BS en 60669-2-4-2005
BS en 60669-2-4-2005
60669-2-4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
ICS 29.120.40
12&23<,1*:,7+287%6,3(50,66,21(;&(37$63(50,77('%<&23<5,*+7/$:
BS EN 60669-2-4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
National foreword
This British Standard is the official English language version of
EN 60669-2-4:2005. It was derived by CENELEC from IEC 60669-2-4:2005.
The CENELEC common modifications have been implemented at the
appropriate places in the text and are indicated by tags .
The UK participation in its preparation was entrusted to Technical Committee
PEL/23, Electrical accessories, which has the responsibility to:
Summary of pages
This document comprises a front cover, an inside front cover, the EN title page,
pages 2 to 37 and a back cover.
The BSI copyright notice displayed in this document indicates when the
document was last issued.
NORME EUROPÉENNE
EUROPÄISCHE NORM March 2005
ICS 29.120.40
English version
This European Standard was approved by CENELEC on 2004-10-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
© 2005 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Foreword
The text of the International Standard IEC 60669-2-4:2004, prepared by SC 23B, Plugs, socket-outlets
and switches, of IEC TC 23, Electrical accessories, together with the common modifications prepared by
the Technical Committee CENELEC TC 23B, Switches for household and similar fixed electrical
installations, was submitted to the Unique Acceptance Procedure and was approved by CENELEC as
EN 60669-2-4 on 2004-10-01.
This European Standard shall be used in conjunction with EN 60669-1:1999. It lists the changes
necessary to convert that standard into a specific standard for isolating switches.
__________
Page 3
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
CONTENTS
1 Scope ...............................................................................................................................5
2 Normative references .......................................................................................................5
3 Definitions ........................................................................................................................5
4 General requirements .......................................................................................................6
5 General notes on tests .....................................................................................................6
6 Ratings .............................................................................................................................6
7 Classification ....................................................................................................................7
8 Marking ............................................................................................................................7
9 Checking of dimensions....................................................................................................8
10 Protection against electric shock ......................................................................................8
11 Provision for earthing .......................................................................................................8
12 Terminals .........................................................................................................................8
13 Constructional requirements ........................................................................................... 12
14 Mechanism ..................................................................................................................... 13
15 Resistance to ageing, protection provided by enclosures of switches and
resistance to humidity..................................................................................................... 14
16 Insulation resistance and electric strength ...................................................................... 14
17 Temperature rise ............................................................................................................ 15
18 Making and breaking capacity ........................................................................................ 16
19 Normal operation ............................................................................................................ 20
20 Mechanical strength ....................................................................................................... 20
21 Resistance to heat.......................................................................................................... 20
22 Screws, current-carrying parts and connections.............................................................. 21
23 Creepage distances, clearances and distances through sealing compound .................... 21
24 Resistance of insulating material to abnormal heat, to fire and to tracking ...................... 21
25 Resistance to rusting ...................................................................................................... 21
26 EMC requirements .......................................................................................................... 21
Annex A (normative) Survey of specimens needed for tests .................................................. 29
Annex B (normative) Additional requirements for switches having facilities for the
outlet and retention of flexible cables ............................................................................. 30
Annex AA (informative) Determination of short-circuit power factor ...................................... 31
Annex BB (informative) SCPDs for short-circuit tests ........................................................... 33
Figure 101 – Test circuit for verification of the short circuit withstand capability with a
SCPD of one-pole isolating switch ........................................................................................ 23
Figure 102 – Test circuit for verification of the short circuit withstand capability with a
SCPD of a two-pole isolating switch ...................................................................................... 24
Figure 103 – Test circuit for verification of the short circuit withstand capability with a
SCPD of a three-pole isolating switch ................................................................................... 25
Figure 104 – Test circuit for verification of the short circuit withstand capability with a
SCPD of a four-pole isolating switch ..................................................................................... 26
Figure 105 – Test apparatus for verification of the minimum I 2 t and I p values to be
withstood by the isolating switch ........................................................................................... 27
This part of IEC 60669 applies to manually operated general purpose isolating switches with a
rated voltage not exceeding 440 V and a rated current not exceeding 125 A, intended for
1 pocS and
household e similar fixed electrical installations, either indoors or outdoors.
NOTE Isolating switches are designed for overvoltage category III and used in environment of pollution degree 2
Thsi clsuae
according ofP
to IEC arta 1 pplseie xcetpa s follows .
60664-1.
2Replcaemneo
Normativetf thf eirstrap agraph :
references
Thsirap
This o tf of
clause IE6Part
C0669a pplies
1 applies to manuallyo
except peratg deerenalrup pose isoltai gnswitchsew ia ht
as follows.
radetlov tgae note xcideegn044 V anda rac deturrent note xceedgni1 25 A, intednedf or
hosuheol dands imilarf ixed elcertciali nstallatisno,e ihtre inodroso r oudtoors .
Addition:
NO ET Isnitalos gwctihsea r esedngif deoro vrevotlgac eagetory dna III use ni denviromnoitullop fo tnenged re2 e
acocrdingt oI EC6 066-41.
IEC 61180-1:1992, High-voltage test techniques for low voltage equipment – Part 1:
Definitions, test and procedure requirements
N 2oitamrve ferenersec
NOTE Normative references to international publications with their corresponding European publications are
listed
Thsi in Annex ofP
clsuae ZA.arta 1 pplseie xcetpa s follows .
3Adtidino:
Definitions
IEC116
This 08-191:,29
clause Hihg-vtloegat
of Part 1 applies etstfollows.
except as echnieuqf sorl owv oltgae eqiuempnt– Part 1:
Definiitons, testa np drcoderu ereuqriements
Additional definitions:
NOTE roNmtaiv efereercnset o intetanrionalp bulictaionsw itht ehic rorrsepondinE guroepp nabulictaisnoa re
siltedni nA nex .AZ
3.101
isolating switch
eD 3finiti
switch designedsno
to provide isolation of the installation or part of the installation and equipment
from the supply and to carry and to make and break the current in all line current carrying
poles
Thsi clsuae foP arta 1 pplseixe ceptsa follows .
3.102
dAtidianod leiftinino:s
conditional short-circuit current
I nc
.3110
value of the a.c. component of a prospective current, which a switch without integral short-
osilatniws gtich
circuit protection, but protected by a suitable short-circuit protective device (hereinafter
switchd esign de otrpovidsi eolati nofot ehinstalalti norop artfo t hei nstallati nona dequipmtne
referred to as SCPD) in series, can withstand under specified conditions of use and behaviour
frmos eht upply nat do carry nat dom ake a dnbreak htc eurren t niall li encurrenc tarrying
oples
.3120
conditoianhs lrot-criuctic uerrnt
I cn
vaulfo e thec.a . componentfo rp aospectiv ecurrenthw ,ci a hswitchiw thoutni tgeral shrot-
circiurp ttoeciton ,ubp trtoecteb dy a suitabls eroht-circiurp ttoecitve edvice( hreeinafter
reefrreda ot s SCPD) nis eries,c an wihtnatsednu dr specifiidnoc detoinso fu se an dbevahiuor
Page 6
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
3.103
I2t
integral of the square of the current over a given time interval (t 0 , t 1 )
t1 2
I 2t = ∫t0 i dt
4 General requirements
5.4 Addition:
6 Ratings
6.2 Modification:
In the first paragraph, delete the values "6 A" and "10 A" and add the values “80 A, 100 A and
125 A.”
Additional note:
NOTE See Annex ZB for special national conditions.
Additional subclause:
7 Classification
7.1.1 Addition:
7.1.6 Addition:
– rail type
7.2 Replacement in Table 1, first column, last line, of the values “16, 20, 25, 32, 40, and 63”
by “equal and above 16”.
8 Marking
8.1 Addition:
The manufacturer shall provide reference(s) of one or more short circuit protection devices
(SCPDs) in his catalogue and/or in the instructions which are provided with the isolating
switch.
8.2 Addition:
8.3 Addition
Isolating switches shall be marked with the symbols for isolating function and for the closed
and open position. These markings shall be visible from the front after installation, even after
removal of the front cover of the enclosure when the isolating switch is mounted and wired as
in normal use. The isolating symbol may be included in a wiring diagram even combined with
symbols of other functions, provided that it is visible from the front under the conditions
specified before.
The marking for the rated conditional short-circuit current (I nc ) shall be on the isolating switch
or in the manufacturer's published literature.
Isolating switches shall be so marked that the actual contact position is clearly indicated.
Deletion of Note 1 .
Page 8
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
9 Checking of dimensions
Accessible parts of isolating switches shall be made of insulating material, with the exception
of the following:
12 Terminals
Replacement of Table 2:
Replacement of Table 4:
Table 4 – Test values for flexion and pull-out for copper conductors
NOTE In tU ehNIETDK INGDOM, islotasro havi gntar ac deurrtneb elo1 w6 A era widelyu sena dep dmrittde.
NOTE See Annex ZB for special national conditions.
Int U ehNITEDK INDGOM,baT lo 5 efP atr pa 1plies.
rCos-s
cesitlano
eraao f orFm 5,1 morF 5,2 morF 4 morF 6 morF01 morF61 morF52 morF53
cudnocto sr 2 ot pu, 5 puto4 ut po 6 ut po 01 t puo 61 t puo 52 t puo 53 t puo 05
ccatpeedb y inclisuv e inclisuv e inclisuv e inlcuisv e inlcuisv e inlcuisv e inlcuisv e inlcuisv e
ehtterminal
mm 2
uP ll 505 0 09 08 06 001
1 09 532
N
ONTE In the UNITED KIGNDOM,i solators having a rated currentb elow 16A arewidely used an pedrmitt.ed
In the UNITEDK IGDNOM, Tablfe 5 o Part 1 applies.
Page 11
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Conductors
Rated current Nominal cross- Diameter of largest Diameter of largest
sectional areas rigid conductor flexible conductor
A mm 2 mm mm
Table 8 – Test current for the verification of electrical and thermal stresses
in normal use of screwless terminals
16 1,5 2,5
Cross-sectional area of the test conductor Force for deflecting the test conductor a
mm 2 N
1,5 0,5
2,5 1,0
a The forces are chosen so that they stress the conductors close to the limit of elasticity.
13 Constructional requirements
Additional subclause:
13.2.101 Isolating switches when in the open position shall provide an isolation distance in
accordance with the requirements necessary to satisfy the isolating function.
Indication of the contact position shall be provided by the position of the actuating member
and/or by suitable means.
NOTE A pilot light alone is not considered as suitable means.
The actuating member shall be connected to the moving contacts in a reliable way. The
actuating member shall not indicate the open position unless all the moving contacts are in
the open position.
Isolating switches shall be so designed that the actuating member can only be fitted in a
manner which ensures correct contact position and correct locking, if the isolating switch is
provided with means for locking. When means are provided or specified by the manufacturer
to lock the isolating switch in the open position, locking in that position shall only be possible
when the contacts are in the open position.
14 Mechanism
Additional subclause:
16.101 Isolating switches shall be suitable for isolation. They shall be tested in the new,
clean and dry conditions, when in the open position, across the terminals of each pole.
The 1,2/50 impulse voltage according to Figure 1 of IEC 61180-1 is applied between the line
terminals connected together and the load terminals connected together with the contacts in
the open position.
The impulses are given by a generator producing positive and negative impulses having a
front time of 1,2 µs and a time to half value of 50 µs, the tolerances being
The shape of the impulses is adjusted with the isolating switch under test connected to the
impulse generator. For this purpose appropriate voltage dividers and voltage sensors shall be
used.
Small oscillations in the impulses are allowed, provided that their amplitude near the peak of
the impulse is less than 5 % of the peak value.
For oscillations on the first half of the front, amplitudes up to 10 % of the peak value are
allowed.
The test voltage shall be chosen from Table 101, in accordance with the rated voltage of the
isolating switch.
NOTE 1 The surge impedance of the test apparatus should be 500 Ω; a substantial reduction of this value is
under consideration.
NOTE 2 The expression “discharge“ is used to cover the phenomena associated with the failure of insulation
under electric stress, which includes current flow and a drop in voltage.
Page 15
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Table 101 – Test voltage across the open contacts for verifying the suitability
for isolation, referred to the rated voltage of the isolating switch and
to the altitude where the test is carried out
Rated voltage Test voltage [kV] and corresponding altitudes above sea level [m]
V Sea level 200 500 1 000 2 000
Not exceeding
3,5 3,5 3,4 3,2 3
130 V
Exceeding
6,2 6 5,8 5,6 5
130 V
17 Temperature rise
Nominal cross-sectional
Rated current Test current area of conductors
A A mm 2
16 20 4a
20 25 4
25 32 6
32 38 10
40 46 16
45 51 16
50 57,5 16
63 75 25
80 90 25
100 115 35
125 145 50
a For isolating switches having a rated voltage not exceeding 250 V, other than those of
pattern number 3 and 03 the test shall be carried out with conductors having a
cross-sectional area of 2,5 mm 2 .
The temperature rise test of the terminals shall not exceed 45 K for isolating switches having
rated current up to and including 63 A, 65 K for isolating switches having rated current greater
than 63 A.
Page 16
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Additional subclause:
The test is intended to verify that the isolating switch is able to withstand, without damage,
short-circuit currents up to and including its rated conditional short-circuit current.
The conditions of 18.101 are applicable to any test intended to verify the behaviour of the
isolating switches under short-circuit conditions.
a) Test circuit
Figures 101, 102, 103 and 104 respectively give diagrams of the circuits to be used for the
tests concerning:
– a single pole isolating switch;
– a two-pole isolating switch;
– a three-pole isolating switch;
– a four-pole isolating switch.
The supply S feeds a circuit including resistors R, reactors L, the short circuit protection
device SCPD and the isolating switch under test D.
The values of the resistors and reactors of the test circuit shall be adjusted to satisfy the
specified test conditions.
The reactors L shall be air-cored. They shall always be connected in series with the
resistors R, and their value shall be obtained by connecting individual reactors in series;
parallel connecting of reactors is allowed when these reactors have practically the same
time-constant.
Since the transient recovery voltage characteristics of test circuits including large air-
cored reactors are not representative of normal service conditions, the air-cored reactor in
any phase shall be shunted by a resistor taking approximately 1 % of the current through
the reactor, unless otherwise agreed between manufacturer and user.
In each test circuit the resistors R and the reactors L are inserted between the supply
source S and the isolating switch D.
The SCPD is inserted between the resistor R and the isolating switch D.
For the tests of 18.101.2 the isolating switch D shall be connected with cables having a
length of 0,75 m per pole and the maximum cross-sectional area corresponding to the
rated current according to Table 2.
NOTE It is recommended to connect 0,5 m on the supply side and 0,25 m on the load side of the isolating
switch.
The diagram of the test circuit shall be given in the test report. It shall be in accordance
with the relevant figure.
There shall be one and only one point of the test circuit which is directly earthed; this shall
be the neutral point of the supply.
Page 17
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
The SCPD may be a circuit-breaker, or a fuse, having an I 2 t and peak current I p not
exceeding the I 2 t and peak current I p withstand capabilities stated by the manufacturer for
the isolating switch D.
For the purpose of verifying the minimum I 2 t and I p values to be withstood by the isolating
switch, as given in Table 102, tests have to be performed. The SCPD shall be adjusted
and shall be embodied either by a silver wire using the test apparatus shown in Figure 105
or by a fuse (as proposed in Annex BB) or by any other means.
For the purpose of this test, verification of the correctly selected and adjusted SCPD (I 2 t
and I p ) is made prior to testing, the isolating switch being replaced by a temporary
connection having a negligible impedance.
The minimum values of let-through energy I 2 t and peak current based on an electrical
angle of 45°, are given in Table 102.
Unless otherwise specified by the manufacturer, these values shall not be higher than
1,1 times the values given in Table 102.
NOTE 1 At the request of the manufacturer higher values of I 2 t and I p may be used.
NOTE See Annex ZB for special national conditions.
For intermediate values of short-circuit test currents the next higher short-circuit current
shall apply.
The verification of the minimum I 2 t and I p values is not needed if the manufacturer has
stated for the isolating switches values higher than the minimum ones, in which case the
stated values shall be verified.
For co-ordination with circuit-breakers, tests with this combination are necessary.
All the conductive parts of the isolating switch D normally earthed in service, including the
metal support on which the isolating switch is mounted or any metal enclosure (see
18.101.1 f), shall be connected to the neutral point of the supply or to a substantially non-
inductive artificial neutral permitting a prospective fault current of at least 100 A.
This connection shall include a copper wire F of 0,1 mm diameter and not less than 50 mm
in length for the detection of the fault current and, if necessary, a resistor R 1 limiting the
value of the prospective fault current of approximately 100 A.
The current sensors O 1 are connected on the load side of the isolating switch D.
The voltage sensors O 2 are connected across the supply terminals.
Resistors R 2 drawing a current of 10 A per phase are connected on the supply side of the
isolating switch D between the reactor for adjusting the prospective current to the rated
conditional short-circuit current of the isolating switch and the isolating switch D.
Page 18
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Unless otherwise stated in the test report, the resistance of the measuring circuits shall be
at least 100 ohm per volt of the power frequency recovery voltage.
The verification tests for the conditional short-circuit withstand capability shall be
performed at values of influencing quantities and factors as stated by the manufacturer in
accordance with Clause 5, unless otherwise specified.
The tests are considered as valid if the values as recorded in the test report are within the
following tolerances for the specified values:
+5
– current: ( ) %;
0
– rated frequency: ± 5 %;
– voltage: ± 5 % (including recovery voltage).
The power factor of each phase of the test circuit shall be determined according to a
recognised method which shall be stated in the test report.
Two examples are given in Annex C.
The power factor of a polyphase circuit is considered as the mean value of the power
factor of each phase.
The power factor shall be in accordance with Table 103.
The value of the power frequency recovery voltage shall be equal to a value
corresponding to 105 % of the rated voltage of the isolating switch D.
NOTE 2 The value of 105 % of the rated voltage is deemed to cover the effects of the variations of the
system voltage under normal service conditions. The upper limit value may be increased with the approval of
the manufacturer.
The isolating switch D and the SCPD are replaced by temporary connections G 1 having
negligible impedance compared with that of the test circuit.
For the test of 18.101.2 the load terminals of the isolating switch D being short-circuited
by means of the connections of negligible impedance, the resistors R and the reactors L
are adjusted so as to obtain, at the test voltage, a current equal to the rated conditional
short-circuit current at the prescribed power-factor; the test circuit is energised
simultaneously in all poles and the current curve is recorded with the current sensor O 1 .
Page 19
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
g) Sequence of operations
The test procedure consists of a sequence of operations. The following symbols are used
for defining the sequence of operations:
O represents an automatic opening operation of the SCPD, the short-circuit being
established by the closing device T, with the isolating switch under test (D) and the
SCPD in the closed position;
CO represents a closing operation of the isolating switch under test (D), both the closing
device T and the SCPD being in the closed position, followed by an automatic
operation of the SCPD.
t represents the time interval between two successive short-circuit operations, which
shall be at least 3 min.
During tests, the isolating switch D shall not endanger the operator.
Furthermore, there shall be no permanent arcing, no flashover between poles or between
poles and exposed conductive parts, no melting of the fuse F.
After the test carried out in accordance with 18.101.2 the isolating switch D shall show no
damage impairing its further use and shall be capable, without maintenance, of
– complying with the requirements of 16.2 without previous humidity treatment, the test
voltage of 4 000 V being reduced by 1 000 V, and the other test voltages by 500 V;
– switching on and off its rated current at its rated voltage once only.
18.101.2 Verification of the co-ordination between the isolating switch and the SCPD
These tests are intended to verify that the isolating switch D, protected by the SCPD, is able
to withstand, without damage, short-circuit currents up to and including its rated conditional
short-circuit current (see 6.101).
The following test is made under the general conditions of 18.101.1, to check that at the rated
conditional short-circuit current I nc the SCPD protects the isolating switch.
For the breaking operations (sequence O), the closing device T is synchronised with respect
to the voltage wave so that a point of initiation is +45° ± 5° from the 0 crossing point. The
same phase shall be used as reference for the purpose of synchronisation for the different
specimens.
Page 20
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
a) Test condition
The connections G 1 of negligible impedance are replaced by the isolating switch D and by
the SCPD.
b) Test procedure
The following sequence of operations is performed:
O - t - CO
NOTE For the explanation of this sequence of operations see 18.101.1 g).
19 Normal operation
Addition:
After the normal operation tests the isolating switch shall comply with 6 mA maximum leakage
current test with a voltage of 110 % of the rated voltage.
16 A, for isolating switches having a rated voltage not exceeding 250 V a.c. of pattern
40 000
number 2
16 A, for pattern number 3 and 03 having a rated voltage not exceeding 250 V
20 000
16 A, for isolating switches having a rated voltage exceeding 250 V a.c.
Above 16 A up to and including 40 A 10 000
Above 40 A up to and including 80 A 5 000
Above 80 A up to and including 125 A 1 000
After the test, the specimen shall withstand an electric strength test as specified in 16.2
without previous humidity treatment, the test voltage of 4 000 V being reduced by 1 000 V,
and the other test voltages by 500 V, and a temperature rise test as specified in Clause 17,
the test current being reduced to a value of the rated current.
NOTE See Annex ZB for special national conditions.
20 Mechanical strength
21 Resistance to heat
101 If the value is lower than 4 mm but not lower than 3 mm compliance with this standard is given when the
isolating switches fulfil the conditions of the test of 16.101.
For isolating switches, parts of insulating material retaining live parts in position shall be of
material resistant to tracking.
25 Resistance to rusting
26 EMC requirements
Figures
Figure 1
Addition:
Figure 2
Addition:
Up to 35 8,2 – – – –
Up to 50 10 – – – –
Figure 3
Addition:
Up to 35 8,2 –
Up to 50 10 –
Figure 4
Addition:
Up to 35 9 – –
Up to 50 9 – –
Figure 5
Addition:
Up to 35 8.2 –
Up to 50 10 –
Page 23
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Additional figures:
R
F
L
R1
R2
G1 P
O2
G1
O1
IEC 419/04
Key
S = Supply
R = Adjustable load resistor
L = Adjustable load reactor
T = Closing device
F = Copper wire fuse
R1 = Fault current limiting resistor
R2 = Resistor drawing a current of 10 A per phase
P = SCPD
G1 = Temporary connection for calibration
O1 = Current sensor
O2 = Voltage sensor
D = Isolating switch under test
Figure 101 – Test circuit for verification of the short circuit withstand capability
with a SCPD of one-pole isolating switch
Page 24
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
S
N
R R
F
L L
R1
R2
G1 P G1
O2
G1 G1
O1
IEC 420/04
Key
S = Supply
R = Adjustable load resistor
L = Adjustable load reactor
T = Closing device
F = Copper wire fuse
R1 = Fault current limiting resistor
R2 = Resistor drawing a current of 10 A per phase
P = SCPD
G1 = Temporary connection for calibration
O1 = Current sensor
O2 = Voltage sensor
D = Isolating switch under test
Figure 102 – Test circuit for verification of the short circuit withstand capability
with a SCPD of a two-pole isolating switch
Page 25
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
S
N
R R R
F
L L L
R1
R2
G1
G1 P G1
O2 O2
O2
G1
G1 G1
D
O1 O1 O1
IEC 421/04
Key
S = Supply
R = Adjustable load resistor
L = Adjustable load reactor
T = Closing device
F = Copper wire fuse
R1 = Fault current limiting resistor
R2 = Resistor drawing a current of 10 A per phase
P = SCPD
G1 = Temporary connection for calibration
O1 = Current sensor
O2 = Voltage sensor
D = Isolating switch under test
Figure 103 – Test circuit for verification of the short circuit withstand capability
with a SCPD of a three-pole isolating switch
Page 26
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
S N
R R R
F
L L L
R1
R2
G1
G1 P G1
O2 O2
O2
G1 G1
G1 G1
O1 O1 O1
IEC 422/04
Key
S = Supply
R = Adjustable load resistor
L = Adjustable load reactor
T = Closing device
F = Copper wire fuse
R1 = Fault current limiting resistor
R2 = Resistor drawing a current of 10 A per phase
P = SCPD
G1 = Temporary connection for calibration
O1 = Current sensor
O2 = Voltage sensor
D = Isolating switch under test
Figure 104 – Test circuit for verification of the short circuit withstand capability
with a SCPD of a four-pole isolating switch
Page 27
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
1
48 200
20
40
2 2
80
200
4
5
10 10 80 10
5,5
3
5 79
90
R=1
25
12
1
IEC 423/04
Dimensions in millimetres
Key
1) Gliding plates
2) Terminal
3) Stop for gliding plate
4) Silver wire
Figure 105 – Test apparatus for verification of the minimum I 2 t and I p values
to be withstood by the isolating switch
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Page 28
Annex A
Annexes
Replacement:
EN 60669−2−4:2005
066-96-24 IE:C002 4
Annex A
(normative)
Survey of specimens needed for tests
The numbers of specimens needed for the tests according to 5.4 are as follows:
Number of
additional
Number
Clauses and subclauses specimens for
of specimens
dual current
rating
6 Ratings A
7 Classification A
8 Marking A
9 Checking of dimensions ABC
10 Protection against electric shock ABC
11 Provision for earthing ABC
12 Terminals a ABC JKL
13 Constructional requirements b ABC
14 Mechanism ABC
15 Resistance to ageing, protection provided by enclosures of ABC
switches and resistance to humidity
16 Insulation resistance and electric strength ABC
17 Temperature rise ABC JKL
18.1 and18.2 Making and breaking capacity ABC JKL
19 Normal operation c ABC JKL
16.101 Impulse test d ABC
20 Mechanical strength subclauses 20.1 to 20.9 e ABC
21 Resistance to heat ABC
22 Screws, current-carrying parts and connections ABC
23 Creepage distances, clearances and distances through sealing
compound ABC
18.101 Short circuit withstand capability XYZ + PQR
16.101 Impulse test d XYZ
19.2 Normal operation for fluorescent lamp circuits DEF MNO
24.1 Resistance to abnormal heat and to fire GHI
24.2 Resistance to tracking f GHI
25 Resistance to rusting GHI
TOTAL 15 6
a Five extra screwless terminals are used for the test of 12.3.11 and one extra set of specimens is used for the
test of 12.3.12.
b An extra set of membranes are needed for each of the tests of 13.15.1 and 13.15.2.
c For isolating switches of pattern number 2 one extra set of specimens is used.
d Test to be carried out only if the clearance of item 6 of Clause 23 is lower than 4 mm.
e One extra set of specimens of cord-operated isolating switches is needed for the test of 20.9.
f One extra set of specimens may be used.
Page 30
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Annex B
(normative)
Additional requirements for switches having facilities for the outlet and
retention of flexible cables
Additional annexes:
Annex AA
(informative)
AA.1 Introduction
There is no method by which the short-circuit power factor can be determined with precision.
Two examples of acceptable methods are given in this annex.
The angle may be determined from the curve of the d.c. component of the asymmetrical
current wave between the instant of the short-circuit and the instant of contact separation as
follows:
i d = I do . e -Rt/L
where
The time-constant L/R can be ascertained from the above formula as follows:
1) measure the value of I do at the instant of short-circuit and the value of i d at another
instant t before contact separation;
2) determine the value of e -Rt/L by dividing i d by I do ;
3) from a table of values of e -x , determine the value of -x corresponding to the ratio of i d /
I do
4) the value x represents Rt/L from which L/R is obtained.
This method should not be used when the currents are measured by current transformers.
Page 32
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
When a pilot generator is used on the same shaft as the test generator, the voltage of the
pilot generator on the oscillogram may be compared in phase first with the voltage of the test
generator and then with the current of the test generator.
The difference between the phase angles between pilot generator voltage and main generator
voltage on the one hand and pilot generator voltage and test generator current on the other
hand gives the phase angle between the voltage and current of the test generator, from which
the power factor can be determined.
Page 33
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Annex BB
(informative)
BB.1 Introduction
For the verification of the minimum I 2 t and l p values to be withstood by the isolating switch as
given in Table 102, short-circuit tests have to be performed. The short-circuit tests shall be
made by the use of a fuse or a silver wire using the test apparatus shown in Figure 105 or by
the use of any other means producing the required I 2 t and l p values.
For the purpose of verifying the minimum I 2 t and l p values to be withstood by the isolating
switch, in order to obtain reproducible test results, the SCPD, if any, may be a silver wire
using the test apparatus shown in Figure 105.
For silver wires with at least 99,9 % purity, Table BB.1 gives an indication of the diameters
according to the rated current l n and the short-circuit currents l nc .
The silver wire shall be inserted horizontally in the appropriate position of the test apparatus
shown in Figure 105 and stretched. The silver wire shall be replaced after each test.
BB.3 Fuses
For the purpose of verifying the minimum I 2 t and l p values to be withstood by the isolating
switch, in order to obtain reproducible test results, the SCPD, if any, may be a corresponding
fuse.
The rating of the fuse shall not be smaller than the rating of the isolating switch. Higher
ratings of fuses may be used to obtain the I 2 t and l p values of Table 102.
Other means may be used provided that the values of Table 102 are fulfilled.
Page 34
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Addition:
Bibliography
IEC 60664-1:1992, Insulation coordination for equipment within low-voltage systems – Part 1:
Principles, requirements and tests
IEC 60999 (all parts), Connecting devices – Electrical copper conductors – Safety require-
ments for screw-type and screwless-type clamping units
___________
Page 35
–5– NE 066-96-2:42005
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Annex ZA
(normative)
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
NOTE Where an International Publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Annex ZB
(normative)
Special national condition: National characteristic or practice that cannot be changed even over a long
period, e.g. climatic conditions, electrical earthing conditions.
For the countries in which the relevant special national conditions apply these provisions are normative,
for other countries they are informative.
Add:
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, this clause in Part 1 applies.
12 United Kingdom
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 2 of Part 1 applies.
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 4 of Part 1 applies.
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 5 of Part 1 applies.
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 6 of Part 1 applies.
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 7 of Part 1 applies.
Page 37
–7– NE 066-96-2:42005
EN 60669−2−4:2005
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 8 of Part 1 applies.
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Tables 9 and 10 of Part 1 applies.
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 12 of Part 1 applies.
17 United Kingdom
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 15 of Part 1 applies.
Isolators having a rated current below 16 A are widely used and permitted. For current
rating less than 16 A, the column for 16 A rating applies.
Isolators having a rated current below 16 A are widely used and permitted. In the United
Kingdom, Table 17 of Part 1 applies.
Isolators having a rated current below 16 A are widely used and permitted. For current
rating less than 16 A, the column for 16 A rating applies.
__________
BS EN
60669-2-4:2005
BSI — British Standards Institution
Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Fri Aug 31 18:56:54 GMT+00:00 2007, Uncontrolled Copy, (c) BSI
Revisions
British Standards are updated by amendment or revision. Users of
British Standards should make sure that they possess the latest amendments or
editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: +44 (0)20 8996 9000. Fax: +44 (0)20 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: +44 (0)20 8996 9001.
Fax: +44 (0)20 8996 7001. Email: [email protected]. Standards are also
available from the BSI website at http://www.bsi-global.com.
In response to orders for international standards, it is BSI policy to supply the
BSI implementation of those that have been published as British Standards,
unless otherwise requested.
Information on standards
BSI provides a wide range of information on national, European and
international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which give
details on all its products and services. Contact the Information Centre.
Tel: +44 (0)20 8996 7111. Fax: +44 (0)20 8996 7048. Email: [email protected].
Subscribing members of BSI are kept up to date with standards developments
and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration.
Tel: +44 (0)20 8996 7002. Fax: +44 (0)20 8996 7001.
Email: [email protected].
Information regarding online access to British Standards via British Standards
Online can be found at http://www.bsi-global.com/bsonline.
Further information about BSI is available on the BSI website at
http://www.bsi-global.com.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
BSI written permission of BSI must be obtained.
389 Chiswick High Road Details and advice can be obtained from the Copyright & Licensing Manager.
London Tel: +44 (0)20 8996 7070. Fax: +44 (0)20 8996 7553.
Email: [email protected].
W4 4AL