OPA 250-560 Econex TD 0123

The document describes a line of ducted packaged air conditioner units called the OPA 250-560 Econex. The units utilize the lower global warming potential refrigerant R32 and feature variable capacity inverters, high efficiency EC motors, and user friendly controls. They are suitable for both commercial and residential applications.

Uploaded by

Jikash Prasad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
342 views28 pages

OPA 250-560 Econex TD 0123

The document describes a line of ducted packaged air conditioner units called the OPA 250-560 Econex. The units utilize the lower global warming potential refrigerant R32 and feature variable capacity inverters, high efficiency EC motors, and user friendly controls. They are suitable for both commercial and residential applications.

Uploaded by

Jikash Prasad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

Ducted Packaged Units

Technical Data

OPA 250, 350, 450, 560 Econex R32

Cooling Capacity Heating Capacity


10.1kW – 64.8kW 6.5kW – 63.0kW
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex

OPA 250–560 LKT SERIES CONTROLS


General 3 TZT-100 Controller (Optional) 7
Applications 4
Features PERFORMANCE DATA
Lower GWP 4 Cooling Capacity (kW) 8
User Friendly 4 Heating Capacity (kW) 12
Economy 4 Indoor Air Flow Correction Factors 11
Efficient 4 Air Handling 13
Performance 4
Sound Levels
Air Flow Selection 4
Indoor Unit 14
Quiet 5
Outdoor Unit 15
Durable 5
Easy Access 5
DIMENSIONS
Inverter Compressor 5
OPA 250 16
Insulation 5
OPA 350 18
Control Option 5
OPA 450 20
Extended Capability 5
OPA 560 22
Safety Features 5
Accessories 24
Self Diagnostics 6
Wiring 6
SPECIFICATIONS 25
Configurations 6
Optional Equipment 6
Economiser 6 Other relevant documents:
- Specification Sheets
- Part Load Data
- Installation & Maintenance
econe
Air Cooled
AIR COOLED PACKAGED

nex gen R32 inver ter

lo w c a r b o n f u t u re

Packaged
Units

COOLING CAPACITY
25.4kW - 55.6kW
HEATING CAPACITY
26.9kW - 57.0kW
Overview brochure available

Page 2 of 28
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex

The OPA provides a variable capacity reverse cycle (heat pump)


packaged rooftop air conditioner designed and developed to
comply with and exceed Minimum Energy Performance
Standards (MEPS AS/NZS 3823). Each system has been
successfully tested at 52°C ambient.

Page 3 of 28
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex

Applications
These units have been specifically developed for air conditioning of light
commercial and residential premises, e.g. offices, motels shops and homes.
Suitable for applications using high proportions of fresh air
(nb pre-heating on heating cycle may be required). Also suitable for VAV, close
control and supply air temperature control.

Features

Lower GWP Efficient Air Flow Selection


Utilising R32 Refrigerant, Temperzone’s These units include high efficiency If the air returning to the indoor coil is
Econex Packaged Units enable a 75-80% electronically commutated (EC) motors, regularly expected to be above 50%RH,
reduction of Global Warming Potential for both indoor and outdoor air fans. Part then the coil face velocity should be
(GWP) per kW of cooling when compared load operation at low loads (75% airflow limited to be 2.5 m/s or less.
to R410A units. equates to 55% power use) using
High humidity levels can occur in tropical
Temperzone algorithms. Each unit
or subtropical conditions, and/or when
User Friendly incorporates a high efficiency inverter
heavily moisture laden fresh air is
compressor. Heat exchange coils use
The air conditioning system is available introduced. Consideration must always
inner grooved (rifled) tube for better heat
with an optional TZT-100 Controller or be given to selecting an air flow and face
transfer.
Climate Touch Controller. These velocity that avoids water carry-over
thermostats have been designed to problems.
maintain a high level of comfort for room Performance
Applications using high proportions
occupants. Emphasis has been placed on The variable capacity inverter compressor
of fresh air should be referred to your
providing controls that are easy to install technology can provide close comfort
nearest Temperzone sales office to
and use — despite the sophisticated control of the room temperature. Each
establish the correct selection of units.
microprocessor system that runs it. Use OPA unit has an extra boost capacity
of the Auto and Timer function settings available for fast response when well
allows you to “set it and forget it”. away from set point at start-up, and an
energy saving low capacity turn-down.
Economy A dynamically balanced backward curved
Each OPA unit has a variable capacity fan with a multi-speed EC motor enables
compressor which uses less energy than fine tuning of the indoor unit to match the
alternative types of compressor. supply air requirements. These EC motor
fans have a fully integrated speed control
that enables soft starting. Fan speed can
be stepped to your own requirements or
continuously variable using a 0–10V DC
control signal.
The system also includes a temperature
sensing head pressure control which
enables the system to compensate for
outdoor ambient temperatures below
20°C on cooling cycle, and above 15°C on
heating cycle.

Page 4 of 28
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex

Features
Quiet balance created by the indoor air fan. Extended Capability
Each integral high efficiency EC motor A controlled outdoor section drainage Inverters are particularly suitable for
can vary from zero to full speed. This system directs water to a drainage point applications requiring high proportions of
allows slow ramp up with no sudden and prevents ponding of water that could fresh air, VAV, close control. Supply air
noise change. The motor can be create a home for moss, mould and slime. temperature control is also possible using
controlled to have the best air flow for the BMS or other controls.
ducting and requirements as well as used Inverter Compressor Refer to Temperzone for capacity range
for de-humidifying the space. Each high efficiency variable capacity variation options.
The outdoor coil design permits low fan inverter compressor is hermetically
speeds and hence low noise levels. The sealed, quiet running and supported on Safety Features
compressor is isolated in a built-in, rubber mounts to minimise vibration. 1. HP and loss of refrigerant protection.
insulated compartment to minimise Inverter compressors provide the 2. Anti-rapid cycle timer and internal
noise. The indoor air section is also economy of part load performance. overload for compressor protection.
insulated for noise attenuation and to 3. Circuit breaker control circuits.
prevent exterior condensation. Soft Starting 4. Time-and-temperature controlled
EC motors and inverter compressors are electronic de-ice switch prevents
Durable soft starting therefore have none of the icing up of the outdoor coil during
problems associated with high in rush heating cycle.
The cabinet is constructed from high
current. 5. Frost protection on cooling cycle.
grade galvanised steel - polyester powder
6. Sensor fault indication.
coated (colour Grey) for all weather
Insulation 7. Compressor minimum run time to
protection (IP 44). External fasteners are
ensure oil return.
marine grade SKT® coated steel. The Closed cell foam insulation has been used 8. 12V control circuit.
units include a polyester powder coated in the indoor air section to ensure no
drain tray. Heat exchange coils comprise particles are introduced into the air Note: Consideration must be given to the
aluminium corrugated plate fins on stream. Both indoor and outdoor minimum floor area requirements of R32
mechanically expanded rifled copper chambers are insulated to prevent refrigerant.
tube. Both the indoor and outdoor air coil external condensation forming on the
fins are epoxy coated for extra protection cabinet exterior. The insulation is foil
in corrosive environments, e.g. salt laden faced and meets fire test standards AS Self Diagnostics
sea air. Fan motor bearings are sealed for 1530.3 (1989) and BS 476 parts 6 & 7. The Unit Controller (UC8) has a LED
life so as not to incur regular display to indicate faults and running
maintenance. Coil protection guards Control Option conditions. A non-specific fault indicator
protect against hail, accidental damage or is included for interface to external
vandalism. Commissioned air flow can be maintained systems via the optional relay board.
through use of the supplied differential
pressure transducer and controller
Easy Access (supplied by others) to compensate for
These packaged outdoor units are varying duct static pressures caused by
typically installed on a rooftop, where dirty filters or modulating dampers.
maintenance access is relatively easy Commissioning is made easier. The EC
during operating hours. Service panels plug fan motor is controlled variably
are hinged with turn locks for ease of (within a restricted range, p11) by a 0–10
access. Air filters are easily accessible volt DC signal that can be supplied either
through hinged door on the side of the by a BMS system, a sophisticated
unit. controller or Temperzone’s optional
TZT-100 Controller.
Low Maintenance The systems’ UC8 controller is BMS
Commissioning and maintenance costs compatible with multi-unit control
are reduced through use of a fan that possible – either via digital and analogue
requires no pulley and belt adjustments or signals or via Modbus. Refer to
changes like traditional fans. Dust is Temperzone for other protocols available.
discouraged from entering the electrical
compartment through a positive pressure

Page 5 of 28
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex

Features
Wiring Configurations Economiser option
The electrical supply required (including 1. Horizontal supply & return air (Controls by Temperzone or others)
voltage fluctuation limits) is: versions
3 phase 380–440 V a.c. 50 Hz with 2. Downward supply & return air If the outdoor air heat content or wet bulb
neutral and earth. versions temperature (dry bulb not recommended)
3. Opposite hand versions of the above. is below that of the return air, the fresh air
The compressor crankcase heater
damper opens and the return air damper
requires a 24hr power supply
Optional Equipment closes to provide the first stage of
The control panel is fully wired ready to cooling. Operating costs are reduced as
4. Filters (G4) rated to AS1324.1.2001 -
accept the main power supply. Each free cooling is obtained. (Note: A spill air
disposable or washable,
system complies with the requirements of facility in the building may be necessary
50 or 100 mm thick.
the Regulatory Compliance Mark (RCM) for when the return air damper is closed.)
for electrical safety (AS/NZS 60335.2.40) 5. Drain tundish connection kits Fresh air dampers close to a minimum
and EMC (AS/NZS CISPR.14). – pack of 2 (pn 060-000-653). setting and return air dampers open
6. Factory fitted economiser -includes before normal compressor operation
For your convenience, a single phase
dampers, fresh air cowl. resumes.
auxiliary power outlet (10A) is included in
the electrical box. 7. Electronic control systems (available
by arrangement) for temperature and Temperzone offers a factory fitted
Provision has been made for compliance economy cycle. Economiser control package, if required.
with DRED, ie demand response enabling
8. Factory fitted adjustable fresh air
device standard AS/NZS 4755.3.1. Dust Protection option
damper and cowl.
9. Interface to BACnet/IP networks. The compressor/electrical compartment
Plant Room Use can be pressurised with indoor supply air.
Each unit is supplied with a high static This assists in keeping dust out of the
(125+ Pa) condenser fan. Nominal compartment.
outdoor airflow, correct unit clearances
and no air recirculation must be
maintained in order for the unit to achieve
its performance specification.

Page 6 of 28
Packaged Rooftop
Air Conditioners R32
Controls

TZT-100 Controller (Optional)

Features
• Cool / Cool Dry / Heat / Auto Dry / • Continuous or Intermittent selection of
Auto / Fan Only modes. fan run-on in dead zone. Optional:
• Auto / High / Medium / Low fan speed • Backlit screen for ease of reading; Remote return air sensor
selection. (customisable).
• Soft touch tab keys
• Temperature setting range from
• PIN protected menus (Installer PIN)
1°C – 38°C. For more information visit
• Keypad and/or temperature lock www.temperzone.biz;
• LED to indicate status of the unit model search 'TZT-100'
[Power On/Off]. • Filter monitor option (by hours)

• Room & set temperature display. • Occupancy sensor inputs

• Real time clock. • Integrated Modbus option

• 12 or 24 hour time display • Battery backup (Lithium).

• °C or °F display • Sleep function – improves night time


comfort and saves energy.
• 7 day timer – up to two events (four start
and/or stops per day) • Audible beep to acknowledge key entry
or wireless remote control.
• On demand countdown run timer,
up to 9 hours. • 24V control cable.

• Auto-Restart or No Restart after • Optional remote air temperature sensor


power failure

Page 7 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data

Cooling Capacity (kW)


TC = Total Capacity (kW) Nominal Air Flow: 1250 l/s
SC = Sensible Capacity (kW)
PI = Power Input (kW) Note: Capacities are gross and do not include allowance
EAT = Entering Air Temperature for fan motor heat loss.
= Nominal Capacity (kW)

OPA 250 Econex @Nominal Capacity (1250 l/s)


Indoor coil
E.A.T. Outdoor coil Entering Air Temperature °C DB
D.B. W.B. 23 27 31 35 39 43
°C °C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
14 23.3 18.0 6.1 22.8 18 6.5 22.4 18.1 6.9 21.8 18 7.4 21.3 17.9 7.9 20.7 17.8 8.5
15 24.1 16.6 6.2 23.6 16.6 6.6 23.1 16.6 7.0 22.6 16.5 7.5 22 16.4 8.0 21.4 16.2 8.5
21
16 25 14.9 6.2 24.5 14.9 6.6 23.9 14.8 7.1 23.4 14.7 7.5 22.8 14.6 8.0 22.1 14.4 8.6
17 25.8 13.1 6.3 25.3 13.0 6.7 24.8 12.9 7.1 24.2 12.8 7.6 23.6 12.6 8.1 22.9 12.4 8.7
15 24 19.5 6.2 23.5 19.5 6.6 23 19.6 7.0 22.5 19.6 7.5 21.9 19.5 8.0 21.3 19.3 8.5
16 24.7 18.1 6.2 24.2 18.2 6.6 23.7 18.1 7.0 23.2 18.1 7.5 22.6 18.0 8.0 21.9 17.8 8.6
23
17 25.6 16.7 6.3 25.1 16.7 6.7 24.5 16.6 7.1 24.0 16.5 7.6 23.3 16.4 8.1 22.7 16.2 8.7
18 26.5 15.0 6.3 25.9 15.0 6.7 25.4 14.9 7.2 24.8 14.8 7.6 24.1 14.6 8.2 23.4 14.4 8.7
18 26.3 21.1 6.3 25.8 21.2 6.7 25.2 21.3 7.2 24.6 21.2 7.6 24.0 21.2 8.2 23.3 21 8.7
19 27.1 19.9 6.4 26.5 19.9 6.8 26 19.9 7.2 25.4 19.9 7.7 24.7 19.8 8.2 24.0 19.6 8.8
27
20 27.9 18.5 6.4 27.3 18.5 6.8 26.7 18.4 7.3 26.1 18.4 7.8 25.4 18.3 8.3 24.7 18.1 8.9
22 29.5 15.0 6.5 28.9 15.0 6.9 28.2 14.9 7.4 27.5 14.7 7.9 26.8 14.6 8.4 26.1 14.4 9.0
21 28.9 22.9 6.5 28.3 23.0 6.9 27.7 23.1 7.3 27.0 23.1 7.8 26.4 23.0 8.4 25.6 22.8 8.9
22 29.6 21.6 6.5 29.0 21.7 6.9 28.3 21.7 7.4 27.7 21.7 7.9 27.0 21.6 8.4 26.2 21.5 9.0
31
23 30.3 20.2 6.6 29.6 20.2 7.0 29.0 20.2 7.4 28.3 20.2 7.9 27.6 20.1 8.5 26.8 19.9 9.0
25 31.8 16.9 6.6 31.1 16.9 7.1 30.4 16.8 7.5 29.7 16.7 8.0 29.0 16.6 8.6 28.1 16.4 9.2

Page 8 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data

Cooling Capacity (kW)


TC = Total Capacity (kW) Nominal Air Flow: 1800 l/s
SC = Sensible Capacity (kW)
PI = Power Input (kW) Note: Capacities are gross and do not include allowance
EAT = Entering Air Temperature for fan motor heat loss.
= Nominal Capacity (kW)

OPA 350 Econex @Nominal Capacity (1800 l/s)


Indoor coil
E.A.T. Outdoor coil Entering Air Temperature °C DB
D.B. W.B. 23 27 31 35 39 43
°C °C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
14 33.0 25.2 8.8 32.3 25.3 9.4 31.6 25.3 10.0 30.9 25.3 10.7 30.2 25.2 11.4 29.4 25.0 12.2
15 34.1 23.2 8.8 33.5 23.2 9.4 32.7 23.2 10.1 32.0 23.1 10.8 31.2 22.9 11.5 30.4 22.8 12.3
21
16 35.3 20.9 8.8 34.6 20.8 9.5 33.9 20.7 10.2 33.1 20.6 10.9 32.3 20.4 11.6 31.4 20.2 12.4
17 36.5 18.2 8.9 35.8 18.1 9.5 35.0 18.0 10.2 34.2 17.8 10.9 33.4 17.6 11.7 32.5 17.3 12.5
15 34.0 27.3 8.8 33.3 27.4 9.4 32.6 27.4 10.1 31.8 27.4 10.8 31.1 27.3 11.5 30.2 27.2 12.3
16 35.0 25.3 8.8 34.3 25.4 9.5 33.6 25.4 10.1 32.8 25.3 10.8 32.0 25.2 11.6 31.1 25.1 12.4
23
17 36.2 23.3 8.9 35.5 23.3 9.5 34.7 23.2 10.2 33.9 23.1 10.9 33.1 23.0 11.7 32.2 22.8 12.5
18 37.4 20.9 8.9 36.7 20.9 9.6 35.9 20.8 10.3 35.1 20.6 11.0 34.2 20.4 11.8 33.3 20.2 12.6
18 37.3 29.6 8.9 36.5 29.7 9.6 35.7 29.8 10.3 34.9 29.8 11.0 34.0 29.7 11.8 33.1 29.5 12.6
19 38.3 27.8 8.9 37.6 27.9 9.6 36.8 27.9 10.3 35.9 27.9 11.1 35.0 27.8 11.8 34.0 27.6 12.6
27
20 39.4 25.8 9.0 38.6 25.8 9.7 37.8 25.8 10.4 36.9 25.7 11.1 36.0 25.6 11.9 35.0 25.4 12.7
22 41.7 20.9 9.0 40.9 20.9 9.7 40.0 20.7 10.5 39.0 20.6 11.2 38.0 20.4 12.1 37.0 20.1 12.9
21 40.9 32.1 9.0 40.1 32.3 9.7 39.2 32.4 10.4 38.3 32.4 11.2 37.3 32.3 12.0 36.3 32.1 12.8
22 41.9 30.3 9.0 41.1 30.4 9.7 40.2 30.5 10.5 39.2 30.4 11.3 38.2 30.3 12.1 37.2 30.1 12.9
31
23 42.9 28.3 9.1 42.0 28.3 9.8 41.1 28.3 10.5 40.1 28.3 11.3 39.1 28.1 12.1 38.0 27.9 13.0
25 45.1 23.6 9.1 44.2 23.6 9.9 43.2 23.5 10.6 42.2 23.3 11.4 41.1 23.2 12.3 39.9 22.9 13.1

Page 9 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data

Cooling Capacity (kW)


TC = Total Capacity (kW) Nominal Air Flow: 2200 l/s
SC = Sensible Capacity (kW)
PI = Power Input (kW) Note: Capacities are gross and do not include allowance
EAT = Entering Air Temperature for fan motor heat loss.
= Nominal Capacity (kW)

OPA 450 Econex @Nominal Capacity (2200 l/s)


Indoor coil
E.A.T. Outdoor coil Entering Air Temperature °C DB
D.B. W.B. 23 27 31 35 39 43
°C °C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
14 41.4 31.9 11.5 40.6 32.0 12.3 39.7 32.0 13.1 38.7 31.9 14.0 37.7 31.7 15.0 36.6 31.4 16.0
15 42.9 29.4 11.5 42.0 29.4 12.3 41.1 29.3 13.2 40.1 29.1 14.1 39.0 28.9 15.1 37.9 28.6 16.1
21
16 44.4 26.5 11.6 43.5 26.4 12.4 42.5 26.3 13.3 41.4 26.1 14.3 40.4 25.8 15.2 39.2 25.5 16.3
17 45.9 23.2 11.7 44.9 23.0 12.5 43.9 22.8 13.4 42.9 22.6 14.4 41.7 22.2 15.4 40.5 21.9 16.4
15 42.7 34.6 11.5 41.8 34.6 12.3 40.8 34.6 13.2 39.9 34.6 14.1 38.8 34.4 15.1 37.7 34.1 16.1
16 43.9 32.1 11.6 43.0 32.2 12.4 42.1 32.1 13.3 41.0 32.0 14.2 40.0 31.8 15.2 38.8 31.5 16.2
23
17 45.5 29.6 11.6 44.5 29.5 12.5 43.5 29.4 13.4 42.5 29.3 14.3 41.3 29.0 15.3 40.2 28.7 16.4
18 47.0 26.6 11.7 46.0 26.5 12.6 45.0 26.3 13.5 43.9 26.1 14.4 42.7 25.8 15.4 41.5 25.5 16.5
18 46.8 37.5 11.7 45.8 37.6 12.6 44.8 37.7 13.5 43.7 37.6 14.4 42.5 37.4 15.4 41.3 37.1 16.5
19 48.2 35.3 11.7 47.1 35.4 12.6 46.1 35.3 13.5 44.9 35.2 14.5 43.7 35.0 15.5 42.5 34.7 16.6
27
20 49.6 32.8 11.8 48.5 32.8 12.7 47.4 32.7 13.6 46.2 32.5 14.6 45.0 32.3 15.6 43.7 32.0 16.7
22 52.4 26.7 11.9 51.3 26.6 12.8 50.1 26.4 13.8 48.9 26.1 14.8 47.5 25.8 15.8 46.2 25.4 17.0
21 51.4 40.8 11.9 50.3 40.9 12.8 49.2 40.9 13.7 48.0 40.9 14.7 46.7 40.7 15.8 45.3 40.4 16.9
22 52.6 38.5 11.9 51.5 38.6 12.8 50.3 38.6 13.8 49.1 38.4 14.8 47.8 38.2 15.9 46.4 37.9 17.0
31
23 53.9 35.9 12.0 52.7 36.0 12.9 51.5 35.9 13.9 50.2 35.8 14.9 48.9 35.5 15.9 47.4 35.2 17.1
25 56.6 30.1 12.0 55.4 30.0 13.0 54.1 29.9 14.0 52.8 29.6 15.0 51.3 29.3 16.1 49.8 28.9 17.3

Page 10 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data

Cooling Capacity (kW)


TC = Total Capacity (kW) Nominal Air Flow: 2600 l/s
SC = Sensible Capacity (kW)
PI = Power Input (kW) Note: Capacities are gross and do not include allowance
EAT = Entering Air Temperature for fan motor heat loss.
= Nominal Capacity (kW)

OPA 560 Econex @Nominal Capacity (2600 l/s)


Indoor coil
E.A.T. Outdoor coil Entering Air Temperature °C DB
D.B. W.B. 23 27 31 35 39 43
°C °C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
14 51.2 38.6 14.2 50.2 38.7 15.2 49.1 38.7 16.2 48.0 38.6 17.3 46.8 38.4 18.5 45.5 38.2 19.8
15 53.0 35.4 14.3 52.0 35.4 15.3 50.8 35.4 16.3 49.6 35.2 17.5 48.4 35.0 18.7 47.1 34.7 19.9
21
16 54.9 31.8 14.3 53.7 31.7 15.4 52.6 31.6 16.5 51.3 31.4 17.6 50.0 31.1 18.8 48.7 30.7 20.1
17 56.7 27.7 14.4 55.6 27.5 15.5 54.4 27.3 16.6 53.1 27.0 17.7 51.7 26.7 19.0 50.3 26.3 20.3
15 52.8 41.8 14.2 51.7 41.9 15.3 50.6 42.0 16.3 49.4 41.9 17.5 48.1 41.8 18.6 46.8 41.5 19.9
16 54.3 38.8 14.3 53.2 38.8 15.3 52.1 38.8 16.4 50.8 38.7 17.6 49.6 38.5 18.8 48.2 38.2 20.0
23
17 56.2 35.5 14.4 55.1 35.5 15.4 53.9 35.5 16.5 52.6 35.3 17.7 51.2 35.0 18.9 49.8 34.7 20.2
18 58.1 31.9 14.4 56.9 31.8 15.5 55.7 31.6 16.6 54.3 31.4 17.8 53.0 31.1 19.1 51.5 30.7 20.4
18 57.8 45.4 14.4 56.7 45.5 15.5 55.4 45.6 16.6 54.1 45.6 17.8 52.7 45.4 19.0 51.2 45.1 20.3
19 59.5 42.6 14.5 58.3 42.7 15.6 57.0 42.7 16.7 55.6 42.6 17.9 54.2 42.4 19.2 52.7 42.1 20.5
27
20 61.2 39.4 14.6 59.9 39.4 15.6 58.6 39.4 16.8 57.2 39.2 18.0 55.7 39.0 19.3 54.2 38.7 20.6
22 64.7 31.9 14.7 63.4 31.7 15.8 61.9 31.5 17.0 60.5 31.2 18.2 58.9 30.9 19.5 57.2 30.5 20.9
21 63.5 49.2 14.6 62.2 49.4 15.7 60.8 49.5 16.9 59.4 49.5 18.1 57.8 49.4 19.4 56.2 49.1 20.8
22 65.0 46.4 14.7 63.7 46.5 15.8 62.2 46.6 17.0 60.7 46.5 18.2 59.2 46.3 19.5 57.5 46.0 20.9
31
23 66.5 43.2 14.7 65.1 43.3 15.9 63.7 43.3 17.1 62.1 43.2 18.3 60.5 42.9 19.6 58.8 42.6 21.0
25 69.9 36.0 14.8 68.4 35.9 16.0 66.9 35.7 17.2 65.3 35.5 18.5 63.5 35.2 19.9 61.7 34.8 21.3

Indoor Air Flow Correction Factors @ nominal conditions


Indoor Air Flow (%)

-20 -10 Rated +10

Total Capacity 0.95 0.975 1.0 1.025

Sensible Capacity 0.90 0.950 1.0 1.050

Page 11 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data

Heating Capacity (kW)


G = Gross Capacity kW, based on nominal air flow.
N = Net Heating Capacity kW allowing for average defrost.
= Nominal Capacity (kW).

OPA 250 at Nominal Capacity (1250 l/s)


Air on Outdoor coil entering air temperature °C DB

D.B. -5 -3 -1 1 3 5 7 9
°C G N PI G N PI G N PI G N PI G N PI G N PI G N PI G N PI
15 26.6 19.0 8.0 26.1 19.1 8.4 25.6 19.2 8.9 25.0 19.2 9.5 24.9 21.4 7.3 24.3 19.1 10.1 23.6 18.9 10.7 30.9 30.9 8.9
20 27.6 17.4 8.1 27.1 17.4 8.5 26.5 17.4 9.0 25.9 17.4 9.6 24.6 21.1 7.9 25.2 17.3 10.2 24.5 17.1 10.8 30.6 30.6 9.5
25 28.6 15.4 8.2 28.0 15.5 8.6 27.4 15.4 9.1 26.8 15.3 9.7 23.9 20.6 8.5 26.1 15.2 10.3 25.3 15.1 11.0 29.9 29.9 10.2

OPA 350 at Nominal Capacity (1800 l/s)


Air on Outdoor coil entering air temperature °C DB

D.B. -5 -3 -1 1 3 5 7 9
°C G N PI G N PI G N PI G N PI G N PI G N PI G N PI G N PI
15 27.9 24.4 10.2 29.5 24.1 10.3 31.0 24.5 10.5 32.6 26.1 10.5 34.2 29.4 10.5 35.8 35.0 10.6 37.4 37.4 10.8 39.0 39.0 10.9
20 27.5 24.1 10.9 29.0 23.8 11.0 30.6 24.2 11.2 32.2 25.8 11.3 33.8 29.1 11.2 35.4 34.7 11.4 37.0 37.0 11.5 38.6 38.6 11.7
25 26.6 23.4 11.6 28.2 23.1 11.8 29.8 23.5 12.0 31.3 25.1 12.1 32.9 28.4 12.0 34.5 34.0 12.2 36.1 36.1 12.4 37.7 37.7 12.5

OPA 450 at Nominal Capacity (2200 l/s)


Air on Outdoor coil entering air temperature °C DB

D.B. -5 -3 -1 1 3 5 7 9
°C G N PI G N PI G N PI G N PI G N PI G N PI G N PI G N PI
15 33.5 29.3 12.6 35.4 28.9 12.8 37.3 29.4 13.0 39.2 31.3 13.1 41.1 35.3 13.0 43.0 42.1 13.2 44.9 44.9 13.3 46.8 46.8 13.5
20 33.0 28.9 13.4 34.9 28.6 13.6 36.8 29.0 13.9 38.7 30.9 13.9 40.6 34.9 13.9 42.5 41.7 14.1 44.4 44.4 14.2 46.3 46.3 14.4
25 31.9 28.1 14.3 33.8 27.7 14.5 35.7 28.2 14.8 37.6 30.1 14.9 39.5 34.1 14.8 41.5 40.8 15.0 43.4 43.4 15.2 45.3 45.3 15.4

OPA 560 at Nominal Capacity (2600 l/s)


Air on Outdoor coil entering air temperature °C DB

D.B. -5 -3 -1 1 3 5 7 9
°C G N PI G N PI G N PI G N PI G N PI G N PI G N PI G N PI
15 42.9 37.6 16.8 45.4 37.1 17.0 47.8 37.7 17.4 50.3 40.2 17.4 52.7 45.3 17.4 55.2 54.0 17.6 57.6 57.6 17.8 60.1 60.1 18.0
20 42.3 37.1 17.9 44.7 36.6 18.2 47.2 37.2 18.6 49.6 39.7 18.6 52.1 44.8 18.6 54.5 53.5 18.8 57.0 57.0 19.1 59.4 59.4 19.3
25 40.9 36.0 19.1 43.4 35.6 19.5 45.8 36.2 19.9 48.3 38.6 19.9 50.7 43.7 19.9 53.2 52.4 20.2 55.6 55.6 20.4 58.1 58.1 20.7

Page 12 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data

Air Handling
Airflows are for a dry coil. Reduce airflow by 10% in high moisture removal conditions. In a free blow application, beware of exceeding indoor
fan motor’s full load amp limit. Refer back page for filter losses. Air flows given are for OPA units without filters installed.
Amps
OPA 250 OPA 350
l/s - Pa - - - - l/s - W l/s - Pa - - - - l/s - W
500 3.5 500 4.0
4.9
INPUT (kW)

4.7

INPUT (kW)
1.7 2.5 3.4 2.4 3.4
9V 3.0 3.5
8V 9V

AVAILABLE EXTERNAL PRESSURE (Pa)


AVAILABLE EXTERNAL PRESSURE (Pa)

7V
400 2.5 400 3.0
8V 9V
6V
2.0 2.5
8V
7V
300 1.5 300 2.0
6V 7V 1.5
1.0
5V 8V 4.3
200 6V 1.0
200 0.5
7V 5V
6V 5V
100 100
5V 2.9

1.1 1.5 2.2 3.1 1.0 1.5 2.0


0 0
0 500 1000 1500 2000 2500 0 500 1000 1500 2000 2500
NOMINAL
AIR FLOW (l/s) 2.5 m/s Face Velocity
NOMINAL
AIR FLOW (l/s) 2.5 m/s Face Velocity

OPA 450 OPA 560


l/s - Pa - - - - l/s - W l/s - Pa - - - - l/s - W
500 5.0 500 5.0
4.6 5.4
INPUT (kW)

5.6

INPUT (kW)
2.3 6.7
4.0 10V
3.3 10V 4.0
4.0 9V
AVAILABLE EXTERNAL PRESSURE (Pa)

AVAILABLE EXTERNAL PRESSURE (Pa)

400 9V 3.0 400


1.7 3.0
8V
8V
2.0 2.0
7V
6V 2.8 7V
300 1.0 300 1.0
5V 6V
5V 10V
0.0 9V 0.0
10V 1.9
9V 8V
200 200
8V
7V 7V
6V 1.3
5V 6V
100 100
4.5 5V
5.1 6.1
1.0 1.4 2.0 2.8 3.9 1.2 1.8 2.5 3.5
0 0
500 1000 1500 2000 2500 3000 1000 1500 2000 2500 3000 3500 4000
NOMINAL NOMINAL
AIR FLOW (l/s) 2.5 m/s Face Velocity AIR FLOW (l/s) 2.5 m/s Face Velocity

Filter Pressure Drop (optional Filters)


EU4/G4 rated filter media
100

MAX. FINAL
80
PRESSURE
PRESSURE DROP (Pa)

DROP
60
250 Pa
40

ilter)
an F
20
ITIA L (Cle
IN
0
0 0.5 1.0 1.5 2.0 2.5 3.0
FILTER FACE VELOCITY (m/s)

Page 13 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data

Sound Levels – Indoor


Test Conditions: EN 12102-1:2017.
Diffuse field method in a reverberant room.
Measured in decibels re 1 picowatt.

Sound Power Levels (SWL) – Supply Air Outlet


Octave Band Frequency Hz

125 250 500 1k 2k 4k


Static
Models Fan Speed (Pa) SWL dB(A) Sound Power Levels (SWL) dB

4V 75 72 51 64 65 68 64 60

OPA 250 5.5 V * 75 78 57 70 71 74 70 66

10 V 75 88 67 80 81 84 80 76

4V 85 72 63 64 65 67 63 58

OPA 350 6.5 V * 85 80 71 72 73 75 71 66

10 V 85 87 78 79 80 82 78 73

4V 25 72 63 64 65 67 63 58

OPA 450 75* 85 84 75 76 77 79 75 70

10 V 110 89 80 81 82 84 80 75

4V 50 73 64 66 66 68 63 56

OPA 560 7.5 V * 110 84 75 77 77 79 74 67

10 V 300 91 82 84 84 86 81 74

* Note: Indoor Air fan running at nominal speed

Sound Pressure Levels (SPL) Within A Room


Deduct the room absorption effect below from the Sound Power Levels (SWL) above to obtain Sound Pressure Levels within a room.
Note: Occupant at least 1.5 m from sound source.

Octave Band Frequency Hz

125 250 500 1k 2k 4k

Room type Room Absorption Effect

Soft 4 8 11 11 11 11

Medium 3 7 8 9 9 9

Hard 0 1 3 4 4 5

Page 14 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data

Sound Levels – Outdoor

Sound Power Levels (SWL) – Radiated Measured in decibels re 1 picowatt

Octave Band Frequency Hz

125 250 500 1K 2K 4K

Models Fan Speed SWL dB(A) Sound Power Levels (SWL) dB


2.2 V 66 54 56 58 61 59 57
OPA 250 6V* 74 62 64 66 69 67 65
10 V 86 74 76 78 81 79 77
2.2 V 66 54 56 58 61 59 57
OPA 350 7V* 78 66 68 70 73 71 69
10 V 86 74 76 78 81 79 77
2.2 V 69 54 58 63 64 63 57
OPA 450 7V* 80 65 69 74 75 74 68
10 V 86 71 75 80 81 80 74
4V 69 54 58 63 64 63 57
OPA 560 8V* 83 68 72 77 78 77 71
10 V 86 71 75 80 81 80 74
* Note: Outdoor fans running at nominal speed

Sound Pressure Levels (SPL)


Models Fan Speed SPL @ 3 m dB(A) Sound Pressure Levels (SPL) dB
2.2 V 50 38 40 42 45 43 41
OPA 250 6V* 58 46 48 50 53 51 49
10 V 70 58 60 62 65 63 61
2.2 V 50 38 40 42 45 43 41
OPA 350 7V* 62 50 52 54 57 55 53
10 V 70 58 60 62 65 63 61
2.2 V 53 38 42 47 48 47 41
OPA 450 7V* 64 49 53 58 59 58 52
10 V 70 55 59 64 65 64 58
4V 53 38 42 47 48 47 41
OPA 560 8V * 67 52 56 61 62 61 55
10V 70 55 59 64 65 64 58
Sound Pressure Level (SPL) in decibels re 20 µPa

Page 15 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)

OPA 250RLTFPQ Horizontal Supply

PROJECTION
POINT LOADS (kg)
W X Y Z
no F/A 104 149 100 158
Std Hd
cw F/A 104 157 100 158
Not to Scale
Op Hd no F/A 121 155 91 144

Refer page 26 ror 800 MIN. CLEARANCE TO UNIT Multiple units side-by-side:
Optional Economiser Cowl 570 220 Allow a minimum of 1m
500 MIN. CLEARANCE
dimensions between coil faces.
Filter
Access Optional
Fresh Air OPPOSITE
W Cowl X HAND

RETURN
AIR
500 MIN. CLEARANCE

SUPPLY
AIR

RETURN
AIR

SUPPLY
AIR

Z Opposite Y
Hand
Electrical F/A Cowl
Access
Fan
2000 MIN. CLEARANCE Access

376 376

Optional
Fresh Air
Cowl
441

Drain 25 ID
BSP female
16 DIA. HOLES 360

Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.

Page 16 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)

OPA 250RLTFPQ Downward Supply

PROJECTION
POINT LOADS (kg)
W X Y Z
no F/A 104 149 100 158
Std Hd
cw F/A 104 157 100 158
Filter Not to Scale
Op Hd no F/A 121
Access155 91 144

800 MIN. CLEARANCE


Refer previous page for Filter Multiple units side-by-side:
full dimensions 500 MIN. CLEARANCE Access Allow a minimum of 1m
between coil faces.
Optional
Fresh Air
Cowl X
W
500 MIN. CLEARANCE

Z Y
Electrical
Access
Fan
2000 MIN. CLEARANCE Access

1000 MIN. CLEARANCE

Optional
Fresh Air
Cowl

SUPPLY RETURN
AIR AIR

OPPOSITE RETURN SUPPLY


HAND AIR AIR

Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.

Page 17 of 28
Ducted Split
Packaged Rooftop
System R32
Air Conditioners R32
Dimensions (mm)

OPA 350RLTFPQ Horizontal Supply

POINT LOADS (kg) PROJECTION

W X Y Z
no F/A 164 133 153 146
Std Hd
cw F/A 164 141 153 146
Not to Scale
Op Hd no F/A 159 152 132 153

Refer page 26 ror 800 MIN. CLEARANCE TO UNIT Multiple units side-by-side:
Optional Economiser Cowl 500 MIN. CLEARANCE
570 220
Allow a minimum of 1m
dimensions Filter
between coil faces.
Access Optional
Fresh Air OPPOSITE
W Cowl X HAND

RETURN
AIR
500 MIN. CLEARANCE

SUPPLY
AIR

RETURN
AIR

SUPPLY
AIR

Z
Opposite Y
Electrical Hand
Access F/A Cowl
2000 MIN. CLEARANCE
Fan
Access
1000 MIN. CLEARANCE

102 376 547 376 102


464

Optional
Fresh Air
Cowl
711

595
154
576

Drain 25 ID
16 DIA. HOLES BSP female 360

Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.

Page 18 of 28
Ducted Split
Packaged Rooftop
System R32
Air Conditioners R32
Dimensions (mm)

OPA 350RLTFPQ Downward Supply

POINT LOADS (kg) PROJECTION

W X Y Z
no F/A 164 133 153 146
Std Hd
cw F/A 164 141 153 146
Not to scale
Op Hd no F/A 159 152 132 153

800 MIN. CLEARANCE


Refer previous page for Filter
Multiple units side-by-side:
full dimensions 500 MIN. CLEARANCE Access Allow a minimum of 1m
between coil faces.
Optional
Fresh Air
Cowl
W X
500 MIN. CLEARANCE

Z Y
Electrical
Access
2000 MIN. CLEARANCE Fan
Access
1000 MIN. CLEARANCE

Optional
Fresh Air
Cowl

SUPPLY RETURN
AIR AIR

OPPOSITE RETURN SUPPLY


HAND AIR AIR

Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.

Page 19 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)

OPA 450RLTFPQ Horizontal Supply

POINT LOADS (kg) PROJECTION

W X Y Z
no F/A 134 170 134 205
Std Hd
cw F/A 134 179 134 205
Not to scale
Op Hd no F/A 148 173 133 189

Refer page 26 ror 1000 MIN. CLEARANCE TO UNIT Multiple units side-by-side:
Optional Economiser Cowl Allow a minimum of 1m
dimensions 500 MIN. CLEARANCE 570 406 between coil faces.
Filter Optional
Access Fresh Air
Cowl OPPOSITE
W X HAND

RETURN
AIR
SUPPLY
500 MIN. CLEARANCE

AIR

RETURN
AIR
SUPPLY
AIR

Z Y
Opposite
Electrical Hand
Access F/A Cowl

2000 MIN. CLEARANCE Fan


Access

1000 MIN. CLEARANCE

Optional
Fresh Air
Cowl
420

Drain 25 ID
BSP female
16 DIA. HOLES
449

Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.

Page 20 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)

OPA 450RLTFPQ Downward Supply

POINT LOADS (kg) PROJECTION

W X Y Z
no F/A 134 170 134 205
Std Hd
cw F/A 134 179 134 205
Not to scale
Op Hd no F/A 148 173 133 189

Refer previous page for


Multiple units side-by-side:
full dimensions 1000 MIN. CLEARANCE TO UNIT Allow a minimum of 1m
Filter between coil faces.
500 MIN. CLEARANCE Access

Optional
Fresh Air
Cowl
W X
500 MIN. CLEARANCE

Z Y
Electrical
Access

2000 MIN. CLEARANCE Fan


Access

1000 MIN. CLEARANCE

Optional
Fresh Air
Cowl

SUPPLY RETURN
AIR AIR

OPPOSITE RETURN SUPPLY


HAND AIR AIR

Page 21 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)

OPA 560RLTFPQ Horizontal Supply

PROJECTION
POINT LOADS (kg)
W X Y Z
no F/A 182 171 195 211
Std Hd
cw F/A 196 199 207 217
Not to scale
Op Hd no F/A 168 218 153 220

1000 MIN. CLEARANCE TO UNIT


Multiple units side-by-side:
Refer page 26 ror
Allow a minimum of 1m
Optional Economiser Cowl 570 406
500 MIN. CLEARANCE between coil faces.
dimensions
Filter
Access Optional
Fresh Air OPPOSITE
Cowl
W X HAND

RETURN
AIR
500 MIN. CLEARANCE

SUPPLY
AIR

RETURN
AIR
SUPPLY
AIR

Z Y
Opposite
Hand
Electrical
Access F/A Cowl

Fan
2000 MIN. CLEARANCE Access

1000 MIN. CLEARANCE

Optional
Fresh Air
Cowl
572
155

Drain 25 ID
BSP female
2260 MTG CTRS 449
16 DIA. HOLES

Page 22 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)

OPA 560RLTFPQ Downward Supply

PROJECTION
POINT LOADS (kg)
W X Y Z
no F/A 182 171 195 211
Std Hd
cw F/A 196 199 207 217
Not to scale
Op Hd no F/A 168 218 153 220

1000 MIN. CLEARANCE TO UNIT


Refer previous page for Filter
Access Multiple units side-by-side:
full dimensions 500 MIN. CLEARANCE
Allow a minimum of 1m
Optional between coil faces.
Fresh Air
Cowl
W X
500 MIN. CLEARANCE

Z Y
Electrical
2000 MIN. CLEARANCE Access

Fan
Access

1000 MIN. CLEARANCE

Optional
Fresh Air
Cowl

SUPPLY RETURN
AIR AIR

OPPOSITE RETURN SUPPLY


HAND AIR AIR

Page 23 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)

Accessories
Note: Both Economiser and Fresh Air Cowls are mounted on a hinged access door.
PROJECTION

Economiser Cowl Fresh Air Cowl


Not to scale
Dimension

Model A B C Model A B C

OPA 250-Z 608 201 1000 OPA 250-C 235 505 286

OPA 350-Z 608 201 1000 OPA 350-C 235 658 286

OPA 450-Z 803 290 1200 OPA 450-C 421


Dimension: 480
A 453
B C
Dimension: A B OPA 250 235 505 286
OPA 350 ” 658 286
OPA 560-Z OPA 250/350
803 290
608 1200
201 OPA 560-C 421
OPA 450
633
421
453
480 453
OPA 450/560 803 290
OPA 560 ” 633 453

800 MIN. CLEARANCE TO UNIT


‘C’ MIN. CLEARANCE TO UNIT

540
A

A
B

800 MIN. CLEARANCE


TO UNIT

Economiser
Cowl
Fresh Air
Cowl
CLEARANCE)
(300 MIN.
CLEARANCE)
(300 MIN.

Page 24 of 28
Packaged Rooftop
Air Conditioners R32
Specifications
System
Model OPA 250RLTFPQ OPA 350RLTFPQ OPA 450RLTFPQ OPA 560RLTFPQ
Cooling Capacity 1 kW 25.4 (10.1~29.1) 35.9 (18~45.4) 44.9 (18.2~52.4) 55.6 (27.4~64.8)
Net Cooling Capacity (MEPS) 1 kW 24.6 34.8 43.3 53.6
TCSPF (cold/mixed/hot)
1
6.43 / 5.41 / 4.73 4.71 / 5.60 / /4.85 5.20 / 4.56 / 4.34 5.22 / 4.60 / 4.21
EER / AEER (cooling) 3.20 / 3.18 3.15 / 3.14 2.99 / 2.98 2.99 / 2.98
Heating Capacity 2 kW 26.9 (6.5~29.3) 37.0 (13.9~47) 44.4 (16.5~54.5) 57.0 (24.0~63.0)
HSPF 2 (cold/mixed/hot) 2.21 / 2.60 / 3.30 2.85 / 3.00 / 3.07 2.72 / 2.82 / 2.86 2.66 / 2.83 / 2.94
COP / ACOP (heating) 3.33 / 3.31 3.21 / 3.19 3.14 / 3.13 2.98 / 2.97
Nominal Air Flow l/s
3
1250 (625~1950) 1800 (1100~2450) 2200 (1100~2900) 2600 (1300~3610)
Unit Controller UC8
Power Source 4 3 phase 400 V a.c. 50 Hz + N + E
Refrigerant R32 (Class A2L)
Compressor type inverter scroll
Indoor air fan type backward curved EC plug
Outdoor air fan type EC axial
Indoor Fan Max. Current A/ph. 6 5.5 5.5 6.4
Running Amps (Total) A/ph. 12.5 / 11.5 /13 17.5 / 15.5 / 19.5 24 / 22 / 24 28 / 26 / 29
Max. Running Amps (Total) A/ph. 24 35 40 44
IP Rating IP44 / IPX4 5
Finish grey polyester powder coat
Operating Range (outdoor ambient)
Cooling –10°C to 52°C
Heating –15°C to 25°C
Weight (net/shipping) kg
Unit 511 / 567 596 / 652 643 / 708 759 / 823
Unit c/w Fresh Air 519 / 575 604 / 660 652 / 717 817 / 881
Unit c/w Economiser 556 / 612 649 / 674 697 / 762 831 / 895

Notes:
1
 ominal Cooling Capacity (gross) at AS/NZS 3823 conditions:
N 3
 upply air flow at Nominal Cooling Capacity conditions stated above.
S
– Indoor Entering Air Temperature 27°C D.B., 19°C W.B.; Air lows less than Nominal will reduce cooling capacity.
– Outdoor Entering Air Temperature 35°C D.B. 4
Voltage range: 380–440 V
2
Heating Capacity at AS/NZS 3823 conditions: 5
Outdoor fan clearance <100mm (ref. IEC 60529)
– Indoor Entering Air Temperature 20°C D.B.;
– Outdoor Entering Air Temperature 7°C D.B., 6°C W.B.

Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.

Page 25 of 28
Packaged Rooftop
Air Conditioners R32
Notes

Page 26 of 28
Packaged Rooftop
Air Conditioners R32
Notes

Page 27 of 28
www.temperzone.biz

Auckland Sydney Newcastle


Phone: (02) 4692 1155
Head Office Head Office
Fax: (02) 4961 5101
38 Tidal Rd, Mangere, Auckland 14 Carnegie Place, Blacktown
Private Bag 93303, Otahuhu NSW 2148
New Zealand PO Box 8064, Seven Hills West
NSW 2147, Australia
Email: [email protected] Launceston
Phone: (09) 279 5250 Email: [email protected] Phone: (03) 6331 4209
Fax: (09) 275 5637 Phone: (02) 8822 5700 Fax: (03) 6333 0224
Fax: (02) 8822 5711

Wellington Adelaide Singapore


Phone: (04) 569 3262 Phone: (08) 8115 - 2111 Phone: +65 6733 4292
Fax: (04) 566 6249 Fax: (08) 8115 2118 Fax: +65 6235 7180

Christchurch Melbourne Shanghai


Phone: (03) 379 3216 Phone: (03) 8769 7600 Phone: +86 (21) 5648 2078
Fax: (03) 379 5956 Fax: (03) 8769 7601

Brisbane
Phone: (07) 3308 8333
Fax: (07) 3308 8330

Perth
Phone: (08) 9314 3844
Fax: (08) 9314 3855

GISTERED
RE

AS/NZS
ISO 9001:
2015
SU
PPLIER

Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.

© temperzone ltd 2022 03/23 Pamphlet No. 4131