip with ampere interrupting capacity (AIC) rating
of 65,000 amps.2 The entire package is UL/CUL listed.
1 option for NEMA 12 enclosure
2 SCCR/AIC of 65,000 amps standard for 460/480V with option for 100,000 amps.
I
F

Data Table

460/480V 575/600V Dimensions (inches) Estimated


Frame Power (hp) Max. Amps Power (hp) Max. Amps Width Depth Height Weight (lbs.)
D3h 150-200 213 150-200 171 48 24 86 953
250-350 394 250-400 356 48 24 86 1158
D4h
450 476 56 24 90 1292
500-600 649 450 400 56 24 90 1634
E2
500-650 560 64 24 90 1681
650-750 791 750-1050 840 127 24 90 2885
F3
900-1100 1031 127 24 90 2885
F4 1200-1350 1360 1150-1350 1120 150 24 90 3419

Weights and dimensions are provided for general information only. Always refer to the Trane submittal package for information
specific to your chiller.

Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy efficient indoor
environments through a broad portfolio of heating, ventilating and air conditioning systems and controls, services,
parts and supply. For more information, please visit trane.com or tranetechnologies.com.

All trademarks referenced in this document are the trademarks of their respective owners. © 2020 Trane. All Rights Reserved.
CTV-SLB031-EN
05/19/2020

You might also like