Modbus I/O Module | LN820MOD-ATL
PRODUCT SPECIFICATION
FEATURE LIST
- Power Supply: 24VAC or 24VDC
- Modbus RTU RS-485 communication with 1 jumper setting for end-of-line and 2 jumper settings for bias
- DIP switch digit 8 selects baud rate 9600/19200 bps. Auto-search feature removed.
- DIP switch selects 0-127 slave address for Modbus
- All parameters can be monitored and adjusted through Modbus
- Designed for Din-rail installation
- Unpluggable Terminal Blocks
Electrical Interface
Function Label Description
24V
Power Supply 24VAC or 24VDC
COM
Analog Output AO
0 ~10VDC / 4 ~ 20mA
COM
R-type Analog AI-R 2 types of sensor characteristic (@)
Input COM AI-to-COM ratio, 1:1
V-type Analog AI-V 0 ~10VDC
input COM AI-to-COM ratio, 1:1
D+
Modbus
D- RS485 interface
connection
Com
DI1
Digital Input DI2 Sinking (#)
DI(n) DI-to-COM ratio, 1:1
COM
DO1 230VAC 2A (or 30VDC 2A) (^)
Digital Output
DO2 dry contact
DO(n) individually isolated
(#) input signals share the same power and ground with power supply. Refer to Figure 9 on Page 7
(^) primary function – to drive contactors. Refer to Figure 8 on Page 6
(@) AI-R accommodates 2 types of external temperature sensor. See Table 2 and 3 on Page 10.
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 1
Dimensions
Figure 1 – Outline of LN820MOD-ATL
Versions of LN820MOD-ATL
AI-R AI-V AO DI DO
I/O 1 0 0 0 16 8
I/O 2 0 0 0 16 0
I/O 8 1 1 1 8 4
I/O 9 1 0 1 4 2
Table 1 – I/O Module configuration
Silkscreen printing on I/O 1 and I/O 2
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 2
Terminal Diagram of I/O #1
Figure 2a – terminal arrangement in I/O#1
Terminal Diagram of I/O #2
Figure 2b – terminal arrangement in I/O#2
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 3
Terminal Diagram of I/O #8
Figure 2c – terminal arrangement in I/O#8
Terminal Diagram of I/O #9
Figure 2d – terminal arrangement in I/O#9
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 4
Terminal Blocks
(I) Pluggable, screwless, stacked Vertical Terminal Blocks for DI, AI and AO
Figure 3a – TLPHDC-010V-08P-G12 Figure 3b – TLPSD-010-08P-G12
(II) Pluggable and screwless Vertical Terminal Blocks for D+, D- and D_GND
Figure 4a – TLPH-200V-1112-03P-G12 Figure 4b – TLPS-201V-03P-G12
(III) Pluggable and screwless Vertical Terminal Blocks for 24VAC and COM
Figure 5a – TLPH-200V-1112-02P-K (black in delivery) Figure 5b – TLPS-201V-02P-K (black in delivery)
(IV) Pluggable with screws, Horizontal Terminal Blocks for DO
Figure 6a – TLPH-200R-1112-02P-G12 Figure 6b – TLPS-207-02P-G12
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 5
RS-485 Jumper Setting
Provides flexibility in biasing and end-of-line configuration.
Open the cabinet of LN820MOD-ATL to access the circuitry.
Figure 7 – RS-485 Jumpers. J1 for End of Line (EOL), J2 and J3 for Bias
Digital Output
Provides voltage-free contact for 230VAC 2A or 30VDC 2A.
e.g. power supply at 24VDC, DO drives relay (coil) and the contact allows a maximum of 230V, 2A.
Figure below shows current comes in through inA and out to outA when contact closes.
Figure 8 – illustration of DO in action
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 6
Digital Input
Figure 9 – DI Circuit
Analog Output
Figure 10 – AO Circuit for Voltage Figure 11 – AO Circuit for current
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 7
Analog Input
Figure 12 – AI Circuit for Voltage source
Figure 13 – AI Circuit for resistive source
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 8
Modbus Address / Baud Rate
Figure 14 – Graphical representation of DIP switches on the side of LN820MOD-ATL
Switch to “ON” for “1”. For the other direction, “0”
Digits 1-7 are for Modbus Address
Digit 8 is for Baud Rate.
E.g Dip switch 1, 3, 5 set to “ON”, MAC address is 21 (sum of 1,4 and 16)
Mac Address is limited to 1 – 127. Any other value (include “0”) will be treated as “1”.
When Digit 8 is set to “0”, the baud rate is 9600.
When Digit 8 is set to “1”, the baud rate is 19200.
LN820 reads the dipswitch every 10 seconds so the updated setting (modbus address and baud rate) goes into effect after a
maximum of 10 seconds.
LED Indication
Figure 15 – LED and terminal labelling
Pwr LED: turns solid red when 24Vac/24Vdc is supplied
HB LED: flashes every half a second when controller enters working mode
Rx LED: flashes once when a packet (correct address) is received from the network
Tx LED: flashes once when controller replies a packet
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 9
Thermistor Characteristic
Temp Ohm Temp Ohm
0.56 7418 21.67 5338
1.67 7319 22.78 5225
2.78 7218 23.89 5112
3.89 7116 25 5000
5 7012 26.11 4889
6.11 6906 27.22 4778
7.22 6799 28.33 4668
8.33 6691 29.44 4559
9.44 6582 30.56 4450
10.56 6470 31.67 4344
11.67 6359 32.78 4238
12.78 6247 33.89 4134
13.89 6135 35 4031
15 6022 36.11 3930
16.11 5908 37.22 3830
17.22 5794 38.33 3732
18.33 5681 39.44 3635
19.44 5567 40.56 3540
20.56 5452
Table 2 – Type I thermistor characteristic
Temp Ohm
0 7660
5 7182
10 6666
15 6125
20 5573
30 4492
35 3986
40 3517
Table 3 – Type II thermistor characteristic
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 10
ModBus Map
RS-485 Modbus RTU: Data – 8bit, Stop bit – 1, None parity, Baud rate: 9600/19200, Device: 1-127
Register Parameter Description Data Type Value Range
Address
Function code 04 Read Input Registers
0001 DI#1 ~ DI#16 Signed 16 0~65536 MSB (Most Significant Bit) refers to
DI#16, LSB (Least Significant Bit)
refers to DI#1
0002 AI#1(^1) Signed 16 0-65535 Temperature value that according to
table 2/3 and value of function 03
register 0004
0003 AI#2(^2) Signed 16 0-65535 AI#2 value (i.e. 0-10 volt) multiply by
function 03 register 0005 and divided by
10
(e.g. if AI#2=2, Func 03 R0005=50
Value = 2*50 = 100)
Function code 03 Read Holding Registers / 06 Write Holding Registers
0001 DO#1 ~ DO#8 (^3) Signed 16 0~255 MSB (Most Significant Bit) refers to
DO#8, LSB (Least Significant Bit) refers
to DO#1
0002 AO#1_Type(^1) Bit 0/1 0 cor. V / 1 cor. A
0003 AO#1_cor(^1) Signed 16 0~100 0~100% cor. 0~10DC / 4~20mA
0004 AI#1 R_Type(^1) Bit 0/1 0 = Type 1 Thermistor
1 = Type 2 Thermistor
0005 AI#2 V_Scale(^2) Signed 16 0~6553 0~6553
Function code 02 Read Discrete Inputs
0001 DI#1 Bit 0/1 Low/High
0002 DI#2 Bit 0/1 Low/High
0003 DI#3 Bit 0/1 Low/High
0004 DI#4 Bit 0/1 Low/High
0005 DI#5 Bit 0/1 Low/High
0006 DI#6 Bit 0/1 Low/High
0007 DI#7 Bit 0/1 Low/High
0008 DI#8 Bit 0/1 Low/High
0009 DI#9 Bit 0/1 Low/High
0010 DI#10 Bit 0/1 Low/High
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 11
0011 DI#11 Bit 0/1 Low/High
0012 DI#12 Bit 0/1 Low/High
0013 DI#13 Bit 0/1 Low/High
0014 DI#14 Bit 0/1 Low/High
0015 DI#15 Bit 0/1 Low/High
0016 DI#16 Bit 0/1 Low/High
Function code 01 Read Coils / 05 Write Single Coil (^3)
0001 DO#1 Bit 0/1 OFF/ON
0002 DO#2 Bit 0/1 OFF/ON
0003 DO#3 Bit 0/1 OFF/ON
0004 DO#4 Bit 0/1 OFF/ON
0005 DO#5 Bit 0/1 OFF/ON
0006 DO#6 Bit 0/1 OFF/ON
0007 DO#7 Bit 0/1 OFF/ON
0008 DO#8 Bit 0/1 OFF/ON
(^1) available only for LN820MOD-ATL 8/9
(^2) available only for LN820MOD-ATL 8
(^3) available only for LN820MOD-ATL 1/8/9
OPERATING SPECIFICATIONS
- Supply Voltage: 24VAC+/-15% or 24VDC +/-15%
- Power Consumption: (TBA)
- Operating Temperature: 0 – 50 ºC
- Storage Temperature: -10 – 60 ºC
- Operating Humidity Range: 5 – 95 %RH non-condensing
- Terminal Block: 26-14 AWG wire
Modbus I/O module | Product Specification | v1.2 | July 4, 2022 12