Features: MINIPLEX Transponders With ES-PS Power Supplies

The document describes 4100ES MINIPLEX transponders that allow remotely located initiating and notification functions by connecting to a host 4100ES Fire Alarm Control Panel using Simplex remote unit interface communications. Transponders provide the same initiating and notification functions as the host panel and support conventional and addressable devices. They also have local mode operation to provide default fire alarm response if communications are lost with the host panel.

Uploaded by

Cost Roots
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
120 views12 pages

Features: MINIPLEX Transponders With ES-PS Power Supplies

The document describes 4100ES MINIPLEX transponders that allow remotely located initiating and notification functions by connecting to a host 4100ES Fire Alarm Control Panel using Simplex remote unit interface communications. Transponders provide the same initiating and notification functions as the host panel and support conventional and addressable devices. They also have local mode operation to provide default fire alarm response if communications are lost with the host panel.

Uploaded by

Cost Roots
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

4100ES Fire Control Units

UL, ULC, CSFM Listed; FM Approved, MINIPLEX Transponders with ES-PS Power Supplies
OTCR/NYC Approved*

Features • ULC/ORD-C100 Smoke Control System Equipment (UUKL7)

4100ES Series MINIPLEX transponders allow remotely located


Introduction
initiating and notification functions:
4100ES MINIPLEX transponders connect to a host 4100ES Fire
• Transponder operation is available as standard or with local mode Alarm Control Panel using Simplex remote unit interface (RUI)
operation communications. At the transponder, RUI communications are received
by the transponder interface module and translated into the same
• Communications with the host fire alarm control panel use the Remote
internal communications format that is used in the host control panel.
Unit Interface (RUI and RUI+) formats
Remotely located modules. With RUI communications, the
Initiating functions include: transponder can remotely provide the same initiating and notification
functions that occur at the host control panel without requiring multiple
• Conventional initiating device circuit (IDC) support long distance wiring runs. Connections to the host panel are low current
• Addressable device support including TrueAlarm analog sensor communications and audio wiring with distances up to 2500 ft (762 m).
compatibility Please refer to document S4100-1031 and the other documents listed
Notification functions include: in Additional 4100ES Product Reference for additional information
concerning the extensive initiating and notification features of the
• Addressable strobe and horn notification using enhanced power 4100ES fire alarm control panels.
delivery IDNAC SLCs
• Conventional DC notification appliance circuits including TrueAlert
strobe and horn appliances
• Emergency voice/alarm communications

Local mode operation provides:

• Default local initiating and notification operation in the event of a


communications loss with the host control panel
• Enabling of an optional Local Mode Controller with a local alarm
sounder, LED status indicators, and keyswitch enabled control switches
• Support for conventional Initiating Device Circuits (IDC's), conventional
Notification Appliance Circuits (NAC's), addressable IDNet devices,
addressable IDNAC notification appliances, and default output tones
from local amplifiers

Optional modules include:

• Digital or Analog audio riser modules for connection to system audio


signals
• Digital or analog input audio amplifiers with integral on-board NACs
• Power supplies with or without battery chargers
• City Connect modules and RS-232 ports for printers or maintenance
terminals
• Alarm relays, auxiliary relays, additional IDC modules, and NAC Figure 1: Typical 4100ES MINIPLEX System One-Line Drawing
expansion modules

NEMA 1/IP30 cabinets are equipped with solid doors (platinum or


Module Bay Description
red) and in one, two, or three bay sizes Transponder model 4100-9600 includes a bay assembly, a power
distribution interface module (PDI), a Basic Transponder Interface
Listed to: Module, and an interconnect harness. Communications with the host
fire alarm control panel are via a Remote Unit Interface (RUI) connection
• UL 864, Fire Detection and Control (UOJZ), Smoke Control Service that allows for up to 2500 ft (762 m) distance. RUI can communicate with
(UUKL), Releasing Device Service (SYZV), Emergency Communication up to a total of 31 remote devices and can be either Class B or Class X
and Relocation Equipment (UOQY) communications.
• UL 1076, Proprietary Alarm Units - Burglar (APOU) Transponder model 4100-9601 substitutes a Local Mode Transponder
• UL 2017, Process Management Equipment (QVAX), Emergency Alarm Module for the Basic Transponder Module.
System Control Units (FSZI) Optional Expansion Bays each include a PDI and accept a variety of
• UL 1730, Smoke Detector Monitor (UULH) optional modules (refer to tables from MINIPLEX Transponder Product
• UL 2572, Mass Notification Systems (PGWM) Selection onwards).
• CAN/ULC-S527 Control Units for Fire Alarm Systems (UOJZ7), Releasing The Battery Compartment (bottom) accepts two batteries, up to 50
Device Service (SYZV7) Ah, that can be mounted within the cabinet. Battery mounting does
• CAN/ULC-S559 Central Station Fire Alarm System Units (DAYR7) not interfere with available module space. A power supply with battery
charger is required for each battery set.
• ULC/ORD-C1076 Proprietary Burglar Alarm Units and Systems (APOU7)

* Additional listings may be applicable; contact your local Simplex product supplier for the latest status.

S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

Packaging Availability
• Modules are power-limited (except as noted, such as battery chargers, city circuits and relay modules)
• Enclosure are available for one, two, or three bay sizes or for cabinet rack mounting
• NEMA 1/IP30 boxes and solid doors are available in platinum or red (ordered separately)
• Up to eight close-nippled cabinets can be connected at one transponder location (close-nippled is mounted within 20 ft (6 m) and with
interconnecting wiring enclosed in conduit)
• Refer to document S4100-0037 for enclosure details.

Local Mode Control Operation


Default Stand-Alone Operation. In the event of a communications loss with the host fire alarm control panel, model 4100-9601 MINIPLEX Local
Mode Transponders provide fire alarm response default operation for its connected devices and appliances per the following:
Input Operation. During local mode operation, conventional initiating devices and addressable IDNet initiating devices shall be capable of reporting
an alarm condition to the MINIPLEX transponder. TrueAlarm sensors will cause an alarm at their least sensitive alarm threshold:
• Photoelectric sensors will alarm at 3.7%/ft smoke obscuration
• Heat sensors will alarm at a fixed temperature of 135 °F (57 °C)
• TrueAlarm device LEDs will be activated to indicate a device in alarm
Notification Operation. Fire alarm conditions reported against a fire alarm point type within a transponder in local mode will cause all notification
appliance circuits in that transponder to:
• Sound a general alarm temporal pattern horn tone
• Activate visible notification appliance circuits
Local Mode Module Support. Local mode operation provides support for the following MINIPLEX transponder circuits:
• Conventional NAC and addressable IDNAC notification appliance circuits, operated at a temporal pattern,
• IDNet, IDNet 2 and IDNet 2+2 addressable device circuits
• 4100ES amplifiers will provide their on-board horn tones (500 Hz) at a temporal pattern through their on-board amplifier NACs
• Firefighter Telephone control modules in local mode
Local Mode Operation Module Exclusion. Modules and circuits not listed above but that are listed as compatible with MINIPLEX transponders per
this document, do not interfere with local mode operation but are not supported during local mode operation.

Local Mode Controller


Operation. During local mode operation, an optional Local Mode Controller will indicate status (see Figure 2) and can be enabled using a
keyswitch to perform local alarm silence or reset. If alarms occurring during local mode are reset using a Local Mode Controller, upon restoration of
communications, those alarms will not be sent to the master controller. If alarms are still present upon restoration of communications, then the
alarm condition will be reported and host fire alarm control panel programmed alarm functions will occur. When communications are re-established,
the local mode transponder restores automatically.
Mounting. Local Mode Controllers are mounted on three-gang plates, are available in beige or red, and for either flush or semi-flush mounting. (See
Local Mode Controller and 579-343 operating instructions for details).

Figure 2: Local Mode Controller Module

Page 2 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

Typical Multi-Floor MINIPLEX Audio System

Page 3 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

Expansion Bay Module Loading Reference

Size Definitions: Block = 4" W x 5" H (102 mm x 127 mm) card area
Slot = 2" W x 8" H (51 mm x 203 mm) motherboard with daughter card

Description Mounting
Transponder Interface Modules Block A
Audio Riser Modules Block B
Terminal Block Module 1 Block
IDNet 2 and IDNet 2+2 Modules 1 Block
4, 2 A Relays 1 Block
4, 10 A Relays NON Power-limited 4", 2 Slots
8, 3 A Relays 1 Block
VESDA Interface 2", 1 Slot
8 Point Zone/Relay Card 1 Block
Class B IDC 2", 1 Slot
Class A IDC 2", 1 Slot
MAPNET II Module 4", 2 Slots
MAPNET II Isolator 2", 1 Slot
Decoder Module 6", 3 Slots
Flex-35 Amplifiers, 2 max /bay* Blocks E & F; C & D; or A & B
Flex-50 Amplifiers, 2 max/bay* Blocks E & F or C & D
100 W Amplifiers, 1 max/bay Blocks E, F, G & H
100 W Backup Amplifiers, 1 max. per bay with primary amplifier Blocks A, B, C & D
Telephone Expansion Module 1 Block
Expansion Signal Module 1 Block
NAC Card 1 Block
IDNAC Card 2 Blocks (on ES Power Supply only)
ES-PS Blocks G & H ONLY
ES-PS Configured as backup Blocks E & F ONLY
ES-XPS 2 Blocks

Note: * When mounting dual Flex amplifiers on an expansion bay, special mounting rules apply.

Page 4 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

General Specifications
Table 1: ES Power Supply Specifications (ES-PS and ES-XPS)
Specifications Rating
AC Input Power 120-240 VAC
120 VAC 3.72 A
220 - 240 VAC 1.82 A
Total DC Output Power Capacity
Without Fan 9.5 A
With 4100-5131 Fan and 4100-5451 IDNAC Module(s) 9.7 A
With 4100-5131 Fan (without 4100-5451 IDNAC Module) 12.7 A
With Regulated 24V Appliance Loads (with or without 4100-5131 Fan) 5.0 A
Special Application Appliance Loads: supports full total DC output Simplex horns, strobes, and combination horn/strobes and speaker/
power capacity ratings above strobes (contact your Simplex product representative for compatible
appliances)
Regulated 24V Appliances: reduces total DC output power capacity to Power for other UL listed appliances; use associated external
5.0 A synchronization modules where required
Auxiliary Power Tap 2 A maximum (taken from total output power capacity)
NACs Programmed for Auxiliary Power 3 A maximum per NAC, 5 A maximum total (taken from total output power
capacity)
Battery Charger (ES-PS only) Sealed Lead-Acid Batteries
Battery Ah Capacity UL/ULC listed for battery charging of up to 110 Ah (batteries larger than 50
Ah require a remote battery cabinet)
Charger characteristics and performance Temperature compensated, dual rate, recharges depleted batteries within
48 hours
Environmental
Operating Temperature 32 °F to 120 °F (0 °C to 49 °C)
Operating Humidity Up to 93% RH, non-condensing @ 90 °F (32 °C) maximum
Option Card Mounting 2 vertical blocks are available for compatible modules (refer to 579-1288
installation instructions for additional details)

Note:
1. Battery charger is only available on the ES-PS power supply.
2. When an ES-PS is used to power Flex-35 or Flex-50 Amplifiers the ES-PS battery charger is not available.
Table 2: IDNet, MAPNET II, IDNet 2, and IDNet 2+2 SLC Wiring Common Specifications
Specification Description
Maximum Distance from Control Panel per Device 1 to 125 4000 ft (1219 m); 50 ohms
Load 126 to 250 2500 ft (762 m); 35 ohms
2 2
Connections Terminals for 18 to 12 AWG (0.82 mm to 3.31 mm )
Table 3: IDNet and MAPNET II Specifications
Specification Description
Wire Type New Installation Shielded twisted pair (STP)
Retrofit Only Unshielded twisted pair (UTP)
Total Wire Length Allowed With "T" Taps for Class B Wiring Up to 10,000 ft (3 km); 0.58 μF

Note: For retrofit installations consult with your local Simplex product supplier, restrictions may apply.
Table 4: IDNet 2 and IDNet 2+2 Wiring Specifications
Specification Description
Wire Type New Installation Unshielded twisted pair (UTP)
Retrofit Only Shielded or unshielded, twisted or untwisted wire
Total Wire Length Allowed With "T" Taps for Class B Wiring Up to 12,500 ft (3.8 km); 0.60 μF
Maximum Capacitance Between IDNet 2 Channels 1 μF
IDNet 2 and IDNet 2+2 Module Compatibility: IDNet communicating devices and TrueAlarm sensors including QuickConnect and QuickConnect2
sensors

Page 5 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

MINIPLEX Transponder Product Selection


Table 5: Transponder Type
SKU Description Supv. Alarm
Basic Transponder, includes bay equipment with power distribution interface, and 4100-0620 Basic Transponder
4100-9600 36 mA 36 mA
Interface Module mounted in Block A
Local Mode Transponder, includes bay equipment with power distribution interface, and normal 38 mA 38 mA
4100-9601
4100-0625 Local Mode Transponder Interface Module mounted in Block A in local mode 23 mA 23 mA
Table 6: ES Power Supplies
Model Voltage Description Includes Provides Size Supv. Alarm
Power to
Bay
4100-5401 120-240 V ES-PS 24 V Aux. Relay, 24 V Aux. Power 2 A Tap/ Simple NAC, Yes 2 Blocks 68 mA 77 mA
50/60 Hz 110 Ah Battery Charger, 2 PDI Blocks for compatible
option cards.
4100-5402 120-240 V ES-XPS Same as ES-PS above except without battery charger No
50/60 Hz
Table 7: Power supply accessories
Model Description Size Current
4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum
4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block included w/loads
4100-5130 Voltage Regulator Module, 22.8 to 26.4 VDC (25VDC nominal); isolated and resettable 1 Block 3 A maximum with
output; includes earth detection circuit and trouble relay for status monitoring. 2.5 A load, 4.9 A
maximum with 4 A
load
4100-5131 ES-PS Fan Module, allows more than one power supply to be installed in a single bay N/A 0 mA Supv. 200 mA
and may increase total DC output power capacity per power supply. See Table 1 for Alarm
specifications.
4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet
4100-0638 4100 Slot Module Additional 24 VDC Harness; needed when 4100 Slot module requirements exceed 2 A from ES-PS
4100-5403 Harness for ES-PS Backup Power Supply
4100-0644 120 VAC PDM Harness 1 PDM harness is required per power
4100-0645 220 VAC PDM Harness supply, select as required for appropriate
4100-0646 230 VAC PDM Harness input voltage
4100-0647 240 VAC PDM Harness
Table 8: Conventional and Addressable Notification Appliance Modules
Model Description Outputs Size Max Load - Special Max Load - Regulated 24 V Current Draw
Application*
On ES-PS / In Bay On ES-PS / In Bay Supv. Alarm
ES-XPS ES-XPS
4100-5450** Conventional Three 3 A 1 Block 3.0 A / NAC 3.0 A / NAC 2.0 A / NAC 2.0 A / NAC 66 mA 66 mA
NAC Module NACs 9.0 A / Card 6.0 A / Card 5.0 A / Card 2.0 A / Card
4100-5451** IDNAC Three 3 A 2 Blocks (on 3.0 A / NAC N/A N/A 124 mA 230 mA
Addressable SLCs ES Power 9.0 A / Card
Notification Supply only)
SLC Module
*Special Application specifications apply to both Special Application and Steady Aux Power loads during alarm operation. Available power during non-
alarm operation is 5.0 A maximum.
**The 4100-5450 and 4100-5451 can only be powered from a 4100-5401 and 4100-5402 power supply.
Table 9: Dual Class A Isolator for IDNAC
Model Description Size Supv. Alarm
4100-6103 Dual Class A IDNAC Isolator (DCAI), converts a single Class B IDNAC SLC input to two 1 Block 8.3 mA 18.5 mA
Class A SLC outputs; provides short circuit isolation between each Class A output circuit;
connect up to two DCAI Modules per IDNAC SLC input up to a maximum of 6 DCAI Modules
per IDNAC SLC; each isolated output SLC used requires one IDNAC address; the total current
remains controlled by the Class B input source SLC at 3 A maximum; each isolated loop
supports up to 30 device addresses
Note: Up to 30 additional device addresses may be installed between each 4905-9929
TrueAlert Addressable Isolator+ Module, not to exceed the maximum address and unit load-
ing specifications for the IDNAC channel)

Page 6 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

Table 10: Addressable Interface Modules


Model Description Devices Supv. Alarm
4100-3109* IDNet 2 Module, 250 point capacity; electrically isolated output with two short circuit no devices 50 mA 60 mA
isolating Class B or Class A output loops, 1 block; standard on EPS with IDNet 2 Module 50 devices 90 mA 150 mA
125 devices 150 mA 225 mA
250 devices 250 mA 350 mA
4100-3110* IDNet 2+2 Module, 250 point capacity; electrically isolated output with four short circuit no devices 50 mA 60 mA
isolating Class B or Class A output loops, 1 block; mounts in expansion bay or available 50 devices 90 mA 150 mA
master controller bay module locations only, not applicable for EPS mounting 125 devices 150 mA 225 mA
250 devices 250 mA 350 mA
4100-3111* IDNet Short Circuit Isolating Loop Output Module; for Aftermarket Field Installation Only; mount up to two on a 4100-3109
module; for use with 4100-3109 modules only
4100-3102 MAPNET II Module, 127 point capacity, add devices separately; Module size = 2 Slots; Module without 255 mA 275 mA
Loading per MAPNET II device = 1.7 mA devices
4100-3103 Isolator Module for MAPNET II communications; converts a single connected SLC into four isolated outputs 50 mA 50 mA
selectable as Class A or Class B; up to two Isolator Modules can be connected to one SLC; Module size = 1
Slot;
Note: Compatible with MAPNET II Remote Isolators only
*Note: See Table for current draw for each IDNet device
Table 11: Current draw for each IDNet device
Condition Current
Standby 0.8 mA
Alarm, with LED off 1.0 mA
Alarm, with LED on 3.0 mA
Note: A maximum of 20 devices with LED on is supported for each channel. Additional device LEDs do not turn on.
Table 12: 8-Point Zone/Relay Card
Model Description Size Supv. Alarm
4100-5013 8 point zone/relay 4x5” flat module. Mounts in any open block in a master 1 block 83 mA 351 mA
controller or expansion bay. Alarm current shown is for 8 Class B IDCs using 3.3K
end-of-line-resistors with 4 in alarm and 4 in standby. Standby current shown
is for all 8 IDCs in standby. Refer to 579-1236 Zone/Relay Module Installation
Instructions for additional information.
4100-6305 25V regulator harness for 8 point zone/relay module. One required for each 8 N/A N/A N/A
point zone/relay module to be powered by the 4100-5130 25V regulator module. A
maximum of (5) 8 point zone/relay modules may be powered from the 4100-5130
per bay.

Note: Modules in Table 12 requires 4100ES Version 3.06 or later.


Table 13: Relay Modules; Non-power-limited
Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm
4100-3202 4 DPDT w/ 10 A 250 VAC 10 A 250 VAC 2 Slots 15 mA 175 mA
feedback
4100-3204 4 DPDT w/ 2A 30 VDC/VAC ½A 30 VDC/120 1 Block 15 mA 60 mA
feedback VAC
4100-3206 8 SPDT 3A 30 VDC/120 1½A 30 VDC/120 1 Block 15 mA 190 mA
VAC VAC

Current Calculation Notes:


1. For total supervisory current, add panel module currents to base system and add all external loads panel-powered loads.
2. For total alarm current, add panel module currents to base system alarm current and add all panel NAC loads and all external loads powered from
panel power supplies.
Table 14: Communication Modules
SKU Description Size Supv. Alarm
4100-1291 Remote Unit Interface Module (RUI, unisolated), up to 3 maximum per control panel; for use with 1 Slot 85 mA 85 mA
4100-9600 only
4100-6031 Select one per ES City Circuit, with disconnect switches For use with ES-PS only (not for 1 Block 20 mA 36 mA
4100-6032 Power Supply (non City Circuit, without disconnect switches backup ES-PS or ES-XPS) 20 mA 36 mA
4100-6033 power-limited) Alarm Relay, 3 Form C relays, 2 A @ 32 15 mA 37 mA
VDC; for ES-PS
4100-6038 Dual RS-232 Interface 1 Slot 132 mA 132 mA
4100-6045 Decoder Module 3 Slots 85 mA 163 mA

Page 7 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

Table 14: Communication Modules


SKU Description Size Supv. Alarm
4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA
4100-9816 Master Clock Interface Module with one standard RS-232 port (see S4100-0033 ) 1 Slot 132 mA 132 mA
Table 15: Miscellaneous Options and Accessories
Model Description
4100-1290 24 Point I/O Module for external connections, select each point as either a switch input (momentary or maintained) or an output (for
lamp/LED/relay); requires 1 Slot (refer to data sheet S4100-0032 for additional information)
4100-0632 Terminal Block Utility Module with 2, 16 position terminal blocks on 4" x 5" single block, for of up to 12 AWG wire (3.31 mm )
2

4100-0633 Door Tamper Switch, connects into Transponder Interface Module, one per cabinet assembly if required
4100-0634 120 VAC Power Distribution Module (PDM) select per system voltage; one required per box
4100-0635 220/230/240 VAC Power Distribution Module (PDM) select per system voltage; one required per box
4100-9837 Green LED Power-on Indicator Kit, required for ULC listing of MINIPLEX transponder; mounts on solid door knockout
2081-9031 Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 Ω, 1 W,
2
encapsulated, two 18 AWG leads (0.82 mm ), 2 ½" L x 1 ⅜" W x 1" H (64 mm x 35 mm x 25 mm)
Table 16: Audio Riser Modules
SKU Description Size Supv. Alarm
4100-0621 Dual Channel Analog Audio Riser Module; accepts one or two separate audio signals from 1 Block 0 mA 15 mA
host control panel; mounts in Block B, is controlled by Transponder Interface Module
4100-0622 3-8 Channel Digital Audio Riser Module; similar to analog module, except receives and 1 Block 70 mA 70 mA
decodes a digital input signal with up to eight audio channels; with Non-Alarm Audio input
Table 17: Analog Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible*
SKU Description Details
4100-1361 25 VRMS output Flex-35, 35 W Amplifier, constant Includes three on-board Class B audio NAC rating = 1.4 A 35 W,
4100-1362 70.07 VRMS output supervision compatible NACs; power is supplied from an ES-PS NAC rating = 0.5 A or 100
speakers
4100-1312 25 VRMS output Flex-50, 50 W Amplifier, constant NAC rating = 2 A 50 W,
4100-1313 70.7 VRMS output supervision compatible NAC rating = 0.707 A or 100
speakers
* Refer to document S4100-1034 for additional audio information.
Table 18: 100 W Analog Amplifiers with Power Supply, Constant Supervision Compatible
SKU/Output Voltage Power Supply Input/Listing Description Details
25 VRMS 70.7 VRMS
4100-1314 4100-1315 120 VAC, 60 Hz UL Primary 100 W Includes six, Class B audio NACs; NAC rating = 50 W or 100
Amplifier speakers maximum; 2 A @ 25 VRMS; 1.4 A @ 70.7 VRMS
4100-1316 4100-1317 120 VAC, 60 Hz ULC Primary 100 W Includes six, Class B audio NACs; NAC rating = 50 W or 100
Amplifier speakers maximum; 2 A @ 25 VRMS; 1.4 A @ 70.7 VRMS
ULC models have low battery dropout circuit
4100-1318 4100-1319 220/230/240 VAC, UL Primary 100 W Includes six, Class B audio NACs; NAC rating = 50 W or 100
50/60 Hz Amplifier speakers maximum; 2 A @ 25 VRMS; 1.4 A @ 70.7 VRMS
4100-1320 4100-1321 120 VAC, 60 Hz UL Backup 100 W Uses the six Class B NACs of primary amplifier
Amplifier
4100-1322 4100-1323 120 VAC, 60 Hz ULC Backup 100 W Uses the six Class B NACs of primary amplifier
Amplifier ULC models have low battery dropout circuit
4100-1324 4100-1325 220/230/240 VAC, UL Backup 100 W Uses the six Class B NACs of primary amplifier
50/60 Hz Amplifier
Table 19: Digital Emergency Voice/Alarm Communications Equipment*
Model Description Details
4100-1363 25 VRMS output Flex-35, 35 W Amplifier, constant Includes three on-board Class B NAC rating = 1.4 A 35 W, or 100
4100-1364 70.07 VRMS output supervision compatible audio NACs; power is supplied from NAC rating = 0.5 A speakers
4100-1326 25 VRMS output Flex-50, 50 W Amplifier, constant an ES-PS NAC rating = 2 A 50 W, or 100
4100-1327 70.7 VRMS output supervision compatible NAC rating = speakers
0.707 A
* Refer to document S4100-1034 for additional audio information.

Page 8 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

Table 20: 100 W Digital Amplifiers with Power Supply, Constant Supervision Compatible
SKU/Output Voltage Power Supply Input/Listing Description Details
25 VRMS 70.7 VRMS
4100-1328 4100-1329 120 VAC, 60 Hz UL Primary 100 W Includes six, Class B audio NACs; NAC rating = 50 W or 100
Amplifier speakers maximum; 2 A @ 25 VRMS; 1.4 A @ 70.7 VRMS
4100-1330 4100-1331 120 VAC, 60 Hz ULC Primary 100 W Includes six, Class B audio NACs; NAC rating = 50 W or 100
Amplifier speakers maximum; 2 A @ 25 VRMS; 1.4 A @ 70.7 VRMS
ULC models have low battery dropout circuit
4100-1332 4100-1333 220/230/240 VAC, UL Primary 100 W Includes six, Class B audio NACs; NAC rating = 50 W or 100
50/60 Hz Amplifier speakers maximum; 2 A @ 25 VRMS; 1.4 A @ 70.7 VRMS
4100-1334 4100-1335 120 VAC, 60 Hz UL Backup 100 W Uses the six Class B NACs of primary amplifier
Amplifier
4100-1336 4100-1337 120 VAC, 60 Hz ULC Backup 100 W Uses the six Class B NACs of primary amplifier
Amplifier ULC models have low battery dropout circuit
4100-1338 4100-1339 220/230/240 VAC, UL Backup 100 W Uses the six Class B NACs of primary amplifier
50/60 Hz Amplifier
Table 21: Options for use with either Analog or Digital Amplifiers
Model Description Details and Mounting Reference
4100-1245 Flex-35/50 Expansion NAC Module; adds three Choose one per amplifier Mounts on Flex-35/50 assembly; NAC ratings =
Class B audio NACs 1.5 A, 35/50 W, or 100 speakers maximum; Supv
= 8 mA, Alarm = 60 mA
4100-1246 Flex-35/50 Class A Adapter Module; converts Mounts on Flex-35/50 assembly; NAC ratings = 2
three on-board NACS to Class A operation A, 50 W, or 100 speakers maximum; Supv =10 mA,
Alarm = 30 mA
4100-1248 100 W Amplifier Expansion NAC Module; NAC Provides six additional Class B audio NACs,
ratings = 1.5 A, 50 W, or 100 speakers max. mounts on 100 W amplifier assembly; Supv = 17
mA, Alarm = 60 mA
4100-1249 100 W Class A Adapter Module; NAC ratings = 2 A, Converts six on-board NACs to Class A operation,
50 W, or 100 speakers max. mounts on 100 W amplifier assembly; Supv = 1
mA, Alarm = 60 mA
4100-1259 25 VRMS Output; NAC rating = 2 A, 50 W, or 100 Constant Supervision Adapter Supv = 10 mA on Converts three Class
speakers max. for three NACs; select batteries; B audio NACS to Class
per amplifier output; not Alarm = 35 mA A or Class B Constant
4100-1260 70.7 VRMS Output; NAC rating = 0.707 A, 50 W, or compatible with amplifier Supv = 38 mA on Supervision NACs; mounts
100 speakers max. NAC expansion modules; batteries; on Flex-35/50 or 100 W
deactivated when on batteries amplifier assembly; use
Alarm = 70 mA
two for the six NACs on
100 W amplifiers
Table 22: Audio Expansion Signal Module and Options
Model Description Details and Mounting Reference
4100-5116 Expansion Signal Module; three, 1.5 A Class B NACs for Converts one NAC input to three NAC outputs; selects between two inputs;
Audio applications; up to five maximum per amplifier; for Flex-35/50 amplifiers only, two input NACs are required; Single Block
NAC rating = 1.5 A, 50 W, or 100 speakers maximum module mounts in expansion bay; Supv = 20 mA; Alarm = 80 mA
4100-1266 Expansion Signal Module NAC Expander; NAC rating = 1.5 Expands module capacity to six, Class B These modules mount on the
A, 50 W, or 100 speakers max. NACs; 4100-5116; select one max. per
Supv = 0.84 mA; Alarm = 60 mA 4100-5116 as required
4100-1267 Expansion Signal Module Class A Adapter; NAC rating = Converts 3 Class B, NACs to Class A;
1.5 A, 50 W, or 100 speakers maximum Supv = 0 mA; Alarm = 30 mA
4100-1268 Expansion Signal Module Constant Supervision Adapter; NAC rating = 1.4 A, 50 W, or 100 speakers
Converts 3 Class B NACs to Constant Supervision Class B max.;
or Class A NACs; for 25 VRMS or 70.7 VRMS audio Supv = 38 mA on batteries (constant
supervision deactivated); Alarm = 70 mA
Table 23: Firefighters Telephone Options
SKU Description Size Supv. In Use
4100-1272 Expansion Telephone Control Module with three Class B telephone NACS; required 1 Block 80 mA 130 mA
when telephone circuits are mounted in transponder;
4100-1273 Telephone Class A Adapter Module; mounts on 4100-1272; no additional current required

Page 9 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

Table 24: General Audio Options


Model Description
4081-9018 End-of-line resistor harness for 70.7 VRMS NACs; 10 kΩ, 1 W
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
Table 25: Local Mode Controller Selection
SKU Description Supv. Alarm
4601-9108 Flush mount Red with white Local Mode Controller, 3-gang plate mounted; flush normal 44 mA 44 mA
4601-9109 Surface mount lettering mount requires a 1 ½" (38 mm) deep 3-gang box; surface
4601-9110 Flush mount Beige with black mount controllers include a matching mounting box; see in local mode 44 mA 58 mA
4601-9111 Surface mount lettering Local Mode Controller Detail

Local Mode Controller Detail

Figure 3: Local Mode Controller Detail

Note: Matching box is supplied with surface mount models 4601-9109 (red) and 4601-9111 (beige); for semi-flush models 4601-9108 (red) and
4601-9110 (beige), use a 1-1/2" (38 mm) minimum depth, 3-gang box.

Local Mode Controller to Transponder Wiring:


1. Wire close-nippled to transponder, maximum distance = 20 ft (6.1 m).
2. Nine wires required: 24 VDC (2), one per LED indicator (4), and one per switch (3).
3. Wire size, 18 AWG (0.82 mm² ).

Page 10 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

Enclosure Installation Reference

Note:

1. Side View dimensions are shown with minimal cabinet and door protrusion from the exterior wall. For 6 inch stud construction with minimum
protrusion shown, the door will open 90 degrees. To allow the door to open 180 degrees, the exposed cabinet dimension from the exterior wall
must be a minimum of 3 inches (76 mm) for both 4 inch and 6 inch stud construction.

2. A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved,
dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.

Additional 4100ES Product Reference


Table 26: Additional 4100ES Product Reference
Subject Datasheet
Battery and Battery Cabinet Reference for 4100ES S2081-0006
110 Ah Batteries and Cabinets for 4100ES S2081-0012
Seismic Battery Brackets Reference S2081-0019
4100ES LED/Switch Modules & Printer S4100-0032
4100ES Enclosures S4100-0037
4100ES Basic Panels with ES-PS Power Supplies S4100-1031
NDU with ES-PS Power Supplies for 4120 Network S4100-1036
NDU with ES-PS Power Supplies for ES Net S4100-1077

Page 11 S4100-1035 Rev. 5 09/2021


MINIPLEX Transponders with ES-PS Power Supplies

© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S4100-1035 Rev. 5 09/2021