Standard For Substation Equipment Identification 2947172
Standard For Substation Equipment Identification 2947172
If this standard is a printed version, to ensure compliance, reference must be made to the Energy
Queensland internet site www.energyq.com.au to obtain the latest version.
Abstract: This document sets out the general requirements for substation electrical design drawings
with respect to equipment identification codes, voltage colours for single line operating diagrams,
indicator light colours, small wire numbering and small wire colouring.
STNW3001
CONTENTS
1 Overview.................................................................................................................................. 5
2 References .............................................................................................................................. 5
Annex A ........................................................................................................................................ 37
Annex B ........................................................................................................................................ 38
Application Guide.......................................................................................................................... 38
STNW3001
Annex C ........................................................................................................................................ 41
Annex D ........................................................................................................................................ 47
Annex E ........................................................................................................................................ 51
Annex F ........................................................................................................................................ 52
Appendix A ................................................................................................................................... 56
FIGURES
Figure 1: Function Coding for an ‘H’ Configuration Substation & Function Coding for a Folded Bus
Substation..................................................................................................................................... 13
Figure 2: Function Coding for a Breaker and a Half Arrangement & Revenue Metering ................ 13
Figure 3: Location Coding for Outside a Control Building .............................................................. 16
Figure 4: Location Coding for Inside a Control Building................................................................. 17
Figure 5: Location Coding within an Assembly in a Cubicle .......................................................... 17
Figure 6: Location Coding for Cubicle Surfaces (Plan View) ......................................................... 19
Figure 7: Item Coding for a ‘H’ Configuration Substation & for a Folded Bus Substation ............... 23
Figure 8: Item Coding for a Breaker and a Half Arrangement & for a Double Bus Substation ....... 24
Figure 9: Item Coding for an Assembly ......................................................................................... 24
Figure 10: Item Coding for an Assembly within a Cubicle.............................................................. 25
Figure 11: Item Coding within a Panel Assembly .......................................................................... 25
Figure 12: Coding for a Terminal Block Assembly......................................................................... 26
Figure 13: Coding within a Matrix Terminal Block.......................................................................... 26
Figure 14: Phase Layout ............................................................................................................... 28
Figure 15: Phase Layout for a Folded Bus arrangement ............................................................... 28
Figure 16: Multicore Cable Numbering.......................................................................................... 30
Figure 17: Multicore Cable Numbering within a Building ............................................................... 30
Figure 18: Scope of reference designations standards ................................................................. 54
TABLES
Table 1: Code Abbreviation Example .............................................................................................. 8
Table 2: Position 2 of the Function Code ........................................................................................ 9
Table 3: Position 6 of the Function Code ...................................................................................... 11
Table 4: Position 3 of the Location Code Internal Equipment ........................................................ 14
Table 5: Position 3 of the Location Code External Equipment ....................................................... 14
Table 6: Location Letters for Cubicle Surfaces .............................................................................. 18
Table 7: Position 2 of the Item Code ............................................................................................. 19
Table 8: Position 7 of the Item Code ............................................................................................. 21
Table 9: Position 3 of the Item Code for Isolators and Transformers ............................................. 21
STNW3001
STNW3001
1 Overview
1.1 Purpose
This document provides guidance on the identification of substation equipment both inside the
control room and in the yard of a substation.
1.2 Scope
This standard shall be applied to all new greenfield substation designs or where total replacement is
occurring. Where a whole section is being replaced or reworked, such as a new panel or bay, it is
desirable for this standard to be applied at the discretion of the project owner.
This standard was developed after the formation of Ergon Energy. Prior to this, each regional
distribution authority had their own identification methods developed based on different standards,
philosophies and practices. The intention of this standards was to provide one complete system for
all Ergon Energy Substation Equipment based on current Australian and International Standards.
These standards have been revised, redesignated and withdrawn over the years to align with
international standards. Annex F has been added to detail how these changes have occurred.
2 References
2.1 Legislation, regulations, rules, and codes
(AS 2067, 2016), Substations and high voltage installations exceeding 1 kV a.c.
(AS 3000, 2018), Substations and high voltage installations exceeding 1 kV a.c.
(AS/NZS 60076.1, 2014), Substations and high voltage installations exceeding 1 kV a.c.
(IEC 81346-1, 2009) Superseded – IEC 61346-1, 1996, Substations and high voltage installations
exceeding 1kV a.c.
(IEC 81346-2, 2019) Superseded – IEC 61346-2, 2009, Substations and high voltage installations
exceeding 1kV a.c.
STNW3001
(IEC 60073, 2002), Substations and high voltage installations exceeding 1 kV a.c.
(IEC 60757, 1983), Substations and high voltage installations exceeding 1 kV a.c.
(IEEE Std C37.2, 2008), Substations and high voltage installations exceeding 1 kV a.c.
CIGRE Technical Brochure 585, June 14th, Substations and high voltage installations exceeding 1
kV a.c.
‘A’, ‘N’: Within the code positions an “A” represents an identification letter and “N”
represents a numeral. The number of A’s or N’s shown are the maximum
allocated for the given position and aren’t required to be completely filled
unless otherwise stated.
Bay (of a feeder bays, transformer bays, bus coupler bays, etc. (IEV 605-02-09)
substation):
Busbars: The busbar represents the central point in the substation. It collects and
distributes the power through the incoming and outgoing feeders. The
circuit configuration and the number of busbars will be selected
according to the importance of a substation, that is, its required reliability
and availability in the network. It is therefore essential to clear any fault
on a busbar as quickly as possible. The number of busbars with or
without transfer bus is a factor for the flexibility and security of the
substation. (Cigre TB 585)
Busbar segments: The physical conductor types and materials used to construct busbars.
Busbars may consist of many different conductors to connect substation
plant and equipment.
Busbar sections: The part of a busbar located between two switching devices (or
disconnectors) put in series or between a switching device and the end of
the busbar (IEV 605-02-08)
STNW3001
Where it is considered that a different identification arrangement is required for an electrical design
drawing then approval shall be sought for the deviation from the Manager Substation Standards.
STNW3001
5 Equipment Identification
5.1 Component Identification
Each component within the substation shall be uniquely identified using DESIGNATION BLOCKS
according to the IEC 81346-1 and this document.
The FUNCTION CODES shall normally be used to identify all the components that together perform
a major function e.g. switching, transforming, controlling or schemes not covered by switching such
as bus zone. The function code groupings shall be shown on the plant data sheet for the project.
The LOCATION CODE identifies the physical location of a component within the substation. It is not
necessarily related to functional aspects.
The TERMINAL CODE qualifier shall be used where appropriate. The code can be used alone or
appended to an item code ( – ) or a location code ( + ) as necessary.
The full code for equipment identification would rarely be used as it would usually be unnecessary
to show the function or location codes more than once on the same drawing.
For a single designation block, if no confusion can arise, the initial prefix sign or qualifier may be
omitted. Similarly, when the item designators appear in tables, for example wiring tables, the
columns may be arranged so that the qualifiers can be omitted.
It is permissible and, on occasions, desirable to identify an item within an item e.g. sub-rack A08
containing a relay J51 could be identified as –A08–J51. If no confusion can arise the intermediate
qualifier(s) may be omitted giving a short notation of the code e.g. –A08J51.
The coding shall only be as long as it needs to be to uniquely identify equipment and its function and
location. Any sub codes are therefore not required in every situation and are only used where further
classification is required. This is shown in the definitions of the blocks with the statement ‘when used’
given in brackets.
STNW3001
The letters “I” and “O” should not be used within identification codes as they cause confusion and
misunderstandings with the numbers 0 and 1.
LETTER FUNCTION
A SPARE
EA SWITCHING FUNCTION at 66 kV
EB SWITCHING FUNCTION at 33 kV
FA SWITCHING FUNCTION at 22 kV
FB SWITCHING FUNCTION at 11 kV
JX D.C. SUPPLIES
KX VT SUPPLIES
STNW3001
LETTER FUNCTION
TX TRANSFORMER
UX AUXILIARY EQUIPMENT
V SPARE
W SPARE
YA COMMUNICATIONS - STRUCTURE
YB COMMUNICATIONS - BUILDING
YE AGGREGATE E
YF COMMUNICATIONS - FIBRE
STNW3001
LETTER FUNCTION
YM AGGREGATE M
YP POINT OF PRESENCE
YR COMMUNICATIONS - RADIO
YS AGGREGATE S
YT TRANSIT
YW COMMUNICATIONS - CELLULAR
YX COMMUNICATIONS - COMMON
Z SPARE
LETTER DESCRIPTION
The letter used for SWER voltages shall be the three-phase voltage letter as given in Table 2, i.e.
for a SWER voltage of 19.1 kV the letter ‘EB’ (as in 33 kV) shall be used.
When differentiating between switching voltage levels covered by the same first letter, it shall be as
per Table 2. For voltages above 66kV the voltage codes are not differentiated in this manner, as
they are not used in Ergon Operational Numbering system. The Powerlink Queensland Operational
numbering system is used for voltages above 66 kV.
This method is used to identify equipment voltage levels for Bus Zone Protection and Circuit Breaker
Fail Schemes, e.g. =REA for Bus Zone Protection at 66 kV, =SFB for Circuit Breaker Fail Scheme
at 11 kV.
The =LX function code is for SYSTEM / SUBSTATION WIDE CONTROL AND PROTECTION BAYs including:
STNW3001
If a substation has a Load Control Bay this will be designated =LX01. If the same substation has a
Substation Wide Control and Protection bay, this will be designated =LX02. If a substation has no
Load Control Bay but does have a Substation Wide Control and Protection Bay, this will be
designated =LX01.
The =LX function code is used for Summated Backup Neutral Earth Fault Protection Schemes.
These older summated schemes joined Current Transformers from two or more power transformer
neutrals, usually in the same circuits as Frame Leakage Check schemes and Sensitive Earth Fault
Check schemes. They typically provide backup protection for LV feeders, busbars and transformers,
tripping all transformer CBs and clearing all supply to the LV feeders. This function aligns with a
Substation Wide Control and Protection Scheme
However, the =TX function code shall be used for BackUp Neutral Earth Fault relays that align with
the latest protection schemes from the Protection Standard STNW1002, having one (1) BU NEF
relay for each one (1) Transformer.
For a breaker and a half arrangement, each breaker and a half scheme shall be initially numbered
with a single digit (e.g. 1, 2, 3, etc.). A second digit shall be added to uniquely identify each breaker
section, numbered 1 for the bus 1 breaker, 2 for the bus 2 breaker and 3 for the middle breaker.
Refer to Figure 2.
For all function codes the position 3 number shall be two digits with a leading zero if necessary.
Function code boundaries should be indicated on the single line diagrams by a faint dashed line
clearly indicating the boundary of the function code in situations where further clarification is desired.
Below are examples of Function Coding with Figure 1 and Figure 2 also showing graphic examples
of function code allocation.
Examples:
=EA01 66 kV Bay 1
=EB01 33 kV Bay 1
=FA01 22 kV Bay 1
=FB01 11 kV Bay 1
=TX01 Transformer 1
=TX02 Transformer 2
Figure 1: Function Coding for an ‘H’ Configuration Substation & Function Coding for a Folded Bus
Substation
Figure 2: Function Coding for a Breaker and a Half Arrangement & Revenue Metering
STNW3001
LETTER INTERPRETATION
Internal
LETTER INTERPRETATION
External
A SPARE
EA 66 kV SWITCHYARD AREA
EB 33 kV SWITCHYARD AREA
STNW3001
FA 22 kV SWITCHYARD AREA
FB 11 kV SWITCHYARD AREA
The location code number position 4 should be allocated to follow the function code numbering for
external areas, padded with a leading zero if necessary.
If a substation has multiple modular control buildings, the first number in the location code is for
building number, followed by alphabet character for level (where multi-storey), then followed by room
number. If there is only one building this is not required. Rows of abutted Cubicles shall be coded
together from left to right, preferably clockwise in the room. Surface Rows (U-Spacing) are coded
from bottom to top of the cubicle.
Below are examples of Location Coding with Figure 3, Figure 4 and Figure 5 also showing graphic
examples of location code allocation.
Examples:
+1A4.D24.10 Control building room 1, row A, cubicle 4, surface D, row 24, column 10
STNW3001
+2B1A4.D24.10 Control building 2, Floor B, room 1, row A, cubicle 4, surface D, row 24, column
10
STNW3001
STNW3001
Rack layout location letters for cubicle surfaces of a typical floor standing cubicle looking at the front
of the cubicle shall be generally applied as given in Table 6.
Back B
Front D
Floor or ground G
Roof or top R
The letter A shall always refer to the left-hand side as viewed from the front of the cubicle. All other
surfaces shall be labelled in a general clockwise direction, as viewed in plan view, around the outside
and circling inward, including any internal surfaces. Where required, equipment shall be given the
location code letter of the surface on which it is mounted.
If a swing rack is used inside, but not on, the front door, it belongs to another plane and has to be
labelled with a letter other than D. The swing rack shall then be given the next available letter. If the
rack is hung directly off the back of the door, it shall have the D code.
The allocation of letters to a cubicle shall be clearly shown on a key diagram similar to Figure 6 for all
panel layout drawings referencing such numbers.
STNW3001
STNW3001
LETTER FUNCTION
C CAPACITORS
J PROTECTION RELAYS
M MOTORS
R RESISTORS, SHUNTS
TC CURRENT TRANSFORMERS
TV VOLTAGE TRANSFORMERS
TE EARTHING TRANSFORMERS
STNW3001
LETTER DESCRIPTION
P Primary
S Secondary
The meaning of each item code, including all suffixes, shall be designated on the drawings in which
they are used.
When numbering equipment (position 3, except for item letters J and K), items closest to an adjacent
bus should be given the lowest number.
For all devices, position 3 numbering shall be at least two digits padded with a leading zero if
necessary.
For item letters Q (isolators, etc.) and T (transformers) only, position 3 shall be numbered by its
device type as given by Table 9. If the number of any particular item needs to extend outside the
ranges given in Table 9, then multiples of ten shall be added to the range e.g. –Q10, –Q15, –T13, –
T17, etc.
T03-06, T13-16
T07-08, T17-18
Naming of earthing transformers shall be relative to the bay the earthing transformer is situated in
e.g. =TX01-T02. In the situation where an earthing transformer is situated remotely to the associated
power transformer it shall be issued with its own bay number as well e.g. =TX03-T01.
STNW3001
For a breaker and a half arrangement, the isolators and transformers shall be numbered as per
Figure 8. The first digit shall match the Function Code (i.e. 1 for bus 1 breaker, 2 for bus 2 breaker
and 3 for the middle breaker) with the second digit as per Table 9 for Q and T Item Codes.
A Frame Leakage Relay or Current Transformer associated to Bus Section 1 shall use
codes =RFB01-J50N, =RFB01-T03.
A Frame Leakage Relay or Current Transformer associated to Bus Section 2 shall use
codes =RFB02-J50N, =RFB02-T03.
A Frame Leakage Relay or Current Transformer associated to Bus Section 3 shall use
codes =RFB03-J50N, =RFB03-T03
A Frame Leakage Relay or Current Transformer associated to both Bus Section 1 and
2 shall use codes =RFB12-J50N, =RFB12-T03
A Frame Leakage Relay or Current Transformer associated to both Bus Section 2 and
3 shall use codes =RFB23-J50N, =RFB23-T03
When substation standards arrange new period contracts it should request Manufacturers to apply
this standard STNW3001 for coding. However, when this is not possible or in brownfield sites, when
manufactures apply their own codes to equipment mounted or housed in Transformers and
Switchgear, these codes should be used instead of this standard, primarily to ensure that safety and
asset data capture are not compromised.
STNW3001
Figure 7: Item Coding for a ‘H’ Configuration Substation & for a Folded Bus Substation
STNW3001
Figure 8: Item Coding for a Breaker and a Half Arrangement & for a Double Bus Substation
STNW3001
STNW3001
Below are examples of Terminal Coding with Figure 12 and Figure 13 showing graphic examples of
terminal code allocation.
Examples:
:58 Terminal 58
Each bay shall be given a function letter code in accordance with Table 2 and a number that is
unique to that function letter in the substation.
STNW3001
1) Obtain the ultimate development and preliminary layout drawings for the switchyard in
question.
2) Determine any factor that would limit additional extension of the busbars in any
direction; e.g. Transformers installed at the end of the busbars.
3) Allocate bay numbers such that the lowest number is adjacent to the determined
limiting factor.
If there is no natural limiting factor to busbar extension in either direction, then the lowest number is
allocated to the first bay on the left-hand side of the ultimate line diagram, where the line diagram is
drawn with the highest voltage circuits to the top of the page. The commencing bay number may be
greater than one to allow for future extensions using the lower numbers.
Where there is provision for two or more busbar sections, they shall be numbered such that the
lowest numbered bays are connected to or between the lowest numbered busbars. For example, if
there are two busbar sections containing switching functions =EA01 and =EA02 on one and =EA03
and =EA04 on the other, they shall be numbered bus 1 and bus 2 respectively.
In double busbar arrangements, the lowest numbered busbar shall be at the top of the ultimate line
diagram where the line diagram is drawn with the highest voltage circuits to the top of the page.
The layout of the phase shall be dictated by the labelling of the power transformer phasing, where
included, as detailed in the Australian Standards for Power Transformers (AS 2374, 2003) and
(AS/NZS 60076.1, 2014) and the following clauses.
a) The order of the phase labels with respect to the high voltage side of the power
transformer shall be R W B from left to right. This matches R W B to A B C of the
transformer as per Figure 14.
b) For connections from the transformer the labelling shall match the transformer phase
layout.
c) For lines perpendicular to the power transformer bay, the phase labels with respect to
the high voltage side of the transformer shall be R W B respectively from the line
closest to the transformer to the line furthest from the transformer as per Figure 14. This
may not apply in exceptional circumstances, for example, where the orientation of an
additional transformer is such that Clause (a) disallows the labelling of Clause (c).
d) Where a power transformer is not shown on a diagram, the labelling shall be as per
Clauses (a) and (c) when facing into the substation along the incoming feeder in
accordance with the Figure 14.
f) Where there is a folded bus arrangement, the phase layout shall be as for Clauses (a),
(b), (c), (d) and (e) as per Figure 15.
STNW3001
For the placement of the phase identifiers, refer to the standard drawings Figure 14 and Figure 15.
STNW3001
For DC identification, when required, the identification shall be the voltage level of the supply
followed by a capital V and the polarity sign, + or – (e.g. 110V+, 110V–).
The identifier N (neutral) shall be used when a device is connected in the residual of a polyphase
circuit, across a broken delta, or is internally derived from the polyphase current or voltage quantities.
The identifier G (ground) shall be used where the measured quantity is in the path to ground, or in
the case of ground fault detectors, is the current flowing to ground.
Cables shall be numbered using item code Wxxx where W is the Item Designation code and xxx is
a unique number within a particular substation. The Item code shall be prefixed with a Function Code
(e.g. =FB02-W01) for HV cabling. For secondary cabling, the Item code shall not include the Function
code. The numbering of secondary cabling shall start at 10 (to prevent confusion with HV cables)
and numbered in ascending order.
The HV cables shall be given the Function Code associated with a host switching device or plant
device such as a Transformer or Generator. Where the host is not clear the following rules are to be
applied for function code selection:
Examples:
STNW3001
To assist the preparation of diagrams, checking circuits, fault finding and modifications; the ends of
each wire shall be identified by suitable marking to show its function. The Ergon Energy wire
numbering method is based on withdrawn British Standard (BS 158, 1961) and AS 2067: 2016,
STNW3001
Appendix E; with variations as set out in this document. Wire marking and installation shall be in
accordance with the Ergon Energy Panel Wiring Standard (STNW3021). Each circuit function should
be defined by a code consisting of letters and numbers as per Table 10.
Every branch of any connection should bear the same identification mark. Where, however, it is
necessary to identify branches that are connected to a common point, e.g. current transformer leads,
different numbers for the branches may be employed only if they are connected through links or are
connected to separate terminals which are then joined by removable connections.
A system of providing functional identification is described below and summarised in Table 10.
a) Each wire should have a letter to denote its function, e.g. control of circuit breaker,
current transformer for primary protection, voltage for instruments, metering and
protection.
b) Each wire should have a suffix number identifying the individual wire and its function.
This may consist of one or more digits as required. For functions A-G, H, J and M, the
suffix numbers should be in accordance with Table 10.
c) Wire numbers shall increment sequentially on passing through a link or device, but not
a terminal.
d) Where a number of similar leads from separate units are taken to a common panel, e.g.
bus-zone protection, summation metering, the function code prefix, e.g. =FB09, should
be used to distinguish them.
e) Where common apparatus covers more than one function, the first of the appropriate
function letters in the table should be used. This applies only to parallel circuits, and
where these circuits split at a separate contact, e.g. fuse-link, switch or relay contact,
the function letter should change if necessary from the splitting point onwards.
f) Where relays are employed, the wiring to the coil and the contact circuits do not
necessarily bear the same function letter, which should be determined by the function of
the individual circuit containing them. For example, the coil circuit of an interposing
relay should be ‘W’ but the contact circuits may bear letters such as ‘K’, ‘L’, or ‘N’, as
appropriate.
g) Current and voltage transformer function letters should follow through any interposing
and auxiliary current and voltage transformers.
i) Earth wiring for CT and VT secondaries, Relays, RTUs and cases of other devices shall
use a wire marker code of the circuit they are from or the code of the device they are
connected to.
STNW3001
M Auxiliary and control motor devices, e.g. Any number from 1 upwards
governor motor, rheostat motor, generator
automatic voltage regulator control, spring-
charging motors, transformer cooler-motor
control, motors for isolator operation
STNW3001
P d.c. tripping circuits used solely for busbar Any number from 1 upwards
protection For modifying legacy drawings
only Not to be used on new
designs
S d.c. instruments and relays, exciter and field Any number from 1 upwards
circuits for generators
U Spare cores and connections to spare contacts Spare cores should be numbered
NOTES:
1. If, for functions A-G and for functions H, J and M, more numbers are required, add
multiples of one hundred, e.g. 10-29 may be extended to 110-129, 210-229.
2. The term ‘remote selective control’ denotes ‘control at a point distant from the
switchgear by the transmission of electrical signals through common communications
channels using selective means to operate one of a number of switching devices’.
Wiring colours shall be selected in accordance with the Panel Wiring Standard (STNW3021) Colour
abbreviations shall be as per Table 11.
STNW3001
Colour Abbreviation
Black BK
Brown BN
Red RD
Orange OG
Yellow YE
Green GN
Blue BU
Violet VT
Purple PP
Grey (slate) GY
White WH
Pink PK
Magenta MG
Turquoise TQ
Where separate cores are coloured differently, the codes for different colours are separated by the
sign “plus” (+) e.g. a five-core cable with two black, a brown, a blue and green-and-yellow core is
given by BK+BK+BN+BU+GN/YE.
Colour combinations shall be designated by adding the codes for the different colours, in sequence
from the top of Table 11, with a back slash ‘/’ between each colour abbreviation used e.g. a g reen
core with a yellow stripe is given as GN/YE.
Where a colour is being associated with another colour, brackets ‘( )’ shall be used e.g. white
associated with blue WH(BU).
STNW3001
The colours of indicator lights and controls shall be as per Table 13 and Table 14 as taken from (IEC
60073, 2002).
Green does not necessarily indicate a safe situation for access to equipment, which
may still be alive.
White may be used in preference to Yellow for alarm annunciators on central alarm
panels labelled as alarm indications, to enable the annunciation to be more easily read.
STNW3001
Indication Colour
CB Opened Green
CB Closed Red
The application of the colours in Table 14 shall be only where the indication is provided, and the
indicators are separate to the relays. Where the indication is made by the relay, the colour may be
red if unavoidable, except for CB open which must be green. Indication may be through a mimic
diagram; however text indication is not acceptable.
If there are other functions that are not included in these tables, contact Substation Standards for
approval.
Where control and indication are a combined assembly, such as a backlit pushbutton, the lens cover
shall be clear and the LED / lamp shall be coloured, as per Table 14. Circuit breaker control and
indication shall not be combined in the same assembly. Circuit breaker open or closed state
indication shall be provided using two separate devices.
STNW3001
Annex A
Normative
The meaning of each code used shall be designated on the drawing in which it is used or on a key
index drawing to the set.
Device No Description
95
97 Fire Protection
98 Security Systems
STNW3001
Annex B
Normative
Application Guide
This application guide is to be used to determine what codes should be applied. As these situations
arise, this section will be added to for future users of this standard.
The assignment of item designation codes for relays and protection devices shall be to the definitions
given below:
Other protective devices that don’t comply with the definitions above, such as fuses and
miniature circuit breakers, shall be designated the letter F.
Situation Code
STNW3001
When this is the case, substation standards agreed with Design and Asset Managers to use
manufactures codes instead of STNW3001 codes for equipment mounted or housed in Transformers
and Switchgear. This was primarily to ensure that safety and asset data capture is not compromised.
In rare special circumstance that manufacturer codes are not able to be used in Ellipse, both the
manufacturer codes and the STNW3001 codes should both be applied on all drawings and then the
STNW3001 codes may be used in Ellipse. This method is not preferred and should be avoided
whenever possible.
Frame Leakage protection has been implemented in various methods across the legacy energy
board regions including:
Some use individual relays for each zone, some use one relay with 3 internal elements and have
various arrangements of tripping relays. Standards engaged with Substation Design and Protection.
A Frame Leakage Relay or Current Transformer associated to Bus Section 1 shall use
codes =RFB01-J50N, =RFB01-T03.
A Frame Leakage Relay or Current Transformer associated to Bus Section 2 shall use
codes =RFB02-J50N, =RFB02-T03.
A Frame Leakage Relay or Current Transformer associated to Bus Section 3 shall use
codes =RFB03-J50N, =RFB03-T03
STNW3001
A Frame Leakage Relay or Current Transformer associated to both Bus Section 1 and
2 shall use codes =RFB12-J50N, =RFB12-T03
A Frame Leakage Relay or Current Transformer associated to both Bus Section 2 and
3 shall use codes =RFB23-J50N, =RFB23-T03
STNW3001
Annex C
Normative
Aerial W Counter P
Antenna W Detector B
Attenuator Z Dimmer S
Battery G Diode V
Beacon H Dipole W
STNW3001
Butt-connector X Dynamometer B
Buzzer H Earphone B
Capacitor C Equaliser Z
Capacitor-synchronous C Expander Z
Clamper Z Filter Z
Clock P Fuse F
Coder U Galvanometer P
Conductor W Gyrator, G
ideal/current/voltage
Connector X Headphones B
Contactor K Heater E
STNW3001
Isolator Q Pyrometer P
Joint X Reactor L
STNW3001
Loudspeaker B Resistor R
Luminaries B Resolver B
Machine Y Rheostat R
Motor M Siren H
Network Z Socket-outlet X
STNW3001
Oscilloscope P Subassembly A
Potentiometer R Tachometer P
STNW3001
Thyristor V Voltmeter P
Transductor L Waveguide W
Transformer T Wavemeter P
STNW3001
Annex D
Informative
This annex should be used as a reference guide only with full details given in this standard and the
IEEE standard
STNW3001
19 Starting-to-Running 70 Rheostat
Transition Contactor
STNW3001
STNW3001
Suffix Meaning
A A leg protection
B B leg protection
G In ground lead
S Sensitive relay
M Main Protection
B Backup Protection
1 Protection 1
2 Protection 2
Z Impedance
C Close Function
STNW3001
Annex E
Informative
Colour Abbreviation
Black BK
Brown BN
Red R
Orange O
Yellow Y
Green G
Blue B
Violet V
Grey GY
Slate S
White W
Turquoise T
STNW3001
Annex F
Informative
These standards have been revised, redesignated and withdrawn over the years to align with
international standards. This Annex has been added to detail these changes.
Australian Standards
AS1103.2 (1973) Diagrams, charts and tables for electrotechnology Definitions and classifications
Revised
AS1103.2 (1982) Diagrams charts and tables for electrotechnology, Part 2: Item designation.
This Standard is a comprehensive revision of the former Standard (AS 1103.2 —1982), which was
one part of the AS 1103 series of Standards on diagrams, charts and tables for electrotechnology.
Since the revised system of item designation specified in this Standard is not only used to correlate
information in different documents (such as diagrams, parts lists, circuit descriptions and
instructions) but may also be displayed on or near the item itself in the equipment, this Standard has
been removed from the AS 1103 series and is now a ‘stand -alone’ Standard.
It should be noted that this Standard is technically equivalent to IEC 750 (1983), Item designation in
electrotechnology. It follows the same principles including the removal of the publication from IEC
113 series (on which the AS 1103 series is based) to a new IEC number (i.e. IEC 750).
However, a major deviation from IEC 750 is the provision of a comprehensive alphabetical list of
items and their letter codes given in Table 2, which has been included as a quick-reference guide.
Redesignated
STNW3001
IEC 61346-1(1996) Industrial systems, installations and equipment and industrial products -
Structuring principles and reference designations - Part 1: Basic rules
IEC 81346-1:2009 Industrial systems, installations and equipment and industrial products -
Structuring principles and reference designations - Part 1: Basic rules
IEC 81346-2 (2009) Industrial systems, installations and equipment and industrial products -
Structuring principles and reference designations - Part 2: Classification of objects and codes for
classes
Industrial systems, installations and equipment and industrial products - Structuring principles and
reference designations - Part 2: Classification of objects and codes for classes
IEC 81346-1 is a revision of IEC 61346-1:1996, considering also the content of ISO/TS 16952-1.
The number of the publication has been changed in order to facilitate a common ISO/IEC standard
series on reference designations.
IEC 61346-1 had two predecessors; IEC 60750:1983 and before that IEC 60113-2:1971. Table I on
letter codes in IEC 60750:1983 is in its essential parts taken from IEC 60113-2:1971. The application
domain of the standards has increased with time.
Although it can be argued about where exactly the boundaries should be, it is possible to illustrate
roughly the ambitions and the scope of the three documents as in Figure 18 below.
STNW3001
Item designations (which is the term used in IEC 60113-2) were, when they first appeared just a
classification/coding of discrete components with an added sequential number for separation
between components of the same class. Since sequential numbering is impractical for larger
designs, IEC 60113-2 included the possibility to put hierarchical designations in front of the
component code, and thus to obtain a simple form of structuring.
Information was at that time only contained in documents, and the purpose of the item designation
was to make possible cross-referencing inside and among documents, especially from circuit
diagram to component lists and connection tables/diagrams.
The life cycle perspective was restricted. The immediate need was to produce the documents for the
production of the equipment and for putting it into service.
The possibilities for computer processing at that time where limited. It was necessary to economise
with memory space, and the processing was, at least mentally, still related to a "punch card-oriented
technology", i.e. fixed data format and "smart" use of available format and memory space was very
important.
With IEC 60750 it was recognised that hierarchical structuring was not to be seen just as an
addition to the letter code for the components, but as a basic tool for the management of the
documentation of larger designs. It is probably correct to say that there had been a shift in view so
that the structuring became more emphasised than the component coding.
STNW3001
As a consequence, the use of item designations had become more widespread; also used in other
documents than in circuit diagrams. Documents were, however, generally still considered to be the
most important carrier of the information.
The possibilities for computer processing had been improved; the "punch card-oriented
technology" had been left for the "relational oriented technology".
With the revision of IEC 60750, the use of item/reference designations became further extended. It
was recognised that reference designation could be used as a powerful tool for information
management. The information was not necessarily contained in ready-made documents, but could
be fragmented, put into data bases, from which documents could be put together as needed
(including graphical presentations). They could be seen as "windows" into the data base. It was
required to use the reference designation system as a "navigation tool" in such an environment.
There was also an urgent need to extend the use to other equipment than electrical, to process
equipment, to software, etc.
The possibilities for computer processing had been tremendously improved. It was realised that the
"relational oriented technology" could not solve all problems, and the "object-oriented technology"
was becoming used.
NOTE The use of the term ”object” in "object-oriented system design" and "object-oriented
programming", is related to but not identical with, the term used in this publication.
Instead of "smart" economising with computing power it had become more essential to describe
things logically and straightforward in order to enhance functionality, exchangeability and
communication.
Another very important requirement had become emphasised, namely that the reference
designations should be possible to use over the entire life cycle of the "objects".
In IEC 81346-1, the rules established in IEC 61346-1 are maintained, but more emphasis is put on
the description of the concepts in order to enhance the understanding and applicability of the
standard. The rules and requirements have, based on input from ISO TC10, been adapted to
improve the usability of the standard outside the electrotechnical field.
IEC 81346-1 is intended to become a basis for a common reference designation system within IEC
and ISO and should be the first part in a series of publications with a common number with split
responsibility for the different parts.
STNW3001
Appendix A
For definitive document version and control detail, please refer to the information stored on the
Process Zone
Revision History
Revision date Version Author Description of change/revision
number
STNW3001
STNW3001
STNW3001
STNW3001