0% found this document useful (0 votes)
97 views9 pages

Fire Hose System Report

This report provides information on the fire hose system for a petrol station in Dammam 3rd Industrial City, Saudi Arabia. It was prepared by the mechanical department of the petrol station. The report details the project specifications, including the hazard being protected, hose specifications, water supply data from testing, and hydraulic calculation results. It analyzes the flow through each pipe and node to ensure code-compliant water pressure and flow throughout the system.

Uploaded by

Shaik J Ahammed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
97 views9 pages

Fire Hose System Report

This report provides information on the fire hose system for a petrol station in Dammam 3rd Industrial City, Saudi Arabia. It was prepared by the mechanical department of the petrol station. The report details the project specifications, including the hazard being protected, hose specifications, water supply data from testing, and hydraulic calculation results. It analyzes the flow through each pipe and node to ensure code-compliant water pressure and flow throughout the system.

Uploaded by

Shaik J Ahammed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

PETROL STATION

Fire Hose System Reports

for

PETROL STATION

DAMMAM 3RD INDUSTERIAL CITY

Prepared By:

ALFARID OFFICE DEPT MECH


PETROL STATION
DAMMAM 3RD INDUSTERIAL CITY
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr PETROL STATION
Hell Page 2

General Project Data Report

General Data
Project Title: PETROL STATION Project File Name: HC PETROL STATION..fiw
Designed By: ALFARID OFFICE DEPT MECH Date: 3/3/2021
Code Reference: SBC801 &NFPA 13&14 Approving Agency: CIVIL DEFANCE
Client Name: PETROL STATION Phone:
Address: DAMMAM 3RD INDUSTERIAL
City, State Zip Code:
CITY
Company Name: PETROL STATION Representative:
Company Address: DAMMAM 3RD INDUSTERIAL
City And State:
CITY
Phone:
Building Name: PETROL STATION Building Owner:
Contact at Building: Phone at Building:
Address Of Building: DAMMAM 3RD INDUSTERIAL
City, State Zip Code:
CITY

Project Data
Description Of Hazard: Ordinary 1 Hose System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Hose: 130 ft²
Default Hose K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 100.00 gpm Outside Hose Stream Allowance: 250.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Hose Specifications
Make: Model:
Size: 1/2" Temperature Rating: 155 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 343.62 gpm Calculated Inflow Residual Pressure: 106.57 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 95.00 psi Minimum Desired Flow Density: 0.15 gpm/ft²
Maximum Water Velocity: 25.00 ft/s Maximum Frictional Loss / 100 feet: 0.00 psi
Number Of Active Nodes: 5
Number Of Active Pipes: 4 Number Of Inactive Pipes: 0
Number Of Active Hoses: 1 Number Of Inactive Hoses: 0
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr PETROL STATION
Hell Page 3

Fire Hose Input Data

Node Input Data


Hose KFactor Pressure Node Elev (ft) Fixed Flow
Area Group
Node Node Description (K) Estimate (psi) Branch Non- (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Hose ---- 25.00 95.00 3.28 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 98.04 -3.28 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 73.67 4.92 100.00


3
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 103.66 -3.28 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 106.57 -9.84 0.00


5
---- 0.000 0.0 ---- 0.0 0.00
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr PETROL STATION
Hell Page 4

Fire Hose Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

1 2 SCHED 40 WET STEEL 6.000 0 78.74 0.00 78.74 120

3 2 SCHED 40 WET STEEL 1.500 0 65.62 0.00 65.62 120

2 4 SCHED 40 WET STEEL 6.000 0 1151.57 0.00 1151.57 120

4 5 SCHED 40 WET STEEL 6.000 0 13.12 0.00 13.12 120


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr PETROL STATION
Hell Page 5

Fire Hose Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 -243.79 243.67 0.00 0.00 95.00

2 1 0 243.79 0.00 0.00 0.00 98.04 0.15414


2 3 0 99.98
2 4 0 -343.61

3 2 0 -99.98 0.00 100.00 0.00 73.67 0.01937

4 2 0 343.61 0.00 0.00 0.00 103.66 -0.00817


4 5 0 -343.62

5 4 0 343.62 0.00 0.00 -343.62 106.57


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr PETROL STATION
Hell Page 6

Fire Hose Output Data

Overall Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

1 25.00 3.28 243.67 95.00 6.00 243.67 0.00259 78.74 0.204


2 0.00 -3.28 0.00 98.04 6.065 243.79 ----- 0.00 2.841
SCHED 40 WET STEEL 120 2.71 0 78.74 3.045

3 0.00 4.92 100.00 73.67 1.50 100.00 0.31735 65.62 20.823


2 0.00 -3.28 0.00 98.04 1.610 99.98 ----- 0.00 3.552
SCHED 40 WET STEEL 120 15.76 0 65.62 24.375

2 0.00 -3.28 0.00 98.04 6.00 0.00 0.00488 1151.58 5.619


4 0.00 -3.28 0.00 103.66 6.065 343.61 ----- 0.00 0.000
SCHED 40 WET STEEL 120 3.82 0 1151.57 5.619

4 0.00 -3.28 0.00 103.66 6.00 0.00 0.00488 13.12 0.064


5 0.00 -9.84 0.00 106.57 6.065 343.62 ----- 0.00 2.841
SCHED 40 WET STEEL 120 3.82 0 13.12 2.905
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr PETROL STATION
Hell Page 7

Fire Hose Output Data

Overall Hose Output Data


Flowing Node Residual Flowing Hose
Area Group Hose Flowing Area
Hose Node Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
No. (feet) (psi) (gpm/ft²) (gpm)

1 25.00 3.28 95.00 130.00 1.874 243.67


Sub Totals For Non-Group 130.00 1.874 243.67

Totals For All Groups 130.00 1.874 243.67


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr PETROL STATION
Hell Page 8

Fire Hose Output Summary

Hydraulically Most Demanding Hose Node


HMD Hose Node Number: 1
HMD Actual Residual Pressure: 95.00 psi
HMD Actual GPM: 243.67 gpm

Hose Summary
Hose System Type: Wet
Specified Area Of Application: 1499.95 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 0.162 gpm/ft²
Application Average Area Per Hose: 1499.95 ft²
Hose Flow: 243.67 gpm
Average Hose Flow: 243.67 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 2 - 3 ) 15.76 ft/sec
Maximum Velocity Pressure ( In Pipe 2 - 3 ) 1.67 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi


Actual Maximum Nodal Pressure Imbalance: 0.0076 psi
Actual Average Nodal Pressure Imbalance: 0.0022 psi
Actual Maximum Nodal Flow Imbalance: 0.1541 gpm
Actual Average Nodal Flow Imbalance: 0.0363 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 4
Number Of Flowing Hoses: 1

Pipe System Water Volume: 1873.08 gal

Hose Flow: 243.67 gpm


Fixed Flow: 100.00 gpm

Minimum Required Residual Pressure At System Inflow


106.57 psi
Node:
Demand Flow At System Inflow Node: 343.62 gpm
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr PETROL STATION
Hell Page 9

Fire Hose Output Data

Hydraulic Supply/Demand Graph

200

180

160

140
Pressure psi

120
107
100

80

60

40

20

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 106.57 psi
Calculated Flow Rate: 343.62 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 5.68 psi