Technical Data
lo w c a r b o n f u t u re
Packaged
Units
COOLING CAPACITY
25.4kW - 55.6kW
HEATING CAPACITY
26.9kW - 57.0kW
Overview brochure available
Page 2 of 28
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex
Page 3 of 28
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex
Applications
These units have been specifically developed for air conditioning of light
commercial and residential premises, e.g. offices, motels shops and homes.
Suitable for applications using high proportions of fresh air
(nb pre-heating on heating cycle may be required). Also suitable for VAV, close
control and supply air temperature control.
Features
Page 4 of 28
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex
Features
Quiet balance created by the indoor air fan. Extended Capability
Each integral high efficiency EC motor A controlled outdoor section drainage Inverters are particularly suitable for
can vary from zero to full speed. This system directs water to a drainage point applications requiring high proportions of
allows slow ramp up with no sudden and prevents ponding of water that could fresh air, VAV, close control. Supply air
noise change. The motor can be create a home for moss, mould and slime. temperature control is also possible using
controlled to have the best air flow for the BMS or other controls.
ducting and requirements as well as used Inverter Compressor Refer to Temperzone for capacity range
for de-humidifying the space. Each high efficiency variable capacity variation options.
The outdoor coil design permits low fan inverter compressor is hermetically
speeds and hence low noise levels. The sealed, quiet running and supported on Safety Features
compressor is isolated in a built-in, rubber mounts to minimise vibration. 1. HP and loss of refrigerant protection.
insulated compartment to minimise Inverter compressors provide the 2. Anti-rapid cycle timer and internal
noise. The indoor air section is also economy of part load performance. overload for compressor protection.
insulated for noise attenuation and to 3. Circuit breaker control circuits.
prevent exterior condensation. Soft Starting 4. Time-and-temperature controlled
EC motors and inverter compressors are electronic de-ice switch prevents
Durable soft starting therefore have none of the icing up of the outdoor coil during
problems associated with high in rush heating cycle.
The cabinet is constructed from high
current. 5. Frost protection on cooling cycle.
grade galvanised steel - polyester powder
6. Sensor fault indication.
coated (colour Grey) for all weather
Insulation 7. Compressor minimum run time to
protection (IP 44). External fasteners are
ensure oil return.
marine grade SKT® coated steel. The Closed cell foam insulation has been used 8. 12V control circuit.
units include a polyester powder coated in the indoor air section to ensure no
drain tray. Heat exchange coils comprise particles are introduced into the air Note: Consideration must be given to the
aluminium corrugated plate fins on stream. Both indoor and outdoor minimum floor area requirements of R32
mechanically expanded rifled copper chambers are insulated to prevent refrigerant.
tube. Both the indoor and outdoor air coil external condensation forming on the
fins are epoxy coated for extra protection cabinet exterior. The insulation is foil
in corrosive environments, e.g. salt laden faced and meets fire test standards AS Self Diagnostics
sea air. Fan motor bearings are sealed for 1530.3 (1989) and BS 476 parts 6 & 7. The Unit Controller (UC8) has a LED
life so as not to incur regular display to indicate faults and running
maintenance. Coil protection guards Control Option conditions. A non-specific fault indicator
protect against hail, accidental damage or is included for interface to external
vandalism. Commissioned air flow can be maintained systems via the optional relay board.
through use of the supplied differential
pressure transducer and controller
Easy Access (supplied by others) to compensate for
These packaged outdoor units are varying duct static pressures caused by
typically installed on a rooftop, where dirty filters or modulating dampers.
maintenance access is relatively easy Commissioning is made easier. The EC
during operating hours. Service panels plug fan motor is controlled variably
are hinged with turn locks for ease of (within a restricted range, p11) by a 0–10
access. Air filters are easily accessible volt DC signal that can be supplied either
through hinged door on the side of the by a BMS system, a sophisticated
unit. controller or Temperzone’s optional
TZT-100 Controller.
Low Maintenance The systems’ UC8 controller is BMS
Commissioning and maintenance costs compatible with multi-unit control
are reduced through use of a fan that possible – either via digital and analogue
requires no pulley and belt adjustments or signals or via Modbus. Refer to
changes like traditional fans. Dust is Temperzone for other protocols available.
discouraged from entering the electrical
compartment through a positive pressure
Page 5 of 28
Packaged Rooftop
Air Conditioners R32
OPA 250 – 560 Econex
Features
Wiring Configurations Economiser option
The electrical supply required (including 1. Horizontal supply & return air (Controls by Temperzone or others)
voltage fluctuation limits) is: versions
3 phase 380–440 V a.c. 50 Hz with 2. Downward supply & return air If the outdoor air heat content or wet bulb
neutral and earth. versions temperature (dry bulb not recommended)
3. Opposite hand versions of the above. is below that of the return air, the fresh air
The compressor crankcase heater
damper opens and the return air damper
requires a 24hr power supply
Optional Equipment closes to provide the first stage of
The control panel is fully wired ready to cooling. Operating costs are reduced as
4. Filters (G4) rated to AS1324.1.2001 -
accept the main power supply. Each free cooling is obtained. (Note: A spill air
disposable or washable,
system complies with the requirements of facility in the building may be necessary
50 or 100 mm thick.
the Regulatory Compliance Mark (RCM) for when the return air damper is closed.)
for electrical safety (AS/NZS 60335.2.40) 5. Drain tundish connection kits Fresh air dampers close to a minimum
and EMC (AS/NZS CISPR.14). – pack of 2 (pn 060-000-653). setting and return air dampers open
6. Factory fitted economiser -includes before normal compressor operation
For your convenience, a single phase
dampers, fresh air cowl. resumes.
auxiliary power outlet (10A) is included in
the electrical box. 7. Electronic control systems (available
by arrangement) for temperature and Temperzone offers a factory fitted
Provision has been made for compliance economy cycle. Economiser control package, if required.
with DRED, ie demand response enabling
8. Factory fitted adjustable fresh air
device standard AS/NZS 4755.3.1. Dust Protection option
damper and cowl.
9. Interface to BACnet/IP networks. The compressor/electrical compartment
Plant Room Use can be pressurised with indoor supply air.
Each unit is supplied with a high static This assists in keeping dust out of the
(125+ Pa) condenser fan. Nominal compartment.
outdoor airflow, correct unit clearances
and no air recirculation must be
maintained in order for the unit to achieve
its performance specification.
Page 6 of 28
Packaged Rooftop
Air Conditioners R32
Controls
Features
• Cool / Cool Dry / Heat / Auto Dry / • Continuous or Intermittent selection of
Auto / Fan Only modes. fan run-on in dead zone. Optional:
• Auto / High / Medium / Low fan speed • Backlit screen for ease of reading; Remote return air sensor
selection. (customisable).
• Soft touch tab keys
• Temperature setting range from
• PIN protected menus (Installer PIN)
1°C – 38°C. For more information visit
• Keypad and/or temperature lock www.temperzone.biz;
• LED to indicate status of the unit model search 'TZT-100'
[Power On/Off]. • Filter monitor option (by hours)
Page 7 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data
Page 8 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data
Page 9 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data
Page 10 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data
Page 11 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data
D.B. -5 -3 -1 1 3 5 7 9
°C G N PI G N PI G N PI G N PI G N PI G N PI G N PI G N PI
15 26.6 19.0 8.0 26.1 19.1 8.4 25.6 19.2 8.9 25.0 19.2 9.5 24.9 21.4 7.3 24.3 19.1 10.1 23.6 18.9 10.7 30.9 30.9 8.9
20 27.6 17.4 8.1 27.1 17.4 8.5 26.5 17.4 9.0 25.9 17.4 9.6 24.6 21.1 7.9 25.2 17.3 10.2 24.5 17.1 10.8 30.6 30.6 9.5
25 28.6 15.4 8.2 28.0 15.5 8.6 27.4 15.4 9.1 26.8 15.3 9.7 23.9 20.6 8.5 26.1 15.2 10.3 25.3 15.1 11.0 29.9 29.9 10.2
D.B. -5 -3 -1 1 3 5 7 9
°C G N PI G N PI G N PI G N PI G N PI G N PI G N PI G N PI
15 27.9 24.4 10.2 29.5 24.1 10.3 31.0 24.5 10.5 32.6 26.1 10.5 34.2 29.4 10.5 35.8 35.0 10.6 37.4 37.4 10.8 39.0 39.0 10.9
20 27.5 24.1 10.9 29.0 23.8 11.0 30.6 24.2 11.2 32.2 25.8 11.3 33.8 29.1 11.2 35.4 34.7 11.4 37.0 37.0 11.5 38.6 38.6 11.7
25 26.6 23.4 11.6 28.2 23.1 11.8 29.8 23.5 12.0 31.3 25.1 12.1 32.9 28.4 12.0 34.5 34.0 12.2 36.1 36.1 12.4 37.7 37.7 12.5
D.B. -5 -3 -1 1 3 5 7 9
°C G N PI G N PI G N PI G N PI G N PI G N PI G N PI G N PI
15 33.5 29.3 12.6 35.4 28.9 12.8 37.3 29.4 13.0 39.2 31.3 13.1 41.1 35.3 13.0 43.0 42.1 13.2 44.9 44.9 13.3 46.8 46.8 13.5
20 33.0 28.9 13.4 34.9 28.6 13.6 36.8 29.0 13.9 38.7 30.9 13.9 40.6 34.9 13.9 42.5 41.7 14.1 44.4 44.4 14.2 46.3 46.3 14.4
25 31.9 28.1 14.3 33.8 27.7 14.5 35.7 28.2 14.8 37.6 30.1 14.9 39.5 34.1 14.8 41.5 40.8 15.0 43.4 43.4 15.2 45.3 45.3 15.4
D.B. -5 -3 -1 1 3 5 7 9
°C G N PI G N PI G N PI G N PI G N PI G N PI G N PI G N PI
15 42.9 37.6 16.8 45.4 37.1 17.0 47.8 37.7 17.4 50.3 40.2 17.4 52.7 45.3 17.4 55.2 54.0 17.6 57.6 57.6 17.8 60.1 60.1 18.0
20 42.3 37.1 17.9 44.7 36.6 18.2 47.2 37.2 18.6 49.6 39.7 18.6 52.1 44.8 18.6 54.5 53.5 18.8 57.0 57.0 19.1 59.4 59.4 19.3
25 40.9 36.0 19.1 43.4 35.6 19.5 45.8 36.2 19.9 48.3 38.6 19.9 50.7 43.7 19.9 53.2 52.4 20.2 55.6 55.6 20.4 58.1 58.1 20.7
Page 12 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data
Air Handling
Airflows are for a dry coil. Reduce airflow by 10% in high moisture removal conditions. In a free blow application, beware of exceeding indoor
fan motor’s full load amp limit. Refer back page for filter losses. Air flows given are for OPA units without filters installed.
Amps
OPA 250 OPA 350
l/s - Pa - - - - l/s - W l/s - Pa - - - - l/s - W
500 3.5 500 4.0
4.9
INPUT (kW)
4.7
INPUT (kW)
1.7 2.5 3.4 2.4 3.4
9V 3.0 3.5
8V 9V
7V
400 2.5 400 3.0
8V 9V
6V
2.0 2.5
8V
7V
300 1.5 300 2.0
6V 7V 1.5
1.0
5V 8V 4.3
200 6V 1.0
200 0.5
7V 5V
6V 5V
100 100
5V 2.9
5.6
INPUT (kW)
2.3 6.7
4.0 10V
3.3 10V 4.0
4.0 9V
AVAILABLE EXTERNAL PRESSURE (Pa)
MAX. FINAL
80
PRESSURE
PRESSURE DROP (Pa)
DROP
60
250 Pa
40
ilter)
an F
20
ITIA L (Cle
IN
0
0 0.5 1.0 1.5 2.0 2.5 3.0
FILTER FACE VELOCITY (m/s)
Page 13 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data
4V 75 72 51 64 65 68 64 60
10 V 75 88 67 80 81 84 80 76
4V 85 72 63 64 65 67 63 58
10 V 85 87 78 79 80 82 78 73
4V 25 72 63 64 65 67 63 58
10 V 110 89 80 81 82 84 80 75
4V 50 73 64 66 66 68 63 56
10 V 300 91 82 84 84 86 81 74
Soft 4 8 11 11 11 11
Medium 3 7 8 9 9 9
Hard 0 1 3 4 4 5
Page 14 of 28
Packaged Rooftop
Air Conditioners R32
Performance Data
Page 15 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)
PROJECTION
POINT LOADS (kg)
W X Y Z
no F/A 104 149 100 158
Std Hd
cw F/A 104 157 100 158
Not to Scale
Op Hd no F/A 121 155 91 144
Refer page 26 ror 800 MIN. CLEARANCE TO UNIT Multiple units side-by-side:
Optional Economiser Cowl 570 220 Allow a minimum of 1m
500 MIN. CLEARANCE
dimensions between coil faces.
Filter
Access Optional
Fresh Air OPPOSITE
W Cowl X HAND
RETURN
AIR
500 MIN. CLEARANCE
SUPPLY
AIR
RETURN
AIR
SUPPLY
AIR
Z Opposite Y
Hand
Electrical F/A Cowl
Access
Fan
2000 MIN. CLEARANCE Access
376 376
Optional
Fresh Air
Cowl
441
Drain 25 ID
BSP female
16 DIA. HOLES 360
Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.
Page 16 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)
PROJECTION
POINT LOADS (kg)
W X Y Z
no F/A 104 149 100 158
Std Hd
cw F/A 104 157 100 158
Filter Not to Scale
Op Hd no F/A 121
Access155 91 144
Z Y
Electrical
Access
Fan
2000 MIN. CLEARANCE Access
Optional
Fresh Air
Cowl
SUPPLY RETURN
AIR AIR
Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.
Page 17 of 28
Ducted Split
Packaged Rooftop
System R32
Air Conditioners R32
Dimensions (mm)
W X Y Z
no F/A 164 133 153 146
Std Hd
cw F/A 164 141 153 146
Not to Scale
Op Hd no F/A 159 152 132 153
Refer page 26 ror 800 MIN. CLEARANCE TO UNIT Multiple units side-by-side:
Optional Economiser Cowl 500 MIN. CLEARANCE
570 220
Allow a minimum of 1m
dimensions Filter
between coil faces.
Access Optional
Fresh Air OPPOSITE
W Cowl X HAND
RETURN
AIR
500 MIN. CLEARANCE
SUPPLY
AIR
RETURN
AIR
SUPPLY
AIR
Z
Opposite Y
Electrical Hand
Access F/A Cowl
2000 MIN. CLEARANCE
Fan
Access
1000 MIN. CLEARANCE
Optional
Fresh Air
Cowl
711
595
154
576
Drain 25 ID
16 DIA. HOLES BSP female 360
Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.
Page 18 of 28
Ducted Split
Packaged Rooftop
System R32
Air Conditioners R32
Dimensions (mm)
W X Y Z
no F/A 164 133 153 146
Std Hd
cw F/A 164 141 153 146
Not to scale
Op Hd no F/A 159 152 132 153
Z Y
Electrical
Access
2000 MIN. CLEARANCE Fan
Access
1000 MIN. CLEARANCE
Optional
Fresh Air
Cowl
SUPPLY RETURN
AIR AIR
Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.
Page 19 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)
W X Y Z
no F/A 134 170 134 205
Std Hd
cw F/A 134 179 134 205
Not to scale
Op Hd no F/A 148 173 133 189
Refer page 26 ror 1000 MIN. CLEARANCE TO UNIT Multiple units side-by-side:
Optional Economiser Cowl Allow a minimum of 1m
dimensions 500 MIN. CLEARANCE 570 406 between coil faces.
Filter Optional
Access Fresh Air
Cowl OPPOSITE
W X HAND
RETURN
AIR
SUPPLY
500 MIN. CLEARANCE
AIR
RETURN
AIR
SUPPLY
AIR
Z Y
Opposite
Electrical Hand
Access F/A Cowl
Optional
Fresh Air
Cowl
420
Drain 25 ID
BSP female
16 DIA. HOLES
449
Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.
Page 20 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)
W X Y Z
no F/A 134 170 134 205
Std Hd
cw F/A 134 179 134 205
Not to scale
Op Hd no F/A 148 173 133 189
Optional
Fresh Air
Cowl
W X
500 MIN. CLEARANCE
Z Y
Electrical
Access
Optional
Fresh Air
Cowl
SUPPLY RETURN
AIR AIR
Page 21 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)
PROJECTION
POINT LOADS (kg)
W X Y Z
no F/A 182 171 195 211
Std Hd
cw F/A 196 199 207 217
Not to scale
Op Hd no F/A 168 218 153 220
RETURN
AIR
500 MIN. CLEARANCE
SUPPLY
AIR
RETURN
AIR
SUPPLY
AIR
Z Y
Opposite
Hand
Electrical
Access F/A Cowl
Fan
2000 MIN. CLEARANCE Access
Optional
Fresh Air
Cowl
572
155
Drain 25 ID
BSP female
2260 MTG CTRS 449
16 DIA. HOLES
Page 22 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)
PROJECTION
POINT LOADS (kg)
W X Y Z
no F/A 182 171 195 211
Std Hd
cw F/A 196 199 207 217
Not to scale
Op Hd no F/A 168 218 153 220
Z Y
Electrical
2000 MIN. CLEARANCE Access
Fan
Access
Optional
Fresh Air
Cowl
SUPPLY RETURN
AIR AIR
Page 23 of 28
Packaged Rooftop
Air Conditioners R32
Dimensions (mm)
Accessories
Note: Both Economiser and Fresh Air Cowls are mounted on a hinged access door.
PROJECTION
Model A B C Model A B C
OPA 250-Z 608 201 1000 OPA 250-C 235 505 286
OPA 350-Z 608 201 1000 OPA 350-C 235 658 286
540
A
A
B
Economiser
Cowl
Fresh Air
Cowl
CLEARANCE)
(300 MIN.
CLEARANCE)
(300 MIN.
Page 24 of 28
Packaged Rooftop
Air Conditioners R32
Specifications
System
Model OPA 250RLTFPQ OPA 350RLTFPQ OPA 450RLTFPQ OPA 560RLTFPQ
Cooling Capacity 1 kW 25.4 (10.1~29.1) 35.9 (18~45.4) 44.9 (18.2~52.4) 55.6 (27.4~64.8)
Net Cooling Capacity (MEPS) 1 kW 24.6 34.8 43.3 53.6
TCSPF (cold/mixed/hot)
1
6.43 / 5.41 / 4.73 4.71 / 5.60 / /4.85 5.20 / 4.56 / 4.34 5.22 / 4.60 / 4.21
EER / AEER (cooling) 3.20 / 3.18 3.15 / 3.14 2.99 / 2.98 2.99 / 2.98
Heating Capacity 2 kW 26.9 (6.5~29.3) 37.0 (13.9~47) 44.4 (16.5~54.5) 57.0 (24.0~63.0)
HSPF 2 (cold/mixed/hot) 2.21 / 2.60 / 3.30 2.85 / 3.00 / 3.07 2.72 / 2.82 / 2.86 2.66 / 2.83 / 2.94
COP / ACOP (heating) 3.33 / 3.31 3.21 / 3.19 3.14 / 3.13 2.98 / 2.97
Nominal Air Flow l/s
3
1250 (625~1950) 1800 (1100~2450) 2200 (1100~2900) 2600 (1300~3610)
Unit Controller UC8
Power Source 4 3 phase 400 V a.c. 50 Hz + N + E
Refrigerant R32 (Class A2L)
Compressor type inverter scroll
Indoor air fan type backward curved EC plug
Outdoor air fan type EC axial
Indoor Fan Max. Current A/ph. 6 5.5 5.5 6.4
Running Amps (Total) A/ph. 12.5 / 11.5 /13 17.5 / 15.5 / 19.5 24 / 22 / 24 28 / 26 / 29
Max. Running Amps (Total) A/ph. 24 35 40 44
IP Rating IP44 / IPX4 5
Finish grey polyester powder coat
Operating Range (outdoor ambient)
Cooling –10°C to 52°C
Heating –15°C to 25°C
Weight (net/shipping) kg
Unit 511 / 567 596 / 652 643 / 708 759 / 823
Unit c/w Fresh Air 519 / 575 604 / 660 652 / 717 817 / 881
Unit c/w Economiser 556 / 612 649 / 674 697 / 762 831 / 895
Notes:
1
ominal Cooling Capacity (gross) at AS/NZS 3823 conditions:
N 3
upply air flow at Nominal Cooling Capacity conditions stated above.
S
– Indoor Entering Air Temperature 27°C D.B., 19°C W.B.; Air lows less than Nominal will reduce cooling capacity.
– Outdoor Entering Air Temperature 35°C D.B. 4
Voltage range: 380–440 V
2
Heating Capacity at AS/NZS 3823 conditions: 5
Outdoor fan clearance <100mm (ref. IEC 60529)
– Indoor Entering Air Temperature 20°C D.B.;
– Outdoor Entering Air Temperature 7°C D.B., 6°C W.B.
Materials and specifications are subject to change without notice due to the manufacturer’s ongoing research and development programme.
Page 25 of 28
Packaged Rooftop
Air Conditioners R32
Notes
Page 26 of 28
Packaged Rooftop
Air Conditioners R32