MINI MCR-SL-I-I
Standard signal 3-way signal conditioners
Data sheet
101946_en_05 © PHOENIX CONTACT 2021-02-22
1 Description
MINI MCR-SL-I-I(-SP) standard signal 3-way signal Features
conditioners are used to electrically isolate, condition,
– 3-way isolating amplifier
amplify, and filter standard signals.
– Input and output signal range 0 mA ... 20 mA or
Electrically isolated 0...20 mA or 4...20 mA standard analog 4 mA ... 20 mA
signals are available on the input and output sides.
– Screw connection available
The power supply (19.2...30 V DC) can be supplied either
via connection terminal blocks "3"/"4" or "7"/"8" on the
modules or in conjunction with the DIN rail connector.
Please refer to the section titled "Power supply" for more
information.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This document is valid for the products listed in the “Ordering data”.
MINI MCR-SL-I-I
2 Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 4
5 Safety regulations and installation notes.................................................................................. 6
5.1 Installation notes ................................................................................................................. 6
5.2 UL notes............................................................................................................................ 6
6 Installation ............................................................................................................................... 7
6.1 Connection notes ................................................................................................................ 7
6.2 Structure ........................................................................................................................... 7
6.3 Block diagram ..................................................................................................................... 7
6.4 Power supply ...................................................................................................................... 7
6.5 Mounting ........................................................................................................................... 8
6.6 Connection of the cables ....................................................................................................... 8
101946_en_05 PHOENIX CONTACT 2/8
MINI MCR-SL-I-I
3 Ordering data
Description Type Order No. Pcs./Pkt.
MCR 3-way isolating amplifier, for electrical isolation of MINI MCR-SL-I-I 2864406 1
analog signals, with screw connection, input signal: 0(4)
mA ... 20 mA, output signal: 0(4) mA ... 20 mA
Accessories Type Order No. Pcs./Pkt.
DIN rail connector for DIN rail mounting. Universal for ME 6,2 TBUS-2 1,5/5-ST-3,81 2869728 10
TBUS housing. Gold-plated contacts, 5-pos. GN
MCR power terminal block for supplying several MINI MINI MCR-SL-PTB 2864134 1
Analog modules via the DIN rail connector, with screw
connection, maximum current consumption of up to 2 A
Primary-switched MINI POWER supply for DIN rail MINI-SYS-PS-100-240AC/ 2866983 1
mounting, input: 1-phase, output: 24 V DC/1.5 A 24DC/1.5
Fold up transparent cover for MINI MCR modules with MINI MCR DKL 2308111 10
additional labeling option using insert strips and flat Zack
marker strip 6.2 mm
Label for extended marking of MINI MCR modules in MINI MCR-DKL-LABEL 2810272 10
connection with the MINI MCR-DKL
101946_en_05 PHOENIX CONTACT 3/8
MINI MCR-SL-I-I
4 Technical data
Input
Number of inputs 1
Configurable/programmable no
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Max. current input signal 50 mA
Input resistance current input approx. 50 Ω
Output
Number of outputs 1
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal 28 mA
Non-load voltage approx. 12.5 V
Configurable/programmable no
Ripple < 20 mVPP (at 500 Ω)
Load/output load current output < 500 Ω (at 20 mA)
Supply
Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2
TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to
bridge the supply voltage. It can be snapped onto a 35 mm DIN
rail according to EN 60715))
Max. current consumption < 20 mA
Power consumption < 450 mW
General data
Limit frequency (3 dB) approx. 100 Hz
Maximum transmission error ≤ 0.1 % (of final value)
Temperature coefficient, typical < 0.002 %/K
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) approx. 3.2 ms
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Mounting position any
Degree of protection IP20
Degree of pollution 2
Rated insulation voltage 50 V AC/DC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Dimensions W/H/D 6.2 mm / 93.1 mm / 101.2 mm
Type of housing PBT green
101946_en_05 PHOENIX CONTACT 4/8
MINI MCR-SL-I-I
Connection data
Connection method Screw connection
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12
Stripping length 12 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Maximum altitude for use above sea level ≤ 2000 m
Conformance with EMC directive
Noise immunity according to EN 61000-6-2
When being exposed to interference, there may be minimal deviations.
Noise emission according to EN 61000-6-4
Conformance/Approvals
CE CE-compliant
UL, USA/Canada UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
Shipbuilding approval (DNV GL TAA000020N)
Temperature B
Humidity B
Vibration B
EMC A
Enclosure Required protection according to the Rules shall be provided
upon installation on board
101946_en_05 PHOENIX CONTACT 5/8
MINI MCR-SL-I-I
5 Safety regulations and installation
notes
5.1 Installation notes
• Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the
installation instructions as described. When installing
and operating the device, the applicable regulations
and safety directives (including national safety
directives), as well as generally approved technical
regulations, must be observed. The safety data is
provided in this package slip and on the certificates
(conformity assessment, additional approvals where
applicable).
• The device must not be opened or modified. Do not
repair the device yourself, replace it with an equivalent
device. Repairs may only be carried out by the
manufacturer. The manufacturer is not liable for
damage resulting from violation.
• The IP20 degree of protection (IEC/EN 60529)
specifies that the device is intended for use in a clean
and dry environment. Do not subject the device to
mechanical and/or thermal stress that exceeds the
specified limits.
• The device is not designed for use in atmospheres with
a danger of dust explosions.
• The potentiometer under the cover is only used for
adjusting the measured values during production. An
additional adjustment is not necessary.
5.2 UL notes
PROCESS CONTROL EQUIPMENT FOR HAZARDOUS
LOCATIONS 31ZN
1 Suitable for use in class 1, division 2, groups A, B, C and
D hazardous locations, or nonhazardous locations only.
2 WARNING - EXPLOSION HAZARD: Do not disconnect
equipment while the circuit is live or unless the area is
known to be free of ignitable concentrations.
3 WARNING - EXPLOSION HAZARD: Substitution of any
components may impair suitability for Class I, Division
2.
101946_en_05 PHOENIX CONTACT 6/8
MINI MCR-SL-I-I
6 Installation 6.3 Block diagram
Figure 2 Block diagram
6.1 Connection notes
Sensor / Field IN OUT PLC / DCS
NOTE: electrostatic discharge!
The device contains components that can be OUT I
1 + 1
IN I OUT I
5 + 5
damaged or destroyed by electrostatic discharge. US 4-wire active passive
When handling the device, observe the necessary GND
2 – 2
GND 1 GND 2
6 – 6
safety precautions against electrostatic discharge
(ESD) according to EN 61340-5-1 and EN 61340-
+24V +24V
+ 3 7 +
5-1.
GND 3
– 4 GND 3
8 –
6.2 Structure
Figure 1 Structure +24V
GND 3
2
1
6.4 Power supply
3
NOTE:
-I-I
-SL 0 6
CR 4 4
Never connect the supply voltage directly to the
I M 28 6 5
DIN rail connector. It is not permitted to draw
r
MIN o.: lifie
d.-
N mp A
Or gA 0m
power from the DIN rail connector or from
tin ..2 le
4 Iso
la ) . ca
0(4 0 W full s min. 49°F
£ 50 of z, 1 ..+1
,1 50 H / -4°.
individual modules.
ut: %
O < ,0
/ C
In d: or: 5kV 65°
a Err 1, ..+
Lo sm. e: 20°.
n g - I
Tra volta p.:
In
s t m 1
Te . Te
1 D
GN DC
b 0V
Am IN 2 ...3
www.interface.phoenixcontact.com
9,2
Supply via the module
1
5 T 3
OU +3 D
GN
t I 6
Ou -4
R
2 WE
Where the total current consumption of the aligned modules
D 7+ PO
GN
C
VD 8-
.30
,2..
does not exceed 400 mA, the power can be supplied directly
19 D
3
GN
5
XX
XX
X at the connection terminal blocks of the module.
CeriaEl No. X
XX 7
S
A 400 mA fuse should be connected upstream.
6 Supply via a power terminal block
The MINI MCR-SL-PTB power terminal block (Order No.
1. Input: Standard signals 2864134) of the same shape is used to feed in the supply
voltage to the DIN rail connector.
2. Cover
3. Groove for ZBF 6 zack marker strip A 2 A fuse should be connected upstream.
4. Output: Standard signals Supply via a system power supply unit
5. Supply voltage
The system power supply unit with 1.5 A output current
6. Connection option for DIN rail bus connector
connects the DIN rail connector to the supply voltage and
7. Universal snap-on foot for EN DIN rails can therefore be used to supply several modules from the
mains.
– MINI-SYS-PS-100-240AC/24DC/1.5 (Order No.
2866983)
101946_en_05 PHOENIX CONTACT 7/8
MINI MCR-SL-I-I
6.5 Mounting
Figure 3 Mounting and removing
A B
D E
– Mount the module on a 35 mm DIN rail according to EN
60715.
– When using the DIN rail connector, first place it into the
DIN rail (see A – C). It is used to bridge the power
supply. It is also absolutely vital that you snap the
module and the DIN rail connector into position in the
correct direction: the snap-on foot should be at the
bottom and the connector on the left.
6.6 Connection of the cables
Figure 4 Screw connection
MINI MCR-... AWG 26-12
0,2-2,5 mm2
B 12 mm
A 0,5-0,6 Nm
5-7 lb In
• Insert the wire into the corresponding connection
terminal block.
• Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
101946_en_05 PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 8/8
phoenixcontact.com