0% found this document useful (0 votes)
27 views28 pages

MZC 5 NJ A1 X01 HBN VHB F83 MJ I1 NF9 FTL VF X1 D TRL JFSQ

This document provides information about the ICPlus 915 electronic controller with 2 intervention points. It includes details about the user interface keys and icons, connection terminals for different input/output models including NTC/PTC, V/I, and PT100/Tcj-Tck. Specifications are given for the display range, digital and analog inputs, digital and serial outputs, accuracy, and resolution for each model.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views28 pages

MZC 5 NJ A1 X01 HBN VHB F83 MJ I1 NF9 FTL VF X1 D TRL JFSQ

This document provides information about the ICPlus 915 electronic controller with 2 intervention points. It includes details about the user interface keys and icons, connection terminals for different input/output models including NTC/PTC, V/I, and PT100/Tcj-Tck. Specifications are given for the display range, digital and analog inputs, digital and serial outputs, accuracy, and resolution for each model.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

ICPlus 915

EN Electronic controller with 2 intervention points


USER INTERFACE

ICPlus 915
KEYS
UP STAND-BY (ESC)
Press and release Press and release
Scroll menu items Returns to the previous menu level
Increases values Confirms parameter value
Press for at least 5 sec Press for at least 5 sec
Function can be configured by the user (H31) Function can be configured by the user (H33)

DOWN SET (ENTER)


Press and release Press and release
Scroll menu items Displays alarms (if active)
Decrease values Opens Machine Status menu
Press for at least 5 sec Confirm commands
Function can be configured by the user (H32) Press for at least 5 sec
Opens Programming menu
ICONs
Decimal Point Temperature
Permanently on: decimal point Permanently on: displays a temperature
Flashing: Soft Start active Flashing: reduced set active, displays
Off: otherwise a temperature or no unit of
measure selected
Pressure Humidity
Permanently on: displays a pressure Permanently on: displays a humidity
Flashing: reduced set active and displays Flashing: reduced set active and displays
a pressure a humidity
Relay OUT1 Relay OUT2
Permanently on: OUT1 output active Permanently on: OUT2 output active
Flashing: a delay, a protection or a locked Flashing: a delay, a protection or a locked
start-up start-up
Off: otherwise Off: otherwise
Alarm NOTE:
Permanently on: alarm active When switched on, the device performs a Lamp Test; the
Flashing: alarm acknowledged display and LEDs will flash for several seconds to check that
Off: otherwise they all function correctly.
NTC/PTC MODEL
CONNECTIONS INPUT/OUTPUT CHARACTERISTICS
NTC/PTC (12Va/c, 12-24Va/12-36Vc) NTC: -50...110°C (-58...230°F)
Display range: PTC: -50...140°C (-58...302°F)
OUT1 OUT2
on display with 3½ digits + sign
Digital input 1 digital voltage free input
1 2 3 4 5 7 8 9 10 11 12 1 NTC or 1 PTC
Analogue input
(selectable by parameter H00)

Pb1

D.I.
Supply TTL for connection to Copy Card or Televis/
Serial
Modbus remote control systems
NTC/PTC (24Va, 115Va, 230Va) OUT1: 1 SPDT relay 8(4)A 250 Va
Digital outputs
OUT1 OUT2 OUT2: 1 SPST relay 8(4)A 250 Va
Buzzer output only on models where this is provided
Measurement range -50 ... 140°C (-58 ... 284°F)
1 2 3 4 5 6 7 9 10 11 12 Accuracy better than 0.5% of end of scale +1 digit
Resolution 0.1°C (0.1°F up to +199.9°F; 1°F over)
Pb1

D.I.

Supply

TERMINALS
1-2-3 regulator relay OUT1 *7-8 Power supply 12Va/c and 12-24Va/12-36Vc.
4-5 regulator relay OUT2 9-11 Probe Pb1 Input
*6-7 Power supply 24Va, 115Va and 230Va. 9-12 Digital Input (D.I.)
A TTL input for Copy Card and TelevisSystem connection * depends on model
V/I MODEL
CONNECTIONS INPUT/OUTPUT CHARACTERISTICS
V/I (12Va/c, 12-24Va/12-36Vc) -199...199 (ndt = n)
-199.9...199.9 (ndt = y)
OUT1 OUT2 Display range:
-1999...1999 (ndt = int)
on display with 3½ digits + sign
Digital input 1 digital voltage free input
1 2 3 4 5 7 8 9 10 11 12
− + +
1 V/I (0-1V, 0-5V, 0-10V, 0...20mA, 4...20mA)
V (selectable by parameter H00)
Supply Analogue input
I +12V Maximum load: - current = 100 Ω
- voltage = 20 kΩ
V/I (24Va, 115Va, 230Va) TTL for connection to Copy Card or Televis/
Serial
OUT1 OUT2 Modbus remote control systems
OUT1: 1 SPDT relay 8(4)A 250 Va
Digital outputs
OUT2: 1 SPST relay 8(4)A 250 Va
1 2 3 4 5 6 7 9 10 11 12 Buzzer output only on models where this is provided
− + + Measurement range -1999 ... 1999
V
Supply Accuracy better than 0.5% of end of scale +1 digit
I +12V
Resolution 1 or 0.1 digit according to settings
TERMINALS
1-2-3 regulator relay OUT1 *7-8 Power supply 12Va/c and 12-24Va/12-36Vc.
4-5 regulator relay OUT2 *9-10-12 Voltage input (9=GND; 10=”+”; 12=12V)
*6-7 Power supply 24Va, 115Va and 230Va. *9-11-12 Current input (9=GND; 11=”+”; 12=12V)
A TTL input for Copy Card and TelevisSystem connection * depends on model
PT100/Tcj-Tck MODEL
CONNECTIONS INPUT/OUTPUT CHARACTERISTICS
PT100/Tcj-Tck (12Va/c, 12-24Va/12-36Vc) PT100: -150...650°C
TcJ: -40...750°C
OUT1 OUT2
Display range:
TcK: -40...1350°C
on display with 3½ digits + sign
1 2 3 4 6 7 8 9 10 11 12 Digital input 1 digital voltage free input
1 PT100 or 1 TcJ / Tck

Pb1
D.I.
Supply Analogue input
+ − (selectable by parameter H00)
TTL for connection to Copy Card or Televis/
PT100/Tcj-Tck (24Va, 115Va, 230Va) Serial
Modbus remote control systems
OUT1 OUT2
OUT1: 1 SPST relay 8(4)A 250 Va
Digital outputs
OUT2: 1 SPST relay 8(4)A 250 Va
1 2 3 4 5 6 8 9 10 11 12 Buzzer output only on models where this is provided
Measurement range -150 ... 1350°C (-238 ... 2462°F)
Pb1
D.I.

Supply

Accuracy see ‘Pt100/TcJ/TcK models’ table
+
Resolution see ‘Pt100/TcJ/TcK models’ table
TERMINALS
1-2 regulator relay OUT1 8-9 Digital Input (D.I.)
3-4 regulator relay OUT2 *10-11-12 Probe PT100 input - 3 wires (Pb1)
*5-6 Power supply 24Va, 115Va and 230Va. *11-12 TcJ/TcK input
*6-7 Power supply 12Va/c and 12-24Va/12-36Vc.
A TTL input for Copy Card and TelevisSystem connection * depends on model
PT100/Tcj-Tck MODELs
0.5% for whole scale + 1 digit
ACCURACY:
PT100: 0.2% from -150 to 300°C
RESOLUTION: 0.1°C (0.1°F) from -199.9°C up to 199.9°C; 1°C (1°F) beyond
ACCURACY: 0.4% for whole scale + 1 digit
TcJ:
RESOLUTION: 0.1°C (0.1°F) from -199.9°C up to 199.9°C; 1°C (1°F) beyond
0.5% for whole scale + 1 digit
ACCURACY:
Tck: 0.3% from -40 to 800°C
RESOLUTION: 0.1°C (0,1°F) from -199.9°C up to 199.9°C; 1°C (1°F) beyond

MOUNTING - DIMENSIONS
The device is designed for panel mounting. Drill a 29x71 mm hole and insert the instrument; secure it with the special brackets provided.
Do not install the instrument in damp and/or dirty places; in fact, it is suitable for use in places with ordinary or normal levels of pollution.
Keep the area around the instrument cooling slots adequately ventilated.
29 mm

70 mm
71 mm

74 mm
59 mm

32 mm
EWPA-EWHS PROBE CONFIGURATION
EWHS 284 2 wires EWHS 304/314 3 wires

9 10 11 12 9 10 11 12 Probe

V+
Probe
blue RH/T
brown GND (only EWHS314)

EWPA 007/030 2 wires / Transducer EWHS 314 4 wires (V-I model)


ICPlus 1 ICPlus 2
9 10 11 12 9 10 11 12 9 10 11 12
Transducer GND
brown
white
Probe

V+ T
RH
GND
ACCESSING AND USING THE MENUs
The resources are organized into 2 menus which are accessed as follows:
• ‘Machine Status’ menu: press and release the key.
• ‘Programming’ menu: hold down the key for 5 seconds.
Either do not press any keys for 15 seconds (timeout) or press the key once, to confirm the last value displayed and return to the previous
screen.

PASSWORD
Password ‘PA1’: used to access User parameters. The password is not enabled by default (PS1=0).
To enable it (PS1≠0): press and hold for longer than 5 seconds, scroll through the parameters using and until you see the label
PS1, press to display the value, modify it using and , then save it by pressing or . If enabled, it will be required in
order to access the User parameters.
Password ‘PA2’: used to access Installer parameters. The password is enabled by default (PS2=15).
To modify it (PS2≠15): press and hold for longer than 5 seconds, scroll through the parameters using and until you see the
label PA2, press , set the value to ‘15’ using and , then confirm using . Scroll through the folders until you find the label
diS and press to enter. Scroll through the parameters using and until you see the label PS2, press to display the value,
modify it using and , then save it by pressing or .
The visibility of ‘PA2’ is as follows:
1) PA1 and PA2 ≠ 0: Press and hold for longer than 5 seconds to display PA1 and PA2. It will then be possible to decide whether to
access the User parameters (PA1) or the Installer parameters (PA2).
2) Otherwise: The password PA2 is amongst the level1 parameters. If enabled, it will be required when accessing the Installer
parameters; to enter it, proceed as instructed for password PA1.
If the value entered is incorrect, the label PA1/PA2 will be displayed again and the procedure will need to be repeated.
MACHINE STATUS MENU
Access the Machine Status menu by pressing and releasing the key. If no alarms are active, the ‘SP1’ label appears.
Use the keys and to scroll through all the folders in the menu:
- AL: alarms folder (only visible if an alarm is active);
- SP1: Setpoint 1 setting folder;
- SP2: Setpoint 2 setting folder;
- Pb1: probe 1 - Pb1 folder;
Setting the Setpoint: To display the Setpoint value press the key when the ‘SP1’ or ‘SP2’ label is displayed.
The Setpoint value appears on the display. To change the Setpoint value, press the and keys within 15
seconds. Press to confirm the modification.
Displaying probes: When label Pb1 is present, press the key to view the value measured by the corresponding probe
(NOTE: the value cannot be modified).

PROGRAMMING MENU
To access the ‘Programming’ menu, press the key for more than 5 seconds. If specified, an access PASSWORD will be requested: ‘PA1’ for
User parameters and ‘PA2’ for Installer parameters (see ‘PASSWORD’ paragraph).
User Parameter: When accessed, the display will show the first parameter (e.g. ‘dF1’). Press and to scroll through all the parameters on
the current level. Select the desired parameter by pressing . Press and to modify it and to save the changes.
Installer Parameter: When accessed, the display will show the first folder (e.g. ‘rE1’). Press and to scroll through the folders on the
current level. Select the desired folder using . Press and to scroll through the parameters in the current folder and select the
parameter using . Press and to modify it and to save the changes.
NOTE: Make sure you switch the instrument off and on again each time the parameter configuration is changed, in order to prevent mal-
functioning in the configuration and/or timing in progress.
DIAGNOSTICS
Alarms are always indicated by the alarm icon , the buzzer and the relay (if setting).
To switch off the buzzer, press and release any key; the corresponding icon will continue to flash.
N.B.: If alarm exclusion times have been set (see ‘AL’ folder in the parameters table) the alarm will not be signalled.

ALARMs
Label Fault Cause Effects Remedy
• Display label E1
• measured values are outside • Alarm icon permanently on
• check probe type (H00)
Probe1 faulty operating range • Buzzer and Alarm relay (if setting) activation
E1 • check probe wiring
(ambient) • Probe faulty/short-circuited/ • Disable max/min alarm controller
• replace probe
open • Compressor operation based on parameters
On1/2 and OF1/2
• Recording of label AH1/2 in folder AL
value read by Pb1 > HA1/2 after
Alarm for HIGH • Alarm icon permanently on Wait until value read by Pb1
AH1/2 time of tAO.
value (Probe1) • Buzzer and Alarm relay (if setting) activation returns below HA1/2.
(see ‘MAX/MIN TEMP. ALARMS’)
• No effect on regulation
• Recording of label AL1/2 in folder AL
value read by Pb1 < LA1/2 after
Alarm for LOW • Alarm icon permanently on Wait until value read by Pb1
AL1/2 time of tAO.
value (Probe1) • Buzzer and Alarm relay (if setting) activation returns above LA1/2.
(see ‘MAX/MIN TEMP. ALARMS’)
• No effect on regulation
• Recording of label EA in folder AL
Check and remove the external
Digital input activated • Alarm icon permanently on
EA External alarm cause which triggered the alarm
(H11 = ±5) • Buzzer and Alarm relay (if setting) activation
on the D.I.
• Regulation locked
MAX/MIN TEMPERATURE ALARMS
Temperature as a value Temperature as an
relative to Setpoint (Att=1) Absolute value (Att=0)

AFd AFd AFd AFd


SP1/SP2

LA1/2 HA1/2
LA1/2 + AFd LA1/2 - AFd
SP1/SP2 + LA1/2 SP1/SP2 + HA1/2

SP1/SP2 + LA1/2 + AFd SP1/SP2 + HA1/2 – AFd

Minimum alarm Temp. ≤ SP1/2 + LA1/2 * Temp. ≤ LA1/2 (LA1/2 with sign)
Maximum alarm Temp. ≥ SP1/2 + HA1/2 ** Temp. ≥ HA1/2 (HA1/2 with sign)

Temp. ≥ SP1/2 + LA1/2 + AFd or


Returning from minimum Temp. ≥ LA1/2 + AFd
≥ SP1/2 - ILA1/2I + AFd (LA1/2<0)

Returning from maximum Temp. ≤ SP1/2 + HA1/2 - AFd (HA1/2>0) Temp. ≤ HA1/2 - AFd

* if LA1/2 is negative, SP1/2+LA1/2 < SP1/2


** if HA1/2 is negative, SP1/2+HA1/2 < SP1/2
ON-OFF CONTROL DIAGRAM
ON-OFF regulation diagram with independent setpoint (H01=0, HC1=H and HC2=C).
HC1=H HC2=C

The two outputs regulate as though they were completely


On On
independent of each other. Off Off
H01=in
dF1 dF2

SP1-dF1 SP1 SP2 SP2+dF2

ON-OFF regulation diagram with dependent setpoint (H01=1, HC1=H and HC2=C).
HC1=H HC2=C

Setpoint 2 (SP2) regulates relative to SP1.


On On
Off Off
H01=di
dF1 dF2

SP1-dF1 SP1 SP1+SP2 SP1+SP2+dF2

ON-OFF regulation diagram with Neutral zone (or window) (H01=2, HC1and HC2= irrilevant).
OUT2 OUT1

If dF1=0 and dF2 = 0, the outputs are deactivated when


On On
SP1 is reached. Off

dF2 dF1

SP1-db2 SP1-db2+dF2 SP1 SP1+db1-dF1 SP1+db1


TELEVIS SYSTEM

BusAdapter
The Televis remote control systems can be connected using the TTL

TTL serial port (TTL-RS485 BusAdapter 130 or 150 interface


ICPlus
module must be used).
To configure the instrument to do this, you need to access the
RS485
Add folder and use the dEA and FAA parameters.
IMPORTANT! CHECK THE AVAILABILITY OF MODELS
COMPATIBLE WITH REMOTE SUPERVISION SYSTEMS.

DUTY CYCLE DIAGRAM


The device uses parameters On1/2 e OF1/2 set for Duty Cycle.
An error condition in probe1 (regulation) causes one of the following actions:
• Code ‘E1’ is shown on the display
• The regulator is activated as indicated by parameters On1/2 and OF1/2 if set for Duty Cycle

On1/2 OF1/2 Regulator output OUT


0 0 OFF
0 >0 OFF ON OFF ON
>0 0 ON
>0 >0 Duty Cycle On1/2 OF1/2 On1/2
TECHNICAL DATA (EN 60730-2-9)
Classification: operation (not safety) device for incorporation
Mounting: panel mounting with 71x29 mm (+0.2/-0.1 mm) drilling template
Type of action: 1.B
Pollution class: 2
Material class: IIIa
Overvoltage category: II
Rated impulse voltage: 2500V
Temperature: Operating: –5 … +55 °C - Storage: –30 … +85 °C
• 12Va/c (±10%)
• 24 Va ±10%
Power supply: • 12-24Va/12-36Vc ±10% (Dedicated power supply not grounded or earth connected)
• 115Va ±10% 50/60 Hz
• 230 Va ±10% 50/60 Hz
• 1.5 VA max (model 12Va/c)
Consumption:
• 3 W max (models: 24Va, 12-24Va/12-36Vc, 115Va and 230Va)
Digital outputs (relay): refer to the label on the device
Fire resistance category: D
Software class: A
NOTE: check the power supply specified on the instrument label.
FURTHER INFORMATION
Input/Output Characteristics
See ‘Connections’ section
Mechanical Characteristics
Casing: PC+ABS UL94 V-0 resin casing, polycarbonate window, thermoplastic resin keys
Dimensions: front panel 74x32 mm, depth 59 mm (without terminals)
Terminals: screw/disconnectable terminals for cables with a diameter of 2,5mm2
Connectors: TTL for connection of Unicard/Copy Card
Humidity: Operating / Storage: 10…90 % RH (non-condensing)
Regulations
Electromagnetic compatibility: The device conforms to Directive 2004/108/EC
Safety: The device conforms to Directive 2006/95/EC
Food Safety: The device complies with standard EN13485 as follows:
• suitable for storage
• application: air
• climate range A
• measurement class 1 in the range from -25°C to 15°C (*)
(* exclusively using Eliwell probes)
NOTE: The technical specifications given in this document regarding measurement (range, accuracy, resolution, etc.)
refer to the instrument and not to any accessories provided, such as the probes. This means, for example, that the error
introduced by the probe must be added to the typical error of the instrument.
USING THE COPY CARD
The Copy Card is connected to the serial port (TTL) and allows rapid programming of the instrument parameters.
Access Installer parameters by entering ‘PA2’, scroll through the folders using and until folder FPr appears. Select it using ,
scroll through the parameters using and , then select the function using (eg. UL).
• Upload (UL): Select UL and press . This function uploads the programming parameters from the instrument to the card. If the
procedure is a success, ‘y’, will appear on the display, otherwise ‘n’ will appear.
• Format (Fr): This command is used to format the copy card (recommended when using the card for the first time).
Important: the Fr parameter deletes all data present. This operation cannot be cancelled.
• Download: Connect the Copy Card when the instrument is switched off. At power-on, data is downloaded from the copy card to the
instrument automatically. At the end of the lamp test, the display will show ‘dLy’ if the operation was successful and ‘dLn’ if not.
NOTE: After downloading, the instrument works with the settings of the new map just downloaded.

H13 PARAMETER CONFIGURATION


D.I. FROM KEY OR FROM MENU FUNCTION
H13 COMMENTS
STATE ENABLED DISABLED STATE
NO open YES YES ON enabled / disabled with each mode
NO closed YES YES OFF enabled / disabled with each mode
NC open YES YES OFF enabled / disabled with each mode
NC closed YES YES ON enabled / disabled with each mode
NOP open YES YES ON enabled only from D.I. / disabled with each mode
NOP closed NO N/A OFF Enabled only when D.I. is reopened
NCP open YES YES OFF enabled with each mode / disabled only from D.I.
NCP closed N/A NO ON enabled with each mode / disabled only from D.I.
PARAMETERS TABLE
PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
Pb1 value control setpoint SP1. The SEtpoint is visible from the machine NTC/PTC 0.0 °C/°F
SP1 PT100-Tc LS1...HS1 0.0 °C/°F
status menu and not from the programming menu. V/I 0 num
Pb1 value control setpoint SP2. The SEtpoint is visible from the machine NTC/PTC 0.0 °C/°F
SP2 PT100-Tc LS2...HS2 0.0 °C/°F
status menu and not from the programming menu. V/I 0 num
REGULATOR 1 (folder ‘rE1’)
This sets the controller 1 operating mode.
HC1 ALL H/C H flag Inst
H (0) = Hot; C (1) = Cold.
NTC/PTC -30.0...30.0 0.0 °C/°F
OS1 Value to be added to SP1 if reduced set enabled PT100-Tc -30.0...30.0 0.0 °C/°F Inst
V/I -30...30 0 num
Operating band 1. NTC/PTC 0.0...30.0 1.0 °C/°F
db1 PT100-Tc 0.0...30.0 1.0 °C/°F Inst
(See ‘ON/OFF regulation diagram’) V/I 0...30 1 num
Regulator 1 activation differential. NTC/PTC 0.0...30.0 1.0 °C/°F
dF1 The utility stops on reaching the SP1 value (as indicated by control probe) and PT100-Tc 0.0...30.0 1.0 °C/°F User/Inst
restarts at a value equal to T=SP1+dF1 relative to HC1. V/I 0...30 1 num
NTC/PTC 140.0 °C/°F
HS1 Maximum value assignable to setpoint SP1. PT100-Tc LS1...HdL 1350 °C/°F User/Inst
V/I 199 num
NTC/PTC -50.0 °C/°F
LS1 Minimum value assignable to setpoint SP1. PT100-Tc LdL...HS1 -199.9 °C/°F User/Inst
V/I -199 num
Pb1 maximum value alarm on regulator 1. NTC/PTC LA1...150.0 140.0 °C/°F
HA1 PT100-Tc LA1...1999 1350 °C/°F User/Inst
(See ‘Max/Min temperature alarms’) V/I LA1...150 150 num
PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
NTC/PTC -150.0...HA1 -50.0 °C/°F
Pb1 minimum value alarm on regulator 1.
LA1 PT100-Tc -328...HA1 -199.9 °C/°F User/Inst
(See ‘Max/Min temperature alarms’)
V/I -150...HA1 -150 num
Switch-on delay. The indicated time must elapse between the request for
dn1 ALL 0...250 0 secs Inst
activation of the controller 1 relay and switch-on. 0 = not active.
Delay time after switching off. The indicated time must elapse between
dO1 ALL 0...250 0 min Inst
deactivation of the controller 1 relay and the next switch-on. 0 = not active.
Delay between switch-ons. The indicated time must elapse between two
di1 ALL 0...250 0 min Inst
consecutive switch-ons of regulator 1. 0 = not active.
Switch-off delay. The indicated time must elapse between the request for
dE1 ALL 0...250 0 secs Inst
deactivation of the controller 1 relay and switch-off. 0 = not active.
Controller 1 switch-on time in the event of faulty probe.
On1 if On1=1 and OF1=0, the controller remains on; ALL 0...250 0 min Inst
if On1=1 and OF1>0, the controller operates in Duty Cycle mode.
Controller 1 switch-off time in the event of faulty probe.
OF1 if OF1=1 and On1=0, the controller remains off; ALL 0...250 1 min Inst
if OF1=1 and On1>0, the controller operates in Duty Cycle mode.
REGULATOR 2 (folder ‘rE2’)
This sets the controller 2 operating mode.
HC2 ALL H/C H flag Inst
H (0) = Hot; C (1) = Cold.
NTC/PTC -30.0...30.0 0.0 °C/°F
OS2 Value to be added to SP2 if reduced set enabled PT100-Tc -30.0...30.0 0.0 °C/°F Inst
V/I -30...30 0 num
NTC/PTC 0.0...30.0 1.0 °C/°F
Operating band 2.
db2 PT100-Tc 0.0...30.0 1.0 °C/°F Inst
(See ‘ON/OFF regulation diagram’)
V/I 0...30 1 num
PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
Regulator 2 activation differential. The utility stops on reaching the SP2 value NTC/PTC 0.0...30.0 1.0 °C/°F
dF2 (as indicated by control probe) and restarts at a value equal to T=SP2+dF2 PT100-Tc 0.0...30.0 1.0 °C/°F User/Inst
relative to HC2. V/I 0...30 1 num
NTC/PTC 140.0 °C/°F
HS2 Maximum value assignable to setpoint SP2. PT100-Tc LS2...HdL 1350 °C/°F User/Inst
V/I 199 num
NTC/PTC -50.0 °C/°F
LS2 Minimum value assignable to setpoint SP2. PT100-Tc LdL...HS2 -199.9 °C/°F User/Inst
V/I -199 num
Pb1 maximum value alarm on Regulator 2. NTC/PTC LA2...150.0 140.0 °C/°F
HA2 PT100-Tc LA2...1999 1350 °C/°F User/Inst
(See ‘Max/Min temperature alarms’) V/I LA2...150 150 num
Pb1 minimum value alarm on Regulator 2. NTC/PTC -150.0...HA2 -50.0 °C/°F
LA2 PT100-Tc -328...HA2 -199.9 °C/°F User/Inst
(See ‘Max/Min temperature alarms’) V/I -150...HA2 -150 num
Switch-on delay. The indicated time must elapse between the request for
dn2 ALL 0...250 0 secs Inst
activation of the controller 2 relay and switch-on. 0 = not active.
Delay time after switching off. The indicated time must elapse between
dO2 ALL 0...250 0 min Inst
deactivation of the controller 2 relay and the next switch-on. 0 = not active.
Delay between switch-ons. The indicated time must elapse between two
di2 ALL 0...250 0 min Inst
consecutive switch-ons of regulator 2. 0 = not active.
Switch-off delay. The indicated time must elapse between the request for
dE2 ALL 0...250 0 secs Inst
deactivation of the controller 2 relay and switch-off. 0 = not active.
Controller 2 switch-on time in the event of faulty probe.
On2 if On2=1 and OF2=0, the controller remains on; ALL 0...250 0 min Inst
if On2=1 and OF2>0, the controller operates in Duty Cycle mode.
PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
Controller 2 switch-off time in the event of faulty probe.
OF2 if OF2=1 and On2=0, the controller remains off; ALL 0...250 1 min Inst
if OF2=1 and On2>0, the controller operates in Duty Cycle mode.
SOFT START CONTROLLER (folder ‘SFt’)
NTC/PTC 0.0...25.0 0.0 °C/°F
Value of each subsequent increase (dynamic) of the setpoint.
dSi PT100-Tc 0.0...25.0 0.0 °C/°F Inst
0 = disabled.
V/I 0...25 0 num
dSt Time between two subsequent increases (dynamic) of the Setpoint. ALL 0...250 0 hours Inst
Unt Unit of measurement (parameter dSt). 0 = hours; 1 = minutes; 2 = seconds. ALL 0/1/2 0 num Inst
Establishes which outputs the function must be enabled on:
Sen ALL 0/1/2/3 0 num Inst
0 = disabled; 1 = OUT 1; 2 = OUT 2; 3 = OUT 1 & 2
NTC/PTC 1.0...50.0 2,0 °C/°F
Function reactivation threshold. Establishes the threshold beyond which the
Sdi PT100-Tc 1.0...50.0 2.0 °C/°F Inst
SOFT START function is automatically reactivated.
V/I 1...50 2 num
CYCLIC CONTROLLER (folder ‘cLc’)
Con Output ON time. ALL 0...250 0 min Inst
CoF Output OFF time. ALL 0...250 0 min Inst
ALARMs (folder ‘AL’)
Parameters ‘HA1/HA2’ and ‘LA1/LA2’, intended as the absolute value or
Att differential in relation to the setpoint ”SP1/SP2”. ALL AbS/rEL AbS flag Inst
AbS (0) = absolute value; rEL (1) = relative value.
NTC/PTC 1.0...50.0 2.0 °C/°F
AFd Alarm differential. PT100-Tc 1.0...50.0 2.0 °C/°F Inst
V/I 1...50 2 num
PAO Alarm override time after device is switched on following a power failure. ALL 0...10 0 hours Inst
PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
Alarm exclusion time until the Setpoint is reached.
SAO 0 = disabled. If SAO >0, an alarm will be generated if the Setpoint is not ALL 0...10 0 hours Inst
reached after the time SAO (in hours).
tAO Delay preceding indication of temperature alarm. ALL 0...250 0 min Inst
Alarm output polarity. nC (0) = alarm active and output disabled
AOP ALL nC/nO nC flag Inst
nO (1) = alarm active and output enabled
tP Enable all keys to acknowledge an alarm. n (0) = no; y (1) = yes. ALL n/y y flag Inst
COMMUNICATION (folder ‘Add’)
PtS Selection of communication protocol. t = Televis; d = Modbus. ALL t/d t flag Inst
dEA Index of the device within the family (valid values from 0 to 14). ALL 0...14 0 num Inst
FAA Device family (valid values from 0 to 14). ALL 0...14 0 num Inst
Adr Modbus protocol controller address. ALL 1...255 1 num Inst
Baudrate selection. 48/96/
bAU ALL 96 num Inst
48 (0) = 4800; 96 (1) = 9600; 192 (2) = 19200; 384 (3) = 38400. 192/384
Pty Modbus parity bit. n (0) = none; E (1) = even; o (2) = odd. ALL n/E/o E num Inst
StP Modbus stop bit. 1b (0) = 1 bit; 2b (1) = 2 bit. ALL 1b/2b 1b flag Inst
DISPLAY (folder ‘diS’)
LOCk. Setpoint edit lock. The parameter programming menu can still be
LOC accessed, and the settings changed, which means also that the status of this ALL n/y n flag User/Inst
parameter can be changed so as to unlock the keypad. n (0)= no; y (1) = yes.
Password 1. When enabled (PS1 ≠ 0) it is the password to the ‘User’
PS1 ALL 0...250 0 num User/Inst
parameters (User).
Password 2. When enabled (PS2 ≠ 0) it is the password to the ‘Installer’
PS2 ALL 0...250 15 num Inst
parameters (Inst).
Display values with decimal point. n (0) = no (without decimal point);
ndt ALL n/y/int n num User/Inst
y (1) = yes (with decimal point); int (2) = integer (V/I models only).
PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
Calibration 1. Positive or negative value added to the value read by Pb1, NTC/PTC -30.0...30.0 0.0 °C/°F
CA1 PT100-Tc -30.0...30.0 0.0 °C/°F User/Inst
according to the setting of parameter CAI. V/I -30...30 0 num
Intervention of the offset on display, temperature control or both.
0 = only the value shown is modified;
CAI 1 = sum with only the value used by the controllers and not for the display, ALL 0/1/2 2 num Inst
which remains unchanged;
2 = sum with the displayed value, which is also used by the regulators.
NTC/PTC -199.9...HdL -50.0 °C/°F
LdL Minimum value that can be displayed by the device. PT100-Tc -328...HdL -199.9 °C/°F Inst
V/I -199...HdL -199 num
NTC/PTC LdL...199.9 140.0 °C/°F
HdL Maximum value that can be displayed by the device. PT100-Tc LdL...1350 1350 °C/°F Inst
V/I LdL...199 199 num
Select the unit of measurement of probe 1. NTC/PTC C/F C flag
• NTC/PTC: C (0) = °C, F (1) = °F
dro • PT100-Tc: C (0) = °C, F (1) = °F PT100-Tc C/F C flag Inst
• V/I: n (0) = no unit of measure selected,
t (1) = temperature, P (2) = pressure, H (3) = humidity V/I n/t/P/H n num
CONFIGURATION (folder ‘CnF’) If one or more parameters are changed, the controller MUST be switched off and switched on again.
Probe type selection. NTC/PTC Ptc/ntC ntc flag
• NTC/PTC: Ptc (0) = PTC, ntC (1) = NTC PT100-Tc Jtc/Htc/Pt1 Jtc num
H00 • PT100-Tc: Jtc (0) = TcJ, Htc (1) = Tck, Pt1 (2) = PT100. User/Inst
• V/I: 420 (0) = 4...20mA, 020 (1) = 0...20mA, t10 (2) = 0...10V, 420/020
V/I 420 num
t05 (3) = 0...5V, t01 (4) = 0...1V. t10/t05/t01
Output link:
H01 ALL 0/1/2 0 num Inst
0 = independent; 1 = dependent; 2 = Neutral Zone (or window).
PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
Press the ESC, UP and DOWN keys (if configured for a second function) for the
H02 time H02 to activate the function itself. ALL 0...15 5 secs Inst
N.B.: The AUX function has a fixed activation time of 1 second.
Lower input current/voltage limit. NTC/PTC
H03 PT100-Tc User/Inst
(only present on model V/I) V/I -1999...1999 0 num
Upper current/voltage limit for input. NTC/PTC
H04 PT100-Tc User/Inst
(only present on model V/I) V/I -1999...1999 1000 num
Window filter:
H05 ALL -2/-1/0/1/2 0 num Inst
-2 = very fast; -1 = fast; 0 = normal; 1 = slow; 2 = very slow.
Key or Digital Input with aux/light active with the device OFF (but powered). n
H06 ALL n/y y flag Inst
(0) = not active; y (1) = active.
Stand-by operating mode.
H08 0 = only display switches off; 1 = display on and controllers locked; ALL 0/1/2 2 num Inst
2 = display off and controllers locked.
Delay for output activation after Power On. If H10 = 0 the delay is NOT active; if
H10 ALL 0...250 0 min Inst
H10 ≠ 0 the output will not be activated before this time has expired.
Digital Input Configuration. NTC/PTC 0..9 0 num
0 = disabled; 1 = SOFT START; 2 = Offset setpoint; 3 = Outputs stopped;
H11 PT100-Tc 0...9 0 num Inst
4 = Periodic cycle; 5 = AUX; 6 = Stand-by; 7 = Not used;
8 = External alarm; 9 = External alarm to lock regulators. V/I
Polarity and priority of Digital Inputs (D.I.). NTC/PTC no/nc/noP/ncP no num
H13 no (0) = normally open; nc (1) = normally closed; PT100-Tc no/nc/noP/ncP no num Inst
noP (2) = normally open with priority; ncP (3) = normally closed with priority. V/I
NTC/PTC 0...250 0 min
H14 Digital input activation delay. PT100-Tc 0...250 0 min Inst
V/I
PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
Configuration of Digital Output1 (OUT1). 0 = disabled; 1 = on-off (controller 1)
H21 ALL 0...6 1 num Inst
2 = on-off (controller 2); 3 = Alarm; 4 = Cyclic; 5 = Aux/Light; 6 = Stand-by.
H22 Configuration of Digital Output2 (OUT2). Same as H21. ALL 0...6 1 num Inst
Configuration of UP key.
H31 0 = disabled; 1 = SOFT START; 2 = Offset setpoint; 3 = Outputs stopped; ALL 0...7 0 num Inst
4 = Periodic cycle; 5 = AUX output; 6 = Stand-by; 7 = not used.
H32 Configuration of DOWN key. Same as H31. ALL 0...7 0 num Inst
H33 Configuration of ESC key. Same as H31. ALL 0...7 6 num Inst
rEL firmware version. Device software release: read-only parameter. ALL / / / User/Inst
tAb Parameters table. Reserved: read-only parameter. ALL / / / User
COPY CARD (folder ‘FPr’)
UL Upload. Transfer of programming parameters from instrument to Copy Card. ALL / / / Inst
dL Download. Transfer of programming parameters from Copy Card to instrument. ALL / / / Inst
Format. Cancels all data entered in the Copy Card.
Fr IMPORTANT: If parameter Fr (Copy Card formatting) is used, the data entered ALL / / / Inst
in the card will be permanently lost. This operation cannot be reversed.
FUNCTIONS (folder ‘FnC’)
Function Function label ACTIVE Function label NOT ACTIVE D.I. KEY Alarm signaling
Soft start SOn SOF 1 1 Flashing icon
Reduced setpoint OSP SP 2 2 ON Icon
Actuations block bOn bOF 3 3 ON Icon
Periodic cycle Con CoF 4 4 ON Icon
AUX AOn AOF 5 5 ON Icon
Stand-by On OF 6 6 ON Icon
Alarm acknowledgement tAL tAL 7 7 ON Icon
NOTES: - to modify the status of a given function, press the ‘set’ key
- If the instrument is switched off, the function labels will return to the default status
ELECTRICAL CONNECTIONs
Attention! Make sure the machine is switched off before working on the electrical connections.
The instrument is equipped with screw or disconnectable terminal blocks for connecting electrical cables with a max.
diameter of 2.5 mm2 (one wire per terminal for power connections): for the terminal ratings, see the label on the instrument.
Do not exceed the maximum permissible current; in case of higher loads, use a suitably rated contactor.
Make sure the power supply voltage complies with that required by the instrument. NTC/PTC/PT100 probes have no
connection polarity and can be extended using a normal bipolar cable (Note that extending the probes burdens the
behaviour of the instrument in terms of EMC electromagnetic compatibility: specifically, if Pt100 probes with cable longer
than 3 mt are used, an extreme care must be taken during wiring operations).
Probe cables, power supply cables and the TTL serial cable should be routed separately from power cables.

CONDITIONS OF USE
Permitted use
For safety reasons, the instrument must be installed and used according to the instructions supplied and, in particular, parts
under dangerous voltages must not be accessible in normal conditions.
The device must be adequately protected from water and dust with regard to its application, and must only be accessible
using tools (except for the front panel). The device is suitable for use in household refrigeration appliances and/or similar
equipment and has been tested for safety aspects in accordance with the harmonised European reference standards.
Improper use
Any use other than that expressly permitted is prohibited. The relay contacts provided are of a functional type and subject
to failure: any protection devices required by product standards, or suggested by common sense for obvious safety
requirements, must be installed externally to the instrument.
LIABILITY AND RESIDUAL RISKS
ELIWELL CONTROLS SRL declines any liability for damage due to:
• installation/uses different from those specified and, in particular, not complying with the safety regulations and/or
instructions given in this document;
• use on panels that do not provide adequate protection against electric shocks, water or dust when assembled;
• use on panels allowing access to dangerous parts without the use of tools;
• tampering with and/or modifying the product;
• installation/use on panels not complying with current standards and regulations.

DISCLAIMER
This document is the exclusive property of ELIWELL CONTROLS SRL and may not be reproduced or circulated unless expressly
authorised by ELIWELL CONTROLS SRL itself.
Every care has been taken in preparing this document; nevertheless ELIWELL CONTROLS SRL cannot accept liability for
any damage resulting from its use. The same applies to any person or company involved in preparing and editing this
document. ELIWELL CONTROLS SRL reserves the right to make aesthetic or functional changes at any time without notice.

DISPOSAL
The appliance (or the product) must be disposed of separately in compliance with the local standards in
force on waste disposal.
Eliwell Controls s.r.l.
Via dell’Industria, 15 - Z.I. Paludi
32010 Pieve d’Alpago (BL) ITALY
T: +39 0437 986 111
F: +39 0437 989 066
www.eliwell.com

Technical Customer Support:


T: +39 0437 986 300
E: [email protected]

Sales
T: +39 0437 986 100 (Italy)
T: +39 0437 986 200 (other countries) cod. 9IS44317-1 • ICPlus 915 • EN • rel. 10/14
E: [email protected] © Eliwell Controls s.r.l. 2014 • All rights reserved.

You might also like